 |
Plan Review Details - Permit 07010448
Plan Review Stops For Permit 07010448 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2007-09-25 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-09-25 |
Time |
12:11 |
Rev Time |
0.77 |
Received By |
jwitmer |
Date |
2007-09-25 |
Time |
12:11 |
Sent To |
PC |
|
Notes |
2007-09-25 12:14:17 | BUILDING PROVISO:WOOD SUBSHEATHING , 2304.11.2.5 WOOD | | SIDING. CLEARANCE BETWEENWOOD | | SIDING AND EARTH ON THE EXTERIOR OF A BUILDING SHALL | | NOT BE LESS THAN 6 INCHES(152 MM)EXCEPT | | WHERE SIDING, SHEATHING AND WALL FRAMING ARE OF | | NATURALLY DURABLE OR PRESERVATIVE-TREATED WOOD. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2007-07-09 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-07-09 |
Time |
16:15 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-07-09 |
Time |
16:15 |
Sent To |
|
|
Notes |
2007-07-09 16:16:51 | PLANS STAMPED BY JIM WITMER ON 7/7/07 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2007-04-09 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-04-09 |
Time |
08:48 |
Rev Time |
1.11 |
Received By |
jwitmer |
Date |
2007-04-05 |
Time |
11:42 |
Sent To |
|
|
Notes |
2007-04-09 08:49:18 | BUILDING PLAN REVIEW | | PERMIT: 07010448 | | ADD: 771 VILLAGE BLVD | | CONT: FIVE STAR CONSTRUCTION GROUP | | TEL: (561)436-8508 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW | | ACTION: DENIED | | | | 1)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | BER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | 2) 2ND REQUEST, COMMENT # 3 FROM THE PREVIOUS REQUEST, | | 1609.1.4 PROTECTION OF OPENINGS. | | IN WIND-BORNE DEBRIS REGIONS, EXTERIOR | | GLAZING THAT RECEIVES POSITIVE PRESSURE | | IN THE LOWER 60 FEET (18.3 M) IN | | BUILDINGS SHALL BE ASSUMED TO BE | | OPENINGS AND THE BALANCE OF GLAZED | | OPENINGS IN THE REST OF THE BUILDING | | SHALL BE ASSUMED TO BE ZERO UNLESS SUCH | | GLAZING THAT RECEIVES POSITIVE PRESSURE | | IS IMPACT RESISTANT OR PROTECTED WITH AN | | IMPACT RESISTANT COVERING MEETING THE | | REQUIREMENTS OF SSTD 12, ASTM E 1886 AND | | ASTM E 1996, OR MIAMI-DADE TAS 201, 202 | | AND 203 REFERENCED THEREIN AS FOLLOWS: | | 1.GLAZED OPENINGS LOCATED WITHIN 30 | | FEET (9.1 M) OF GRADE SHALL MEET THE | | REQUIREMENTS OF THE LARGE MISSILE TEST. | | 2.GLAZED OPENINGS LOCATED MORE THAN | | 30 FEET (9.1 M) ABOVE GRADE SHALL MEET | | THE PROVISIONS OF THE SMALL MISSILE | | TEST. | | | | 3B)PRODUCT APPROVALS SUBMITTED WITH | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | PLEASE SEE THE STATE WEBSITE AT | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | SUBMITTED WITH A COVER SHEET THAT LISTS | | THE PRODUCT IDENTITY NUMBER FROM THE | | STATE. IF THE PRODUCT DOES NOT HAVE | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | SPECIFIC FORM PER RULE 9B-72. SEE | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | 3C) WPB ADMIN CODE 106.3* PRODUCT | | APPROVALS. THOSE PRODUCT WHICH ARE | | REGULATED BY DCA RULE 9B-72 SHALL BE | | REVIEWED AND APPROVED IN WRITING BY THE | | DESIGNER OF RECORD PRIOR TO SUBMITTAL | | FOR JURISDICTIONAL APPROVAL. | | | | 3D) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, | | PROVIDE 2 COPIES(3 IF THRESH- | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | TESTING REPORTS,MISSING REPORTS ARE AS | | FOLLOWS: | | | | WINDOWS: STOREFRONT | | DOORS: STOREFRONT DOORS | | | | BUILDING PLAN REVIEW | | JIM WITMER C. B. O. | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2007-02-05 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-02-05 |
Time |
12:24 |
Rev Time |
2.22 |
Received By |
jwitmer |
Date |
2007-02-05 |
Time |
12:24 |
Sent To |
|
|
Notes |
2007-02-05 13:02:49 | BUILDING PLAN REVIEW | | PERMIT: 07010448 | | ADD: 771 VILLAGE BLVD | | CONT: FIVE STAR CONSTRUCTION GROUP | | TEL: (561)436-8508 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW | | ACTION: DENIED | | | | 1)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | BER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | 2) 110.2* W. P. B. ADMINISTRATIVE | | CODE, INFORMATION THAT IS REQUIRED FOR | | RECORD KEEPING & FOR CERTIFICATE OF | | OCCUPANCY: | | A) THE EDITION OFTHE CODE UNDER WHICH | | THE PERMIT WAS ISSUED. | | NOTE PLANS SUBMITTED ON OR AFTER DEC. 8/07 SHOULD ALSO | | REFLECT THE 2006 REVISIONS TO THE FBC. | | PLANS ALSO NEED TO REFLECT THE EXISTING BUILDING CODE, | | AND LEVEL OF ALTERATION | | LEVEL 1 | | LEVEL 2 | | LEVEL 3 | | | | B) THE USE AND OCCUPANCY, IN ACCORDANCE | | WITH THE PROVISIONS OF CHAPTER 3. | | C) THE TYPE OF CONSTRUCTION AS DEFINED | | IN CHAPTER 6, TABLE 601. | | NOTE TYPE OF CONSTRUCTION IS FOR THE "BUILDING" NOT THE | | TENANT SPACE. | | D) THE DESIGN OCCUPANT LOAD, SEE 1004. | | NOTE IF THIS IS A CHANGE IN OCCUPANCY? | | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS | | PROVIDED, WHETHER THE SPRINKLER SYSTEM | | IS REQUIRED. | | F) ANY SPECIAL STIPULATIONS & CONDITIONS | | OF THE BUILDING PERMIT. | | G ) SQ. FT. A/CL/ FL | | H) SQ. FT. FOOTPRINT | | I ) SQ. FT. UNDER ROOF (TOTAL) | | | | 3A) 1609.1.4 PROTECTION OF OPENINGS. | | IN WIND-BORNE DEBRIS REGIONS, EXTERIOR | | GLAZING THAT RECEIVES POSITIVE PRESSURE | | IN THE LOWER 60 FEET (18.3 M) IN | | BUILDINGS SHALL BE ASSUMED TO BE | | OPENINGS AND THE BALANCE OF GLAZED | | OPENINGS IN THE REST OF THE BUILDING | | SHALL BE ASSUMED TO BE ZERO UNLESS SUCH | | GLAZING THAT RECEIVES POSITIVE PRESSURE | | IS IMPACT RESISTANT OR PROTECTED WITH AN | | IMPACT RESISTANT COVERING MEETING THE | | REQUIREMENTS OF SSTD 12, ASTM E 1886 AND | | ASTM E 1996, OR MIAMI-DADE TAS 201, 202 | | AND 203 REFERENCED THEREIN AS FOLLOWS: | | 1.GLAZED OPENINGS LOCATED WITHIN 30 | | FEET (9.1 M) OF GRADE SHALL MEET THE | | REQUIREMENTS OF THE LARGE MISSILE TEST. | | 2.GLAZED OPENINGS LOCATED MORE THAN | | 30 FEET (9.1 M) ABOVE GRADE SHALL MEET | | THE PROVISIONS OF THE SMALL MISSILE | | TEST. | | | | 3B)PRODUCT APPROVALS SUBMITTED WITH | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | PLEASE SEE THE STATE WEBSITE AT | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | SUBMITTED WITH A COVER SHEET THAT LISTS | | THE PRODUCT IDENTITY NUMBER FROM THE | | STATE. IF THE PRODUCT DOES NOT HAVE | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | SPECIFIC FORM PER RULE 9B-72. SEE | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | 3C) WPB ADMIN CODE 106.3* PRODUCT | | APPROVALS. THOSE PRODUCT WHICH ARE | | REGULATED BY DCA RULE 9B-72 SHALL BE | | REVIEWED AND APPROVED IN WRITING BY THE | | DESIGNER OF RECORD PRIOR TO SUBMITTAL | | FOR JURISDICTIONAL APPROVAL. | | | | 3D) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, | | PROVIDE 2 COPIES(3 IF THRESH- | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | TESTING REPORTS,MISSING REPORTS ARE AS | | FOLLOWS: | | | | WINDOWS: STOREFRONT | | DOORS: STOREFRONT DOORS | | | | 4)-RESTAURANTS AND CAFETERIAS5.1 | | EXCEPT AS SPECIFIED OR MODIFIED IN THIS SECTION, | | RESTAURANTS AND CAFETERIAS SHALL COMPLY WITH THE | | REQUIREMENTS OF SECTION 11-4.1 TO SECTION 11-4.35 . | | WHERE FIXED TABLES (OR DINING COUNTERS WHERE FOOD IS | | CONSUMED BUT THERE IS NO SERVICE) ARE PROVIDED, AT | | LEAST 5 PERCENT, BUT NOT LESS THAN ONE, OF THE FIXED | | TABLES (OR A PORTION OF THE DINING COUNTER) SHALL BE | | ACCESSIBLE AND SHALL COMPLY WITH SECTION 11-4.32 AS | | REQUIRED IN SECTION 11-4.1.3 (18). IN ESTABLISHMENTS | | WHERE SEPARATE AREAS ARE DESIGNATED FOR SMOKING AND | | NONSMOKING PATRONS, THE REQUIRED NUMBER OF ACCESSIBLE | | FIXED TABLES (OR COUNTERS) SHALL BE PROPORTIONALLY | | DISTRIBUTED BETWEEN THE SMOKING AND NONSMOKING AREAS. | | IN NEW CONSTRUCTION, AND WHERE PRACTICABLE IN | | ALTERATIONS, ACCESSIBLE FIXED TABLES (OR COUNTERS) | | SHALL BE DISTRIBUTED THROUGHOUT THE SPACE OR FACILITY. | | | | | | 11-5.2 COUNTERS AND BARS. | | WHERE FOOD OR DRINK IS SERVED AT COUNTERS EXCEEDING 34 | | INCHES (865 MM) IN HEIGHT FOR CONSUMPTION BY CUSTOMERS | | SEATED ON STOOLS OR STANDING AT THE COUNTER, A PORTION | | OF THE MAIN COUNTER WHICH IS 60 INCHES (1525 MM) IN | | LENGTH MINIMUM SHALL BE PROVIDED IN COMPLIANCE WITH | | SECTION 11-4.32 OR SERVICE SHALL BE AVAILABLE AT | | ACCESSIBLE TABLES WITHIN THE SAME AREA. | | | | 11-5.3 ACCESS AISLES. | | ALL ACCESSIBLE FIXED TABLES SHALL BE ACCESSIBLE BY | | MEANS OF AN ACCESS AISLE AT LEAST 36 INCHES (915 MM) | | CLEAR BETWEEN PARALLEL EDGES OF TABLES OR BETWEEN A | | WALL AND THE TABLE EDGES. | | DINING | | 11-5.4 DINING AREAS. | | IN NEW CONSTRUCTION, ALL DINING AREAS, INCLUDING RAISED | | OR SUNKEN DINING AREAS, LOGGIAS, AND OUTDOOR SEATING | | AREAS, SHALL BE ACCESSIBLE. IN ALTERATIONS, | | ACCESSIBILITY TO RAISED OR SUNKEN DINING AREAS, OR TO | | ALL PARTS OF OUTDOOR SEATING AREAS IS NOT REQUIRED | | PROVIDED THAT THE SAME SERVICES AND DECOR ARE PROVIDED | | IN AN ACCESSIBLE SPACE USABLE BY THE GENERAL PUBLIC AND | | ARE NOT RESTRICTED TO USE BY PEOPLE WITH DISABILITIES. | | | | EXCEPTION: NOTHING IN THIS SECTION SHALL BE CONSTRUED | | TO RELIEVE THE OWNER OF THE DUTY TO PROVIDE VERTICAL | | ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW OCCUPIABLE | | GRADE LEVEL, REGARDLESS OF WHETHER THE CODE REQUIRES AN | | ELEVATOR TO BE INSTALLED IN SUCH BUILDINGS, STRUCTURES | | OR FACILITIES EXCEPT: (1) ELEVATOR PITS, ELEVATOR | | PENTHOUSES, MECHANICAL ROOMS, PIPING OR EQUIPMENT | | CATWALKS, AND AUTOMOBILE LUBRICATION AND MAINTENANCE | | PITS AND PLATFORMS; (2) UNOCCUPIABLE SPACES, SUCH AS | | ROOMS, ENCLOSED SPACES, AND STORAGE SPACES THAT ARE NOT | | DESIGNED FOR HUMAN OCCUPANCY, FOR PUBLIC | | ACCOMMODATIONS, OR FOR WORK AREAS; AND (3) OCCUPIABLE | | SPACES AND ROOMS THAT ARE NOT OPEN TO THE PUBLIC AND | | THAT HOUSE NO MORE THAN FIVE PERSONS INCLUDING, BUT NOT | | LIMITED TO, EQUIPMENT CONTROL ROOMS AND PROJECTION | | BOOTHS. THEREFORE, FACILITIES SUBJECT TO THE ADA MAY BE | | REQUIRED TO PROVIDE VERTICAL ACCESS TO AREAS OTHERWISE | | EXEMPT UNDER SECTION 11-4.1.3 (5), OF THE CODE. | | | | 5) PLANS MAY REQUIRE PALM BCH COUNTY REVIEW FOR IMPACT | | FEES: | | BEFORE A PERMIT TO CONSTRUCT, MAY | | BE ISSUED, IMPACT FEES MUST BE PAID TO | | PALM BEACH COUNTY. THE ACTUAL PERMIT | | SET OF PLANS MUST BE STAMPED BY THAT | | OFFICE, AND A COPY OF THE PAID RECEIPT | | ATTACHED TO THE PERMIT APPLICATION. | | PLEASE CALL (561)233-5025 FOR MORE | | INFORMATION. | | | | BUILDING PLAN REVIEW | | JIM WITMER C. B. O. | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2007-07-24 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-07-24 |
Time |
12:40 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-07-24 |
Time |
12:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2007-06-20 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-06-20 |
Time |
10:28 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-06-20 |
Time |
09:41 |
Sent To |
|
|
Notes |
2007-06-20 10:29:41 | *** UNSAT 3RDREVIEW ** | | | | | | 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED | | NEED TO COORDINATE WITH THE PLANS FOR THE NUMBER OF | | FIXTURES, THE WATTAGE FOR FIXTURES, FIXTURE LEGEND AND | | LIGHTING POWER DENSITIES. | | PLEASE SEE THE WATTAGE ON FIXTURES | | PLEASE SEE THE AMOUNT OF FIXTURES | | PLEASE SEE THE TYPE OF FIXTURES | | PLEASE SEE 13-415.1.AB.1.1, 13-415.2 | | | | 2) NOTE: PLEASE SEE AS RISER HAS BEEN REVISED, PLEASE | | SEE NO FLOATING NEUTRAL INDICATED ON RISER AT NEW | | METER. 250.6 | | | | 3) NOTE: PLEASE INDICATE THE AIC RATING FOR THE NEW | | MAIN. | | | | * ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2007-04-02 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-04-02 |
Time |
10:43 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-03-31 |
Time |
18:35 |
Sent To |
|
|
Notes |
2007-04-02 10:44:19 | ** UNSAT2ND REVIEW ** | | | | 1) NOTE:PLEASE SEE PLANS ARE NOW INDICATING A | | COMPLETE NEW PROPOSED SERVICE WHICH AT THIS TIME DOES | | NOT MEET 230.2 AND IS NOT GRANTED. | | PLEASE SEE THAT THE LANDLORD SERVICE WILL BE REQUIRED | | TO BE UPGRADED. | | PLEASE SEE THE RISER SHOWS FEEDS FROM THE FPL | | TRANSFORMER HOWEVER TWO SEPARATE VOLTAGES ARE ALSO | | SHOWN. | | PLEASE ADJUST AND GIVE INFORMATION FOR EXISTING SERVICE | | TO BE UPGRADED. | | | | 2) NOTE: PLEASE CORRELATE ENERGY CALCULATIONS WITH THE | | PLANS.PLEASE SEE THE LIGHTING POWER DENSITIES FOR | | MANY OF THE AREAS EXCEED THAT OF WHICH IS SHOWN ON | | TABLES IN THE FBC. | | PLEASE SEE THE RESPONSE MENTIONS THAT OCCUPANCY SENSORS | | ARE TO BE INSTALLED, HOWEVER THESE COULD NOT BE LOCATED | | ON PLANS. | | PLEASE SEE THE DETAIL SUBMITTED SHOWS MANUAL SWITCHES | | AFTER THE OC DEVICE, WHICHIF THE SWITCH IS IN THE OFF | | POSITION WOULD NO ALLOW ANY USE OF THE AUTOMATED MEANS | | AS REQUIRED. | | PLEASE PROVIDE MORE INFORMATION FOR THE LIGHTING | | CONTROLS. THE SWITCHES BEING NOTED AS SENSOR TYPES DOES | | NOT PROVIDE THE COVERAGE NEEDED. | | PLEASE SEE 13-415.2.ABC.1.2 AND PLEASE THE AMOUNT OF | | THE WATTAGE ON TRANSFORMERS NEEDS TO BE SPECIFIED. | | PLEASE SEE THE LIMITS ON TRACK. | | PLEASE VERIFY THE METHOD WHICH IS BEING USED. | | ** PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED NEEDS | | THE SEAL TO BE CLEAR AND VISIBLE WITH ALL INFORMATION | | ON SAID SEAL. | | 13-103.1.1.1 FS 471.025 | | | | 3) NOTE: PLEASE PROVIDE A LOAD SUMMARY ON HOW LOADS FOR | | SHOW WINDOWS WERE DERIVED. (X-AMOUNT OF FEET TIMES | | 200VQA PER FT =Y). PLEASE PROVIDE IN THE SUMMARY HOW | | RECEPTACLE LOAD WAS DERIVED. (X AMOUNT OF DEVICES TIMES | | 180VA=?). | | PLEASE SEE THE LOAD SUMMARY WAS REVISED, HOWEVER COULD | | NOT LOCATE THELOAD OF 200VA PER FT ADDED FOR WINDOW | | AREAS. | | 220.43, 220.44 ETC. | | FBC 106.1.2, 106.3.5.1.2. | | | | 4) NOTE: PLEASE SEE THE RESPONSE LETTER MENTIONS A | | GENERAL NOTE FOR THE FS 553.80(2)(B).IT IS UNCLEAR | | WHY THIS COMMENT HAS BEEN MADE AS THERE NOTHING THE | | REVIEW COMMENTS FROM PLAN REVIEW WHICH REFERENCED THIS | | FS. | | | | ** ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | 2007-03-31 18:37:36 | IN ELEC FOR REVIEW. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2007-01-28 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-01-28 |
Time |
18:20 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-01-28 |
Time |
17:24 |
Sent To |
|
|
Notes |
2007-01-28 18:21:36 | ** UNSAT ** | | | | 1) NOTE:PLEASE KNOW AS PROJECT WAS APPLIED FOR PERMIT | | AFTER DECEMBER 8TH, 2006 THE FOLLOWING CODES FOR DESIGN | | AND AS REFERENCED ON PLANS HAVE CHANGED. | | PLEASE KNOW THE STATE HAS NOW ADOPTED THE 2006 | | REVISIONS TO THE 2004 FBC WHICH HAS CHANGES FOR | | BUILDING, MECHANICAL, PLUMBING AND CHANGES FOR CHAPTER | | 13 WHICH WILL AFFECT THE ELECTRICAL PLANS. | | PLEASE ALSO KNOW THE ELECTRICAL CODE NOT ADOPTED AS OF | | 12/8/06 IS THE 2005 NFPA-70 (NEC). | | PLEASE BE SURE THE ARCHITECTURAL PLANS AND MEP'S ARE | | UPDATED WITH CODE REFERENCES. | | | | PLEASE ADJUST PLANS, DESIGNS AND PLEASE BE SURE TO SEE | | ANY COMMENTS FROM OTHER TRADES WHICH MAY AFFECT THE | | ELECTRICAL PLANS. | | | | 2) NOTE: PLEASE CORRELATE ENERGY CALCULATIONS WITH THE | | PLANS. PLEASE SEE THE CALCULATIONS INDICATE THE | | CONTROLS FOR LIGHTING AS MANUAL. | | PLEASE ALSO PROVIDE PERFORMANCE CALCULATIONS PER | | 13-415.2. | | PLEASE VERIFY THE METHOD WHICH IS BEING USED. PLEASE | | SEE THIS IS SUBMITTED AS METHOD *A*WILL THIS | | INCORPORATE ALL AREAS? | | ** PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED ARE NOT | | SEALED BY THE DESIGNER OF RECORD AS REQUIRED. | | 13-103.1.1.1 | | | | 3) NOTE: PLEASE CORRELATE RISER AND PANEL *A*. PLEASE | | SEE ONE SHOWS 600A MLO AND THE OTHER ON RISER AS 400A | | MLO. | | FBC 106.1.2, 106.3.5.1.2 | | | | 4) NOTE: PLEASE SEE THAT IF ANY FIRE ALARM SYSTEMS ARE | | REQUIRED AND INSTALLED. PLEASE INDICATE ALL THE MINIMUM | | LEVELS FOR THESE DEVICES ON PLANS. PLEASE ALSO INDICATE | | THE LOCATIONS. PLEASE SEE KNOW IF APPLICABLE, THESE | | WILL BE REQUIREDTO BE SHOWN ON BASE PLANS EVEN THOUGH | | THESE SYSTEMS WILL BE UNDER SEPARATE PERMITS AND PLANS | | AT A LATER DATE. PLEASE SEE THE 2004 FBC 11-4.28.1,.2 | | AND .3(4) FOR MINIMUM LEVELS TO BE INDICATED. | | | | 5) NOTE: PLEASE CLARIFY ELECTRICAL SHUNT FOR ELECTRICAL | | DEVICES AND/OR EQUIPMENT UNDER HOOD. PLEASE SEE | | NFPA-96. | | | | 6) NOTE: PLEASE PROVIDE LOAD ON THE EXISTING 600AMP | | MAIN SERVICE WHICH THIS NEW SERVICE IS BEING TAPPED | | FROM GUTTER. | | PLEASE INDICATE. 220, 215.5, 220.3, 220.12, | | 220.14,220.42 220.87 ETC | | FBC 106.1.2, 106.3.5.1.2 | | | | 7) NOTE: PLEASE INDICATE A *FLOATING NEUTRAL KIT* | | REQUIRED AT THE METER CAN. THIS CAN BE DONE BY A NOTE | | ON PLANS. 250.6, 250.24B. | | | | 8) NOTE: PLEASE PROVIDE A LOAD SUMMARY ON HOW LOADS FOR | | SHOW WINDOWS WERE DERIVED. (X-AMOUNT OF FEET TIMES | | 200VQA PER FT =Y). PLEASE PROVIDE IN THE SUMMARY HOW | | RECEPTACLE LOAD WAS DERIVED. (X AMOUNT OF DEVICES TIMES | | 180VA=?). | | PLEASE CLARIFY WHERE THE CONTINUOUS LOAD WAS DERIVED. | | THIS CAN BE DONE WITH THE LIGHTING LOADS. | | 220.43, 220.44 ETC. | | FBC 106.1.2, 106.3.5.1.2. | | | | 9) NOTE: PLEASE CLARIFY CONTROL DEVICES BEING SHOWN FOR | | HALLWAY/EGRESS LIGHTS AS A S/D. IS THIS A DIMMER? | | PLEASE CLARIFY HOW THE MINIMUM LIGHTING LEVELS FOR | | EGRESS UNDER NORMAL CONDITIONS WILL BE MET BY PLACING A | | DIMMER ON THESE LIGHTS TO MEET LS 101 7.8,7.9. | | * PLEASE ALSO SEE THESE DEVICE IS LISTED WITH PART OF | | THE CONTROL DEVICES FOR AUTOMATED SHUT OFF OF LIGHTS. | | 13-415.1.ABC.1.1, .1.2, .1.3. | | | | 10) NOTE: PLEASE SEE ALL SWITCHES ARE BEING SHOWN AS | | PASSIVE INFRARED FOR LIGHTING CONTROL WHICH IS OK; | | HOWEVER PLEASE SEE NOTE ABOVE FOR EGRESS AND PLEASE | | CLARIFY HOW COVERAGE WILL BE MET FOR EGRESS AND NORMAL | | OPERATION AS MANY OF THE DEVICES ARE BEING LOCATED AT | | ONE LOCATION ON A WALL IN KITCHEN AREA. PLEASE SEE | | DEVICES WHICH ARE IN INDIVIDUAL ROOMS LIKE THE | | BATHROOMS WHICH CONTAIN FLOOR TO CEILING HEIGHT | | PARTITIONS IS OK, HOWEVER THE COVERAGE FOR OVERRIDING | | DURING NORMAL BUSINESS HOURS SEEMS LIKE IT WILL NOT | | PROVIDE THE NEEDED CONTROL FOR LIGHTING AS SHOWN. | | PLEASE SEE MEANS TO OVER RIDER LIGHTING IS ALSO | | REQUIRED TO BE AT MEANS OF INGRESS INTO AREA/SPACE. | | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3 | | PLEASE CALL TO GO OVER SCENARIO AS SHOWN. | | | | 10) NOTE: PLEASE SEE THE *OR* OPTION FOR FEEDERS FROM | | THE METER TO PANEL *A* WHICH IS SHOWING A 1/0 EQUIPMENT | | GROUNDING CONDUCTOR FOR 400AMPS. THIS IS ONLY BEING | | NOTED AND DOES NOT CREATE ANY CODE COMMENT. | | | | 11) NOTE: PLEASE SEE PLANS MENTIONS EXTERIOR LIGHTING | | IS BY LANDLORD, IF THIS IS THE CASE PLEASE REMOVE FROM | | PLANS. PLEASE SEE THE LIGHTING AS SHOWN ON PLANS MAY BE | | DONE AS PART OF THIS BUILD OUT. | | PLEASE CLARIFY. | | FBC 106.1.2 ADMIN SECTION FOR ADDITIONAL INFORMATION. | | | | 12) NOTE: PLEASE BE SURE TO INCLUDE THE UNIT/SUITE | | NUMBER ON PLANS FOR LOCATION OF SCOPE OF WORK. THE | | PERMIT APPLICAITON AND ADDRESS OF SUITE/UNIT APPLIED | | FOR IN OUR SYSTEM INDICATES SUITE 801. | | FAC 61G1-16.004 | | | | | | ** ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2007-07-26 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-07-26 |
Time |
18:35 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-07-26 |
Time |
18:18 |
Sent To |
|
|
Notes |
2007-07-26 18:35:10 | ****APPROVED***** | | | | ALL COMMENTS FORM THE PREVIOUS FIRE PLAN REVIEWS HAVE | | BEEN ADDRESSED;PLAN SHEETS A-1, A-2, AND FP-1 | | STAMPED, INIOTIALED, AND DATED. | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
F |
Date |
2007-07-09 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-07-09 |
Time |
12:26 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-07-09 |
Time |
11:42 |
Sent To |
|
|
Notes |
2007-07-09 11:48:06 | ****UNSAT***** | | | | THE FOLLOWING COMMENTS WERE TAKEN FROM THE PREVIOUS | | FIRE PLAN REVIEWS STILL NEED TO BE ADDRESSED: | | | | | | 04.THE COMPLETE ADDRESS , INCLUDING THE TENANT SPACE | | NUMBER, SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED | | PLAN SHEET.PLEASE SEE SHEET A-2,A-5,A-6,A-7 | | | | | | 07.PROVIDE A LAYOUT OF THE FIRE SPRINKLER SYSTEM FOR | | THIS TENANT SPACE.IF THE SPRINKLER SYSTEM IS MODIFIED | | DUE TO THE SCOPE OF WORK, SEPARATE PLANS AND PERMIT | | WILL BE REQUIRED. | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING HOW/WHERE EACH COMMENT WAS | | ADDRESSED. | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2007-05-03 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-05-03 |
Time |
11:27 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-05-02 |
Time |
15:56 |
Sent To |
|
|
Notes |
2007-05-02 16:02:03 | ****DENIED***** | | | | THE FOLLOWING COMMENTS WERE TAKEN FROM THE PREIVIOUS | | FIRE PLAN REVIEW STILL NEED TO BE ADDRESSED: | | | | | | 01.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 02.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS | | SHALL BE REMOVED FORM THE SITE AT THE END OF EACH SHIFT | | OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | 03.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF | | NEW BUILDING MATERIALS & SUPPLIES SHALL NOT INTERFERE | | OR HINDER WITH ACCESS TO OR EXIT FROM THE STRUCTURE OR | | THE VICINITY OF THE STRUCTURE (INCLUDING FIRE LANES). | | | | 04.THE COMPLETE ADDRESS , INCLUDING THE TENANT SPACE | | NUMBER, SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED | | PLAN SHEET. | | | | 05.ON THE APPROPIATE EXTERIOR ELEVATION DETAIL, | | DISPLAY THE TENANT SPACE NUMBER FOR THIS SITE.AS PER | | WEST PALM BEACH CODE, THOSE NUMBERS SHALL BE NO LESS | | THAN 3" IN HEIGHT AND NO LESS THAN 1" IN WIDTH. | | | | 06.PROVIDE A LIFE SAFETY PLAN SHEET WHICH INDICATES | | THE TRAVEL DISTANCE TO THE EXIT(S). | | | | 07.PROVIDE A LAYOUT OF THE FIRE SPRINKLER SYSTEM FOR | | THIS TENANT SPACE.IF THE SPRINKLER SYSTEM IS MODIFIED | | DUE TO THE SCOPE OF WORK, SEPARATE PLANS AND PERMIT | | WILL BE REQUIRED. | | | | 08.THE INTERIOR WALL AND CEILING FINISH MATERIALS | | SHALL BE CLASS A, CLASS B, OR CLASS C IN ASSEMBLY AREAS | | HAVING OCCUPANT LOADS OF 300 OR FEWER.PLEASE | | SPECIFY. | | | | 09.COOKING EQUIPMENT SHALL BE PROTECTED IN ACCORDANCE | | WITH NFPA 96.SEPARATE PLANS SND PERMIT WILL BE | | REQUIRED FOR THE COOKING HOOD INSTALLATIN AND THE | | ASSOCIATED SUPPRESSION SYSTEM. | | | | 10.SMOKE DUCT DETECTORS, AS INDICATED ON SHEET M1, | | SHALL INITIATE A GENERAL FIRE ALARM. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING HOW/WHERE EACH COMMENT WAS | | ADDRESSED. | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2007-02-20 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-02-20 |
Time |
13:50 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-02-20 |
Time |
13:50 |
Sent To |
|
|
Notes |
2007-02-20 14:36:58 | *****DENIED***** | | | | | | 01.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 02.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS | | SHALL BE REMOVED FORM THE SITE AT THE END OF EACH SHIFT | | OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | 03.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF | | NEW BUILDING MATERIALS & SUPPLIES SHALL NOT INTERFERE | | OR HINDER WITH ACCESS TO OR EXIT FROM THE STRUCTURE OR | | THE VICINITY OF THE STRUCTURE (INCLUDING FIRE LANES). | | | | 04.THE COMPLETE ADDRESS , INCLUDING THE TENANT SPACE | | NUMBER, SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED | | PLAN SHEET. | | | | 05.ON THE APPROPIATE EXTERIOR ELEVATION DETAIL, | | DISPLAY THE TENANT SPACE NUMBER FOR THIS SITE.AS PER | | WEST PALM BEACH CODE, THOSE NUMBERS SHALL BE NO LESS | | THAN 3" IN HEIGHT AND NO LESS THAN 1" IN WIDTH. | | | | 06.PROVIDE A LIFE SAFETY PLAN SHEET WHICH INDICATES | | THE TRAVEL DISTANCE TO THE EXIT(S). | | | | 07.PROVIDE A LAYOUT OF THE FIRE SPRINKLER SYSTEM FOR | | THIS TENANT SPACE.IF THE SPRINKLER SYSTEM IS MODIFIED | | DUE TO THE SCOPE OF WORK, SEPARATE PLANS AND PERMIT | | WILL BE REQUIRED. | | | | 08.THE INTERIOR WALL AND CEILING FINISH MATERIALS | | SHALL BE CLASS A, CLASS B, OR CLASS C IN ASSEMBLY AREAS | | HAVING OCCUPANT LOADS OF 300 OR FEWER.PLEASE | | SPECIFY. | | | | 09.COOKING EQUIPMENT SHALL BE PROTECTED IN ACCORDANCE | | WITH NFPA 96.SEPARATE PLANS SND PERMIT WILL BE | | REQUIRED FOR THE COOKING HOOD INSTALLATIN AND THE | | ASSOCIATED SUPPRESSION SYSTEM. | | | | 10.SMOKE DUCT DETECTORS, AS INDICATED ON SHEET M1, | | SHALL INITIATE A GENERAL FIRE ALARM. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING HOW/WHERE EACH COMMENT WAS | | ADDRESSED. | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
4 |
Status |
P |
Date |
2007-07-31 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2007-07-31 |
Time |
14:47 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2007-07-31 |
Time |
14:47 |
Sent To |
|
|
Notes |
2007-07-31 15:11:12 | NOTE: SENT TO LUIS MARTINEZ. | | | | ****************PROVISO**************** | | PLEASE REFERENCE THE FOLLOWING FOR THE PLUMBING SERVICE | | SCHEDULE THAT REFLECTS THE EQUIPMENT SUBMITTAL. PLEASE | | REFERENCE THE RED LINE CORRECTIONS TO THE BTU LOAD ON | | THE NATURAL GAS RISER: | | | | G2 - RICE COOKER= 34,000 BTU'S: | | G5 - FRYER= 105,000 BTU'S: | | G6 - HOT PLATE= 44,000 BTU'S: | | G7 - BROILER= 120,000 BTU'S: | | G8 - GRIDDLE= 40,000 BTU'S: | | G9 - GYRO GRILL (SUBMITTAL BOOK IDENTIFIES ITEM AS A | | "VERTICAL BROILER")= 50,000 BTU'S: | | | | THE FOLLOWING IS THE CORRECT TOTAL OF KITCHEN EQUIPMENT | | BTU'S= 483,000 BTU'S: | | | | THE FOLLOWING IS THE CORRECT BTU TOTAL OF GAS SYSTEM | | INCLUDING WATER HEATER= 538,000 BTU'S: | | | | REVIEW BY MIKE PERSON | | PLUMBING PLANS EXAMINER | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL= [email protected] | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
3 |
Status |
F |
Date |
2007-07-06 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-07-06 |
Time |
16:57 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-07-06 |
Time |
16:57 |
Sent To |
|
|
Notes |
2007-07-06 17:09:33 | DENIED | | REFERENCE: FBC-2004 FUEL GAS | | | | ****FROM THE PREVIOUS REVIEW: | | ********FROM PREVIOUS REVIEWS: | | | | 1. THE FOLLOWING INFORMATION IS REQUIRED FOR THE | | SEPARATE GAS PERMIT: | | | | A. OK | | | | B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | ****RESPONSE NOTED, NOT ADDRESSED | | ********RESPONSE NOTED, BUT 4 OUT OF 6 GAS APPLIANCES | | HAVE ONLY A COVER SHEET FROM THE SUPPLIER AND NOT THE | | MANUF. SHEETS AS REQUESTED. THE MANUF. SHEETS ARE | | REQUIRED FOR ITEMS MARK G2, G6, G7 & G8 SHOWING A | | LISTING, INDICATE MODEL NUMBER, AND SHOW THE BTU LOAD | | THAT CORRELATES WITH THE PLUMBING SERVICE SCHEDULE AND | | THE GAS RISER DIAGRAM. | | | | C. N/A | | D. N/A | | E. OK | | | | ****NEW COMMENT: | | | | 1B. OK | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
F |
Date |
2007-04-25 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-04-25 |
Time |
18:29 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-04-25 |
Time |
18:29 |
Sent To |
|
|
Notes |
2007-04-25 18:42:53 | DENIED | | REFERENCE: FBC-2004 FUEL GAS | | | | ****FROM THE PREVIOUS REVIEW: | | | | 1. THE FOLLOWING INFORMATION IS REQUIRED FOR THE | | SEPARATE GAS PERMIT: | | | | A. OK | | | | B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | ****RESPONSE NOTED, NOT ADDRESSED | | | | C. N/A | | D. N/A | | E. OK | | | | ****NEW COMMENT: | | | | 1B. 1" PIPE AND VALVE ARE REQUIRED TO THE APPLIANCES | | WITH 105 CFH AND 108 CFH PER TABLE 402.4(2). | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2007-02-08 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-02-08 |
Time |
14:14 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-02-08 |
Time |
14:14 |
Sent To |
|
|
Notes |
2007-02-08 14:15:04 | DENIED | | REFERENCE: FBC-2004 FUEL GAS | | | | 1. THE FOLLOWING INFORMATION IS REQUIRED FOR THE | | SEPARATE GAS PERMIT: | | | | A. TYPE OF GAS, (LP OR NATURAL). | | | | B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | C. CLEARLY SHOW THE LOCATION AND CAP- | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | OR ASME), THE DISTANCE OF THE TANK FROM | | THE BUILDING AND ADJACENT PROPERTY LINES | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | INGS, AND THE LOCATION OF ANY BUILDING | | OPENINGS BELOW THE RELIEF VALVE OF THE | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | | D. CLEARLY INDICATE ON THE PLAN IF THE | | LP TANK IS ABOVE OR BELOW GROUND, AND | | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES | | PER NFPA 58. IF THE TANK | | IS BELOW GROUND THE CONTAINER SHALL BE | | SECURILY ANCHORED PER NFPA 58 SECTION | | 3-2.2.7(H). | | | | E. WHERE WET GAS EXISTS, A DRIP SHALL BE PROVIDED AT | | ANY POINT IN THE LINE OF PIPE WHERE CONDENSATE COULD | | COLLECT. (SEE THE W/H). SECTION 408.2. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2007-09-13 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-09-13 |
Time |
08:57 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-09-13 |
Time |
08:57 |
Sent To |
|
|
Notes |
2007-09-18 08:26:38 | TO "BOB"#2 | 2007-09-13 08:57:47 | WAITING FOR "BOB" |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2007-07-12 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-07-12 |
Time |
16:06 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-07-12 |
Time |
16:06 |
Sent To |
|
|
Notes |
2007-07-24 10:38:14 | TO "COMM" BD#46 | 2007-07-12 16:07:13 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2007-05-24 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-05-24 |
Time |
13:55 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-05-24 |
Time |
13:55 |
Sent To |
|
|
Notes |
2007-06-14 13:49:12 | TO "COMM" BD#19 | 2007-05-24 13:55:15 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-03-26 |
|
|
Cont ID |
|
Sent By |
mmiller |
Date |
2007-03-26 |
Time |
18:53 |
Rev Time |
0.00 |
Received By |
mmiller |
Date |
2007-03-26 |
Time |
18:53 |
Sent To |
|
|
Notes |
2007-03-26 18:54:01 | SENT TO BOB # 34 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-02-20 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-02-20 |
Time |
13:50 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-01-09 |
Time |
17:55 |
Sent To |
|
|
Notes |
2007-01-22 08:31:28 | TO "COMM" BD#18 | 2007-01-09 17:55:51 | WAITING FOR "COMM" BD |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
N |
Date |
2007-06-20 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-06-20 |
Time |
16:08 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-06-20 |
Time |
16:00 |
Sent To |
|
|
Notes |
2007-06-20 16:08:21 | NO REVIEW. MECH PLANS PASSED PREVIOUS REVIEW. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2007-04-23 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-04-23 |
Time |
17:01 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-04-23 |
Time |
16:49 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2007-02-13 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-02-13 |
Time |
07:58 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-02-13 |
Time |
07:58 |
Sent To |
|
|
Notes |
2007-02-13 08:08:13 | --------------DENIED-------------- | | | | 1. ROOM 104 SHOWS R/A GRILL IN CEILING WITH NO DUCT | | BACK TO AHU 1. IS THIS TO BE A CEILING PLENUM AREA? | | THIS APPEARS TO BE A DUCTED RETURN SYSTEM. PLEASE | | CLARIFY, SHOWING THE BALANCED RETURN REQUIREMENTS OF | | FBC,M 601.4. PLEASE NOTE: A GAS WATER HEATER VENT SHALL | | NOT BE ROUTED THROUGH A PLENUM PER FBC,M 601.3. | | | | 2. R/A GRILL IN CEILING OF ROOM 106 WHICH IS DUCTED | | BACK TO AHU 1, DUCT SIZE IS MISSING FROM PLAN. PLEASE | | CLARIFY PER FBC 106.1.1. | | | | 3. AUXILIARY DRAIN PAN WITH SECONDARY DRAIN LINE SHALL | | DISCHARGE IN A CONSPICUOUS LOCATION PER FBC,M | | 307.2.3(1). PLEASE PROVIDE DETAIL TO SHOW COMPLIANCE | | WITH THIS REQUIREMENT. | | | | 4. AHU MOUNTING DETAIL REFERS TO PLUMBING DRAWING FOR | | LOCATION OF CONDENSATE DISPOSAL. NO SUCH INFORMATION | | COULD BE FOUND ON PLUMBING DRAWINGS. PLEASE PROVIDE | | INFORMATION NEEDED TO SHOW COMPLIANCE WITH ALL OF | | SECTION 307.2. | | | | 5. ACTUATION OF A DUCT SMOKE DETECTOR SHALL ACTIVATE AN | | AUDIBLE AND VISUAL SIGNAL (HORN AND STROBE) IN AN | | APPROVED LOCATION PER FBC,M 606.4.1(2). | | | | 6. SEPERATE PERMITS/APPLICATIONS ARE REQUIRED FOR | | KITCHEN HOOD, HOOD SUPPRESSION AND WALK-IN | | COOLER/FREEZER. | | | | REVIEWED BY: | | RONALD J REGUEIRO | | 561-805-6734 | | [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2007-07-31 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2007-07-31 |
Time |
14:46 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2007-07-31 |
Time |
14:46 |
Sent To |
G |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2007-07-06 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-07-06 |
Time |
17:12 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-07-06 |
Time |
17:12 |
Sent To |
|
|
Notes |
2007-07-06 17:27:44 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 BUILDING | | FBC-2004 FUEL GAS | | FBC-2004 CHAPTER 1 | | WEST PALM BEACH CITY CODE | | | | ***FROM PREVIOUS REVIEW: | | | | ********FROM PREVIOUS REVIEWS: | | | | 1. OK | | 2. OK | | 3. OK | | | | 4. 1 COPY OF THE TWO PAGE "SPECIFICATION WORKSHEETS" | | SHALL BE ATTACHED TO EACH SET OF PLANS STAMPED REVIEWED | | AND STAMPED BY DBPR PLAN REVIEW. | | ****NO RESPONSE, NOT ADDRESSED.--NOW THE REQUIRED | | SHEETS THAT WERE STAMPED BY DBPR HAVE BEEN REMOVED. | | EACH SET OF PLANS SHALL HAVE A DBPR STAMPED SHEET WITH | | THE TWO PAGE WORKSHEETS ATTACHED. | | ******RESPONSE NOTED FROM THE ENGINEER, BUT THIS HAS | | NOT BEEN ADDRESSED. I TALKED TO TONY BONO AND INDICATED | | THAT I WOULD TAKE CARE OF THIS "WORKSHEET" ISSUE, BUT | | SINCE THERE ARE OTHER COMMENT RESPONSES TO BE ADDRESSED | | FOR THE GAS RESPONSE, AND WITH THE WORKLOAD WE HAVE, | | RATHER THAN SLOW DOWN OUR PROCESS, I LEFT THIS | | REQUIREMENT TO THE CONTRACTOR TO ADDRESS. | | | | 5. THE EXISTING GREASE INTERCEPTOR SHALL BE INSPECTED, | | APPROVED, AND SIZED BY ENVIRONMENTAL COMPLIANCE. PLEASE | | CONTACT LYNN MASSON, ENVIRONMENTAL COMPLIANCE MANAGER. | | (561) 822-2271, FAX (561) 722-2279, OR E-MAIL | | [email protected]. WASTE ORD. #3434. | | ****RESPONSE NOTED. SUBJECT NOT ADDRESS. I WILL TRY TO | | GET THE INFORMATION FROM THE ENVIRONMENTAL COMPLIANCE | | MANAGER. | | ******STILL WAITING FOR SOME RESPONSE ON THIS ISSUE. | | | | 6. THE FOLLOWING INFORMATION IS REQUIRED FOR THE | | SEPARATE GAS PERMIT: | | | | A. OK | | | | B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | ****RESPONSE NOTED, NOT ADDRESSED. | | ********RESPONSE NOTED, BUT 4 OUT OF 6 GAS APPLIANCES | | HAVE ONLY A COVER SHEET FROM THE SUPPLIER AND NOT THE | | MANUF. SHEETS AS REQUESTED. THE MANUF. SHEETS ARE | | REQUIRED FOR ITEMS MARK G2, G6, G7 & G8 SHOWING A | | LISTING, INDICATE MODEL NUMBER, AND SHOW THE BTU LOAD | | THAT CORRELATES WITH THE PLUMBING SERVICE SCHEDULE AND | | THE GAS RISER DIAGRAM. | | | | C. N/A | | D. N/A | | E. OK | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2007-04-25 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-04-25 |
Time |
18:03 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-04-25 |
Time |
18:03 |
Sent To |
|
|
Notes |
2007-04-25 18:29:28 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 BUILDING | | FBC-2004 FUEL GAS | | FBC-2004 CHAPTER 1 | | WEST PALM BEACH CITY CODE | | | | ***FROM PREVIOUS REVIEW: | | | | 1. OK | | 2. OK | | | | 3. SHT P-1 THE SANITARY RISER DIAGRAM DOES NOT MEET | | CODE REQUIREMENTS. VENTS ARE REQUIRED FOR THE MOP SINK, | | THE WOMEN'S TOILET ROOM LAV, AND THE 2ND HAND SINK. | | SECTION 901.2.1. THE 3RD HAND SINK REQUIRED BY DBPR | | REVIEW NOTES SHALL BE SHOWN ON THE RISER DIAGRAM. | | SECTION 106.1.1.--THE DISHWASHER SHALL CONNECT TO | | SANITARY, NOT THE GREASE DRAIN AS SHOWN. MUNICIPAL CODE | | SECTION 90-124(7)(B). | | ****RESPONSE NOTED, BUT THE SANITARY RISER DIAGRAM DOES | | NOT SHOW THE ADDED FLOOR SINK FOR THE DISHWASHER. ALSO | | A VENT IS REQUIRED WITHIN 10 FEET OF THE TRAP PER TABLE | | 906.1.--THE GREASE RISER DIAGRAM STILL SHOWS THE | | FLOOR SINK FOR THE DISHWASHER AND DOES NOT SHOW THE | | HAND SINK ADDED. PLEASE CORRELATE THE FLOOR PLAN AND | | RISER DIAGRAM INFORMATION. | | | | 4. 1 COPY OF THE TWO PAGE "SPECIFICATION WORKSHEETS" | | SHALL BE ATTACHED TO EACH SET OF PLANS STAMPED REVIEWED | | AND STAMPED BY DBPR PLAN REVIEW. | | ****NO RESPONSE, NOT ADDRESSED.--NOW THE REQUIRED | | SHEETS THAT WERE STAMPED BY DBPR HAVE BEEN REMOVED. | | EACH SET OF PLANS SHALL HAVE A DBPR STAMPED SHEET WITH | | THE TWO PAGE WORKSHEETS ATTACHED. | | | | 5. THE EXISTING GREASE INTERCEPTOR SHALL BE INSPECTED, | | APPROVED, AND SIZED BY ENVIRONMENTAL COMPLIANCE. PLEASE | | CONTACT LYNN MASSON, ENVIRONMENTAL COMPLIANCE MANAGER. | | (561) 822-2271, FAX (561) 722-2279, OR E-MAIL | | [email protected]. WASTE ORD. #3434. | | ****RESPONSE NOTED. SUBJECT NOT ADDRESS. I WILL TRY TO | | GET THE INFORMATION FROM THE ENVIRONMENTAL COMPLIANCE | | MANAGER. | | | | 6. THE FOLLOWING INFORMATION IS REQUIRED FOR THE | | SEPARATE GAS PERMIT: | | | | A. OK | | | | B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | ****RESPONSE NOTED, NOT ADDRESSED | | | | C. N/A | | D. N/A | | E. OK | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2007-02-08 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-02-08 |
Time |
12:34 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-02-07 |
Time |
16:55 |
Sent To |
|
|
Notes |
2007-02-08 14:13:56 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 BUILDING | | FBC-2004 FUEL GAS | | FBC-2004 CHAPTER 1 | | WEST PALM BEACH CITY CODE | | | | 1. COVER SHEET INDICATES THAT THE KITCHEN AREA IS | | 1,313SF, THE DINING UNCONCENTRATED 210SF, AND THE | | DINING FIXED SEATING 107SF. THIS TOTALS 1,630SF. THE | | FLOOR PLAN SHT A-1 AND THE APPLICATION INDICATE A GROSS | | SF OF 3,511SF, WHICH LEAVES 1,941 SF UNACCOUNTED FOR. | | PLEASE CLARIFY. PLEASE CONFIRM THE MINIMUM REQUIREMENTS | | PER TABLES 1004.1.2 AND 403.1. INDICATE ALL | | OCCUPANCIES, (STORAGE, BUSINESS ETC.), THAT MAY BE | | LOCATED WITHIN THE RESTURANT. PLEASE KEEP IN MIND THAT | | POTTY PARITY MAY BE REQUIRED DEPENDING ON THE NUMBER OF | | WATER CLOSETS/URINALS REQUIRED IN THE MEN'S TOILET | | ROOM. SECTION 403.1.1. | | | | 2. SHT A-3 (49 SEATS NOT COUNTING THE BENCH SEATING). | | INDICATE THE LENGTH OF EACH BENCH. PER SECTION 1004.7, | | THE OCCUPANT LOAD OF SEATING BOOTHS SHALL BE BASED ON | | ONE PERSON FOR EACH 24 INCHES OF BOOTH SEAT LENGTH | | MEASURED AT THE BACKREST OF THE SEATING BOOTH. | | | | 3. SHT P-1 THE SANITARY RISER DIAGRAM DOES NOT MEET | | CODE REQUIREMENTS. VENTS ARE REQUIRED FOR THE MOP SINK, | | THE WOMEN'S TOILET ROOM LAV, AND THE 2ND HAND SINK. | | SECTION 901.2.1. THE 3RD HAND SINK REQUIRED BY DBPR | | REVIEW NOTES SHALL BE SHOWN ON THE RISER DIAGRAM. | | SECTION 106.1.1.--THE DISHWASHER SHALL CONNECT TO | | SANITARY, NOT THE GREASE DRAIN AS SHOWN. MUNICIPAL CODE | | SECTION 90-124(7)(B). | | | | 4. 1 COPY OF THE TWO PAGE "SPECIFICATION WORKSHEETS" | | SHALL BE ATTACHED TO EACH SET OF PLANS STAMPED REVIEWED | | AND STAMPED BY DBPR PLAN REVIEW. | | | | 5. THE EXISTING GREASE INTERCEPTOR SHALL BE INSPECTED, | | APPROVED, AND SIZED BY ENVIRONMENTAL COMPLIANCE. PLEASE | | CONTACT LYNN MASSON, ENVIRONMENTAL COMPLIANCE MANAGER. | | (561) 822-2271, FAX (561) 722-2279, OR E-MAIL | | [email protected]. WASTE ORD. #3434. | | | | 6. THE FOLLOWING INFORMATION IS REQUIRED FOR THE | | SEPARATE GAS PERMIT: | | | | A. TYPE OF GAS, (LP OR NATURAL). | | | | B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | C. CLEARLY SHOW THE LOCATION AND CAP- | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | OR ASME), THE DISTANCE OF THE TANK FROM | | THE BUILDING AND ADJACENT PROPERTY LINES | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | INGS, AND THE LOCATION OF ANY BUILDING | | OPENINGS BELOW THE RELIEF VALVE OF THE | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | | D. CLEARLY INDICATE ON THE PLAN IF THE | | LP TANK IS ABOVE OR BELOW GROUND, AND | | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES | | PER NFPA 58. IF THE TANK | | IS BELOW GROUND THE CONTAINER SHALL BE | | SECURILY ANCHORED PER NFPA 58 SECTION | | 3-2.2.7(H). | | | | E. WHERE WET GAS EXISTS, A DRIP SHALL BE PROVIDED AT | | ANY POINT IN THE LINE OF PIPE WHERE CONDENSATE COULD | | COLLECT. (SEE THE W/H). SECTION 408.2. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2007-09-21 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2007-09-21 |
Time |
13:58 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2007-09-21 |
Time |
13:58 |
Sent To |
|
|
Notes |
2007-09-21 13:58:59 | *ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK | | DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE. |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |