Plan Review Details - Permit 06120548
Plan Review Stops For Permit 06120548
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-08-31 Cont ID  
Sent By shill Date 2007-08-31 Time 07:59 Rev Time 0.00
Received By shill Date 2007-08-31 Time 07:59 Sent To  
Notes
2007-08-31 08:02:18****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)GLASS INSTALLATION IS NOT WITHIN THE SCOPE OF AN
 ALUMINUM SPECIALTIES CONTRACTOR LICENSE.
  
 2.)SPANS SHOULD BE BLADE LENGTH AND CORRELATE WITH
 THE OPENING HEIGHT (ACCORDIONS).HOW CAN A 63" HIGH
 OPENING HAVE A SPAN OF 55"?SEE OPENINGS 1-3.
  
 3.)CONNECTION TYPE IS TO CORRELATE WITH ANCHOR
 SCHEDULES ON SHEETS 10-11.WITH THIS PRODUCT APPROVAL,
 IT WILL BE A THROUGH L.
  
 4.)SHUTTER GLASS SEPARATION NOT ON THE CHART YOU'VE
 USED.SEE SAMPLE INSTALLATION SCHEDULE WHICH INCLUDES
 ALL INFORMATION REQUIRED.
  
 5.)THE ADDRESS ON THE RESUB SHEET DOES NOT MATCH THE
 APPLICATION.PLEASE CONFIRM JOB ADDRESS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-08-13 Cont ID  
Sent By shill Date 2007-08-13 Time 13:36 Rev Time 0.00
Received By shill Date 2007-08-13 Time 13:36 Sent To  
Notes
2007-08-13 13:38:19****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
  
 1.)SEE SHEET 11.IT IS NOT CLEAR ON YOUR
 INSTALLATION SCHEDULE IF YOU ARE SPECIFYING A 3" OR 3
 1/2" EDGE DISTANCE.3" EDGE DISTANCE REQUIRES A FACTOR
 (CLOSER ANCHOR SPACING).
  
 2.)SEE ATTACHED INSTALLATION SCHEDULE.THE FORM YOU
 ARE USING DOES NOT INCLUDE ALL INFORMATION REQUIRED TO
 DETERMINE CODE COMPLIANCE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-07-30 Cont ID  
Sent By shill Date 2007-07-30 Time 16:29 Rev Time 0.00
Received By shill Date 2007-07-30 Time 16:29 Sent To  
Notes
2007-07-30 16:37:56****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)IT IS ACCEPTABLE TO PROVIDE THE INFORMATION
 REQUIRED IN A FORMAT OTHER THAN THE SUGGESTED
 INSTALLATION SCHEDULE BUT YOU MUST INCLUDE ALL
 INFORMATION.SHUTTER CONNECTION MOUNTING TYPE, ANCHOR
 SPACING, SHUTTER GLASS SEPARATION, DESIGN PRESSURE,
 ETC. ARE MISSING FROM YOUR FORM.SEE ATTACHED
 INSTALLATION SCHEDULE AND PROVIDE ALL INFORMATION AS
 REQUESTED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-26 Cont ID  
Sent By shill Date 2007-01-26 Time 14:52 Rev Time 0.00
Received By shill Date 2007-01-26 Time 14:52 Sent To  
Notes
2007-01-26 14:52:51****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY
  
 ____1.A NOTICE OF COMMENCEMENT MUST BE FILED WITH
 THE CLERK OF COURTS BEFORE A PERMIT CAN BE ISSUED,
 FS713.13.
  
 ____2.PROVIDE BUILDING HEIGHT ON THE PLAN.DESIGN
 PRESSURES FOR BUILDINGS OVER 60FEET ARE REQUIRED TO BE
 DESIGNED USING ASCE7, FBC1609.1.1 AND MUST BE DONE BY
 AN ENGINEER. DOCUMENTS PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED SEALED
 ORIGINALS FAC61G15-23.002.
  
 ____3.PROVIDE A COPY OF THE CONDO ASSOCIATION
 APPROVAL.
  
 _XX_4.COMPLETE THE ATTACHED INSTALLATION SCHEDULE
 OR PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT.
  
 ____5.FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG.
  
 _XX_6.ON THE PRODUCT APPROVAL, MARK WHICH DETAILS
 APPLY TO THIS JOB.PLEASE USE INK RATHER THAN A
 HIGHLIGHTER.
  
 ____7.SHOW THE EMERGENCY MEANS OF ESCAPE, FBC
 R310.
  
 ____8.PROVIDE A FLOOR PLAN SHOWING WHERE THE
 SHUTTERS WILL BE INSTALLED AND PANEL SIZES WHICH
 CORRELATES WITH THE INSTALLATION SCHEDULE, ITEM 4
 ABOVE.
  
 ____9.REVISE EXPOSURE CATEGORY FBC1609.6.2.1(2).
 NOTE THAT THE DEFINITION FOR EXPOSURE C HAS CHANGED
 EFFECTIVE DECEMBER 8, 2006 FBC1609.4.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-08-28 Cont ID  
Sent By adarroug Date 2007-08-28 Time 14:05 Rev Time 0.00
Received By adarroug Date 2007-08-28 Time 14:05 Sent To B
Notes
2007-08-28 14:05:44TO "SHILL' DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-08-07 Cont ID  
Sent By mmiller Date 2007-08-07 Time 17:19 Rev Time 0.00
Received By mmiller Date 2007-08-07 Time 17:18 Sent To B
Notes
2007-08-07 17:19:08SENT TO SAMANTHA HILL'S DESK MMILLER

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-27 Cont ID  
Sent By adarroug Date 2007-07-27 Time 15:24 Rev Time 0.00
Received By adarroug Date 2007-07-27 Time 15:24 Sent To B
Notes
2007-07-27 15:24:43TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date 2007-01-26 Cont ID  
Sent By shill Date 2007-01-26 Time 14:53 Rev Time 0.00
Received By shill Date 2006-12-20 Time 08:55 Sent To  
Notes
2006-12-20 08:55:20TO "MISC" BOX#1