Plan Review Details - Permit 06120649
Plan Review Stops For Permit 06120649
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-06-05 Cont ID  
Sent By mjacobs Date 2007-06-05 Time 06:37 Rev Time 0.00
Received By mjacobs Date 2007-06-04 Time 06:57 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-05-25 Cont ID  
Sent By mjacobs Date 2007-05-25 Time 13:27 Rev Time 0.00
Received By mjacobs Date 2007-05-25 Time 13:08 Sent To PC
Notes
2007-05-25 13:27:49BUILDING PLAN REVIEW
 PERMIT: 06120649
 ADD: 741 ROSELAND DR.
 CONT: SLATUR CONST.
 TEL: (561)317-8023
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 3RD
 ACTION: DENIED
  
 1)SEE NOTES FROM PREVIOUS REVIEW. PROVIDE TWO
 COMPLETE SETS OF DRAFTSMAN QUALITY DRAWINGS FOR THE
 PROJECT. THE DRAWINGS SHALL BE SIGN AND SEALED AND
 DATED BY THE RESPONSIBLE PERSON.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-03-28 Cont ID  
Sent By mjacobs Date 2007-03-28 Time 16:23 Rev Time 0.00
Received By mjacobs Date 2007-03-28 Time 15:01 Sent To PC
Notes
2007-03-28 16:23:51BUILDING PLAN REVIEW
 PERMIT:
 ADD:
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)NOW THE CARPORT IS REMOVED FROM THE SCOPE OF WORK,
 PROVIDE TWO SETS OF DRAFTSMAN QUALITY DRAWINGS SHOWING
 WHICH WINDOWS AND DOORS WILL BE CHANGED. IF THESE ITEMS
 ARE NON-IMPACT, THEN, HURRICANE PROTECTION WILL BE
 REQUIRED FOR EACH OPENIG. THE NOA SUBMITTED FOR THE
 WINDOW AND DOOR HAS NO IMPACT RATING.
  
 3)WPB AMENDMENTS. 106.1.3BUILDING PLANS SHALL BE
 DRAWIN TO A MINIMUM 1/8 SCALE UPON SUBSTANTIOAL PAPER.
 THE PLANS MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CLARITY. NO PENCIL DRAWINGS WILL BE ACCEPTED.
  
 4)INDICATE ON THE DRAWING THE SIZE OF EACH OPENING
 WHERE THE WINDOW OR DOOR WILL WILL BE CHANGED.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-02-14 Cont ID  
Sent By mjacobs Date 2007-02-14 Time 10:35 Rev Time 0.00
Received By mjacobs Date 2007-02-13 Time 12:22 Sent To PC
Notes
2007-02-13 13:31:54BUILDING PLAN REVIEW
 PERMIT:06120649
 ADD: 741 ROSELAND DR
 CONT: SLATUR CONST
 TEL: (954) 938-4500
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 3)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 ) NUMBER OF UNITS
 ) NUMBER OF FLOORS
 ) NUMBER OF ROOMS
 ) NUMBER OF BEDROOMS
 ) SQ. FT. LIV SPACE/ FL
 ) SQ. FT. FOOTPRINT
 ) SQ. FT. UNDER ROOF (TOTAL)
  
 4)106.1.2 ADDITIONAL DATA. THE
 BUILDING OFFICIAL MAY REQUIRE DETAILS, COMPUTATIONS,
 STRESS DIAGRAMS, AND OTHER
 DATA NECESSARY TO DESCRIBE THE
 CONSTRUCTION OR INSTALLATION AND THE
 BASIS OF CALCULATION. ALL DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 REQUIRED BY THE BUILDING OFFICIAL TO BE
 PREPARED BY AN ARCHITECT OR ENGINEER
 SHALL BE AFFIXED WITH THIER OFFICIAL
 SEAL, SIGNATURE AND DATE AS STATE LAW
 REQUIRES.
  
 5)WPB AMENDMENTS.106.1.3BUILDING PLANS SHALL BE
 DRAWN TO A MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL
 PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.THE BUILDING
 MAY ESTABLISH THROUGH DEPARTMENTAL POLICY, STANDARDS
 FOR PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE
 CONFORMITY TO ITS RECORD RETENTION PROGRAM.THIS
 POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE,
 CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORDS
 MANAGEMENTS. THE DRAWINGS SHALL BE DRAFTSMAN QUALITY.
 THE DRAWINGS SUBMITTED ARE NOT ACCEPTABLE.
  
 6)WILL THE CARPORT BE CONVERTED INTO A GARAGE OR
 LIVING SPACE?
  
 7)106.1.1CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILINDING OFFICIAL
  
 8)R309.1OPENINGS FROM A PRIVATE GARAGE DIRECTLY
 INTO A ROOM USED FOR SLEEPING PURPOSES SHALL NOT BE
 PERMITTED, OTHER OPENINGS BETWEEN THE GARAGE AND
 RESIDENCE SHALL BEEQUIPPED WITH SOLID WOOD DOORS NOT
 LESS THAN 1 3/8 INCHES IN THICKNESS, SOLID OR HONEYCOMB
 CORE STEEL DOORS NOT LESS THAN 1 3/8 INCHES THICK, OR
 20-MINUTE FIRE-RATED DOORS.
  
 9)R309.2THE GARAGE SHALL BE SEPERATED FROM THE
 RESIDENCE AND ITS ATTIC AREA BY NOT LESS THAN 1/2-INCH
 GYPSUM BOARD APPLIED TO THE GARAGE SIDE. GARAGES
 BENEATH HABITABLE ROOMS SHALL BE SEPERATED FROM ALL
 HABITABLE ROOMS ABOVE BY NOT LESS THAN 5/8-INCH TYPE X
 GYPSUM BOARD OR EQUIVALENT.WHERE THE SEPERATION IS A
 FLOOR-CEILING ASSEMBLY, THE STRUCTURE SUPPORTING THE
 SEPERATIION SHALL ALSO BE PROTECTED BY NOT LESS THAN
 1/2 INCH GYPSUM BOARD OR EQUIVALENT.
  
 10)R309.3THE AREA OF FLOOR USED FOR PARKING OF
 AUTOMOBILES OR OTHER VEHICLES SHALL BE SLOPED TO
 FACILICATE THE MOVEMENT OF LIQUIDS TO A DRAIN OR TOWARD
 THE MAIN VEHICLES SHALL BE SLOPED TO FACILITATE THE
 MOVEMENT OF LIQUIDS TO A DRAIN OR TOWARD THE MAIN
 VEHICLE ENTRY DOORWAY.
  
 11)106.3.3* PRODUCT APPROVALS- 2004
 THOSE PRODUCTS THAT ARE RGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. PROVIDE TWO SETS OF UPDATED
 PRODUCT APPROVALS FOR EACH PRODUCT. SUBMIT A
 WINDOW/DOOR SCHEDULE WITH THE SIZE OF EACH OPENING. ON
 A FLOOR PLAN INDICATE THE LOACTION OF EACH WINDOW OR
 DOOR OPENING.
  
 12)IF THIS AREA WILL BE USED FOR LIVING SPACE, THE
 FLOOR WILL HAVE TO CONFORM TO THE REQUIREMENTS OF
 R506.1CONCRETE SLAB-ON-GROUND FLOORS SHALL BE A
 MINIMUM 3.5 INCHES (89 MM) THICK (FOR EXPANSIVE SOILS,
 SEE SECTION R403.1.8 ). THE SPECIFIED COMPRESSIVE
 STRENGTH OF CONCRETE SHALL BE AS SET FORTH IN SECTION
 R402.2 .
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2007-05-18 Cont ID  
Sent By btrobaug Date 2007-05-18 Time 16:15 Rev Time 0.25
Received By btrobaug Date 2007-05-18 Time 16:07 Sent To P
Notes
2007-05-18 16:15:00 
  
  
  
 ELECTRICAL PERMIT #07020514 ISSUED FOR THIS WORK.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-03-21 Cont ID  
Sent By btrobaug Date 2007-03-21 Time 07:33 Rev Time 0.33
Received By btrobaug Date 2007-03-21 Time 07:27 Sent To M
Notes
2007-03-21 07:33:26 
  
  
  
 DENIED/INCOMPLETE INFORMATION
  
 SECOND REVIEW, SAME COMMENT AS FIRST REVIEW.
  
 THE APPLICATION INDICATES ELECTRICAL WORK IN THE
 DESCRIPTION. SUBMIT PLANS FOR REVIEW PER 106.3.5 AS
 AMMENDED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-01-09 Cont ID  
Sent By btrobaug Date 2007-01-09 Time 07:56 Rev Time 0.33
Received By btrobaug Date 2007-01-09 Time 07:47 Sent To P
Notes
2007-01-09 07:55:54 
  
 DENIED/INCOMPLETE INFORMATION
  
 THE APPLICATION INDICATEDS ELECTRICAL WORK IN THE
 DESCRIPTION. SUBMIT PLANS FOR REVIEW PER 106.3.5 AS
 AMMENDED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-05-11 Cont ID  
Sent By adarroug Date 2007-05-11 Time 13:18 Rev Time 0.00
Received By adarroug Date 2007-05-11 Time 13:18 Sent To E
Notes
2007-05-11 13:18:38TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-03-19 Cont ID  
Sent By adarroug Date 2007-03-19 Time 09:15 Rev Time 0.00
Received By adarroug Date 2007-03-19 Time 09:15 Sent To E
Notes
2007-03-19 09:16:12TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-03-12 Cont ID  
Sent By adarroug Date 2007-03-12 Time 11:36 Rev Time 0.00
Received By adarroug Date 2007-03-12 Time 11:36 Sent To Z
Notes
2007-03-12 11:36:33TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-01-02 Cont ID  
Sent By adarroug Date 2007-01-02 Time 16:24 Rev Time 0.00
Received By adarroug Date 2007-01-02 Time 16:24 Sent To E
Notes
2007-01-02 16:24:52TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-02-14 Time   Rev Time 0.00
Received By adarroug Date 2006-12-26 Time 14:36 Sent To  
Notes
2006-12-26 14:37:34TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2007-05-23 Cont ID  
Sent By tgordon Date 2007-05-23 Time 08:59 Rev Time 0.25
Received By tgordon Date 2007-05-23 Time 08:59 Sent To B
Notes
2007-05-23 09:00:58CUSTOMER HAS AN APPROVED MECHANICAL PERMIT #06111070
 WITH MECH. PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-03-26 Cont ID  
Sent By tgordon Date 2007-03-26 Time 11:14 Rev Time 0.25
Received By tgordon Date 2007-03-26 Time 11:14 Sent To P
Notes
2007-03-26 11:16:45*** DENIED ***
 1) AS NOTED IN LAST REVIEW 1-9-07.APPLICATION
 DESCRIBES (ADD A/C & HEAT),PLANS NEED TO BE SUBMITTED
 AT THIS TIME NOT AT A LATTER DATE. NO MECHANICAL A/C
 PLANS WERE SUBMITTED FOR REVIEW. PLEASE SUBMIT
 MECHANICAL A/C PLANS FOR REVIEW, PER 2004 FBC WPB
 AMEND. 106.3.5.4 (10).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-01-09 Cont ID  
Sent By tgordon Date 2007-01-09 Time 11:15 Rev Time 0.25
Received By tgordon Date 2007-01-09 Time 11:15 Sent To P
Notes
2007-01-09 11:20:54*** DENIED ***
 1) APPLICATION DESCRIBES ( ADD A/C & HEAT),PLANS NEED
 TO BE SUBMITTED AT THIS TIME NOT AT A LATTER DATE. NO
 MECHANICAL PLANS WERE SUBMITTED FOR REVIEW. PLEASE
 SUBMIT MECHANICAL PLANS
 FOR REVIEW, PER 2004 FBC WPB AMEND. 106.3.5.4 (10).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status N Date 2007-05-22 Cont ID  
Sent By mperson Date 2007-05-22 Time 16:47 Rev Time 0.33
Received By mperson Date 2007-05-22 Time 16:47 Sent To M
Notes
2007-05-22 16:50:22 
  
  
 PLUMBING PERMIT #07040409 ISSUED FOR THIS WORK.
  
 REVIEW BY MIKE PERSON
 PLUMBING PLAN REVIEW
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-03-26 Cont ID  
Sent By btrobaug Date 2007-05-18 Time 16:17 Rev Time 0.33
Received By mperson Date 2007-03-26 Time 13:38 Sent To B
Notes
2007-03-26 13:56:48DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 THE FOLLOWING INFORMATION IS STILL REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE DUE TO THE
 FACT THAT THE NOTICE OF COMMENCEMENT STATES "REFURBISH
 PLUMBING REMODEL INTERIOR":
  
 1.**NO** MORE INFORMATION IS REQUIRED:
 A} IF PLUMBING LAYOUT IS THE SAME
 WITH NO CHANGES, PLEASE INDICATE THIS ON
 THE DRAWING.
 B} IF PLUMBING LAYOUT IS THE
 SAME AND THE PLUMBING FIXTURES ARE TO BE
 CHANGED, PLEASE INDCATE ON THE DRAWING.
 "EXACT FIXTURE CHANGE OUT ONLY."
 C} IF THE NEW PROPOSED PLUMBING LAYOUT IS DIFFERENT
 FROM THE EXISTING PLEASE FOLLOW WHAT IS REQUIRED IN
 COMMENT #2.
  
 2.**NO** PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING
 ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT
 LOCATIONS.
  
 3.**NO** FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-01-09 Cont ID  
Sent By mperson Date 2007-01-09 Time 13:03 Rev Time 0.33
Received By mperson Date 2007-01-09 Time 13:03 Sent To B
Notes
2007-01-09 13:12:36DENIED
 REFERENCE: FBC-2004 PLUMBING AND FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS REQUIRED FOR PLUMBING PLAN
 REVIEW TO MEET CODE COMPLIANCE DUE TO THE FACT THAT THE
 NOTICE OF COMMENCEMENT STATES REFURBISH PLUMBING
 REMODEL INTERIOR:
  
 1. MORE INFORMATION REQUIRED. PLEASE
 INDICATE ON DRAWING EXISTING PLUMBING
 LAYOUT, AND ON A SEPERATE DRAWING
 INDICATE ON THAT DRAWING THE NEW PROPOSED
 PLUMBING LAYOUT. IF NEW PROPOSED
 PLUMBING LAYOUT IS DIFFERENT FROM
 EXISTING PLEASE FOLLOW WHAT IS REQUIRED
 IN #2. IF PLUMBING LAYOUT IS THE SAME
 WITH NO CHANGES, PLEASE INDICATE THIS ON
 THE DRAWING. IF PLUMBING LAYOUT IS THE
 SAME AND THE PLUMBING FIXTURES ARE TO BE
 CHANGED, PLEASE INDCATE ON DRAWING
 FIXTURE CHANGE OUT ONLY.
  
 2. PER FBC-2004 CHAPTER 1 SECTION 106.3.5.4 RESIDENTIAL
 (ONE AND TWO
 FAMILY) SUBMIT A PLUMBING SANITARY
 ISOMETRIC RISER DIAGRAM INDICATING ALL
 WASTE, VENTS, TRAPS WITH SIZES, AND
 CLEANOUT LOCATIONS.
  
 3. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop Z ZONING
Rev No 2 Status N Date 2007-03-16 Cont ID  
Sent By jroach Date 2007-03-16 Time 16:25 Rev Time 0.00
Received By jroach Date 2007-03-16 Time 16:25 Sent To I
Notes
2007-03-16 16:28:05***ZONING REVIEW NOT REQUIRED......INTERIOR WORK
 ONLY.....ENCLOSURE OF CARPORT REMOVED FROM THE PERMIT
 DESCRIPTION***
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-12-29 Cont ID  
Sent By mmclean Date 2006-12-29 Time 09:13 Rev Time 0.00
Received By mmclean Date 2006-12-29 Time 09:13 Sent To I
Notes
2006-12-29 09:46:47DENIED,
 1. SHALL PROVIDE TWO COPIES OF CURRENT SURVEYS SHOWING
 THE EXISTING CARPORT.
 2. SHALL PROVIDE THE SETBACK OF THE EXISTING CARPORT
 FROM SIDE PROPERTY LINE AND FRONT SETBACK.
 3. SHALL SHOW INTERIOR ACCESS OF THE ENCLOSED CARPORT
 INTO THE MAIN STRUCTURE.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720