Plan Review Details - Permit 06120655
Plan Review Stops For Permit 06120655
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-01-05 Cont ID  
Sent By lmartine Date 2007-01-05 Time 10:17 Rev Time 0.00
Received By lmartine Date 2007-01-05 Time 10:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-12-26 Cont ID  
Sent By lmartine Date 2006-12-26 Time 17:22 Rev Time 0.00
Received By lmartine Date 2006-12-26 Time 17:22 Sent To  
Notes
2006-12-26 17:44:33 
  
 BUILDING REVIEW COMMENTS
 ------------ ------------ ----------------
  
  
 ASPHALT SHINGLES ARE APPROVED,
  
 PROVIDE RAS 117 CALCULATIONS FOR APPROVAL AS REQUIRED
 IN GENERAL LIMITATIONS #7 ON THE GAF BUILT-UP (NOA),
  
 THE MAXIMUM DESIGN PRESSURES ARE -45 AND -75 ON THE
 REPORT PROVIDED, TABLE 1609.6B, 2004 FBC REQUIRES -89
 PSF IN ZONE 3.
  
  
  
  
  
 L.MARTINEZ
 805-6710

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2006-12-22 Cont ID  
Sent By swurafti Date 2006-12-22 Time 13:42 Rev Time 0.00
Received By swurafti Date 2006-12-22 Time 13:42 Sent To  
Notes
2006-12-22 13:43:09HISTORIC APPROVED BY GJUDGE