Plan Review Details - Permit 07010350
Plan Review Stops For Permit 07010350 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2007-02-05 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-02-05 |
Time |
10:57 |
Rev Time |
0.33 |
Received By |
btrobaug |
Date |
2007-02-05 |
Time |
10:54 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2007-01-08 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-01-08 |
Time |
12:41 |
Rev Time |
0.33 |
Received By |
btrobaug |
Date |
2007-01-08 |
Time |
12:28 |
Sent To |
I |
|
Notes |
2007-01-08 12:41:53 | | | | | DENIED/INCOMPLETE INFORMATION | | | | 1} INDICATE THE SIZE OF THEGROUNDING CONDUCTOR PER | | 250.122, AND THE NUMBER OF UNGROUNDED CONDUCTORS. | | | | 2} INDICATE HOW THE CONDUI AND JUNCTION BOX IS TO BE | | SUPPORTED PER 300.11. | | | | 3} INDICATE THE SIZE OF THE "PVC" JUNCTION BOX SHOWN ON | | THE PLAN PER 314.16. | | | | 4} THE PRIMMARY PERMIT THAT WAS REFERENCED #06031385, | | WAS ISSUED FOR THE EXACT CHANGE OUT OF TWO ROOFTOP | | UNITS.INDICATE ON A SITE PLAN WHICH UNIT THIS | | APPLICATION IS REFERENCING. | | | | NOTE : THE DISCONNECT MUST NOT INTERFERE WITH THE | | REMOVAL OF SERVICE PANELS. | | | | THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2. FBC. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW. | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-02-05 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-02-05 |
Time |
09:19 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-02-05 |
Time |
09:19 |
Sent To |
E |
|
Notes |
2007-02-05 09:19:42 | TO "BTROBAUG" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-01-08 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-01-08 |
Time |
12:42 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-01-05 |
Time |
12:56 |
Sent To |
PC |
|
Notes |
2007-01-05 12:56:25 | TO "E" BOX |
|
|
|