Plan Review Details - Permit 06120605
Plan Review Stops For Permit 06120605 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2006-12-26 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2006-12-26 |
Time |
08:47 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2006-12-26 |
Time |
08:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2006-12-22 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-12-22 |
Time |
13:15 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-12-22 |
Time |
13:15 |
Sent To |
|
|
Notes |
2006-12-22 13:20:38 | **** PLANS REDLINED FOR THE FOLLOWING COMMENTS. | | ** PLANS ALSO ROUTED TO ROBERT BROWN. | | | | | | *MISSINGGFI ON KITCHEN COUNTERSPACE, 210.52C1, 210.8 | | * BATH CIRCUIT PER 210.52D, 210.11C3, #12/20A. | | * SD/SA'S PER NFPA-72 11.5.1, MISSING DOWNSTAIRS SMOKE | | DEVICE, FBC R313 | | 2005 NEC. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2006-12-26 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2006-12-26 |
Time |
08:47 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2006-12-22 |
Time |
08:45 |
Sent To |
|
|
Notes |
2006-12-22 13:59:07 | | | | | ROUTED TO MIKE PERSON DESK FOR PLUMBING REVIEW. | | | 2006-12-22 08:45:46 | TO "Z" BOX |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2006-12-22 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2006-12-22 |
Time |
15:20 |
Rev Time |
0.33 |
Received By |
mperson |
Date |
2006-12-22 |
Time |
15:20 |
Sent To |
B |
|
Notes |
2006-12-22 15:34:10 | ****************PROVISO**************** | | A} SHEET A-1 NOTE #15 STATES WATER HEATER TO BE REMOVED | | AND CAP PLBG. SERVICE LINES. PER FBC-2004 PLUMBING, | | SECTION 607.1 HOT WATER IS REQUIRED AND A SEPERATE | | PERMIT WILL BE REQUIRED TO ADD HOT WATER AT LATER | | DATE. | | B} PER TABLE 403.1, 1 AUTOMATIC CLOTHES WASHER | | CONNECTION PER DWELLING UNIT REQUIRED. IF ONE IS | | REQUIRED A SEPERATE PERMIT WILL BE REQUIRED AT A LATER | | DATE. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2006-12-26 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2006-12-26 |
Time |
08:48 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2006-12-26 |
Time |
08:48 |
Sent To |
|
|
Notes |
2006-12-26 08:49:54 | INTERIOR WORK ONLY, REVIEW NOT REQUIRED. |
|
|
|