Plan Review Details - Permit 06120507
Plan Review Stops For Permit 06120507
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-01-04 Cont ID  
Sent By dpalmer Date 2007-01-04 Time 16:23 Rev Time 0.00
Received By dpalmer Date 2007-01-04 Time 16:09 Sent To PC
Notes
2007-01-04 16:25:40REDLINED, GROUNDING ELECTRODE MAY BE STRANDED.
  
 ALSO REDLINED, DIRECT BURIAL CABLE NOT PERMITTED AT
 THIS TIME.590

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-01-03 Cont ID  
Sent By dpalmer Date 2007-01-03 Time 15:42 Rev Time 0.00
Received By dpalmer Date 2007-01-03 Time 15:42 Sent To PC
Notes
2007-01-03 15:46:20** UNSAT 2ND REVIEW
  
 PERMIT # 06120507 TEMPORARY ELECTRICAL SERVICE.
  
 ** PLEASE SEE AS THE RISE HAS BEEN REVISED IN MANY
 ASPECTS, PLEASE SEE SOME COMMENTS ARE NEW AND SOME ARE
 FROM THE PREVIOUS REVIEW.
  
 1) NOTE: PLEASE SEE 240.21C FOR TAPED CONDUCTORS FROM
 THE TRAILER COMPOUND GUTTER TO THE PANEL. PLEASE SEE
 THE CONDUCTOR SIZES ARE SHOWN AS #8'S TO A 100AMP MAIN
 CIRCUIT BREAKER. PLEASE KNOW THESE ARE NOT BEING SHOWN
 AS ALUMINUM OR COPPER; HOWEVER IN EITHER CASE IF
 ALUMINUM THEY ARE ONLY RATED AT 40AMPS, IF COPPER THEY
 ARE ONLY RATED AT 50AMPS.
 PLEASE SEE 110.4, 240.21C, 240.4 AND 310.16.
  
 2) NOTE: PLEASE SEE THE FEEDER NOTATION #7 WHICH IS
 MISSING WHAT IS EITHER A PHASE CONDUCTOR OR A NEUTRAL
 CONDUCTOR FOR THIS SEPARATELY DERIVED SYSTEM. PLEASE
 SEE THAT ALL EQUIPMENT ON THE SECONDARY SIDE OF THIS
 TRANSFORMER REQUIRES A NEUTRAL.
 PLEASE SEE 250.24B, 250.30, 250.20 ETC.
  
 3) NOTE: PLEASE SEE RISER IS MISSING THE CONDUCTORS ON
 THE SECONDARY SIDE OF THE MAIN DISCONNECT GOING INTO
 GUTTER AT TRAILER COMPOUND.
 RISER SHOWS THIS TO BE 3-PHASE, YET ONLY 3-PHASE
 UN-GROUNDED CONDUCTORS AND AN EQUIPMENT GROUNDING
 CONDUCTOR IS BEING SHOWN.
  
 4) NOTE: PLEASE SEE THE CONDUCTORS ON THE PRIMARY SIDE
 OF THE TRANSFORMER WHICH IS SHOWN AS FEEDER NOTE #5
 WHICH IS MISSING A HOT/PHASE CONDUCTOR.
 THIS IS BEING SHOWN AS A THREE PHASE SERVICE.120/208V
 3-PHASE FROM THE 277/480V THREE PHASE TRANSFORMER.
  
 5) NOTE: PLEASE SEE THE MAIN GROUNDING ELECTRODE
 CONDUCTOR SHALL BE SIZED PER 250.66 AS NOTED. PLEASE
 SEE A 3/0 MIN IS REQUIRED.
 PLEASE ALSO SEE 250.64C AND NOTE HOW ALL PF THESE
 GROUNDING ELECTRODE ARE GOING TO BE CONNECTED.
  
 6) NOTE: PLEASE INDICATE THE LOAD ON THE SECONDARY SIDE
 OF THE TRANSFORMER AND MAIN FEEDING THE GUTTER. BASED
 ON THE LOAD SHOWN ON EACH PANEL SUBMITTED FOR THE
 TRAILERS AND THE PANEL ON THE RISER WHICH SHOWS 43
 AMPS, PLEASE SEE THAT THE LOAD IS BEING SHOWN AT
 334AMPS AND THE OVER CURRENT PROTECTION IS 300AMPS. IF
 THERE IS LOAD CALCULATIONS WHICH INDICATE A LESSER
 LOAD, PLEASE SUBMIT OR ADJUST THE OVER CURRENT
 PROTECTION.
 PLEASE SEE 220, 240, 310.16, 240.4 ETC
  
 7) NOTE: PLEASE SEE THAT THE CONDUITS WHICH ARE
 REQUIRED TO SLEEVE THE DIRECT BURIAL CABLE IS TO BE
 PLACED A MIN OF 24" BELOW THE GRADE, WHERE RISER IN
 SOME PLACES SHOWS THE CONDUIT TERMINATING ABOVE
 GRADE.300 THIS CAN BE REDLINED, AS THESE WILL BE FUTURE
 FOR THE ONES AS SHOWN ON RISER AT THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-12-21 Cont ID  
Sent By dpalmer Date 2006-12-21 Time 18:26 Rev Time 0.00
Received By dpalmer Date 2006-12-20 Time 20:36 Sent To P
Notes
2006-12-21 18:31:08** UNSAT **
  
  
 ** PLEASE SEE PLANS ARE BEING ROUTED TO PLUMBING FOR
 REVIEW AS ELECTRICAL AND PLUMBING WERE SUBMITTED
 TOGETHER. CALLED CATALFUMO REP TO LET THEM KNOW
 ELECTRICAL COMMENTS WERE ONLINE.
  
 1) NOTE: PLEASE SEE 240.21C AS TAPPED CONDUCTORS ON THE
 SECONDARY SIDE OF THE TRANSFORMERS SHALL TERMINATE IN A
 SINGLE MEANS OF OVER CURRENT PROTECTION.
 PLEASE SEE ALL TAPS GOING INTO GUTTERS AS SHOWN ARE NOT
 PERMITTED.
  
 2) NOTE: PLEASE INDICATE TWO GROUND RODS ON THE
 SECONDARY SIDE OF ALL TRANSFORMER FOR THE SD SYSTEM PER
 250.20, 250.30, 250.56
  
 3) NOTE: PLEASE SEE MISSING COLD WATER AS PART OF THE
 GROUNDING ELECTRODE SYSTEM.
 250.50
  
 4) NOTE: PLEASE PROVIDE INFORMATION ON TYPE OF DB CABLE
 BEING INSTALLED.
 PLEASE SEE 590.4
 CONDUCTORS SHALL BE PERMITTED WITHIN CABLE ASSEMBLIES
 OR WITHIN MULTI-CONDUCTOR CORDS OR CABLES OF A TYPE
 IDENTIFIED IN TABLE 400.4 FOR HARD USAGE OR EXTRA-HARD
 USAGE.
 PLEASE ALSO SEE SECTION WHICH SPEAKS OF CABLE.
  
 5) NOTE: PLEASE SEE LOAD CALCULATIONS FOR MAIN 4 OF 5
 ARE NOT COMPLETE. PLEASE THERE IS A PANEL WHICH FEEDS
 LIGHTING, CRANE LIGHTS ETC WHICH IS NOT FIGURED OR
 SHOWN. PLEASE ALSO SEE PREVIOUS COMMENTS WITH RESPECT
 TO TAPS.
  
 6) NOTE: PLEASE SEE NO HAND DRAWN CHANGES MAY BE DONE
 TO PLANS WHICH ARE SIGNED, DATED AND SEALED BY AN
 ENGINEER.
 FS 471.025
  
 7) NOTE: PLEASE SEE POWER AS SHOWN WHICH WILL BE ON THE
 SECONDARY SIDES OF THE CITY HALL, LIBRARY AND GARAGE
 TRANSFORMER IS BEING SHOWN FOR FUTURE PANELS ETC,
 HOWEVER NO MEANS OF DISCONNECT AND OCP IS BEING SHOWN
 ON THE SECONDARY SIDE.
 PLEASE TERMINATE IN A SINGLE MEANS OF OCP WHICH LIMITS
 THE OCP ON THE CONDUCTORS, TRANSFORMER ETC.
 PLEASE SEE 240.21C ETC
  
 8) NOTE: PLEASE SEE 250.66 FOR SIZING OF THE GROUNDING
 ELECTRODE CONDUCTOR(S) ON THE TRANSFORMER. MOST ARE
 OK.
  
 9) NOTE: PLEASE SEE 450.3B FOR THE MAX OCP ON THE
 PRIMARY SIDE OF TRANSFORMERS. PLEASE SEE TRANS #1 AS
 THE OCP IS TOO HIGH. ( OR ) PLEASE SEE EXCEPTIONS AND
 PROVIDE INFORMATION ON THE TYPE OF UNIT BEING
 INSTALLED.
  
 10) NOTE: PLEASE PROVIDE A LAYOUT/SITE PLANS WHICH
 INDICATES THE LOCATIONS OF ALL SERVICE EQUIPMENT BEING
 INSTALLED AND PROPOSED.
 FBC 106.1.2 ADMIN SECTION
  
 11) NOTE: PLEASE SEE THE VALUE FOR COMPLETE SCOPE OF
 WORK FOR THE SERVICE AS SHOWN AND BEING PROPOSED SHALL
 INCLUDE ALL LABOR AND MATERIALS, EVEN IF MATERIALS WERE
 OWNER SUPPLIED. PLEASE KNOW IF NOT ADJUSTED FOR VALUE,
 ONE WILL BE ADJUSTED USING MARSHALL?S AND SWIFT GUIDE
 AS ADOPTED PER THE FBC 108.3 ADMIN SECTION.
  
 12) NOTE: PLEASE SUPPLY INFORMATION ON TRAILERS BEING
 INSTALLED FOR LOADS. THE LOAD AS SHOWN ON RISER CAN NOT
 BE VERIFIED AS THE TRAILERS THEMSELVES ARE NOT
 PERMITTED.
 220, 215.5, ETC
  
 13) NOTE: PLEASE INDICATE CONTINUOUS LOADS AT 125%.
 PLEASE SEE LOAD AS SHOWN IS EXACTLY AT THE RATING OF
 THE SEC?S WHICH ARE BEING INSTALLED. PLEASE AS
 CONTINUOUS LOADS AND OTHER FACTORS HAVE NOT BEEN TAKEN
 OR SHOWN INTO CONSIDERATION THE SIZE OF THE SEC?S DO
 NOT SUPPLY ANY ROOM FOR ANY FUTURE LOADS.?
 215.3, 230.42 , 310.16, 240.4, ETC
  
 14) NOTE:PLEASE SEE RISER SEEMS TO IDENTIFY A
 "GROUND" "G" FROM FPL TO GUTTER AND FROM GUTTER TO ALL
 FIRST MEANS OF DISCONNECTS? PLEASE SEE THIS IS THE SAME
 SYMBOL BEING USED ON ALL OTHER LOCATIONS FOR GROUNDS
 ALSO. PLEASE CLARIFY AS THIS SHOULD BE SHOWN AS THE
 NEUTRAL OR "GROUNDED" CONDUCTOR AS THERE ARE NO
 EQUIPMENT GROUNDING CONDUCTORS BEFORE THE FIRST MEANS
 OF DISCONNECT. 250.6, 250.24B.
 PLEASE PROVIDE COMPLETE NEUTRAL LOAD CALCULATIONS AS
 THE NEUTRAL CONDUCTOR(S) FOR THE SERVICE ENTRANCE
 CONDUCTORS AND FEEDERS ARE SUBSTANTIALLY DECREASED.
 PLEASE INDICATE HOW AND WHERE THE LOAD FOR THE NEUTRAL
 WAS DERIVED AND SHOW ON PLANS IN ORDER TO VERIFY THE
 CORRECT SIZING OF THE CONDUCTORS AS SHOWN.
  
 15) NOTE: PLEASE SEE LABELING OF MAINS SHALL BE AS
 FOLLOWS, 1 OF 5, 2 OF 5 ETC.
 PLEASE SEE RISER NOW SHOWS WHAT APPEARS TO BE A
 MISPRINT OF 105,205,305, ETC
  
 16) NOTE: PLEASE SEE BASED ON THE NUMBER OF CONDUCTORS
 BEING SHOWN ON THE SECONDARY SIDE OF THE TRANSFORMER TO
 GUTTER THESE ARE ONLY SINGLE PHASE BEING BROUGHT TO
 GUTTERS???
 PLEASE SEE PANEL FROM GUTTER WHICH INDICATES A THREE
 PHASE FEED??
 PLEASE KNOW AS THIS TIME THE RISER IS VERY CONFUSING AS
 THREE PHASES ARE BEING BROUGHT TO TRANSFORMERS AND ONLY
 SINGLE PHASE BEING BROUGHT OUT?
 THERE ARE TOO MANY CODE SECTIONS TO PLACE FOR THIS
 NOTE, PLEASE SEE NEC 2005.
  
 17) NOTE: PLEASE SEE THE MINIMUM SIZE OF THE GROUNDING
 ELECTRODE CONDUCTOR SHALL BE SIZED PER 250.66.
  
 ** PLEASE KNOW AS THERE ARE ITEMS ON RISER WHICH WILL
 BE CHANGING, THERE MAY BE COMMENTS ON FUTURE ELECTRICAL
 RISER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-01-03 Cont ID  
Sent By adarroug Date 2007-01-03 Time 09:09 Rev Time 0.00
Received By adarroug Date 2007-01-03 Time 09:09 Sent To E
Notes
2007-01-03 09:10:16TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-12-21 Cont ID  
Sent By   Date 2006-12-21 Time   Rev Time 0.00
Received By adarroug Date 2006-12-19 Time 15:38 Sent To  
Notes
2006-12-19 15:38:54TO "E" BOX