Plan Review Details - Permit 06120640
Plan Review Stops For Permit 06120640
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-19 Cont ID  
Sent By mjacobs Date 2007-01-19 Time 11:06 Rev Time 0.00
Received By mjacobs Date 2007-01-19 Time 05:53 Sent To  
Notes
2007-01-19 06:57:45BUILDING PLAN REVIEW
 PERMIT: 06120640
 ADD: 10452 ORCHID RESERVE DR
 CONT: AGAPAO
 TEL: (561)622-8180
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.NOTE: 713.13(2) IF THE WORK DESCRIBED IN
 THE NOTICE OFCOMMENCEMENT IS NOT ACTUALLYCOMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE
 IS NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE
 NOTICE OF COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE
 THE FIRST INSPECTION.
  
 2)SUBMIT THE DCA APPROVED PLANS FOR THE TRAILER
 SHOWING ALL LIFE SAFETY/ELECTRICAL/PLUMBING AND
 STRUCTURAL INFORMATION. FBC. SEC 107.2 TEMPORARY
 STRUCTURES AND USES SHALL CONFORM TO THE STRUCTURAL
 STRENGTH, FOR SAFETY, MEANS OF EGRESS, ACCESSIBILITY,
 LIGHT, VENTILATION AND SANITARY REQUIREMENTS OF THIS
 CODE AS NECESSARY TO ENSURE THE PUBLIC HEALTH, SAFETY
 AND GENERAL WELFARE.
  
 3)FBC SEC 107.1 TEMPRARY SHALL BE LIMITED AS TO TIME
 OF SERVICE, BUT SHALL NOT BE PERMITTED FOR MORE THAN
 180 DAYS.
  
 4)PROVIDE ELEVATION DRAWINGS OF THE RAMP AND STAIRS
 SHOWING INDICATING ALL MENTIONS. ALL RAMPS SHALL COMPLY
 WITH FBC SEC. 11-4.7AND SEC.11-4.8
  
 5)11-4.5.1 GENERAL.
 GROUND AND FLOOR SURFACES ALONG ACCESSIBLE ROUTES AND
 IN ACCESSIBLE ROOMS AND SPACES INCLUDING FLOORS, WALKS,
 RAMPS, STAIRS, AND CURB RAMPS, SHALL BE STABLE, FIRM,
 SLIP-RESISTANT, AND SHALL COMPLY WITH SECTION 11-4.5 .
 SHELL ROCK WILL NOT MEET THIS REQUIREMENT.
  
 6)STAIRS AND LANDING PLATFORMS SHALL BE DESIGN TO FBC
 SEC 11-4.5.2. CHANGES IN LEVEL UP TO ? INCHES (6 MM)
 MAY BE VERTICAL AND WITHOUT EDGE TREATMENT [SEE FIGURE
 11-7 (C)]. CHANGES IN LEVEL BETWEEN ? INCH AND ? INCH
 (6 MM AND 13 MM) SHALL BE BEVELED WITH A SLOPE NO
 GREATER THAN 1:2 [SEE FIGURE 11-7 (D)]. CHANGES IN
 LEVEL GREATER THAN ? INCH (13 MM) SHALL BE ACCOMPLISHED
 BY MEANS OF A RAMP THAT COMPLIES WITH SECTION 11-4.7 OR
 11-4.8 .
  
 7) WPB AMENDMENTS 108.3THE CLAIM VALUE IS TO LOW.IF
 IN THE OPINION OF THE BUILDING OFFICIAL, THE CLAIMED
 VALUATION OF APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED. FOR PERMITTING
 PURPOSES,VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, NORMAL
 SITE WORK, ARCHITECTURAL AND DESIGNFEES, MARKETING
 COST, ORERHEAD AND PROFIT EXCLUDING LAND. OUR VALUATION
 REFERENCE IS ICC (BVD), MARSHALL-SWIFT AND MEANS COST
 ANALYSIS SERVICES.
  
 8)11-4.6.2 LOCATION.
 ACCESSIBLE PARKING SPACES SERVING A PARTICULAR BUILDING
 SHALL BE LOCATED ON THE SHORTEST SAFELY ACCESSIBLE
 ROUTE OF TRAVEL FROM ADJACENT PARKING TO AN ACCESSIBLE
 ENTRANCE. IN PARKING FACILITIES THAT DO NOT SERVE A
 PARTICULAR BUILDING, ACCESSIBLE PARKING SHALL BE
 LOCATED ON THE SHORTEST ACCESSIBLE ROUTE OF TRAVEL TO
 AN ACCESSIBLE PEDESTRIAN ENTRANCE OF THE PARKING
 FACILITY. IN BUILDINGS WITH MULTIPLE ACCESSIBLE
 ENTRANCES WITH ADJACENT PARKING, ACCESSIBLE PARKING
 SPACES SHALL BE DISPERSED AND LOCATED CLOSEST TO THE
 ACCESSIBLE ENTRANCES.
 EACH PARKING SPACE MUST BE NO LESS THAN 12 FEET (3658
 MM) WIDE.
 (1)ALL SPACES MUST BE LOCATED ON AN ACCESSIBLE
 ROUTE NO LESS THAN 44 INCHES (1118 MM)WIDE SO THAT
 USERS WILL NOT BE COMPELLED TO WALK OR WHEEL BEHIND
 PARKED VEHICLES.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
2007-01-18 16:46:52 
  
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2007-01-17 Cont ID  
Sent By btrobaug Date 2007-01-17 Time 13:11 Rev Time 0.30
Received By btrobaug Date 2007-01-17 Time 11:48 Sent To B
Notes
2007-01-17 13:11:53 
  
 NO ELECTRICAL CONTRACTOR SIGNED ON, NO ELECTRICAL PLANS
 SUBMITTED./WRT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-01-19 Cont ID  
Sent By mawillia Date 2007-01-19 Time 14:08 Rev Time 0.00
Received By mawillia Date 2007-01-19 Time 14:08 Sent To  
Notes
2007-01-19 15:30:15*****DENIED*****
  
  
 PLEASE BE ADVISED THAT THIS STRUCTURE SHALL BE
 CLASSIFIED AS A NEW BUSINESS OCCUPANCY.
  
  
 01.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE
 PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED.
  
 02.THE SET-UP OR ERECTING OPERATIONS FOR THE
 STRUCTURE SHALL NOTINTERFERE OR HINDER EMERGENCY
 RESPONSE ACCESS TO THE SAID PROPERTY OR VICINITY
 THEREOF (INCLUDING FIRE LANES).
  
 03.FIRE DEPARTMENT ACCESS ROADSSHALL BE CAPABLE OF
 SUPPORTING 32 TONS TO SUPPORT THE LOADS IMPOSED BY FIRE
 APPARATUS/FIRE EQUIPMENT AND SHALL BE PROVIDED WITH A
 SURFACE SUITABLE FOR ALL-WEATHER DRIVING CONDITIONS.
  
 04.FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN
 UNOBSTRUCTED WIDTH OF NOT LESS THAN 20' AND AN
 UNOBSTRUCTED VERTICAL CLEARANCE OF NOT LESS THAN 13'
 6IN".
  
 05.SHOW/DISPLAY THE NUMERICAL ADDRESS OF THE
 STRUCTURE ON THE PROPER EXTERIOR ELEVATION.AS PER
 WEST PALM BEACH CODE, THOSE NUMBERS SHALL BE NO LESS
 THAN 6" IN HEIGHT AND 1" IN WIDTH VISIBLE FROM THE
 STREET OR ROADSIDE FRONTING THE STRUCTURE.[THE
 APPLICABLE ADDRESS SHALL BE IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET].
  
 06.INDICATE ON SITE PLAN THE DISTANCE OF THE
 STRUCTURE TO THE NEAREST FIRE HYDRANT.PLEASE BE
 ADVISED THAT IF THIS DISTANCE IS GREATER THAN 500 FEET,
 AN ADDITIONAL FIRE HYDRANT MAY BE REQUIRED.
  
 07.WILL THE STRUCTURE HAVE A FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEM?IF SO, PLEASE PROVIDE A LAYOUT OF
 THE FIRE PROTECTION SYSTEM(S).
  
 08.WHAT IS THE MAXIMUM OCCUPANT LOAD FOR THE
 STRUCTURE?
  
 09.INDICATE THE LOCATION OF EXIT LIGHTS, EMERGENCY
 LIGHTS, AND FIRE EXTINGUISHER(S).
  
 10.PLEASE INDICATE THE LENGHT OF TIME THAT THIS
 TEMPORARY STRUCTURE WILL BE USED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED ON THE PLANS.
  
  
 MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-01-18 Cont ID  
Sent By adarroug Date 2007-01-18 Time 10:59 Rev Time 0.00
Received By adarroug Date 2007-01-18 Time 10:59 Sent To B
Notes
2007-01-18 10:59:53TO "MJACOBS" DESK/PER "RBROWN" DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-01-13 Cont ID  
Sent By adarroug Date 2007-01-13 Time 13:25 Rev Time 0.00
Received By adarroug Date 2007-01-13 Time 13:25 Sent To E
Notes
2007-01-13 13:27:56TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-01-18 Time   Rev Time 0.00
Received By adarroug Date 2006-12-26 Time 14:15 Sent To  
Notes
2006-12-26 14:15:59TO "Z" BOX

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-01-18 Cont ID  
Sent By mperson Date 2007-01-18 Time 09:52 Rev Time 0.33
Received By mperson Date 2007-01-18 Time 09:52 Sent To B
Notes
2007-01-18 10:14:01DENIED
 REFERENCE: FBC-2004 PLUMBING AND CITY OF WEST PALM
 BEACH AMENDMENTS TO FBC-2004, CHAPTER 1,
 ADMINISTRATION.
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PER FBC-2004 CHAPTER 1, SECTION 107, TEMPORARY
 STUCTURES AND USES. SECTION 107.2 CONFORMANCE.
 TEMPORARY STRUCTURES AND USES SHALL CONFORM TO THE
 SANITARY AND WATER REQUIREMENTS OF THIS CODE AS
 NECESSARY TO ENSURE THE PUBLIC HEALTH, SAFETY AND
 GENERAL WELFARE.
  
 2. REQUIREMENTS: SITE PLAN INDICATING TRAILER LOCATION.
 TYPE OF PLUMBING HOOK-UP. IF WATER, INDICATE BACKFLOW
 LOCATION. IF SANITARY HOOK-UP AN ISOMETRIC SANITARY
 RISER DIAGRAM WITH SIZES REQUIRED. IF SANITARY
 DISCHARGES INTO A HOLDING TANK, PALM BEACH COUNTY
 HEALTH DEPARTMENT APPROVAL REQUIRED.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop Z ZONING
Rev No 1 Status F Date 2007-01-10 Cont ID  
Sent By lfranco Date 2007-01-10 Time 17:03 Rev Time 0.00
Received By MCRUZ Date 2007-01-10 Time 17:19 Sent To  
Notes
2007-01-10 17:02:34PLANNING AND ZONING: **FAILED**
  
 1.PROVIDE RESPONSE TO COMMENTS IN WRITING.
  
 2.THIS PROJECT IS PART OF THE IBIS COMMERCIAL PLANNED
 DEVELOPMENT (CPD).PER ORDINANCE NO. 2403-90, FINAL
 BUILDING PERMIT APPROVAL IS CONTINGENT UPON A MINOR
 AMENDMENT APPROVAL.APPLICANT SHALL BE REQUIRED TO
 FILE A DEVELOPMENT APPLICATION WITH THE PLANNING AND
 ZONING DEPARTMENT FOR A MINOR AMENDMENT TO THE CPD FOR
 THE PROPOSED TRAILER LOCATION AND PARKING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME.
  
 MARGARITA CRUZ
 ASSOCIATE PLANNER, PLANNING AND ZONING DEPARTMENT
 OFFICE - 561-822-1444