Plan Review Details - Permit 06120515
Plan Review Stops For Permit 06120515
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-01-10 Cont ID  
Sent By rmcdouga Date 2007-01-10 Time 17:15 Rev Time 0.00
Received By rmcdouga Date 2007-01-10 Time 17:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-12-20 Cont ID  
Sent By rmcdouga Date 2006-12-20 Time 07:21 Rev Time 0.00
Received By rmcdouga Date 2006-12-20 Time 07:21 Sent To  
Notes
2006-12-20 08:36:03DENIED BY BUILDING
  
 1) THE METHOD OF ATTACHMENT FOR THE ROOF TILE IS
 REQUIRED TO BE SPECIFIED. PLEASE CIRCLE THE APPROPRIATE
 FASTENER OR ADHESIVE ON THE PRODUCT APPROVAL.
  
 2) FAC 61G15-23.001 REQUIRES ENGINEER'S SEALS, AFTER
 JANUARY 1, 2006, TO HAVE LICENSE RATHER THAN
 CERTIFICATE SPECIFIED ON THEM. PLEASE CORRECT.
  
 3) IN ADDITION TO THEIR NAME AND ADDRESS THE ENGINEER
 IS REQUIRED TO LEGIBLY INDICATE THEIR LICENSE NUMBER ON
 THE DOCUMENT PER FAC 61G-23.002. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  