Plan Review Stops For Permit 06120592 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2007-04-09 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-04-09 |
Time |
11:42 |
Rev Time |
0.77 |
Received By |
jwitmer |
Date |
2007-04-09 |
Time |
11:12 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2007-01-30 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-01-30 |
Time |
09:57 |
Rev Time |
1.11 |
Received By |
jwitmer |
Date |
2007-01-30 |
Time |
09:55 |
Sent To |
|
|
Notes |
2007-01-30 09:58:50 | BUILDING PLAN REVIEW | | PERMIT: 06120592 | | ADD: 444 W RAILROAD AVESUITE 450 | | CONT: PBM DEVELOPMENT | | TEL: (561)368-2544 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | * WEST PALM BEACH AMENDMENTS | | | | 1STREVIEW | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | BER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | 2) PBM DEVELOPMENT, INC. ACTING AS AN ARCHITECTURAL | | FIRM MUST AQUIRE A CERTIFICATE OF AUTHORIZATION. | | 481.219 F.S.CERTIFICATE OF | | AUTHORIZATION.THE TITLE BLOCK FOR ANY | | SHEET BEARING THE NAME OF AN ARCHITECT | | PRACTICING UNDER A FICTITIOUS NAME, A | | CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL | | SERVICES, SHALL INCLUDE | | THE CERTIFICATE OF AUTHORIZATION | | NUMBER.ADD THE NUMBER TO EACH SHEET. | | THIS MAY BE ADDED BY HAND. | | | | BUILDING PLAN REVIEW | | JIM WITMER C. B. O. | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2007-01-08 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-01-08 |
Time |
13:24 |
Rev Time |
3.33 |
Received By |
jwitmer |
Date |
2007-01-08 |
Time |
13:24 |
Sent To |
|
|
Notes |
2007-01-08 14:06:33 | BUILDING PLAN REVIEW | | PERMIT: 06120592 | | ADD: 444 W RAILROAD AVESUITE 450 | | CONT: PBM DEVELOPMENT | | TEL: (561)368-2544 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | * WEST PALM BEACH AMENDMENTS | | | | 1STREVIEW | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | BER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | 2) PBM DEVELOPMENT, INC. ACTING AS AN ARCHITECTURAL | | FIRM MUST AQUIRE A CERTIFICATE OF AUTHORIZATION. | | 481.219 F.S.CERTIFICATE OF | | AUTHORIZATION.THE TITLE BLOCK FOR ANY | | SHEET BEARING THE NAME OF AN ARCHITECT | | PRACTICING UNDER A FICTITIOUS NAME, A | | CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL | | SERVICES, SHALL INCLUDE | | THE CERTIFICATE OF AUTHORIZATION | | NUMBER.ADD THE NUMBER TO EACH SHEET. | | THIS MAY BE ADDED BY HAND. | | | | 3) THE TITLEBLOCK IS MISSING THE LOCATION OF | | THE JOB, ONLY THE SUITE NUMBER HAS BEEN | | PROVIDED. SEE FL S S 61G1-16.004 TITLE BLOCK(3) | | IDENTIFICATIOJN OF PROPERTY. | | | | 4) SHEET A-03106.1.2 ADDITIONAL INFORMATION REQUIRED. | | THE | | FLOOR PLAN DOESN'T INDICATE DOOR SWINGS WITHIN THE | | UNIT. | | IT APPEARS CONFERENCE ROOM 454 MAY HAVE A | | PAIR OF 30" DOORS. SEE SECTION 11-4.13.4 DOUBLE-LEAF | | DOORWAYS. | | IF DOORWAYS HAVE TWO INDEPENDENTLY OPERATED DOOR | | LEAVES, | | THEN AT LEAST ONE LEAF SHALL MEET THE SPECIFICATIONS | | IN | | SECTION 11-4.13.5 AND SECTION 11-4.13.6 . THAT LEAF | | SHALL BE AN ACTIVE LEAF. | | | | 5)SHEET A-04 IS MISSING EMERGENCY LIGHTING | | REQUIREMENTS SEE TABLE | | 1006, BUSINESS > 2 STORIES ABOVE GRADE LED | | | | 6) SHEET A-04 1006.3.1 | | EXITS SHALL BE MARKED BY AN APPROVED SIGN READILY | | VISIBLE FROM ANY | | DIRECTION OF EXIT ACCESS. EVERY EXIT SIGN SHALL BE | | SUITABLY ILLUMINATED | | BY A RELIABLE LIGHT SOURCE. EXTERNALLY AND INTERNALLY | | ILLUMINATED SIGNS | | SHALL BE VISIBLE IN BOTH NORMAL AND EMERGENCY | | LIGHTING. | | | | | | 7) SHEET A-05 & A-06 BOTH INDICATE CHAIR RAIL AND CROWN | | TRIM, BUT NO MENTION AS TO TYPE OF MATERIAL. 805.3 FOAM | | PLASTIC USED AS TRIM IN ANY OCCUPANCY SHALL | | | | COMPLY WITH SECTION 2604.2 . 2604.2 INTERIOR TRIM. FOAM | | PLASTIC USED AS INTERIOR TRIM SHALL COMPLY WITH | | SECTIONS 2604.2.1 THROUGH 2604.2.4 . | | 2604.2.1 DENSITY. | | THE MINIMUM DENSITY OF THE INTERIOR TRIM SHALL BE 20 | | PCF (320 KG/M 3 ). | | 2604.2.2 THICKNESS. | | THE MAXIMUM THICKNESS OF THE INTERIOR TRIM SHALL BE 0.5 | | INCH (12.7 MM) AND THE MAXIMUM WIDTH SHALL BE 8 INCHES | | (204 MM). | | 2604.2.3 AREA LIMITATION. | | THE INTERIOR TRIM SHALL NOT CONSTITUTE MORE THAN 10 | | PERCENT OF THE AGGREGATE WALL AND CEILING AREA OF ANY | | ROOM OR SPACE. | | 2604.2.4 FLAME SPREAD. | | THE FLAME SPREAD INDEX SHALL NOT EXCEED 75 WHERE TESTED | | IN ACCORDANCE WITH ASTM E 84. THE SMOKE-DEVELOPED INDEX | | SHALL NOT BE LIMITED. | | | | 8) SHEETS A-05 & A-06 BOTH ALSO INDICATE THE USE OF | | GLAZING NEXT TO DOORWAYS, PLANS DO NOT INDICATE WHAT | | TYPE OF GLAZING SHALL BE USED. | | 2406.3 HAZARDOUS LOCATIONS. | | THE FOLLOWING SHALL BE CONSIDERED SPECIFIC HAZARDOUS | | LOCATIONS REQUIRING SAFETY GLAZING MATERIALS: | | 1.GLAZING IN SWINGING DOORS EXCEPT JALOUSIES (SEE | | SECTION 2406.3.1 ). | | 2.GLAZING IN FIXED AND SLIDING PANELS OF SLIDING | | DOOR ASSEMBLIES AND PANELS IN SLIDING AND BIFOLD CLOSET | | DOOR ASSEMBLIES. | | 3.GLAZING IN STORM DOORS. | | 4.GLAZING IN UNFRAMED SWINGING DOORS. | | 5.GLAZING IN DOORS AND ENCLOSURES FOR HOT TUBS, | | WHIRLPOOLS, SAUNAS, STEAM ROOMS, BATHTUBS AND SHOWERS. | | GLAZING IN ANY PORTION OF A BUILDING WALL ENCLOSING | | THESE COMPARTMENTS WHERE THE BOTTOM EXPOSED EDGE OF THE | | GLAZING IS LESS THAN 60 INCHES (1524 MM) ABOVE A | | STANDING SURFACE. | | 6.GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE PANEL | | ADJACENT TO A DOOR WHERE THE NEAREST EXPOSED EDGE OF | | THE GLAZING IS WITHIN A 24-INCH (610 MM) ARC OF EITHER | | VERTICAL EDGE OF THE DOOR IN A CLOSED POSITION AND | | WHERE THE BOTTOM EXPOSED EDGE OF THE GLAZING IS LESS | | THAN 60 INCHES (1524 MM) ABOVE THE WALKING SURFACE. | | | | 9) A-06 INDICATES THE USE OF A BREAKROOM SINK, NO | | ACCESSIBILITY. | | SINKS: | | 11-4.24.2 SINKS, HEIGHT. SINKS SHALL | | BE MOUNTED WITH THE COUNTER NO HIGHER | | THAN 34" ABOVE THE FINISH FLOOR. | | 11-4.24.3 KNEE CLEARANCE THAT IS AT | | LEAST 27" HIGH 30" WIDE, AND 19" DEEP | | SHALL BE PROVIDED UNDERNEATH SINKS. | | 11-4.24.5 CLEAR FLOOR SPACE. | | A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES | | (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4 | | SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD | | APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN | | ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19 | | INCHES (485 MM) UNDERNEATH THE SINK | | | | BUILDING PLAN REVIEW | | JIM WITMER C. B. O. | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
P |
Date |
2007-04-24 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-04-24 |
Time |
13:15 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-04-24 |
Time |
13:15 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
F |
Date |
2007-04-12 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-04-12 |
Time |
08:50 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-04-12 |
Time |
08:48 |
Sent To |
|
|
Notes |
2007-04-12 08:52:29 | ** UNSAT ** | | | | 1) NOTE: PLEASE SEE THE NEW REVISED ENERGY CALCULATIONS | | ARE NOT SEALED BY THE ENGINEER OF RECORD AS REQUIRED | | PER 13-103.1.1.1 | | PLEASE SUBMIT SIGNED, DATED AND SEALED. FS 471.025 | | | | 2) NOTE: PLEASE SEE THE NUMBER OF*B* FIXTURES ON | | PLANS DO NOT CORRELATE WITH THE NUMBER OF FIXTURES ON | | ENERGY CALCULATIONS. PLEASE ADJUST PLANS, OR ENERGY | | CALCULATIONS. | | | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2007-04-04 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-04-04 |
Time |
16:11 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-04-04 |
Time |
16:10 |
Sent To |
|
|
Notes |
2007-04-04 16:11:27 | | | ** UNSAT 2ND REVIEW ** | | | | 1) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEW. THE | | ENERGY CALCULATIONS AND/OR PERFORMANCE DENSITIES WERE | | NOT SHOWN IN COMPLIANCE. PLEASE SEE THE TYPE, AND | | AMOUNT OF FIXTURES, WATTAGE(S) ETC AS SHOWN ON PLANS DO | | NOT CORRELATE WITH THE ENERGY CALCULATIONS SUBMITTED. | | PLEASE ADJUST AND REVISE 13-415.1.AB.1.1, 13-415.2 | | PLEASE SEE THE METHOD OF CONTROL FOR LIGHTING ON ENERGY | | CALCULATIONS NEEDS TO CORRELATE WITH PLANS. | | (AUTOMATED/OCCUPANCY/TIMERS ETC). | | | | 2) NOTE: PLEASE SEE THAT NO HAND DRAWN CHANGES ARE | | PERMITTED ON PLANS. | | PLEASE BE SURE TO STATE THE MAXIMUM TIMES FOR OCCUPANCY | | TYPE DEVICES ON PLANS. | | 13-415.1.ABC.1.1 | | | | | | * ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2007-01-25 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-01-25 |
Time |
15:26 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-01-25 |
Time |
15:23 |
Sent To |
|
|
Notes |
2007-01-25 15:27:09 | ** UNSAT ** | | | | 1) NOTE: PLEASE SEE NOTE #1 FROM PREVIOUS REVIEW. IT IS | | NOTED THAT APPLICATION HAS BEEN MADE TO DBPR, HOWEVER | | UNTIL ISSUANCE OF THE FIRM LICENSE NUMBER HAS BEEN | | DONE, CONFIRMED AND ON TITLE BLOCKS, WE ARE NOT ABLE TO | | STAMP OR PASS PLANS EVEN IF APPLICATION IS MADE. PLEASE | | KNOW THAT THIS OFFICE HAS BEEN IN CONTACT WITH THE | | STATE'S LEGAL COUNSEL ON THIS MATTER AND WE HAVE BEEN | | INFORMED DIRECTLY ON THIS MATTER. | | FS 481.219, FAC 61G1-16.004. | | | | 2) NOTE: PLEASE SEE SUBMIT INCLUDE ENERGY/PERFORMANCE | | CALCULATIONS FOR LIGHTING ALLOWANCES PER 13-415.1.AB.1, | | 13-415.2 (PREVIOUS REVIEW) | | | | 3) NOTE: PLEASE SEE ADDRESS IS STILL MISSING FROM THE | | TITLE BLOCKS ON EACH SHEET. 61G1-16.004/ 61G15-23.002 | | | | | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2007-01-06 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-01-06 |
Time |
19:16 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-01-06 |
Time |
18:37 |
Sent To |
|
|
Notes |
2007-01-06 19:16:37 | ** UNSAT ** | | | | | | 1) NOTE: PLEASE SEE MISSING ADDRESS INFORMATION FROM | | TITLE BLOCKS. PLEASE SEE THE SUITE/UNIT NUMBER IS BEING | | SHOWN, HOWEVER NOT THE ADDRESS/ LOCATION. | | FAC 61G1-16.004, FAC61G15-23.002 | | | | 2) NOTE: PLEASE SEE MISSING COMPLETE INFORMATION FOR A | | TITLE BLOCK FOR THE ARCHITECT OF RECORD. PLEASE SEE | | ATTACHED SHEET FROM DEPARTMENT OF BUSINESS AND | | PROFESSIONAL REGULATION. PLEASE SEE NO ADDRESS | | INFORMATION ETC. | | PLEASE KNOW IF WORKING THROUGH PBM DEVELOPMENT, AND PBM | | IS OFFERING ARCHITECTURAL SERVICES, THEN PBM WOULD BE | | REQUIRED TO LIST THEIR CERTIFICATE OF AUTHORIZATION | | NUMBER. (THIS HAS ALREADY BEEN GONE OVER WITH STAFF | | FROM PBM AND IT IS OUR UNDERSTANDING THAT APPLICATION | | TO THE DEPARTMENT OF BUSINESS AND PROFESSIONAL | | REGULATIONS HAS/IS TAKING OR TAKEN PLACE. | | PLEASE KNOW IF PERMIT ISSUANCE IS DOWN TO ONLY THIS | | COMMENT AND THE CERTIFICATE OF AUTHORIZATION NUMBER HAS | | NOT YET BEEN ISSUED FROM THE STATE, THE TITLE BLOCKS | | WOULD BE REVISED TO BE LISTED WITH THE ARCHITECT ONLY. | | FLORIDA ADMINISTRATIVE CODE 61G1-16.004, FLORIDA | | STATUTES 481.219 | | **THIS IS NOT A COMMENT RELATED TO KAMM CONSULTING, | | HOWEVER TITLE BLOCKS ARE REQUIRED FOR ALL SHEETS PER | | ABOVE AND WHETHER OR NOT COMMENT IS MADE BY ANY OTHER | | TRADE. | | | | 3) NOTE: PLEASE LIST THE FOLLOWING MINIMUM CODES | | RELEVANT TO THIS PROJECT AND DESIGN. | | 2002 NFPA-72, 2005 NFPA-70, 2003 NFPA-101 | | PLEASE SEE AS THE PERMIT WAS APPLIED FOR ON OR AFTER | | DECEMBER 8TH, 2006 THE 2006 REVISIONS TO THE 2004 FBC | | AND THE 2005 NATIONAL ELECTRICAL CODE WAS ADOPTED BY | | THE STATE OF FLORIDA. | | PLEASE ADJUST CODES ON PLANS. | | | | 4) NOTE: PLEASE SEE MISSING LIGHTING CONTROL FOR ALL | | PER 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE SEE | | MISSING CONTROLS FOR COMMON AREAS. PLEASE SEE OVER | | RIDES DEVICES FOR THESE AREAS ALSO DEPENDING ON | | "SYSTEM" OR DEVICES CHOSEN. PLEASE SEE THE SYMBOL | | LEGEND FOR ALL DEVICES SHALL INDICATE ALL MAXIMUM TIMES | | FOR DEVICES. (30MINS FOR OCCUPANCY SENSOR TYPE AND 4HRS | | MAX FOR TIMER TYPE) | | PLEASE PROVIDE SCHEDULING FOR ANY PROPOSED SYSTEM. | | PLEASE SEE ALL AREAS CONTAIN FLOOR TO CEILING HEIGHT | | PARTITIONS SHALL CONTAIN DEVICE(S) FOR CONTROL. (PLEASE | | SEE STORAGE) | | PLEASE SEE 13-415.2, 13-415.2.ABC.1 FOR MISSING MAXIMUM | | PERMITTED LIGHTING POWER DENSITIES. | | PLEASE ALSO SEE 13-415.AB.1 FOR MISSING ENERGY | | CALCULATIONS REQUIRED FOR NEW TENANT BUILD-OUT. | | ** PLEASE SUBMIT THE ABOVE. AS THERE ARE ITEMS NOT YET | | SUBMITTED, A REVIEW OF SAID SYSTEM/DEVICES ETC CAN NOT | | BE FULLY ACCOMPLISHED AT THIS TIME. | | | | 5) NOTE: PLEASE PROVIDE A DETAIL ON ALL EMERGENCY | | AND/OR EXIT LIGHTING WIRED AHEAD OF ANY OVER RIDE | | CONTROL DEVICES PER 700.12E. PLEASE SEE A | | CLOUDED/HIGHLIGHTED NOTE MAY ALSO BE DONE. THIS AHJ HAS | | BEEN HAVING MANY INSTANCES WHERE EMERGENCY AND EXIT | | LIGHTS ARE BEING WIRED ON THE LOAD SIDE OF OC/ TIMER | | DEVICES. | | | | 6) NOTE: PLEASE INDICATE ALL CONTINUOUS LOADS AT 125%. | | 215.3, 230.42 ETC. | | FBC 106.1.2 ADMIN SECTION. | | | | 7) NOTE: PLEASE KNOW EITHER AT THIS POINT OR BEFORE | | FINAL, A REVISION FOR ALL CIRCUITS TO SPECIFIC ROOMS | | AND AREAS WILL BE REQUIRED. (LIGHTING CIRCUITS ETC.) | | 408.4. | | ALL RECEPTACLE CIRCUITS ARE OK AS SHOWN. | | | | 8) NOTE: PLEASE CLARIFY HOW THE PANEL SCHEDULE(S) | | INDICATE ALL THE CIRCUITS AS EXISTING FOR ALL THESE | | SPACES WHICH HAVE YET TO BE PERMITTED. PLEASE INDICATE | | NEW CIRCUITINGAS THESE CAN NOT BE EXISTING. PLEASE | | SEE THAT NO OTHER TENANT BUILD OUTS HAVE BEEN PERMITTED | | AT THIS TIME. | | | | 9) NOTE:** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | OLD/VOIDEDSHEETS AND ONLY INSERT NEW REVISED SHEETS | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.DO NOT | | LEAVE ANY OLD/VOIDED SHEETS IN SETS.PLEASE KNOW ONLY | | ONE SET OF THE OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | DELAYS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | | 2007-01-06 18:37:42 | 2007-01-06 18:37:42 | | IN ELEC FOR REVIEW |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2007-04-16 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-04-16 |
Time |
12:14 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-04-16 |
Time |
11:51 |
Sent To |
|
|
Notes |
2007-04-16 12:13:03 | *****APPROVED***** | | | | | | PLAN SHEETS LS-01, E2.1, FA2.1 AND FS2.1 WERE STAMPED, | | INITIALED, AND DATED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2007-04-04 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-04-04 |
Time |
17:46 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-04-04 |
Time |
17:41 |
Sent To |
|
|
Notes |
2007-04-04 17:42:01 | *****APPROVED***** | | | | | | | | ALL COMMENTS FROM THE 01/18/07 FIRE PLAN REVIEW HAVE | | BEEN ADDRESSED;THE APPRPIATE PLAN SHEET(S) TO BE | | STAMPED WHEN ALL OTHER PLAN REVIEWS HAVE BEEN | | SATISFIED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2007-02-06 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-02-06 |
Time |
10:39 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-02-06 |
Time |
10:39 |
Sent To |
|
|
Notes |
2007-02-06 10:43:29 | *****DENIED***** | | | | | | | | COMMENTS FROM PREVIOUS FIRE PLAN REVIEW OF 01/18/2007 | | STILL HAVE NOT BEEN ADDRESSED.TO EXPEDITE THE PLAN | | REVIEW PROCESS WHEN RESUBMITTING, INCLUDE A RESPONSE | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2007-01-18 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-01-18 |
Time |
10:08 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-01-18 |
Time |
10:00 |
Sent To |
|
|
Notes |
2007-01-18 11:39:45 | *****DENIED***** | | | | | | 01.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE | | PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED. | | | | 02. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 03.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS | | SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT | | OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | 04.THE COMPLETE ADDRESS OF WHERE THE SCOPE OF WORK | | WILL BE CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH | | SUBMITTED PLAN SHEET. | | | | 05.DISPLAY THE TENANT SPACE NUMBER FOR THIS SITE SO | | THAT IT IS DISTINGUISHABLE FROM OTHER TENANT SITES ON | | THE FLOOR.AS PER WEST PALM BEACH CODE, THOSE NUMBERS | | SHALL BE NO LESS THAN 3" IN HEIGHT. | | | | 06.DOOR(S) LEADING DIRECTLY TO THE FOURTH FLOOR | | CORRIDOR SHALL BE AN APPROVED, LISTED, AND LABELED FIRE | | DOOR & ASSEMBLY IN ACCORDANCE WITH THE REQUIREMENTS OF | | NFPA 80. | | | | 07.WHAT IS INTERIOR FINISH CLASSIFICATION FOR THE | | WALLS AND CEILINGS IN THE EXITS, EXIT ACCESS CORRIDORS, | | AND IN ALL OTHER AREAS? | | | | 08.PROVIDE A LIFE SAFETY PLAN SHEET WHICH INDICATES | | THE TRAVEL DISTANCE TO THE EXIT(S).ALSO ON THIS | | SHEET, INDICATE THE LOCATION OFFIRE EXTINGUISHER(S) | | AT DISTANCES TO SATISFY THE 75' TRAVEL DISTANCE | | REQUIREMENT. | | | | 09.ON SHEET FA0.1, FIRE ALARM NOTE #17 SHOULD BE | | CHANGED TO "INITIATE A GENERAL FIRE ALARM". | | | | 10.PROVIDE A LAYOUT OF THE FIRE SPRINKLER SYSTEM FOR | | THIS TENANT SPACE. | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, | | INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH | | ITEM WAS ADDRESSED ON THE PLAN. | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2007-04-23 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-04-23 |
Time |
10:00 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-04-23 |
Time |
10:00 |
Sent To |
E |
|
Notes |
2007-04-23 10:00:44 | TO "DPALMER" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2007-04-11 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-04-11 |
Time |
14:53 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-04-11 |
Time |
14:53 |
Sent To |
|
|
Notes |
2007-04-11 14:54:14 | TO "BOB"#13 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2007-03-30 |
|
|
Cont ID |
|
Sent By |
spalmer |
Date |
2007-03-30 |
Time |
18:47 |
Rev Time |
0.00 |
Received By |
spalmer |
Date |
2007-03-30 |
Time |
18:47 |
Sent To |
|
|
Notes |
2007-04-03 17:35:46 | TO BOB # 18 | 2007-03-30 18:47:55 | WAITING FOR BOB BOARD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-01-25 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-01-25 |
Time |
09:54 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-01-25 |
Time |
09:54 |
Sent To |
|
|
Notes |
2007-01-25 09:56:57 | TO "BOB"#4 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-01-18 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-01-18 |
Time |
10:00 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2006-12-22 |
Time |
15:45 |
Sent To |
|
|
Notes |
2007-01-06 18:33:48 | TO BOB NOARD #1 1/6 | 2006-12-22 15:45:51 | WAITING FOR "BOB" |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2007-04-05 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-04-05 |
Time |
10:24 |
Rev Time |
0.20 |
Received By |
tgordon |
Date |
2007-04-05 |
Time |
10:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2007-01-25 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-01-25 |
Time |
16:37 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2007-01-25 |
Time |
16:37 |
Sent To |
|
|
Notes |
2007-01-25 16:41:22 | *** DENIED *** | | 1) SEE ELECTRICAL REVIEW NOTES #1 AND 3, PLEASE | | CORRECT. | | | | 2)PAGES A-05 AND A-08 SHOW THE SPACE ABOVE THE | | ACCOUSTIC TILE CEILING TO BE AN OPEN PLENUM AND WOULD | | NOT REQUIRE RETURN AIR TRANSFER DUCTS, IF THIS IS SO | | PLEASE DO NOT SHOW RETURN AIR TRANSFER DUCTS ON PAGE | | M-2.1. IF NOT AN OPEN PLENUM RETURN AIR TRANSFER DUCTS | | TO OFFICES 2,3,4,5, AND CONFERENCE ROOM, ARE | | UNDER-SIZED. BALANCED RETURN AIR MAY BE ACHIEVED BY. | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY | | INCREASING THE RETURN TRANSFER ONE AND | | ONE HALF TIMES THE CROSS SECTIONAL AREA | | (SQUARE INCHES) OF THE SUPPLY DUCT | | ENTERING THE ROOM OR SPACE IT'S SERVING | | AND THE DOOR HAVING AT LEAST AN | | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE | | PROPER RETURN AIR BALANCE. PER 2004 FBC/M 601.4. PLEASE | | CORRECT. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2007-01-08 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-01-08 |
Time |
11:07 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2007-01-08 |
Time |
11:07 |
Sent To |
|
|
Notes |
2007-01-08 11:09:03 | *** DENIED *** | | 1) JOB ADDRESS MUST APPEAR ON ALL PLANS. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2007-04-05 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2007-04-05 |
Time |
07:29 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2007-04-05 |
Time |
07:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2007-02-03 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2007-02-03 |
Time |
08:50 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2007-02-03 |
Time |
08:50 |
Sent To |
|
|
Notes |
2007-02-03 09:06:43 | DENIED; | | 1. SEE ELECTRICAL PLAN REVIEW NOTES #1 AND #3. | | 2. PAGE P0.1 PLUMBING NOTE # 11 PLEASE CHANGE NOTE | | SINCE THE AREA ABOVE THE DROP CEILING IS A PLENUM TO | | READ NO PVC PERMITED. PIPING MATERIAL TO BE CAST IRON | | OR COPPER DWV TYPE. | | 3.PREVIOUS NOT #3 FROM LAST REVIEW, THE WATER HAMMER | | ARRESTOR TO BE INSTALLED PER MANUFACTURE'S INSTALLATION | | INSTRUCTIONS, AS CLOSE TO THE SOURCE (FIXTURE) AS | | POSSIBLE. ONE RISER DIAGRAM MARKED IN RED. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2007-01-16 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2007-01-16 |
Time |
07:13 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2007-01-16 |
Time |
07:13 |
Sent To |
|
|
Notes |
2007-01-16 07:42:48 | DENIED; | | 1.ADD MISSING INFORMATION TO TITLE BLOCK. SEE | | ELECTRICAL PLAN REVIEW NOTES 1 & 2. | | 2.BREAK SINK MUST COMPLY TO THE FBC-2004 BUILDING | | CHAPTER 11 ACCESSIBILITY CODE. THE ELEVATION (4) PAGE | | A-06 DOES NOT COMPLY. | | 11-4.24.2 HEIGHT OF SINK IS 34". | | 11-4.24.3 KNEE CLEARANCE 27" HIGH, 30" | | WIDE, AND 19" DEEP. (NO CABINET DOORS) | | 11-4.24.4 DEPTHMAX 6 1/2" DEEP. | | 11-4.24.5 CLEAR FLOOR SPACE 30 X 48 SHOW | | ON FLOOR PLAN. | | 11-4.24.6 INSULATE EXPOSED PIPES. 3.WATER | | RISER, WATER HAMMER ARRESTOR TO BE INSTALLED PER | | MANUFATURE'S SPECS,CLOSE TO THE SOURCE (SHOW AT | | BOTTOM OF DROP) | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|
|