Plan Review Details - Permit 06120721
Plan Review Stops For Permit 06120721
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-12-29 Cont ID  
Sent By tgordon Date 2006-12-29 Time 08:29 Rev Time 0.00
Received By tgordon Date 2006-12-28 Time 14:10 Sent To  
Notes
2006-12-28 14:10:23TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-01-02 Cont ID  
Sent By tgordon Date 2007-01-02 Time 13:48 Rev Time 0.20
Received By tgordon Date 2007-01-02 Time 13:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-12-29 Cont ID  
Sent By tgordon Date 2006-12-29 Time 08:22 Rev Time 0.25
Received By tgordon Date 2006-12-29 Time 08:22 Sent To  
Notes
2006-12-29 08:29:05*** DENIED ***
 1) PLEASE SHOW LOCATION OF CONDENSER UNIT ON PLANS.
  
 2) 7"RETURN AIR TRANSFER DUCTS TO BEDROOMS NEED TO BE
 8".
 BALANCED RETURN AIR MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.