Plan Review Details - Permit 06120434
Plan Review Stops For Permit 06120434
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-02-29 Cont ID  
Sent By rmcdouga Date 2008-02-29 Time 09:21 Rev Time 0.00
Received By rmcdouga Date 2008-02-29 Time 07:03 Sent To  
Notes
2008-02-29 07:13:41BUILDING PROVISO
  
 PROVIDE A COPY OF TRUSS LAYOUT AND TRUSS DRAWINGS WITH
 THE TRUSS ENGINEER'S ORIGINAL WET SIGNATURE AND RAISED
 SEAL TO THE BUILIDING INSPECTOR IN THE FIELD AT THE
 TRUSS FRAMING INSPECTION, TO BE BROUGHT IN AND PLACED
 IN THE FILE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-08-06 Cont ID  
Sent By rmcdouga Date 2007-08-06 Time 08:41 Rev Time 0.00
Received By rmcdouga Date 2007-08-03 Time 16:37 Sent To  
Notes
2007-08-03 19:11:032004 FBC EXISTING BUILDING
 STRUCTURALS REPAIRS
 SECOND REVIEW
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE ENERGY CALCULATION FORMS SPECIFIES R 8.9 FOR THE
 WALLS AND THE PLANS SPECIFY R-11 ON S-1. PLEASE
 COORDINATE.
  
 3) SPECIFY THE REQUIRED LOAD BEARING CAPACITY OF THE
 SOIL IN POUNDS PER SQUARE FOOT, BASED ON THE DESIGN OF
 THE STRUCTURE. SEE NUMBER 12 FROM PREVIOUS REVIEW. SEE
 FBC 106.1.2 AND R401.
  
 4) SPECIFY THE SPACING OF THE ROOF TRUSS ON THE PLANS.
 SEE NUMBER 16 FROM PREVIOUS REVIEW. FBC 106.1.2
  
 5) THE TRUSS DRAWINGS REQUIRE CONNECTIONS TO BEARING
 FOR 2465 LBS. HORIZONTAL REACTION. PLEASE REVIEW THE
 TRUSS DRAWINGS AND SPECIFY ADEQUATE CONNECTIONS ON THE
 ROOF FRAMING PLAN. SEE COMMENT NUMBER 17 FROM LAST
 REVIEW.
  
 6) THE TRUSS DRAWINGS ARE REQUIRED TO HAVE THE ORIGINAL
 SIGNATURE OF THE TRUSS ENGINEER. PHOTO COPIED
 SIGNATURES OR STAMPS ARE NOT ACCEPTABLE. SEE FS471. SEE
 # 18 ON LAST REVIEW. THE TRUSS LAYOUT DOES HAVE THE
 TRUSS ENGINEER'S ORIGINAL SIGNATURE, HOWEVER, THE TRUSS
 DRAWINGS HAVE PHOTO COPIED SIGNATURES.
  
 7) THE APPROVED ROOFING SYSTEM AND FASTENING OPTION
 SELECTED FOR THE GAF MODIFIED ROOF SYSTEM HAS A DESIGN
 PRESSURE OF -45 PSF WHICH IS TOO LOW FOR THE PERIMETER
 AND CORNER ROOF AREAS. SUBMIT RAS 117 CALCULATIONS FOR
 ENHANCED FASTENING IN THESE AREAS AS ALLOWED BY
 LIMITATION NUMBER 7 ON PAGE 32 OF THE NOA. SEE NUMBER
 20 ON LAST REVIEW.
  
 8)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. THE PRODUCT APPROVAL FOR
 THE ROOFING MATERIAL HAS NOT BEEN APPROVED IN WRITING
 BY THE D.O.R.
  
 9) THE PLANS SPECIFY THAT THE WINDOWS AND DOORS WILL BE
 IMPACT RATED. THE PRODUCT APPROVALS THAT WERE SUBMITTED
 FOR THE WINDOWS AND DOORS HAVE NO MISSLE IMPACT RATING.
 PLEASE CORRECT. NOTE: IF NOT USING IMPACT RATED
 PRODUCTS, SUBMIT PRODUCT APPROVALS FOR STORM PANELS
 ALONG WITH A KEY PLAN AND INSTALLATION SCHEDULE.
  
 10) THE INFORMATION SUBMITTED FROM INTERTEK IS NOT
 ACCEPTABLE. THE PRODUCT ARE REQUIRED TO HAVE STATE
 APPROVAL OR MIAMI-DADE APPROVAL. THE MANUFACTURER CAN
 APPLY FOR LOCAL PRODUCT APPROVAL IN COMPLIANCE WITH
 RULE 9B-72.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-02-27 Cont ID  
Sent By rmcdouga Date 2007-02-27 Time 09:42 Rev Time 0.00
Received By rmcdouga Date 2007-02-27 Time 06:30 Sent To  
Notes
2007-02-27 12:14:01DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED. A NEW NOC WITH THE NEW
 CONTRACTOR'S NAME IS REQUIRED.
  
 2) THE STRUCTURE IS 22'X 37' WHICH IS 814 SQFT.
 PLEASE REVISE SHEET A1.
  
 3) THE WRONG ENERGY CALCULATION FORM WAS SUBMITTED.
 THIS IS A SINGLE FAMILY RESIDENCE. THE STRUCTURE IS 814
 SQUARE FEET.
  
 4) SPECIFY THE CEILING INSULATION ON THE PLANS. SPECIFY
 R VALUE.
  
 5) SHOW COMPLIANCE WITH R403.1.4 MINIMUM DEPTH.
 ALL EXTERIOR FOOTINGS SHALL BE PLACED AT LEAST 12
 INCHES (305 MM) BELOW THE UNDISTURBED GROUND SURFACE.
  
 6) SHOW COMPLIANCE WITH R404.1.6 HEIGHT ABOVE FINISHED
 GRADE.
 CONCRETE AND MASONRY FOUNDATION WALLS SHALL EXTEND
 ABOVE THE FINISHED GRADE ADJACENT TO THE FOUNDATION AT
 ALL POINTS A MINIMUM OF 4 INCHES (102 MM) WHERE MASONRY
 VENEER IS USED AND A MINIMUM OF 6 INCHES (152 MM)
 ELSEWHERE
  
 7) SHOW COMPLIANCE WITH SECTION 704
 INSPECTION FOR TERMITES
 IN ORDER TO PROVIDE FOR INSPECTION FOR TERMITE
 INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL COVERINGS
 AND FINAL EARTH GRADE ON THE EXTERIOR OF A BUILDING
 SHALL NOT BE LESS THAN 6 INCHES (152 MM).
 EXCEPTIONS:
 1.PAINT OR DECORATIVE CEMENTITIOUS FINISH LESS
 THAN 5 / 8 INCH (17.1 MM) THICK ADHERED DIRECTLY TO THE
 MASONRY FOUNDATION SIDEWALL.
 2.ACCESS OR VEHICLE RAMPS WHICH RISE TO THE
 INTERIOR FINISH FLOOR ELEVATION FOR THE WIDTH OF SUCH
 RAMPS ONLY.
 3.A 4-INCH (102 MM) INSPECTION SPACE ABOVE PATIO
 AND GARAGE SLABS AND ENTRY AREAS.
 4.IF THE PATIO HAS BEEN SOIL TREATED FOR TERMITES,
 THE FINISH ELEVATION MAY MATCH THE BUILDING INTERIOR
 FINISH FLOOR ELEVATIONS ON MASONRY CONSTRUCTION ONLY.
 5.MASONRY VENEERS.
  
 8)SHOW COMPLIANCE WITH SECTION R319 PROTECTION
 AGAINST DECAY
 R319.1 LOCATION REQUIRED.
 IN AREAS SUBJECT TO DECAY DAMAGE AS ESTABLISHED BY
 TABLE R301.2(1) , THE FOLLOWING LOCATIONS SHALL REQUIRE
 THE USE OF AN APPROVED SPECIES AND GRADE OF LUMBER,
 PRESSURE TREATED IN ACCORDANCE WITH AWPA C1, C2, C3,
 C4, C9, C15, C18, C22, C23, C24, C28, C31, C33, P1, P2
 AND P3, OR DECAY-RESISTANT HEARTWOOD OF REDWOOD, BLACK
 LOCUST, OR CEDARS.
 5.WOOD SIDING, SHEATHING AND WALL FRAMING ON THE
 EXTERIOR OF A BUILDING HAVING A CLEARANCE OF LESS THAN
 6 INCHES (152 MM) FROM THE GROUND.
  
 9)SHOW COMPLIANCE WITH R320.7 PROTECTION AGAINST
 TERMITES AND DECAY. CONDENSATE LINES AND ROOF
 DOWNSPOUTS SHALL DISCHARGE AT LEAST 1 FOOT AWAY FROM
 THE STRUCTURE SIDEWALL, WHETHER BY UNDERGROUND PIPING,
 TAIL EXTENSIONS OR SPLASH BLOCKS. GUTTERS WITH DOWN
 SPOUTS ARE REQUIRED ON ALL BUILDINGS WITH EAVES OF LESS
 THAN 6 INCHES HORIZONTAL PROJECTION EXCEPT FOR GABLE
 END RAKES OR ON A ROOF ABOVE ANOTHER ROOF.
  
 10)SECTION A-B ON S1 SHOULD SPECIFY CDX (EXTERIOR
 GRADE) PLYWOOD. PLEASE CORRECT.
  
 11) PLEASE SPECIFY THAT THE NEW STUCCO IS TO BE APPLIED
 OVER METAL LATH WITH AN ACCEPTABLE MOISTURE BARRIER.
 SEE ASTM C 926, ASTM C 1063 AND FBC R703.
  
 12)SPECIFY THE REQUIRED SOIL BEARING CAPACITY OF THE
 SOIL ON THE PLANS.
  
 13) SECTION R806
 ROOF VENTILATION
  
 14) SHOW COMPLIANCE WITH R806.1 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN. VENTILATING OPENINGS SHALL BE
 PROVIDED WITH CORROSION-RESISTANT WIRE MESH, WIT H 1 /
 8 INCH (3.2 MM) MINIMUM TO ? INCH (6.4 MM) MAXIMUM
 OPENINGS.
  
 15)ROOF SHEATHING IS REQUIRED TO BE IN ACCORDANCE
 WITH SECTION R803.2.3.1 OF 2006 REVISIONS TO 2004 FBC
 RESIDENTIAL CODE. WOOD STRUCTURAL PANEL SHEATHING SHALL
 BE FASTENED TO ROOF FRAMING WITH 8D RING-SHANK NAILS AT
 6 INCHES ON CENTER AT EDGES AND 6 INCHES ON CENTER AT
 INTERMEDIATE FRAMING. SPACING OF RING-SHANK FASTENERS
 SHALL BE 4 INCHES ON CENTER IN NAILING ZONE 3 FOR 130
 MPH OR GREATER DESIGNWIND SPEEDS IN ACCORDANCE WITH
 FIGURE R803.2.3.1. REVISE NOTE ON S1.
  
 16) SPECIFY THE SPACING OF THE ROOF TRUSSES ON THE
 PLANS. IF THE ROOF TRUSSES ARE 24" OC AND THE WALL STUD
 SPACING IS 16" OC, THE TS12 STRAPS THAT ARE SPECIFIED
 FROM THE STUDS TO THE TRUSSES WILL NOT WORK.
  
 17) THE SIMPSON TS12 STRAPS THAT ARE SPECIFIED HAVE NO
 VALUE SPECIFIED IN THE CATALOG FOR LATERAL LOADS.
  
 18) THE TRUSS DRAWINGS ARE REQUIRED TO HAVE THE
 ORIGINAL SIGNATURE OF THE TRUSS ENINEER. PHOTO COPIED
 SIGNATURES OR STAMPS ARE NOT ACCEPTABLE. SEE FS 471.
  
 19)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE.
  
 20) SUBMIT PRODUCT APPROVALS FOR THE FLAT ROOF
 COVERING. INDICATE WHICH ONE OF THE APPROVED ASSEMBLIES
 LISTED IN THE PRODUCT APPROVAL WILL BE INSTALLED.
 INDICATE THE FASTENING OPTION AND DESIGN PRESSURE THAT
 WILL BE USED. CIRCLE THE APPROPRIATE ITEMS ON THE
 PRODUCT APPROVALS. IF ENHANCED FASTENING IS REQUIRED
 FOR PERIMETER OR CORNER AREAS, SUBMIT RAS 117
 CALCULATIONS.
  
 21) GLAZED OPENINGS ARE REQUIRED TO HAVE IMPACT
 PROTECTION PER R301.2.1.2. THE PLANS INDICATE THAT THIS
 WILL BE DONE BY OTHERS UNDER A SEPARATE PERMIT. PLEASE
 NOTE THAT ADDITIONAL FEES WILL BE REQUIRED AND THIS
 PERMIT CAN NOT BE FINALED UNTIL THE STORM PANELS HAVE
 BEEN INSTALLED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-07-30 Cont ID  
Sent By dpalmer Date 2007-07-30 Time 15:22 Rev Time 0.00
Received By dpalmer Date 2007-07-30 Time 14:49 Sent To M
Notes
2007-07-30 15:23:03*** REDLINED PLANS***
  
 1) NOTE: PANEL SCHEDULE DOES NOT INDICATE AFCI
 PROTECTION FOR SMOKE ALARMS. 210.12
  
 2) NOTE: DRYER/WASHER COMBO INDICATES 3KW ON PANEL
 SCHEDULE AND SHOWS 5.5KW ON LOAD CALCULATIONS. MIN PER
 220.54 OF 5KW REQUIRED.
  
 3) NOTE: PLEASE SEE ONE SET, RISER HAS 3/0 CONDUCTORS
 HAND DRAWN FOR FEEDERS AND ONE SET HAS 2/0 FOR THE SAME
 FEEDERS?
 EITHER MEET 310.16, HOWEVER PLANS NEED TO BE REVISED
 ONCE INSTALLED FOR RECORD OF INSTALLATION.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-01-12 Cont ID  
Sent By dpalmer Date 2007-01-12 Time 08:47 Rev Time 0.00
Received By dpalmer Date 2007-01-12 Time 07:02 Sent To Z
Notes
2007-01-12 08:50:10*** UNSAT ***
  
 1) NOTE:
  
 A) PLEASE KNOW THAT THE PLANS WILL BE ROUTED TO ZONING
 FOR DETERMINATION OF THE NEW SERVICE/METER BEING SHOWN
 ON PLANS.
  
 B) PLEASE ALSO KNOW THAT THIS PLAN IS BEING REVIEWED AS
 BEING PERMITTED AND SHOWN AS A DWELLING UNIT. PLEASE
 KNOW AT THIS TIME, DEPENDING ON ZONING OUTCOME, THERE
 MAY BE CHANGES REQUIRED WHICH WILL CHANGE THE
 ELECTRICAL COMMENTS IF NOT PERMITTED AS A DWELLING
 UNIT.
  
  
 2) NOTE: PLEASE SEE MISSING MAIN DISCONNECT FOR
 SERVICE. PLEASE SEE PANEL IS BEING SHOWN A MLO AND NO
 MAIN DISCONNECT IS BEING SHOWN OUTSIDE?
 230.70, 230.71, 240.4, 310.16
  
 3) NOTE: PLEASE SEE 250.6 AND 250.24B AS AN EQUIPMENT
 GROUNDING CONDUCTOR IS BEING SHOWN GOING TO THE PANEL
 P. PLEASE KNOW WITH THE RISER SHOWN, THIS IS NOT
 PERMITTED.
  
 4) NOTE: PLEASE SEE MISSING FOOTER STEEL WHICH IS TO BE
 PART OF THE GROUNDING ELECTRODE SYSTEM. 250.50.
  
 5) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE
 REFLECTED ON PLANS AS REQUIRED.
 2005 NFPA-70, 2002 NFPA-72.
  
 6) NOTE:PLEASE SUBMIT LOAD CALCULATIONS PER NEC
 220.82, 220.52 ETC
 THE LOAD CALCULATIONS AS SHOWN ARE NOT CODE COMPLIANT.
 PLEASE SHOW.
 FBC 106.1.2, 106.3.5.4(8)
  
 7) NOTE: PLEASE SEE NFPA-72 11-5.1.1, 11.8.3. PLEASE
 SEE NFPA-72 DEFINITIONS AS PLANS CALL FOR SD FOR SMOKE
 DETECTORS THIS IS OK, HOWEVER PLEASE KNOW IF THESE ARE
 INDEED SMOKE DETECTORS AS DEFINED IN NFPA72, THESE
 WOULD BE DEVICES WHICH ONLY DETECT AND WOULD SIGNAL TO
 OTHER ALARM/HORN DEVICES. NO ALARM HORN DEVICES ARE
 SHOWN. PLEASE INDICATE IF PART OF A FUTURE LV FA
 SYSTEM.
 PLEASE KNOW AS PER SECTIONS GIVEN IF THESE ARE INDEED
 DEVICES WHICH DETECT AND ALSO SOUND AN ALARM, THEN THEY
 WOULD BE LABELED AS SA FOR SMOKE ALARMS.
 PLEASE KNOW AS OF OCT 06 IT CAME TO OUR ATTENTION AT
 THE SOUTHERN SECTION MEETING FROM NFPA THAT IF UNITS
 ARE INDEED DEVICES WHICH DETECT AND SOUND AN ALARM,
 PLANS SHOULD SHOW THEM AS SA'S AND THIS IS NOT NEW
 CODE. THIS HAS BEEN AN ACCEPTED METHOD IN THE PAST TO
 SHOW SD FOR BOTH HOWEVER ALL PLANS SINCE OCT 06 SHOULD
 BE CHANGING IF AND WHERE APPLICABLE.
 IF PART OF A LV FIRE/SECURITY SYSTEM PLEASE INDICATE AS
 SUCH. PLEASE SHOW DEVICES THEN FOR SOUNDING.
  
 ** PLEASE ALSO SEE MISSING SMOKE ALARMS OUTSIDE
 BEDROOMS FOR EACH SLEEPING ROOM.
 ** PLEASE ALSO SEE SMOKE ALARMS AS SHOWN ARE BEING
 SHOWN WIRED TO MULTIPLE CIRCUITS WHICH IS NOT POSSIBLE
 AS THE CODE REQUIRES THEM TO BE WIRED INLINE, WHICH
 WOULD BE THAT THEY WERE ON THE SAME CIRCUIT.
 ABOVE PER 11.5.1.1
  
 8) NOTE: PLEASE SEE THE BATH(S) ARE REQUIRED TO MEET
 210.52D AND 210.11C3. PLEASE SEE THE CIRCUITING SHOWS
 THEM ON THE KITCHEN CIRCUITS AND BOTH WIRED TOGETHER?
 PLEASE CORRELATE WITH PANEL SCHEDULE.
  
 9) NOTE: PLEASE SEE PANEL SCHEDULE SHOWS CIRCUIT 14 FOR
 KITCHEN. 210.11C1, 408.4 ETC
 FBC 106.1.2, 106.3.5.4 (8)
  
 10) NOTE: PLEASE SEE PANEL SCHEDULE SHOWS CIRCUIT 16
 FEEDING BATHS WHERE PLANS CONTAIN THIS CIRCUIT IN THE
 LIVING ROOM.(HOWEVER BOTH ARE NOT PERMITTED ON THE
 SAME CIRCUIT)
 408.4, 310.16, 210.11C3
  
 11) NOTE: PLEASE SHOW ALL COUNTER SPACES IN THE
 KITCHEN. COMPLIANCE WITH 210.52C1 CAN NO BE DONE AT
 THIS TIME.
  
 12) NOTE: PLEASE SEE IF THIS IS A KITCHEN AS PERMITTED
 FOR A DWELLING, PLEASE SEE MISSING TWO SMALL APPLIANCE
 CIRCUITS AS REQUIRED PER 210.52B1, 210.11C1, 220.52A
 PLEASE KNOW THAT NO OUTLETS OTHER THAN AS PERMITTED PER
 210.52B1 ARE PERMITTED ON THESE CIRCUITS. PLEASE SEE
 OUTSIDE GFI RECEPT ETC.
  
 13) NOTE: PLEASE SEE MISSING WP GFI'S PER 210.52E FRONT
 AND REAR OF DWELLING. (IF THIS APPLIES).
  
 14) NOTE: PLEAS SEE PANEL SCHEDULE CIRCUIT 12, WHICH IS
 SHOWN ON PLANS FOR KITCHEN OUTLETS AND PANEL SHOWS THIS
 PART OF THE WASHER/DRYER UNIT?
 PLEASE CORRELATE CIRCUITING AND PANEL SCHEDULE.
 408.4, 310.16,
 FBC 106.1.2, 106.3.5.4(8).
  
 15) NOTE: PLEASE SEE PLANS ONLY INDICATE THE
 WASHER/DRYER STACK UNIT AS BEING ON A 1-POLE CIRCUIT?
 PLEASE CORRELATE CIRCUITING.
 FBC106.1.2. NEC 408.4, 310.16 ETC
  
 16) NOTE: PLEASE SEE 210.4B AS THE DISHWASHER AND
 DISPOSAL ARE FED BY SINGLE POLE BREAKERS WHICH ARE NOT
 PERMITTED.
  
 17) NOTE: PLEASE CLARIFY ALL RECEPTACLES SHOWN IN
 BEDROOMS AS THE ENTIRE DEVICE BEING SWITCHED? PLEASE
 CLARIFY THIS AS IF SWITCH THE ENTIRE DEVICE THEN
 RECEPTS PER 210.52 WILL BE REQUIRED TO BE INSTALLED.
 PLEASE 210.52, 210.70
  
 18) NOTE: PLEASE SEE MISSING RECEPT PER 210.52
  
 19) NOTE: PLEASE SEE THE AHU BEING FED WITH #6 ON A 30A
 BREAKER. PLEASE KNOW THAT #6 WILL NOT FIT UNDER A 30A
 BREAKER.
  
 20) NOTE: PLEASE SEE WATER HEATER CAN NOT BE PLUGGED
 IN. PLEASE SEE SYMBOL ON PLANS CORRELATES WITH A 220
 OUTLET. MUST BE HARDWIRED/
 422.31, 422.30
  
 21) NOTE: PLEASE SEE PLANS ARE NOT, SIGNED, DATED,
 SEALED ETC NO PERSON HAS TAKEN RESPONSIBILITY FOR
 PLANS.
 FBC 106.1, FS 481, FS 471, FS 468 ETC.
  
 ** PLEASE KNOW BASED ON THE PLANS SUBMITTED AND ITEMS
 NOT PROVIDED FOR CODE COMPLIANCE, THERE MAY BE COMMENTS
 ON THE NEXT REVIEW.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-02-21 Cont ID  
Sent By adarroug Date 2008-02-21 Time 17:03 Rev Time 0.00
Received By adarroug Date 2008-02-21 Time 17:03 Sent To B
Notes
2008-02-21 17:03:48TO "RMCDOUGAL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-07-26 Cont ID  
Sent By adarroug Date 2007-07-26 Time 10:57 Rev Time 0.00
Received By adarroug Date 2007-07-26 Time 10:57 Sent To Z
Notes
2007-07-26 10:58:16TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-01-16 Cont ID  
Sent By adarroug Date 2007-01-16 Time 17:33 Rev Time 0.00
Received By adarroug Date 2007-01-16 Time 17:33 Sent To M
Notes
2007-01-16 17:33:51TO "M" BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-28 Cont ID  
Sent By adarroug Date 2006-12-28 Time 10:28 Rev Time 0.00
Received By adarroug Date 2006-12-28 Time 10:28 Sent To E
Notes
2006-12-28 10:28:42TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-27 Cont ID  
Sent By rmcdouga Date 2007-02-27 Time 12:14 Rev Time 0.00
Received By rmcdouga Date 2006-12-17 Time 16:04 Sent To  
Notes
2006-12-17 16:04:40TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-07-30 Cont ID  
Sent By tgordon Date 2007-07-30 Time 15:47 Rev Time 0.25
Received By tgordon Date 2007-07-30 Time 15:47 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-01-17 Cont ID  
Sent By tgordon Date 2007-01-17 Time 14:20 Rev Time 0.45
Received By tgordon Date 2007-01-17 Time 14:20 Sent To P
Notes
2007-01-17 14:36:02*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON FORM 600 FOR
 RESIDENTIAL NOT 400 FOR COMMERCIAL, PER FBC
 13-600.3.ABC.2 .
  
 2) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 3) COULD NOT FIND THE A/C SYSTEM LISTED OR A 16 SEER IN
 THE ARI DIRECTORY, PLEASE SUBMIT DETAILED
 MANUFACTURER'S SPECIFICATION'S FOR AIR CONDITIONING
 SYSTEM.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-08-03 Cont ID  
Sent By mperson Date 2007-08-03 Time 15:39 Rev Time 0.33
Received By mperson Date 2007-08-03 Time 15:39 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-01-22 Cont ID  
Sent By mperson Date 2007-01-22 Time 13:20 Rev Time 0.55
Received By mperson Date 2007-01-22 Time 13:20 Sent To B
Notes
2007-01-22 14:28:39DENIED
 REFERENCE: FBC-2004 PLUMBING; FBC-2004 BUILDING;
 FBC-2004 CHAPTER 1, CITY OF WEST PALM BEACH AMENDMENTS;
  
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET S-1 OF 2 INDICATES EXISTING 6" X 4" SCUPPERS:
 PLEASE PROVIDE A DETAIL OF THE PRIMARY AND THE
 SECONDARY ROOF DRAINAGE SYSTEMS WITH THE FOLLOWING
 INFORMATION A} SQUARE FEET OF ROOF PER TABLE 1106.7. B}
 VERTICAL WALLS (SQUARE FEET) 1106.4. C} VERTICAL
 CONDUCTORS AND LEADERS 1106.2. D} SECONDARY DRAIN
 REQUIRED 1107.1, SEPERATE SYSTEMS REQUIRED 1107.2 AND
 SIZING OF SECONDARY DRAINS 1107.3.
  
 2. PER FBC-2004 BUILDING SECTION 1503.6 PROTECTION
 AGAINST DECAY AND TERMITES: ROOF DOWNSPOUTS SHALL
 DISCHARGE AT LEAST 1 FOOT AWAY FROM THE STRUCTURE
 SIDEWALL WHETHER BY UNDERGROUND PIPING, TAIL
 EXTENSIONS, OR SPLASH BLOCKS. PLEASE COMPLY ON THE
 RESUBMITTAL.
  
 3. SHEET P-1 OF 1 SANITARY RISER DIAGRAM: A} WASHING
 MACHINE BRANCH DRAIN NEEDS TO BE INDICATED A MINIMUM OF
 THREE INCH (3") PER FBC-2004 PLUMBING SECTION 406.3. B}
 CLEANOUT FOR WASHING MACHINE NEEDS TO BE INDICATED AT
 FOUR FEET ABOVE FINNISH FLOOR (4' A.F.F.) PER FBC-2004
 PLUMBING SECTION 708.9. C} SIZE ALL FIXTURE TRAPS PER
 CHAPTER 1 AMENDMENTS SECTION 106.3.5.4. D} PROVIDE TWO
 WAY CLEANOUT AT THE JUNCTION OF THE BUILDING DRAIN AND
 SEWER PER FBC-2004 PLUMBING SECTION 708.3.5.
  
 4. SHEET P-1 OF 1 DOMESTIC WATER ISOMETRIC: POTABLE
 WATER SYSTEM IS SIZED TO SMALL, IT IS SUGGESTED THAT
 FOUR HOT AND TWO COLD PER HALF INCH PIPE OR PROVIDE
 ENGINEERED COPLIANCE TO APPENDIX "E" WATER PIPE SIZING
 TABLES. PLEASE NOTE THAT FLUID VELOCITIES IN EXCESS TO
 5 TO 8 FEET/SECOND NOT USUALLY RECOMENDED.
  
 5. SHEET P-1 OF 1 DOMESTIC WATER ISOMETRIC: PROVIDE
 WATER HAMMER ARRESTORS FOR WASHING MACHINE PER FBC-2004
 PLUMBING SECTION 604.9.
  
 6. IF REQUIRED PLEASE PROVIDE THERMAL EXPANSION
 PROTECTION ON THE WATER HEATER DETAIL ON SHEET P-1 OF 1
 PER FBC-2004 PLUMBING SECTION 607.3.
  
 7.NOTE: PLEASE SEE THAT NOT ALL SHEETS ARE SIGNED,
 DATED, AND SEALED PER FBC 106.1, FS 481, FS 471 ECT...
 NO PERSON HAS TAKEN RESPONSIBILITY FOR SOME SHEETS.
 PLEASE CORRECT ON THE RESUBMITTAL.
  
 **********IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  

Review Stop Z ZONING
Rev No 3 Status P Date 2007-07-26 Cont ID  
Sent By choops Date 2007-07-26 Time 17:02 Rev Time 0.00
Received By choops Date 2007-07-26 Time 17:02 Sent To E
Notes
2007-07-26 17:09:49PROVISO:1) PROPOSED A/C EQUIPMENT SHALL BE A MINIMUM
 OF 1' FROM THE REAR PROPERTY LINE, AND A MINIMUM OF 6'
 FROM THE NORTH SIDE PROPERTY LINE.
 2) NONCONFORMING STRUCTURES OR BUILDINGS SHALL NOT BE
 IMPROVED, CONSTRUCTED, ENLARGED, OR ALTERED IN ANY
 MANNER TO CREATE A NEW NONCONFORMITY OR TO INCREASE AN
 EXISTING NONCONFORMITY, BUT MAY BE IMPROVED,
 CONSTRUCTED, ENLARGED, OR ALTERED AS LONG AS NO NEW
 NONCONFORMITY IS CREATED OR AN EXISTING NONCONFORMITY
 INCREASED...BUILDING SHALL BE PUT BACK IN EXISTING
 LOCATION, NO NONCONFORMITY SHALL BE INCREASED, OR
 CREATED.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-01-12 Cont ID  
Sent By mmclean Date 2007-01-12 Time 13:33 Rev Time 0.00
Received By mmclean Date 2007-01-12 Time 13:33 Sent To M
Notes
2007-01-12 14:38:28DENIED, NONCONFORMING. - ALTERATION & REPAIRS.
 1. THE VALUE OF THE IMPROVEMENTS HAS EXCEED THE 50% OF
 THE VALUE OF THE STRUCTURE.SEC 94-513(B) 1 (D).
 2. MAY APPLY FOR A VARIANCE WITH THE PLANNING & ZONING
 DEPT, 5TH FLOOR 822-1435.
 3. THE SITEPLAN SUBMITTED DOES NOT PROVIDE THE ADDRESS
 OF THE PROPERTY, LOT DIMENSION, SIDE SETBACK OF THE
 EXISTING STRUCTURE
  
 NOTE: SHALL APPLY FOR A SEPARATE PERMIT FOR THE FENCE
 WITH EASEMENT APPROVAL FROM THE CITY OF WEST PALM BEACH
 UTILITY DEPT.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2006-12-26 Cont ID  
Sent By mmclean Date 2006-12-26 Time 16:46 Rev Time 0.00
Received By mmclean Date 2006-12-26 Time 16:46 Sent To I
Notes
2006-12-26 17:03:56DENIED,
 1. THE SURVEYS SUBMITTED DOES NOT PROVIDE THE SIDE
 SETBACK ON THE NORTH SIDE OF THE PROPERTY.
 2. UPON LIFTING THE STRUCTURE, PLEASE PROVIDE TWO
 COPIES OF SURVEYS SHOWING THE STRUCTURE WILL BE PLACE
 BACK TO THE EXISTING FRONT/SIDES/REAR SETBACKS.
 3. PLEASE SHOW THE LOCATION OF THE PROPOSED A/C UNIT ON
 TWO COPIES OF SURVEYS.
 4. IF ANY WALLS REMOVED OR FALLS, THE STRUCTURE SHALL
 MEET THE REQUIRED SETBACKS.
  
  
 NOTE: A SEPARATE PERMIT IS REQUIRED FOR THE PROPOSED
 FENCE WITH EASEMENT APPROVAL FROM THE CITY OF WEST
 PALMM BEACH UTILITY DEPARTMENT.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720