Plan Review Details - Permit 07010350
Plan Review Stops For Permit 07010350
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-02-05 Cont ID  
Sent By btrobaug Date 2007-02-05 Time 10:57 Rev Time 0.33
Received By btrobaug Date 2007-02-05 Time 10:54 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-01-08 Cont ID  
Sent By btrobaug Date 2007-01-08 Time 12:41 Rev Time 0.33
Received By btrobaug Date 2007-01-08 Time 12:28 Sent To I
Notes
2007-01-08 12:41:53 
  
 DENIED/INCOMPLETE INFORMATION
  
 1} INDICATE THE SIZE OF THEGROUNDING CONDUCTOR PER
 250.122, AND THE NUMBER OF UNGROUNDED CONDUCTORS.
  
 2} INDICATE HOW THE CONDUI AND JUNCTION BOX IS TO BE
 SUPPORTED PER 300.11.
  
 3} INDICATE THE SIZE OF THE "PVC" JUNCTION BOX SHOWN ON
 THE PLAN PER 314.16.
  
 4} THE PRIMMARY PERMIT THAT WAS REFERENCED #06031385,
 WAS ISSUED FOR THE EXACT CHANGE OUT OF TWO ROOFTOP
 UNITS.INDICATE ON A SITE PLAN WHICH UNIT THIS
 APPLICATION IS REFERENCING.
  
 NOTE : THE DISCONNECT MUST NOT INTERFERE WITH THE
 REMOVAL OF SERVICE PANELS.
  
 THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2. FBC.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-02-05 Cont ID  
Sent By adarroug Date 2007-02-05 Time 09:19 Rev Time 0.00
Received By adarroug Date 2007-02-05 Time 09:19 Sent To E
Notes
2007-02-05 09:19:42TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-08 Cont ID  
Sent By btrobaug Date 2007-01-08 Time 12:42 Rev Time 0.00
Received By btrobaug Date 2007-01-05 Time 12:56 Sent To PC
Notes
2007-01-05 12:56:25TO "E" BOX