Plan Review Details - Permit 06120593
Plan Review Stops For Permit 06120593
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-04-12 Cont ID  
Sent By jwitmer Date 2007-04-12 Time 08:57 Rev Time 1.11
Received By jwitmer Date 2007-04-12 Time 08:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-22 Cont ID  
Sent By jwitmer Date 2007-01-22 Time 16:28 Rev Time 1.22
Received By jwitmer Date 2007-01-22 Time 16:01 Sent To  
Notes
2007-01-22 16:53:01BUILDING PLAN REVIEW
 PERMIT: 06120593
 ADD: 444 W. RAILROAD SUITE 440
 CONT: PBM DEVELOPMENT
 TEL: (561)715-1800
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) PBM DEVELOPMENT IF ACTING AS AN ARCHITECTURAL FIRM
 WILL REQUIRE A CERTIFICATE OF AUTHORIZATION.
 FAC 481.219(2)(3).
  
 3) SHEET A-08 KITHEN DETAIL INDICATES THE USE OF A
 KITHEN SINK. SINKS:
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES
 (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4
 SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD
 APPROACH.
 THE CLEAR FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE
 AND
 SHALL EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH
 THE SINK.
  
 4) NOTE: THE PLANS , VARIOUS WALL SECTIONS INDICATE THE
 USE
 OF CROWN MOLDING, THE TYPE OF MATERIAL IS NOT INDICATED
 ON THE PLAN ,
 2604.2 INTERIOR TRIM.
 FOAM PLASTIC USED AS INTERIOR TRIM SHALL COMPLY WITH
 SECTIONS 2604.2.1 THROUGH 2604.2.4 .
  
 2604.2.1 DENSITY.
 THE MINIMUM DENSITY OF THE INTERIOR TRIM SHALL BE 20
 PCF (320 KG/M 3 ).
  
 2604.2.2 THICKNESS.
 THE MAXIMUM THICKNESS OF THE INTERIOR TRIM SHALL BE 0.5
 INCH (12.7 MM) AND THE MAXIMUM WIDTH SHALL BE 8 INCHES
 (204 MM).
  
 2604.2.3 AREA LIMITATION.
 THE INTERIOR TRIM SHALL NOT CONSTITUTE MORE THAN 10
 PERCENT OF THE AGGREGATE WALL AND CEILING AREA OF ANY
 ROOM OR SPACE.
  
 2604.2.4 FLAME SPREAD.
 THE FLAME SPREAD INDEX SHALL NOT EXCEED 75 WHERE TESTED
 IN ACCORDANCE WITH ASTM E 84. THE SMOKE-DEVELOPED INDEX
 SHALL NOT BE LIMITED.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-04-24 Cont ID  
Sent By dpalmer Date 2007-04-24 Time 14:39 Rev Time 0.00
Received By dpalmer Date 2007-04-24 Time 14:12 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-04-12 Cont ID  
Sent By dpalmer Date 2007-04-12 Time 08:45 Rev Time 0.00
Received By dpalmer Date 2007-04-12 Time 08:31 Sent To  
Notes
2007-04-12 08:45:42** UNSAT **
  
 1) NOTE: PLEASE SEE THE NEW REVISED ENERGY CALCULATIONS
 ARE NOT SEALED BY THE ENGINEER OF RECORD AS REQUIRED
 PER 13-103.1.1.1
 PLEASE SUBMIT SIGNED, DATED AND SEALED. FS 471.025
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-04-04 Cont ID  
Sent By dpalmer Date 2007-04-04 Time 15:51 Rev Time 0.00
Received By dpalmer Date 2007-04-04 Time 15:50 Sent To  
Notes
2007-04-04 15:51:21 
 ** UNSAT 2ND REVIEW **
  
 1) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEW. THE
 ENERGY CALCULATIONS AND/OR PERFORMANCE DENSITIES WERE
 NOT SHOWN IN COMPLIANCE. PLEASE SEE THE TYPE, AND
 AMOUNT OF FIXTURES, WATTAGE(S) ETC AS SHOWN ON PLANS DO
 NOT CORRELATE WITH THE ENERGY CALCULATIONS SUBMITTED.
 PLEASE ADJUST AND REVISE 13-415.1.AB.1.1, 13-415.2
 PLEASE SEE THE METHOD OF CONTROL FOR LIGHTING ON ENERGY
 CALCULATIONS NEEDS TO CORRELATE WITH PLANS.
 (AUTOMATED/OCCUPANCY/TIMERS ETC).
  
 2) NOTE: PLEASE SEE THAT NO HAND DRAWN CHANGES ARE
 PERMITTED ON PLANS.
 PLEASE BE SURE TO STATE THE MAXIMUM TIMES FOR OCCUPANCY
 TYPE DEVICES ON PLANS.
 13-415.1.ABC.1.1
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-01-12 Cont ID  
Sent By dpalmer Date 2007-01-12 Time 11:42 Rev Time 0.00
Received By dpalmer Date 2007-01-12 Time 11:20 Sent To  
Notes
2007-01-12 11:45:28 
 ** UNSAT **
  
  
 1) NOTE: PLEASE SEE MISSING ADDRESS INFORMATION FROM
 TITLE BLOCKS. PLEASE SEE THE SUITE/UNIT NUMBER IS BEING
 SHOWN, HOWEVER NOT THE ADDRESS/ LOCATION.
 FAC 61G1-16.004, FAC61G15-23.002
  
 2) NOTE: PLEASE SEE MISSING COMPLETE INFORMATION FOR A
 TITLE BLOCK FOR THE ARCHITECT OF RECORD. PLEASE SEE
 ATTACHED SHEET FROM DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATION. PLEASE SEE NO ADDRESS
 INFORMATION ETC.
 PLEASE KNOW IF WORKING THROUGH PBM DEVELOPMENT, AND PBM
 IS OFFERING ARCHITECTURAL SERVICES, THEN PBM WOULD BE
 REQUIRED TO LIST THEIR CERTIFICATE OF AUTHORIZATION
 NUMBER. (THIS HAS ALREADY BEEN GONE OVER WITH STAFF
 FROM PBM AND IT IS OUR UNDERSTANDING THAT APPLICATION
 TO THE DEPARTMENT OF BUSINESS AND PROFESSIONAL
 REGULATIONS HAS/IS TAKING OR TAKEN PLACE.
 PLEASE KNOW IF PERMIT ISSUANCE IS DOWN TO ONLY THIS
 COMMENT AND THE CERTIFICATE OF AUTHORIZATION NUMBER HAS
 NOT YET BEEN ISSUED FROM THE STATE, THE TITLE BLOCKS
 WOULD BE REVISED TO BE LISTED WITH THE ARCHITECT ONLY.
 FLORIDA ADMINISTRATIVE CODE 61G1-16.004, FLORIDA
 STATUTES 481.219
 **THIS IS NOT A COMMENT RELATED TO KAMM CONSULTING,
 HOWEVER TITLE BLOCKS ARE REQUIRED FOR ALL SHEETS PER
 ABOVE AND WHETHER OR NOT COMMENT IS MADE BY ANY OTHER
 TRADE.
  
 3) NOTE: PLEASE LIST THE FOLLOWING MINIMUM CODES
 RELEVANT TO THIS PROJECT AND DESIGN.
 2002 NFPA-72, 2005 NFPA-70, 2003 NFPA-101
 PLEASE SEE AS THE PERMIT WAS APPLIED FOR ON OR AFTER
 DECEMBER 8TH, 2006 THE 2006 REVISIONS TO THE 2004 FBC
 AND THE 2005 NATIONAL ELECTRICAL CODE WAS ADOPTED BY
 THE STATE OF FLORIDA.
 PLEASE ADJUST CODES ON PLANS.
  
 4) NOTE: PLEASE SEE MISSING LIGHTING CONTROL FOR ALL
 PER 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE SEE
 MISSING CONTROLS FOR COMMON AREAS. PLEASE SEE OVER
 RIDES DEVICES FOR THESE AREAS ALSO DEPENDING ON
 "SYSTEM" OR DEVICES CHOSEN. PLEASE SEE THE SYMBOL
 LEGEND FOR ALL DEVICES SHALL INDICATE ALL MAXIMUM TIMES
 FOR DEVICES. (30MINS FOR OCCUPANCY SENSOR TYPE AND 4HRS
 MAX FOR TIMER TYPE)
 PLEASE PROVIDE SCHEDULING FOR ANY PROPOSED SYSTEM.
 PLEASE SEE ALL AREAS CONTAIN FLOOR TO CEILING HEIGHT
 PARTITIONS SHALL CONTAIN DEVICE(S) FOR CONTROL. (PLEASE
 SEE STORAGE)
 PLEASE SEE 13-415.2, 13-415.2.ABC.1 FOR MISSING MAXIMUM
 PERMITTED LIGHTING POWER DENSITIES.
 PLEASE ALSO SEE 13-415.AB.1 FOR MISSING ENERGY
 CALCULATIONS REQUIRED FOR NEW TENANT BUILD-OUT.
 ** PLEASE SUBMIT THE ABOVE. AS THERE ARE ITEMS NOT YET
 SUBMITTED, A REVIEW OF SAID SYSTEM/DEVICES ETC CAN NOT
 BE FULLY ACCOMPLISHED AT THIS TIME.
  
 5) NOTE: PLEASE PROVIDE A DETAIL ON ALL EMERGENCY
 AND/OR EXIT LIGHTING WIRED AHEAD OF ANY OVER RIDE
 CONTROL DEVICES PER 700.12E. PLEASE SEE A
 CLOUDED/HIGHLIGHTED NOTE MAY ALSO BE DONE. THIS AHJ HAS
 BEEN HAVING MANY INSTANCES WHERE EMERGENCY AND EXIT
 LIGHTS ARE BEING WIRED ON THE LOAD SIDE OF OC/ TIMER
 DEVICES.
  
 6) NOTE: PLEASE INDICATE ALL CONTINUOUS LOADS AT 125%.
 215.3, 230.42 ETC.
 FBC 106.1.2 ADMIN SECTION.
  
 7) NOTE: PLEASE KNOW EITHER AT THIS POINT OR BEFORE
 FINAL, A REVISION FOR ALL CIRCUITS TO SPECIFIC ROOMS
 AND AREAS WILL BE REQUIRED. (LIGHTING CIRCUITS ETC.)
 408.4.
 ALL RECEPTACLE CIRCUITS ARE OK AS SHOWN.
  
 8) NOTE:PLEASE SEE THE ADDRESS OF THE PROJECT IS
 MISSING FROM TITLE BLOCKS. THE SUITE # OF 440 IS OK FOR
 SUITE, NEEDS ADDRESS OF 444 RAILROAD AVE.
  
 9) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE NEW INSTA-HOT TANKLESS WATER HEATER.
 PLEASE SEE PLUMBING REVIEW COMMENTS FOR THIS AND PLEASE
 BE SURE A LISTING FROM A NRTL IS ON PLANS.
  
 10) NOTE:
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDEDSHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.PLEASE KNOW ONLY
 ONE SET OF THE OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-04-16 Cont ID  
Sent By mawillia Date 2007-04-16 Time 12:33 Rev Time 0.00
Received By mawillia Date 2007-04-16 Time 12:19 Sent To  
Notes
2007-04-16 12:33:17*****APPROVED*****
  
  
 PLAN SHEETS LS-01, E2.1, FA2.1 AND FS2.1 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-04-04 Cont ID  
Sent By mawillia Date 2007-04-04 Time 18:05 Rev Time 0.00
Received By mawillia Date 2007-04-04 Time 17:54 Sent To  
Notes
2007-04-04 17:57:06*****APPROVED*****
  
  
  
 ALL COMMENTS FROM THE 02/09/07 FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;THE APPROPIATE PLAN SHEET(S) TO BE
 STAMPED WHEN ALL OTHER PLAN REVIEWS HAVE BEEN
 SATISFIED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-02-09 Cont ID  
Sent By mawillia Date 2007-02-09 Time 09:45 Rev Time 0.00
Received By mawillia Date 2007-02-09 Time 09:45 Sent To  
Notes
2007-02-09 10:03:08*****DENIED*****
  
  
 01.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE
 PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED.
  
 02. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 03.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT
 OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 04.THE COMPLETE ADDRESS OF WHERE THE SCOPE OF WORK
 WILL BE CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.
  
 05.DISPLAY THE TENANT SPACE NUMBER FOR THIS SITE SO
 THAT IT IS DISTINGUISHABLE FROM OTHER TENANT SITES ON
 THE FLOOR.AS PER WEST PALM BEACH CODE, THOSE NUMBERS
 SHALL BE NO LESS THAN 3" IN HEIGHT.
  
 06.DOOR(S) LEADING DIRECTLY TO THE FOURTH FLOOR
 CORRIDOR SHALL BE AN APPROVED, LISTED, AND LABELED FIRE
 DOOR & ASSEMBLY IN ACCORDANCE WITH THE REQUIREMENTS OF
 NFPA 80.
  
 07.WHAT IS INTERIOR FINISH CLASSIFICATION FOR THE
 WALLS AND CEILINGS IN THE EXITS, EXIT ACCESS CORRIDORS,
 AND IN ALL OTHER AREAS?
  
 08.PROVIDE A LIFE SAFETY PLAN SHEET WHICH INDICATES
 THE TRAVEL DISTANCE TO THE EXIT(S).ALSO ON THIS
 SHEET, INDICATE THE LOCATION OFFIRE EXTINGUISHER(S)
 AT DISTANCES TO SATISFY THE 75' TRAVEL DISTANCE
 REQUIREMENT.
  
 09.ON SHEET FA0.1, FIRE ALARM NOTE #17, DELETE
 SUPERVISORY SIGNAL ONLY AND INSERT GENERAL FIRE ALARM.
  
 10.PROVIDE A LAYOUT OF THE FIRE SPRINKLER SYSTEM FOR
 THIS TENANT SPACE.
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED ON THE PLAN.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-04-23 Cont ID  
Sent By adarroug Date 2007-04-23 Time 09:50 Rev Time 0.00
Received By adarroug Date 2007-04-23 Time 09:50 Sent To E
Notes
2007-04-23 09:50:31TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-04-11 Cont ID  
Sent By adarroug Date 2007-04-11 Time 14:43 Rev Time 0.00
Received By adarroug Date 2007-04-11 Time 14:42 Sent To  
Notes
2007-04-11 14:43:16TO "BOB"#13

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-30 Cont ID  
Sent By spalmer Date 2007-03-30 Time 18:46 Rev Time 0.00
Received By spalmer Date 2007-03-30 Time 18:46 Sent To  
Notes
2007-04-03 17:34:25TO BOB # 16
2007-03-30 18:46:46WAITING FOR BOB BOARD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-09 Cont ID  
Sent By mawillia Date 2007-02-09 Time 09:44 Rev Time  
Received By mawillia Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-04-05 Cont ID  
Sent By tgordon Date 2007-04-05 Time 07:47 Rev Time 0.25
Received By tgordon Date 2007-04-05 Time 07:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-01-26 Cont ID  
Sent By tgordon Date 2007-01-26 Time 08:46 Rev Time 0.25
Received By tgordon Date 2007-01-26 Time 08:46 Sent To  
Notes
2007-01-26 08:47:42*** DENIED ***
 1) SEE ELECTRICAL REVIEW NOTES #1 AND 2, PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-04-05 Cont ID  
Sent By jleech Date 2007-04-05 Time 08:45 Rev Time 0.00
Received By jleech Date 2007-04-05 Time 08:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-02-06 Cont ID  
Sent By kstevens Date 2007-02-06 Time 13:47 Rev Time 0.00
Received By kstevens Date 2007-02-06 Time 13:47 Sent To  
Notes
2007-02-06 14:12:17DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 11
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT A-03 SHOW THE CLEAR FLOOR SPACE FOR THE KITCHEN
 SINK PER SECTION 11-4.24.5. FORWARD APPROACH REQUIRED
 AND SHALL EXTEND A MAXIMUM 19" UNDERNEATH THE SINK.
 CABINET DOORS ARE NOT ALLOWED IN THE CLEAR FLOOR SPACE
 OF THE SINK. DELETE FROM CABINET DETAIL.
  
 2. SHT A-08 DETAIL. SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.3 KNEE CLEARANCE
 C. 11-4.24.4 SINK DEPTH
 D. 11-4.24.6 EXPOSED PIPES & SURFACES
 F. 11-4.24.7 FAUCETS
  
 3. SHT P0.1 WATER RISER DIAGRAM. THE WATER HAMMER
 ARRESTOR SHALL BE LOCATED NEAR THE FIXTURE, IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING AS SHOWN. PDI-WH
 201 AND MANUF. INSTALLATION INSTRUCTIONS. (ALSO SEE
 PLUMBING NOTE #13).
  
 4. ALL ARCHITECTURAL SHEETS. A TITLE BLOCK MUST APPEAR
 ON ALL ARCHITECTURAL DRAWINGS AND SPECIFICATION
 IDENTIFICATIONS SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
 PLEASE MAKE SURE ALL INFORMATION IS IN THE TITLE BLOCK
 ON EACH SHEET. FAC 61G1-16.004 & FS 481.219, 481.2055.
  
 5. THE ADDRESS OF THE BUILDING SHALL BE INDICATED ON
 THE PLANS. SECTION 106.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]