Plan Review Details - Permit 06120501
Plan Review Stops For Permit 06120501
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-01-02 Cont ID  
Sent By rmcdouga Date 2007-01-02 Time 08:07 Rev Time 0.00
Received By rmcdouga Date 2007-01-02 Time 08:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-12-19 Cont ID  
Sent By rmcdouga Date 2006-12-19 Time 07:55 Rev Time 0.00
Received By rmcdouga Date 2006-12-19 Time 07:55 Sent To  
Notes
2006-12-19 08:10:22DENIED BY BUILDING
  
 1) THE MAXIMUM DESIGN PRESSURE FOR THE SYSTEM INDICATED
 ON THE PRODUCT APPROVAL IS -52.5, WHICH IS TOO LOW FOR
 THE PERIMETER AND CORNER ZONES ROOF ZONES FOR A
 BUILDING WITH A 12' MEAN ROOF HEIGHT. ENHANCED
 FASTENING IS REQUIRED. SEE LIMITATION NUMBER 7. SUBMIT
 RAS 117 CALCULATIONS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  