Plan Review Details - Permit 07010051
Plan Review Stops For Permit 07010051
Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2008-08-06 Cont ID  
Sent By mawillia Date 2008-08-06 Time 13:13 Rev Time 0.00
Received By mawillia Date 2008-08-06 Time 12:47 Sent To  
Notes
2008-08-06 12:53:06*****REVISION #1, DATED 07/23/2008, APPROVED*****
  
  
 THE REVISED PLAN SHEET FP-1 STAMPED, INITIALED, AND
 DATED BY THIS WRITER.

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2008-04-15 Cont ID  
Sent By mawillia Date 2008-04-15 Time 16:22 Rev Time 0.00
Received By mawillia Date 2008-04-15 Time 16:02 Sent To  
Notes
2008-04-15 16:09:30*****REVISION, DATED 04/11/2008, APPROVED*****
  
  
 THE REVISED PLAN SHEET FP-5 AND FP-7 WERE STAMPED,
 INITIALED, AND DATED BY THIS WRITER.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-10-30 Cont ID  
Sent By mawillia Date 2007-10-30 Time 11:40 Rev Time 0.00
Received By mawillia Date 2007-10-30 Time 09:58 Sent To  
Notes
2007-10-30 11:40:14*****REVISIONAPPROVED*****
  
 THE REVISED PLAN SHEET FP-5 STAMPED, INITIALED, AND
 DATED BY THIS WRITER.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-04-30 Cont ID  
Sent By mawillia Date 2007-04-30 Time 15:51 Rev Time 0.00
Received By mawillia Date 2007-04-30 Time 14:50 Sent To  
Notes
2007-04-30 15:11:13*****REVISIONS APPROVED*****
  
 THESE REVISED PLANS WERE ACTUALLY REVIEWED BY FIRE
 MARSHAL MIKE CARSILLO; PLAN SHEETS FP-1 THRU FP-10 WERE
 STAMPED, INITIALED, AND DATED BY THIS WRITER.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-02-12 Cont ID  
Sent By mawillia Date 2007-02-12 Time 16:03 Rev Time 0.00
Received By mawillia Date 2007-02-12 Time 16:03 Sent To  
Notes
2007-02-12 16:15:16*****APPROVED W/PROVISO******
 AS AGREED UPON AT A MEETING WITH FIRE MARSHAL MIKE
 CARSILLO ON 02/02/2007, REVISED DRAWINGS SHOWING FIRE
 SPRINKLER HEADSINSTALLED AT THE TOP AND BOTTOM OF
 DRYER EXHAUST DUCT WILL BE SUBMITTED BY CONTRACTOR.
 MECHANICAL GUARDS WILL BE REQUIRED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-02-03 Cont ID  
Sent By mawillia Date 2007-02-03 Time 15:32 Rev Time 0.00
Received By mawillia Date 2007-02-03 Time 15:32 Sent To  
Notes
2007-02-03 16:00:11*****DENIED*****
  
  
  
 1.AS AGREED UPON AT MEETING WITH FIRE MARSHAL MIKE
 CARSILLO ON 02/02/2007, FIRE SPRINKLER HEADS WILL BE
 INSTALLED AT THE TOP AND BOTTOM OF DRYER EXHAUST DUCT.
 MECHANICAL GUARDS WILL BE REQUIRED.DRAWINGS NEED TO
 REFLECT THESE INSTALLATIONS.
  
 2.AS PER FLORIDA STATUTES 471.023 AND FLORIDA
 ADMINISTRATIVE CODES61G15-23.002:THE PRINTED NAME,
 PRINTED PE NUMBER, AND THE CERTIFICATE OF AUTHORIZATION
 NUMBER IS NEEDED ON ALL THE TITLE BLOCKS.
  
  
 PLEASE BE ADVISED THAT ONLY THREE (3) SETS OF PLANS AND
 HYDRAULIC CALCULATIONS WILL BE PROCESSED BY THIS
 OFFICE.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-07-24 Cont ID  
Sent By adarroug Date 2008-07-24 Time 14:13 Rev Time 0.00
Received By adarroug Date 2008-07-24 Time 14:13 Sent To FIRE
Notes
2008-07-24 14:13:51TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-04-16 Cont ID  
Sent By adarroug Date 2007-04-16 Time 08:34 Rev Time 0.00
Received By adarroug Date 2007-04-16 Time 08:34 Sent To FIRE
Notes
2007-04-16 08:34:29TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-02-08 Cont ID  
Sent By adarroug Date 2007-02-08 Time 09:54 Rev Time 0.00
Received By adarroug Date 2007-02-08 Time 09:54 Sent To FIRE
Notes
2007-02-08 09:55:13TO "F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-03 Cont ID  
Sent By mawillia Date 2007-02-03 Time 15:33 Rev Time 0.00
Received By mawillia Date 2007-01-04 Time 12:29 Sent To  
Notes
2007-01-04 12:30:02TO "F" BOX