Plan Review Details - Permit 06120504
Plan Review Stops For Permit 06120504
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-27 Cont ID  
Sent By adarroug Date 2006-12-27 Time 10:32 Rev Time 0.00
Received By adarroug Date 2006-12-27 Time 10:32 Sent To M
Notes
2006-12-27 10:32:47TO "TGORDON" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-12-21 Cont ID  
Sent By tgordon Date 2006-12-21 Time 09:53 Rev Time 0.00
Received By tgordon Date 2006-12-19 Time 14:49 Sent To  
Notes
2006-12-19 14:49:33TO 'M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-12-27 Cont ID  
Sent By tgordon Date 2006-12-27 Time 16:36 Rev Time 0.45
Received By tgordon Date 2006-12-27 Time 16:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-12-21 Cont ID  
Sent By tgordon Date 2006-12-21 Time 09:53 Rev Time 0.30
Received By tgordon Date 2006-12-21 Time 09:53 Sent To  
Notes
2006-12-21 10:00:48*** DENIED ***
 1) A MECHANICAL PERMIT WAS ALREADY ISSUED FOR THIS WORK
 TO ACTION MECHANICAL, PERMIT # 06060520. THIS PERMIT
 NEEDS TO BE CLOSED OR WILL NEED A CHANGE OF CONTRACTOR
 WILL NEED TO BE FILED.
  
 2) RETURN AIR TRANSFER GRILLS TO BEDROOMS ARE TO SMALL.
 BALANCED RETURN AIR MAY BE ACHIEVED BY.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.