Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-02-28 Cont ID  
Sent By mjacobs Date 2007-02-28 Time 10:35 Rev Time 0.00
Received By mjacobs Date 2007-02-28 Time 07:28 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-30 Cont ID  
Sent By mjacobs Date 2007-01-30 Time 07:23 Rev Time 0.00
Received By mjacobs Date 2007-01-30 Time 06:40 Sent To  
Notes
2007-01-30 07:23:27BUILDING PLAN REVIEW
 PERMIT:06120578
 ADD: 9477 LANTERN BAY CIR
 CONT: PIONEER SCREEN
 TEL: (772)283-9197
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 2)106.1.2 ADDITIONAL DATA. THE
 BUILDING OFFICIAL MAY REQUIRE DETAILS, COMPUTATIONS,
 STRESS DIAGRAMS, AND OTHER
 DATA NECESSARY TO DESCRIBE THE
 CONSTRUCTION OR INSTALLATION AND THE
 BASIS OF CALCULATION. ALL DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 REQUIRED BY THE BUILDING OFFICIAL TO BE
 PREPARED BY AN ARCHITECT OR ENGINEER
 SHALL BE AFFIXED WITH THIER OFFICIAL
 SEAL, SIGNATURE AND DATE AS STATE LAW
 REQUIRES. THE DRAWINGS HAS TO BE SIGNED AND SEALED BY
 THE ENGINEER OF RECORD. THE DRAWINGS ARE ALSO MISSING
 SOME DIMENTIONS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-02-27 Cont ID  
Sent By adarroug Date 2007-02-27 Time 12:01 Rev Time 0.00
Received By adarroug Date 2007-02-27 Time 12:01 Sent To B
Notes
2007-02-27 12:01:32TO "MJACOBS" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-29 Cont ID  
Sent By adarroug Date 2006-12-29 Time 09:16 Rev Time 0.00
Received By adarroug Date 2006-12-29 Time 09:16 Sent To B
Notes
2006-12-29 09:17:38TO "MISC" BOX#2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-01-30 Time   Rev Time 0.00
Received By adarroug Date 2006-12-21 Time 10:48 Sent To  
Notes
2006-12-21 10:49:10TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status P Date 2006-12-28 Cont ID  
Sent By mmclean Date 2006-12-28 Time 15:34 Rev Time 0.00
Received By mmclean Date 2006-12-28 Time 15:34 Sent To I
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved