Plan Review Details - Permit 06120511
Plan Review Stops For Permit 06120511
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-26 Cont ID  
Sent By shill Date 2007-01-26 Time 14:59 Rev Time 0.00
Received By shill Date 2007-01-26 Time 14:59 Sent To  
Notes
2007-01-26 15:00:49****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 1.)ORIGINAL SIGNATURES REQUIRED FOR THE ENGINEER PER
 FBPE.
  
 2.)BOTTOM OF RAMP IS TO HAVE NOT LESS THAN 72 IN
 STRAIGHT AND LEVEL CLEARANCE, FBC11-4.8.3(2).
  
 3.)PROVIDE A DETAIL FOR THE HANDRAILS.NO EXTENSIONS
 SHOWN.SEE FBC11-4.8.5.
  
 4.)ALL INFORMATION REQUIRED BY FAC61G16-23.002
 REQUIRED ON EACH SHEET (ENGINEER).

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-01-02 Cont ID  
Sent By adarroug Date 2007-01-02 Time 16:20 Rev Time 0.00
Received By adarroug Date 2007-01-02 Time 16:20 Sent To B
Notes
2007-01-02 16:21:11TO "MISC" BOX#1

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-26 Cont ID  
Sent By shill Date 2007-01-26 Time 15:01 Rev Time 0.00
Received By shill Date 2006-12-19 Time 15:40 Sent To  
Notes
2006-12-19 15:40:22TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status N Date 2006-12-29 Cont ID  
Sent By mflis Date 2006-12-29 Time 10:34 Rev Time 0.00
Received By mflis Date 2006-12-29 Time 10:34 Sent To  
Notes
2006-12-29 10:35:07REVIEWED - NOT REQUIRED
  
 TEMPORARY CONSTRUCTION DECK; ACCESSORY TO CONSTRUCTION
 TRAILERS.
  