Plan Review Details - Permit 06120363
Plan Review Stops For Permit 06120363
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-05-23 Cont ID  
Sent By rmcdouga Date 2007-05-23 Time 09:44 Rev Time 0.00
Received By rmcdouga Date 2007-05-23 Time 09:02 Sent To  
Notes
2007-05-23 10:29:30REVISION TO A4 AND SUPPLEMENTAL PAGE A5.1 IS OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-05-08 Cont ID  
Sent By rmcdouga Date 2007-05-08 Time 13:20 Rev Time 0.00
Received By rmcdouga Date 2007-05-08 Time 13:19 Sent To  
Notes
2007-05-08 13:40:49BUILDING REVISION TO A4 AND A5 IS DENIED
  
 THE TECHNICAL INFORMATION ON THE REVISIONS APPEARS TO
 BE CORRECT. HOWEVER, IT CAN NOT BE APPROVED DUE TO THE
 FOLLOWING ITEMS.
  
 1) SHEET A4 OF THE APPROVED PLAN WAS SIGNED AND SEALED
 BY THE ENGINEER AND THE REVISED A4 IS SIGNED AND SEALED
 BY THE ARCHITECT. ONLY THE PERSON THAT SIGNED AND
 SEALED THE APPROVED PLAN SHEET CAN REVISE IT.
  
 2) THE SUPPLEMENTAL DRAWING A5 THAT WAS SUBMITTED CAN
 NOT BE ACCEPTED BECAUSE IT DOES NOT REVISE SHEET A5 OF
 THE APPROVED PLANS. FOR RECORD KEEPING PURPOSES AND TO
 AVOID CONFUSION, IT SHOULD BE NUMBER DIFFERENTLY FOR
 EXAMPLE A5.1. SEE CITY AMENDMENT FBC 106.1.3.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-04-06 Cont ID  
Sent By rmcdouga Date 2007-04-06 Time 09:55 Rev Time 0.00
Received By rmcdouga Date 2007-04-06 Time 09:55 Sent To  
Notes
2007-04-06 09:55:14BUILDING PROVISO
  
 1) AN ELEVATION CERTIFICATE FOR THE ADDITION WILL BE
 REQUIRED BEFORE THE C.O. WILL BE ISSUED.
  
 2) A SUBSURFACE SOIL INVESTIGATION REPORT PER R 401.4
 IS REQUIRED AFTER THE DEMOLITION WORK IS COMPLETED AND
 PRIOR TO COMMENCING NEW CONSTRUCTION.
  
 3) THE ROOFER IS REQUIRED TO SUBMIT RAS 117 CALULATIONS
 FOR ENHANCED FASTENING FOR THE GAF MODIFIED ROOF
 SYSTEM, NOA #03-0501.02PAGE 26 (-52.5 PSF DESIGN
 PRESSURE) WHEN APPLYING FOR THE ROOF PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-03-07 Cont ID  
Sent By rmcdouga Date 2007-03-07 Time 14:40 Rev Time 0.00
Received By rmcdouga Date 2007-03-07 Time 10:41 Sent To  
Notes
2007-03-07 16:14:35DENIED BY BUILDING
  
 1) IN REGUARD TO THE SUBSURFACE SOIL REPORT REQUIRED BY
 FBC 1802.2.1. THE REPORT CAN BE SUBMITTED AFTER THE
 DEMO WORK BUT BEFORE COMMENCING THE NEW CONSTRUCTION.
 IT WILL BE A PROVISO.
  
 2) ON SHEET A6 A SIMPSON LTH 1 WAS ADDED TO THE ANCHOR
 SCHEDULE. THERE IS NO SIMPSON CONNECTOR THAT
 CORRESPONDS WITH THIS. DID YOU INTEND TO SPECIFY A
 SIMPSON LTA 1?
  
 3) SPECIFY ON THE PLANS THE METHOD OF TERMITE TREATMENT
 WILL BE EMPLOYED TO SATISFY THE REQUIREMENTS OF
 R320.1.
  
 4)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 5) RAS 117 CALCULATIONS ARE REQUIRED FOR THE GAF
 RUBEROID MODIFIED ROOF SYSTEM SPECIFING THE ENHANCED
 FASTENER SPACING IN THE SAMPLE SUBMITTED DOES NOT
 CORRESPOND TO THE SYSTEM SPECIFIED IN THE NOA. THE RAS
 117 CALCULATIONS CAN BE SUBMITTED AS A PROVISO WHEN THE
 ROOFING CONTRACTOR APPLIES FOR PERMIT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-29 Cont ID  
Sent By rmcdouga Date 2007-01-29 Time 15:24 Rev Time 0.00
Received By rmcdouga Date 2007-01-26 Time 17:22 Sent To  
Notes
2007-01-26 18:02:40DENIED BY BUILDING
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3)BASED ON THE 2006 SUPPLEMENT TO THE 2004 FBC
 RESIDENTIAL EFFECTIVE DECEMBER 8, 2006, THE EXPOSURE
 CATEGORY FOR THIS PROJECT IS EXPOSURE C. PLEASE MAKE
 ALL NECESSARY CORRECTIONS.
  
 4)SUBMIT A SUBSURFACE SOIL REPORT. FBC 1802.2.1
 QUESTIONABLE SOILS,
 1802.2.1 QUESTIONABLE SOIL.
 WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT
 SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION
 BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 .
  
 5)THE PROPERTY IS LOCATED IN AN A5 FLOOD ZONE. THE
 MINIMUM ELEVATION FOR THE FINISHED FLOOR IS 7' 6",
 WHICH INCLUDES THE 6" FREEBOARD REQUIRED BY THE CITY OF
 WEST PALM BEACH. AN ELEVATION CERTIFICATE WILL BE
 REQUIRED.
  
 6)PLEASE UPDATE THE STRUCTURAL NOTES ON SHEET A0. THE
 2006 AMENDMENTS TO THE 2004 FBC WILL APPLY TO THIS
 PROJECT. ALSO, THE 2002 EDITIONS OF ACI- 315, 318 AND
 530 APPLY PER THE REFERENCED STANDARDS OF THE FLORIDA
 BUILDING CODE.
  
 7)ROOF SHEATHING FASTENER SPACING IS REQUIRED TO
 COMPLY WITH FBC R803.2.3.1 (2006 AMENDMENTS) . WOOD
 STRUCTURAL PANELS SHALL BE FASTENED TO ROOF FRAMING
 WITH 8D RING- SHANK AT 6 INCHES ON CENTER AT EDGES AND
 6 INCHES ON CENTER AT INTERMEDIATE FRAMING. SPACING OF
 RING-SHANK FASTENERS SHALL BE 4 INCHES ON CENTER IN
 NAILING ZONE 3FOR 130MPH OR GREATER DESIGN WIND
 SPEEDS. PLEASE REVISE NOTE ON A6.
  
 8) PLEASE SPECIFY THE NUMBER OF FASTENERS AND CORRECT
 THE FASTENER TYPE FOR THE SIMPSON HETAL 20 CONNECTORS
 IN THE TRUSS ANCHOR SCHEDULE ON A6.
  
 9) SHOW COMPLIANCE WITHR320.1.
 TERMITE PROTECTION SHALL BE PROVIDED BY REGISTERED
 TERMITICIDES, INCLUDING SOIL APPLIED PESTICIDES,
 BAITING SYSTEMS, AND PESTICIDES APPLIED TO WOOD, OR
 OTHER APPROVED METHODS OF TERMITE PROTECTION LABELED
 FOR USE AS A PREVENTATIVE TREATMENT TO NEW CONSTRUCTION
 (SEE SECTION 202 , REGISTERED TERMITICIDE). UPON
 COMPLETION OF THE APPLICATION OF THE TERMITE PROTECTIVE
 TREATMENT, A CERTIFICATE OF COMPLIANCE SHALL BE ISSUED
 TO THE BUILDING DEPARTMENT BY THE LICENSED PEST CONTROL
 COMPANY THAT CONTAINS THE FOLLOWING STATEMENT: ?THE
 BUILDING HAS RECEIVED A COMPLETE TREATMENT FOR THE
 PREVENTION OF SUBTERRANEAN TERMITES. TREATMENT IS IN
 ACCORDANCE WITH RULES AND LAWS ESTABLISHED BY THE
 FLORIDA DEPARTMENT OF AGRICULTURE AND CONSUMER
 SERVICES.?
  
 10) SUBMIT TRUSS DRAWINGS AS REQUIRED BY R802.10.1.
 TRUSS DESIGN DRAWINGS.
 TRUSS DESIGN DRAWINGS, PREPARED IN CONFORMANCE WITH
 SECTION R802.10.1 , SHALL BE PROVIDED TO THE BUILDING
 OFFICIAL AND APPROVED PRIOR TO INSTALLATION. THE TRUSS
 LAYOUT AND TRUSS DRAWING ARE REQUIRED TO BE SIGNED,
 SEALED AND DATED BY THE TRUSS ENGINEER AND REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR THE
 PROJECT.
  
 11) SPECIFY THE TRUSS DEAD AND LIVE LOADS FOR THE TOP
 AND BOTTOM CORDS AND TOTAL LOADS ON THE PLANS.
  
 12)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 13) THE PRODUCT APPROVAL FOR THE POLYGLASS MODIFIED
 BITUMEN ROOF SYSTEM ON PAGE 37 OF NOA 06-0410.06 HAS A
 MAXIMUM DESIGN PRESSURE OF -45 WITH LIMITATION NUMBER
 9. THIS LIMITATION DOES NOT ALLOW ENHANCED FASTENING
 WHICH IS REQUIRED TO ACHIEVE THE UPLIFT PRESSURES OF
 ROOF ZONES 2 AND 3. PLEASE ALSO NOTE THAT LIMITATION
 NUMBER 7 OF THIS NOA REQUIRES SIGNED AND SEALED RAS 117
 CALCULATIONS FOR ENHANCED FASTENING.
  
 14)SPECIFYTHE METHOD OF ATTACHMENT THAT WILL BE
 USED TO INSTALL THE MONIER CONCRETE ROOF TILE. PLEASE
 CIRCLE THE APPROPRIATE FASTENER OR ADHESIVE SYSTEM ON
 THE NOA. PLEASE BE SURE THAT THE ATTACHMENT SELECTED
 WILL PROVIDE ADEQUATE RESISTANCE FOR A MOMENT BASED
 SYSTEM.
  
 NOTE: SEE MARKS ON THE PLAN.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-09-15 Cont ID  
Sent By dpalmer Date 2007-09-15 Time 09:55 Rev Time 0.00
Received By dpalmer Date 2007-09-15 Time 09:55 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2007-09-07 Cont ID  
Sent By dpalmer Date 2007-09-07 Time 10:42 Rev Time 0.00
Received By dpalmer Date 2007-09-07 Time 07:58 Sent To PC
Notes
2007-09-07 10:44:45** DENIED 2ND REVIEW FOR REVISIONS **
  
 ** PLEASE SEE NOTE(S) FROM PREVIOUS REVIEW.
  
  
 1) NOTE: PLEASE SUBMIT PLANS WHICH CORRELATE. PLEASE
 SEE EACH SHEET CONTAINS TWO COMPLETELY DIFFERENT PANEL
 SCHEDULES FOR CIRCUITING.
 IF THE FRONT SHEET E-1 IS ONLY FOR THE EXISTING PANELS,
 THEN WHY ARE THERE NEW CIRCUITS BEING SHOWN?
 THE SECOND SHEET E-2 INDICATES THESE AS EXISTING WITH
 NEW CIRCUITS SHOWN?
 PLEASE SEE EACH SHEET FOR POWER AND LIGHTING ALSO
 CONTAINS ITEMS WHICH ARE BEING FED FROM SEPARATE
 CIRCUITS TO THE SAME ITEMS DEPENDING ON THE PANEL
 SCHEDULE YOU LOOK AT.
 408.4, 310.16, 240.4
 FBC 106.1.3, 106.3.5.4
  
 2) NOTE: ** THE PREVIOUS REVIEW NOTE WITH RESPECT TO
 THE OVEN. PLEASE KNOW THE PREVIOUS PLANS INDICATED A
 *LOCK OFF* DEVICE WAS GOING TO BE USED. THIS LED TO AN
 UNDERSTANDING THAT THE OVENWAS A *HARDWIRED* UNIT AND
 NOT CORD AND PLUG CONNECTED FROM THE MANUFACTURE. THIS
 RESPONSE LETTER AND PLANS NOW MENTIONS THE RECEPTACLE
 WAS REMOVED? IS THIS UNIT *HARWIRED* OR CORD AND PLUG
 CONNECTED*?
 IF THIS UNIT IS LISTED TO BE CORD AND PLUG CONNECTED
 AND COMES LISTEDR AND/OR WITH A CORD FOR PLUGGING IN,
 THEN DISCONNECT IS NOT REQUIRED AND A STANDARD
 RANGE/OVEN RECEPTACLES MAY BE SUED WITH OUT A
 DISCONNECT BEING REQUIRED.
 IF THIS UNIT IS LISTED TO BE HARDWIRED OR COMES WITH A
 WHIP TO HARDWIRE THEN A DISCONNECTING MEANS IF NOT
 WITHIN SITE OF THE PANEL IS REQUIRED.
  
 3) NOTE: PLEASE SEE SHEET E-1 IS NOT SIGNED, DATED OR
 SEALED BY THE ENGINEER OF RECORD.
 FAC 61G15-23.002, FS 471.025
  
  
 ** AS STATED ON THE PREVIOUS REVIEW, IF THERE ARE
 COMMENTS OR QUESTIONS WHICH CAN BE GONE OVER ON THE
 PHONE, PLEASE CALL.
 THIS WOULD ALLEVIATE THE BACK AND FORTH ON PLANS ON ANY
 ITEMS NOT CLEAR AND PERHAPS NOT UNDERSTOOD OR NOT TYPED
 IN ANY MANOR.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-08-27 Cont ID  
Sent By dpalmer Date 2007-08-27 Time 18:33 Rev Time 0.00
Received By dpalmer Date 2007-08-27 Time 18:12 Sent To PC
Notes
2007-08-27 18:33:44 
 *** DENIED REVIEW ***
  
 1) NOTE: PLEASE SUBMIT PLANS WHICH CORRELATE. PLEASE
 SEE EACH SHEET CONTAINS TWO COMPLETELY DIFFERENT PANEL
 SCHEDULES FOR CIRCUITING.
 PLEASE SEE EACH SHEET FOR POWER AND LIGHTING ALSO
 CONTAINS ITEMS WHICH ARE BEING FED FROM SEPARATE
 CIRCUITS TO THE SAME ITEMS DEPENDING ON THE PANEL
 SCHEDULE YOU LOOK AT.
 408.4, 310.16, 240.4
 FBC 106.1.3, 106.3.5.4
  
 2) NOTE: PLEASE SEE THE RE-LOCATED OVEN MENTIONS THIS
 WILL HAVE A BREAKER LOCK OFF DEVICE. ** IMPORTANT,
 PLEAS KNOW THAT THE TYPE OF DEVICE MUST HAVE THE LOCK
 OFF MECHANISM PERMANENTLY A PART OF THE BREAKER. *SNAP
 OR CLIP ON TYPE DEVICES ARE NOT ACCEPTABLE AND A
 DISCONNECTING MEANS WILL BE REQUIRED.
 ** 110.3, 90.4, 422.30, 422.31
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-03-18 Cont ID  
Sent By dpalmer Date 2007-03-18 Time 09:30 Rev Time 0.00
Received By dpalmer Date 2007-03-18 Time 09:14 Sent To M
Notes
2007-03-18 09:32:06REDLINE DPLANS.
  
 ALL SMOKE DEVICES ARE BEING NOTED AS EXISTING AND ALL
 AS LOW VOLTAGE. ALL DEVICES , LOCATIONS, AND SOUNDING
 SHALL BE VERIFIED TO MEET THE CURRENT NFPA-72 11.5.1.1,
 11.8.3. DEVICES ARE ALL NOTED AS EXISTING ON PLANS AT
 THIS TIME.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-03-02 Cont ID  
Sent By dpalmer Date 2007-03-02 Time 12:18 Rev Time 0.00
Received By dpalmer Date 2007-03-02 Time 10:07 Sent To M
Notes
2007-03-02 12:18:55*** UNSAT 2NDREVIEW ***
  
 1) NOTE: PLEASE SEE ONLY THE 2005 NFPA-70 WAS ADDED TO
 PLANS.
 THE FOLLOWING SHALL BE ON PLANS AT A MINIMUM ON
 ELECTRICAL SHEETS.
 2005 NFPA-2005
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE FBC R313, PLEASE SHOW ALL EXISTING
 OR NEW TO BE INSTALLED *SMOKE ALARMS* AS REQUIRED PER
 NFPA-72 11-5.1.1, 11.8.3
 PLEASE SEE THIS WAS NOT DONE, ONLY WHAT APPEARS TO BE
 THREE VERY FAINT *SMOKE DETECTORS* WERE ADDED TO FIRST
 FLOOR ONLY. PLEASE KNOW THIS COMMENT IS FOR ALL
 EXISTING TO BE SHOWN MEETING THE CURRENT CODE OR NEW TO
 BE INSTALLED.
 * PLEASE KNOW THAT A MEETING WAS HELD AT THE SOUTHERN
 SECTION MEETING IN OCT 06 WHERE WE WERE DIRECTLY
 INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE DETECTORS
 ON PLANS FOR RESIDENTIAL HOMES IS NOT ACCEPTABLE WHEN
 THESE DEVICES ANY ACTUALLY FALL UNDER THE DEFINITIONS
 OF SMOKE ALARMS WHICH WOULD BE SHOWN AS SA/SMOKE
 ALARMS.THIS WAS MENTIONED IN PREVIOUS NOTE FOR SMOKE
 ALARMS UNLESS THIS RESIDENCE DOES CONTAIN A FIRE ALARM
 PANEL?
 THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE
 OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED.
 BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE
 DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL
 NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY
 HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF
 SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS
 SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS
 SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS
 FOR OTHER NEW HOMES.
 ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC
 RESIDENTIAL CODE/ FBC AND IN NFPA-72.
 IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE*.
 PLEASE SEE NFPA-72 11.5.1.1, 11.8.3
  
 3) NOTE: PLEASE VERIFY RECEPTACLE SPACING FOR NEW WALL
 AREAS IN ADDITION AREA OF KITCHEN/BREAKFAST AREA PER
 210.52. PLEASE SEE WALLS 2FT OR MORE. PLEASE SEE ONLY
 ONE WAS ADDED.
  
 4) NOTE: PLEASE CLARIFY THESE CIRCUITS. PANEL SCHEDULES
 DO NOT DIFFERENTIATE THE NEW AND EXISTING CIRCUITS WITH
 ANY DESIGNATION SO IT IS UNCLEAR IF THE NEW ADDITION
 AREA FOR BREAKFAST/DINING MEETS THIS REQUIREMENT.
 PLEASE SEE 210.52B1 WHICH REQUIRES ALL RECEPTACLE
 CIRCUITS IN DINING, KITCHEN, BREAKFAST AREAS AND AREAS
 OF THE LIKE TO BE ON ONE OR MORE OF THE SMALL APPLIANCE
 CIRCUITS.
 PLEASE KNOW IF THERE ARE MORE THAN 3, THEN THE LOADS
 SHALL BE FIGURED ACCORDINGLY.
 PLEASE SEE THE FOLLOWING SECTIONS. 210.52B1, 210.11B1,
 220.52A
  
 5) NOTE: PLEASE SEE NEW RECEPTACLES BEING ADDED TO
 VESTIBULE AREA WHICH ARE REQUIRED TO BE GFI /GFI
 PROTECTED. PLEASE SEE THE PREVIOUS PLANS WERE REDLINED
 FOR THE SINGLE RECEPTACLE WHICH WAS PREVIOUSLY SHOWN TO
 BE GFI PER 210.8 AND THE SAME ONE AS PREVIOUSLY SHOWN
 AND NOW THE NEW ONES ALSO NEED TO INDICATE THE GFI
 PROTECTION.
 210.8A7
  
 6) NOTE: PLEASE CLARIFY LOAD CALCULATIONS AS NOTED IN
 PREVIOUS REVIEW. PLEASE SEE THESE NOW INDICATE *SPACE
 HEATERS*? PLEASE SEE THIS SECTIONS INDICATES *SPACE
 HEATERS* AND *CENTRAL HEAT*, HOW DOES THE LOAD
 CALCULATIONS SHOW ALL THESE ARE SPACE HEATERS AND AT
 65%. ? ARE THESE *SPACE HEATERS*?
 SEE 220.83B FOR LOAD CALCULATIONS WHEN ADDING HEAT LOAD
 TO AN EXISTING DWELLING. PLEASE SEE THE HEAT LOADS FOR
 UNITS SHALL BE FIGURED AT 100% AS SHOWN ON PANEL B.
 THIS DOES PERMIT THE FIRST 8KVA AT 100% REMAINDER AT
 40%,INSTEAD OF THE FIRST 10KVA AT 100% ,THEN HEAT AT
 100%.
  
 8) NOTE:PLEASE SEE LOAD CALCULATIONS INDICATE THE NEW
 RECESSED LIGHTS, HOWEVER RESPONSE DOES NOT MENTION IF
 THERE ARE OTHER FIXTURES IN THE EXISTING DWELLING? ARE
 THESE THE ONLY ONES?
 PLEASE SEE 220.14D WHICH IF THE AMOUNT OF RECESSED
 LIGHTS IN DWELLING ARE ABOVE 20, THEN THE TOTAL NUMBER
 SHALL BE BASED ON THE MAXIMUM WATTAGE PER FIXTURE TIMES
 THE AMOUNT OF FIXTURES ADDED TO THE 3VA PER SQ FT.
 PLEASE SEE THE 2002 NEC SECTION 220.3(B)(4)
  
 9) NOTE:PLEASE SEE THE CIRCUIT FOR THE AHU ON PLANS
 SHOWS 28/30 YET PANEL SCHEDULE SHOWS THESE SAME
 CIRCUITS FOR GENERAL LTS ETC.
 PLEASE SEE 408.4 AND COMMENTARY FROM CODE WHICH IS
 BEING SHOWN BELOW. PLEASE INDICATE NEW AND EXISTING
 CIRCUITS.
  
 * SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO
 REQUIRE THAT THE IDENTIFICATION FOR EVERY CIRCUIT
 SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND
 CLEARLY STATE THE SPECIFIC PURPOSE FOR WHICH THE
 CIRCUIT IS USED. CIRCUITS USED FOR THE SAME PURPOSE
 MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR EXAMPLE,
 SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY OUTLETS IN
 THE KITCHEN, DINING ROOM, AND KITCHEN COUNTERTOPS.
 IDENTIFYING THE CIRCUITS AS SMALL APPLIANCE BRANCH
 CIRCUITS IS NOT ACCEPTABLE; INSTEAD, THEY SHOULD BE
 IDENTIFIED AS ``KITCHEN WALL RECEPTACLES,'' ``DINING
 ROOM FLOOR RECEPTACLE,'' OR ``KITCHEN COUNTERTOP
 RECEPTACLES LEFT OF SINK.'' CIRCUIT DIRECTORIES
 CONTAINING MULTIPLE ENTRIES WITH ONLY ``LIGHTS'' OR
 ``OUTLETS'' DO NOT PROVIDE THE SUFFICIENT DETAIL
 REQUIRED BY THIS SECTION.*
  
 10) NOTE: PLEASE SEE AS SOME NOTES WERE REPEATED FOR
 CODE COMPLIANCE ONLY A NOTICE FOR FS 553.80(2)(B) IS
 BEING GIVEN AT THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-12-27 Cont ID  
Sent By dpalmer Date 2006-12-27 Time 19:12 Rev Time 0.00
Received By dpalmer Date 2006-12-27 Time 17:56 Sent To M
Notes
2006-12-27 19:13:40** UNSAT **
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED
 ON PLANS AS THIS PERMIT APPLICATION HAS BEEN MADE UNDER
 THE NEW 2005 NEC.
 THE FOLLOWING SHALL BE ON PLANS AT A MINIMUM ON
 ELECTRICAL SHEETS.
 2005 NFPA-2005
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE FBC R313, PLEASE SHOW ALL EXISTING
 OR NEW TO BE INSTALLED SMOKE ALARMS AS REQUIRED PER
 NFPA-72 11-5.1.1, 11.8.3
  
 3) NOTE: PLEASE VERIFY RECEPTACLE SPACING FOR NEW WALL
 AREAS IN ADDITION AREA OF KITCHEN/BREAKFAST AREA PER
 210.52. PLEASE SEE WALLS 2FT OR MORE.
  
 4) NOTE: PLEASE SEE 210.52B1 WHICH REQUIRES ALL
 RECEPTACLE CIRCUITS IN DINING, KITCHEN, BREAKFAST AREAS
 AND AREAS OF THE LIKE TO BE ON ONE OR MORE OF THE SMALL
 APPLIANCE CIRCUITS.
 PLEASE SEE PANEL SCHEDULES DO NOT INDICATE THESE. ?
 PLEASE SEE LOAD CALCULATIONS FOR SERVICE SEEM TO SHOW
 3- SMALL APPLIANCE CIRCUITS, HOWEVER THESE ARE NOT
 LISTED ON EITHER PANEL SCHEDULE?
 PLEASE KNOW IF THERE ARE MORE THAN 3, THEN THE LOADS
 SHALL BE FIGURED ACCORDINGLY.
 PLEASE SEE THE FOLLOWING SECTIONS. 210.52B1, 210.11B1,
 220.52A
  
 5) NOTE: PLEASE INDICATE A NEW OR EXISTING GFI RECEPT
 LOCATED AT THE NEW CONDENSING UNIT BEING ADDED AT THE
 SIDE OF DWELLING. PLEASE SEE 210.63 AND 210.8A3.
  
 6) NOTE: PLEASE SEE NEW LIVING ROOM WHICH WILL REQUIRE
 A LIGHT FIXTURE OF SOME KIND TO BE INSTALLED. PLEASE
 SEE OTHER EXCEPTIONS IN 210.70 WHICH WILL PERMIT THE
 SWITCHING OF ? SWITCHED RECEPT ? OR RECESSED LTS.
 PLEASE SEE LS 101 7.8
  
 7) NOTE: PLEASE SEE 220.83B FOR LOAD CALCULATIONS WHEN
 ADDING HEAT LOAD TO AN EXISTING DWELLING. PLEASE SEE
 THE HEAT LOADS FOR UNITS SHALL BE FIGURED AT 100% AS
 SHOWN ON PANEL B.
 THIS DOES PERMIT THE FIRST 8KVA AT 100% REMAINDER AT
 40%,INSTEAD OF THE FIRST 10KVA AT 100% ,THEN HEAT AT
 100%.
  
 8) NOTE: PLEASE SEE 220.14D WHICH IF THE AMOUNT OF
 RECESSED LIGHTS IN DWELLING ARE ABOVE 20, THEN THE
 TOTAL NUMBER SHALL BE BASED ON THE MAXIMUM WATTAGE PER
 FIXTURE TIMES THE AMOUNT OF FIXTURES ADDED TO THE 3VA
 PER SQ FT.
 PLEASE SEE THE 2002 NEC SECTION 220.3(B)(4)
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2006-12-13 Cont ID  
Sent By ssherman Date 2006-12-13 Time 10:42 Rev Time 0.00
Received By ssherman Date 2006-12-13 Time 10:41 Sent To  
Notes
2006-12-13 10:42:17HISTORICAL APPROVAL PER JILLIAN PAPA

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-09-14 Cont ID  
Sent By adarroug Date 2007-09-14 Time 10:08 Rev Time 0.00
Received By adarroug Date 2007-09-14 Time 10:08 Sent To E
Notes
2007-09-14 10:08:52TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-09-06 Cont ID  
Sent By adarroug Date 2007-09-06 Time 08:22 Rev Time 0.00
Received By adarroug Date 2007-09-06 Time 08:22 Sent To E
Notes
2007-09-06 08:23:20TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-08-27 Cont ID  
Sent By adarroug Date 2007-08-27 Time 14:06 Rev Time 0.00
Received By adarroug Date 2007-08-27 Time 14:06 Sent To E
Notes
2007-08-27 14:06:18TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-05-14 Cont ID  
Sent By adarroug Date 2007-05-14 Time 14:07 Rev Time 0.00
Received By adarroug Date 2007-05-14 Time 14:07 Sent To B
Notes
2007-05-14 14:08:08TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-05-04 Cont ID  
Sent By adarroug Date 2007-05-04 Time 15:04 Rev Time 0.00
Received By adarroug Date 2007-05-04 Time 15:04 Sent To B
Notes
2007-05-04 15:05:05TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-03-16 Cont ID  
Sent By adarroug Date 2007-03-16 Time 16:37 Rev Time 0.00
Received By adarroug Date 2007-03-16 Time 16:37 Sent To  
Notes
2007-03-16 16:37:57TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-02-22 Cont ID  
Sent By adarroug Date 2007-02-22 Time 15:23 Rev Time 0.00
Received By adarroug Date 2007-02-22 Time 15:23 Sent To E
Notes
2007-02-22 15:23:39TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-27 Cont ID  
Sent By adarroug Date 2006-12-27 Time 10:19 Rev Time 0.00
Received By adarroug Date 2006-12-27 Time 10:19 Sent To E
Notes
2006-12-27 10:19:52TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-29 Cont ID  
Sent By rmcdouga Date 2007-01-29 Time 15:24 Rev Time 0.00
Received By rmcdouga Date 2006-12-16 Time 17:31 Sent To  
Notes
2006-12-16 17:31:47TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-03-19 Cont ID  
Sent By tgordon Date 2007-03-19 Time 07:39 Rev Time 0.25
Received By tgordon Date 2007-03-19 Time 07:39 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-03-05 Cont ID  
Sent By tgordon Date 2007-03-05 Time 08:45 Rev Time 0.20
Received By tgordon Date 2007-03-05 Time 08:45 Sent To P
Notes
2007-03-05 08:49:55*** DENIED ***
 1) THE ENGINEER WHO SEALED THE PLANS HAI-VINH LY
 LICENSE HAS EXPIRED 2-28-07, PLEASE CORRECT.
  
 2)THE ENGINEER HEI-VINH LY MUST HAVE PRINTED NAME,
 ADDRESS, AND LICENSE NUMBER IN THE TITLE BLOCK, SEE FAC
 61G15-23.002. PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-12-28 Cont ID  
Sent By tgordon Date 2006-12-28 Time 08:40 Rev Time 0.30
Received By tgordon Date 2006-12-28 Time 08:40 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-03-29 Cont ID  
Sent By mperson Date 2007-03-29 Time 16:46 Rev Time 0.33
Received By mperson Date 2007-03-29 Time 16:46 Sent To B
Notes
2007-03-29 16:48:09NOTE: NO PLUMBING PERMIT APPLIED FOR. A PLUMBING PERMIT
 IS REQUIRED FOR THE SCOPE OF WORK BEING DONE.

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-03-06 Cont ID  
Sent By mperson Date 2007-03-06 Time 08:13 Rev Time 0.33
Received By mperson Date 2007-03-06 Time 08:13 Sent To B
Notes
2007-03-06 08:31:45DENIED 2ND TIME
 REFERENCE: FBC-2004 PLUMBING; FLORIDA ADMINISTRATIVE
 CODE;
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 THE FOLLOWING ARE FROM THE PREVIOUS REVIEW:
  
 1.OK
  
 2. OK
  
 THE FOLLOWING ARE NEW COMMENTS:
  
 1. THE ENGINEER (HAI-VINH LY)WHO SEALED THE PLANS ON
 SHEET MP-1 LICENSE HAS EXPIRED 2/28/07. PLEASE SEE THE
 ATTACHED DBPR SEARCH RESULTS INDICATING THIS. PLEASE
 CORRECT AND RESUBMIT.
  
 2. THE ENGINEER (HAI-VINH LY) PER FAC 61G15-23.002
 SHALL HAVE PRINTED NAME, ADDRESS, AND LICENSE NUMBER IN
 THE TITLE BLOCK. PLEASE CORRECT AND RESUBMIT.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-01-04 Cont ID  
Sent By mperson Date 2007-01-04 Time 11:29 Rev Time 0.33
Received By mperson Date 2007-01-04 Time 11:29 Sent To B
Notes
2007-01-04 11:56:55DENIED
 REFERENCE: FBC-2004 PLUMBING
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET A-4 INDICATES AN ICE MACHINE, PLEASE PROVIDE
 MANUFACTURER CUT SHEETS INDICATING HOW IT DRAINS. IF
 UNIT NEEDS A DRAIN PLEASE SHOW COMPLIANCE TO FBC-2004
 CHAPTER 8 ON THE RESUBMITTED SANITARY RISER DIAGRAM.
  
 2. SHEET MP-1 SANITARY RISER DIAGRAM: THE EXISTING WC
 IS MISLABELED EXISTING LAV, PLEASE CORRECT THIS ON THE
 RESUBMITTAL.
  
 3.SHEET MP-1 SANITARY RISER DIAGRAM: PLEASE INCREASE
 THE WASTE AND VENT SIZE OF BARTO 2" PER TABLES
 710.1(1) AND 909.3 DUE TO INCREASE OF DFU LOAD.
  
 ********IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2006-12-22 Cont ID  
Sent By mmclean Date 2006-12-22 Time 16:10 Rev Time 0.00
Received By mmclean Date 2006-12-22 Time 16:10 Sent To I
Notes
***NONE***