Plan Review Details - Permit 06120355
Plan Review Stops For Permit 06120355
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2007-01-19 Cont ID  
Sent By lursu Date 2007-01-19 Time 08:03 Rev Time 0.00
Received By lursu Date 2007-01-19 Time 08:03 Sent To  
Notes
2007-01-19 08:06:06PEMIT HAS BEEN ATTACHED TO THE CORRECT SITE ADDRESS
 :355 JEFFERSON RD WITH THE CORRECT PCN = 74 43 43 27 26
 006 0010.
 NOTE: THE PERMIT APPLICATION AND SITE PLANS SHOULD
 REFLECT THIS ADDRESS SINCE THE NEW BUILDING IS
 CONSTRUCTED AT THIS LOCATION.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-07-20 Cont ID  
Sent By jwitmer Date 2007-07-20 Time 09:17 Rev Time 0.55
Received By jwitmer Date 2007-07-20 Time 09:17 Sent To PC
Notes
2007-07-20 09:26:53BUILDING PLAN REVIEW
 PERMIT:06120355 / 07020510 (FOUN)
 ADD: 355 JEFFERSON RD
 CONT: ROBLING ARCHITECTURE CONSTRUCTION
 TEL: (561)662-0000
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 FOUNDATION REVISIONREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) PLEASE PROVIDE UPDATED FOUNDATION PLANS FOR BOTH THE
 FOUNDATION PERMIT AND THE BUILDING PERMIT SHEET F-1 TO
 SHOW ACCURATELY WHERE THE FOUNDATION REVISION OCCURS.
 106.1.2* ADDITIONAL INFORMATION REQUIRED.
 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL (SEE ALSO SECTION
 106.3.5 ).
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-06-28 Cont ID  
Sent By jwitmer Date 2007-06-28 Time 08:11 Rev Time 1.33
Received By jwitmer Date 2007-06-28 Time 08:11 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-17 Cont ID  
Sent By jwitmer Date 2007-01-17 Time 09:44 Rev Time 5.55
Received By jwitmer Date 2007-01-16 Time 14:15 Sent To Z
Notes
2007-01-17 09:31:33BUILDING PLAN REVIEW
 PERMIT: 06120355
 ADD: 900 S OLIVE AVE
 CONT: ROBLING ARCHITECTURE
 TEL: (561)662-0000
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1SSTREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.NOTE: 713.13(2) IF THE WORK DESCRIBED IN
 THE NOTICE OFCOMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE
 IS NULL
 & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 3) PLEASE CORRECT THE ADDRESS AND PROPERTY CONTROL
 NUMBER ON THE PERMIT APPLICATION.
 PLANS INDICATE WORK TO BE ACCOMPLISHED ON JEFFERSON RD.
 PLEASE CONTACT LILI URSA AT 822-1239
 FOR A NEW ADDRESS AND PLEASE CORRECR THE PROPERTY
 CONTROL NUMBER TO REFLECT THE CORRECT LOT. 106.1.2.*
 ADDITIONAL INFORMATION REQUIRED.
  
 4) PLEASE PROVIDE ENERGY CALCS. CHAPTER 13 FBC.
  
 5) PLEASE PROVIDE SOILS REPORTS,FBC 1802.2.1
 QUESTIONABLE SOILS,
 1802.2.1 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING
 POWER OF THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING
 VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING
 OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION
 BE MADE.
 SUCH INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 6) PLEASE PROVIDE A SITE PLAN PROVIDING THE FOLLOWING:
 11-4.1.2 ACCESSIBLE SITE AND EXTERIOR FACILITIES: NEW
 CONSTRUCTION.
 THIS EDITION OF THE CODE DOES NOT APPLY TO BUILDINGS,
 STRUCTURES, OR FACILITIES WHICH WERE EITHER UNDER
 CONSTRUCTION OR UNDER CONTRACT FOR CONSTRUCTION ON
 OCTOBER 1, 1997.
 NOTHING IN THIS CODE SHALL BE CONSTRUED TO RELIEVE THE
 OWNER OF ANY BUILDING, STRUCTURE OR FACILITY FROM THE
 DUTY TO PROVIDE VERTICAL ACCESSIBILITY TO ALL LEVELS
 ABOVE AND BELOW THE OCCUPIABLE GRADE LEVEL, REGARDLESS
 OF WHETHER THE CODE REQUIRES AN ELEVATOR TO BE
 INSTALLED IN SUCH BUILDING, STRUCTURE OR FACILITY,
 EXCEPT: (1) ELEVATOR PITS, ELEVATOR PENTHOUSES,
 MECHANICAL ROOMS, PIPING OR EQUIPMENT CATWALKS, AND
 AUTOMOBILE LUBRICATION AND MAINTENANCE PITS AND
 PLATFORMS; (2) UNOCCUPIABLE SPACES, SUCH AS ROOMS,
 ENCLOSED SPACES, AND STORAGE SPACES THAT ARE NOT
 DESIGNED FOR HUMAN OCCUPANCY, FOR PUBLIC
 ACCOMMODATIONS, OR FOR WORK AREAS; AND (3) OCCUPIABLE
 SPACES AND ROOMS THAT ARE NOT OPEN TO THE PUBLIC AND
 THAT HOUSE NO MORE THAN FIVE PERSONS INCLUDING, BUT NOT
 LIMITED TO, EQUIPMENT CONTROL ROOMS AND PROJECTION
 BOOTHS. HOWEVER AS PROVIDED IN SECTION 553.509, FLORIDA
 STATUTES, BUILDINGS, STRUCTURES, AND FACILITIES MUST,
 AT A MINIMUM, COMPLY WITH THE REQUIREMENTS OF THE
 ADAAG. THEREFORE, FACILITIES SUBJECT TO THE ADAAG MAY
 BE REQUIRED TO PROVIDE VERTICAL ACCESS TO AREAS
 OTHERWISE EXEMPT UNDER SECTION 11-4.1.3 (5) OF THIS
 CODE.
 AN ACCESSIBLE SITE SHALL MEET THE FOLLOWING MINIMUM
 REQUIREMENTS:
 (1)AT LEAST ONE ACCESSIBLE ROUTE COMPLYING WITH
 SECTION 11-4.3 SHALL BE PROVIDED WITHIN THE BOUNDARY OF
 THE SITE FROM PUBLIC TRANSPORTATION STOPS, ACCESSIBLE
 PARKING SPACES, PASSENGER LOADING ZONES IF PROVIDED,
 AND PUBLIC STREETS OR SIDEWALKS, TO AN ACCESSIBLE
 BUILDING ENTRANCE.
 (2)AT LEAST ONE ACCESSIBLE ROUTE COMPLYING WITH
 SECTION 11-4.3 SHALL CONNECT ACCESSIBLE BUILDINGS,
 ACCESSIBLE FACILITIES, ACCESSIBLE ELEMENTS, AND
 ACCESSIBLE SPACES THAT ARE ON THE SAME SITE.
 (3)ALL OBJECTS THAT PROTRUDE FROM SURFACES OR
 POSTS INTO CIRCULATION PATHS SHALL COMPLY WITH SECTION
 11-4.4 .
 (4)GROUND SURFACES ALONG ACCESSIBLE ROUTES AND IN
 ACCESSIBLE SPACES SHALL COMPLY WITH SECTION 11-4.5 .
  
 7) PLANS DO NOT PROVIDE DETAILS TO THE ENTRY OF ANY
 EXTERIOR DOORS.
 1003.5.2
 WHERE CHANGE IN ELEVATION OF 12 INCHES (305 MM) OR LESS
 OCCURS IN EXIT ACCESS CORRIDORS, EXITS AND EXIT
 DISCHARGE, RAMPS COMPLYING WITH SECTION 1010 SHALL BE
 PROVIDED.
 1003.5.2
 WHERE CHANGE IN ELEVATION OF 12 INCHES (305 MM) OR LESS
 OCCURS IN EXIT ACCESS CORRIDORS, EXITS AND EXIT
 DISCHARGE, RAMPS COMPLYING WITH SECTION 1010 SHALL BE
 PROVIDED.
  
 8)SHEET A-3 INDICATES THE USE OF 2 SINKS PLANS
 INDICATE A CLEAR FLOOR SPACE FOR FRONT APPROACH BUT
 THERE IS NO
 ELEVATION INDICATING THE FRONT OF THE CABINET
 CONFIGURATION. PLEASE PROVIDE.
 SINKS:
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES
 (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4
 SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD
 APPROACH.
 THE CLEAR FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE
 AND
 SHALL EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH
 THE SINK.
  
 9) PLANS DO NOT INDICATE THE USE OF A VAPOR RETARDER.
 1816.1.4
 IF SOIL TREATMENT IS USED FOR SUBTERRANEAN TERMITE
 PREVENTION, CHEMICALLY TREATED SOIL SHALL BE PROTECTED
 WITH A MINIMUM 6 MILLIMETER VAPOR RETARDER TO PROTECT
 AGAINST RAINFALL DILUTION. IF RAINFALL OCCURS BEFORE
 VAPOR RETARDER PLACEMENT, RETREATMENT IS REQUIRED. ANY
 WORK, INCLUDING PLACEMENT OF REINFORCING STEEL, DONE
 AFTER CHEMICAL TREATMENT UNTIL THE CONCRETE FLOOR IS
 POURED, SHALL BE DONE IN SUCH MANNER AS TO AVOID
 PENETRATING OR DISTURBING TREATED SOIL.
  
 10)PLANS DO NOT INDICATE THE USE OF TERMITE
 PROTECTION, PLEASE INDICATE WHICH METHOD OF PROVIDING
 SUBTERRANEAN TERMITE PROTECTION SHALL BE USED. 1816.1
 TERMITE PROTECTION.
 TERMITE PROTECTION SHALL BE PROVIDED BY REGISTERED
 TERMITICIDES, INCLUDING SOIL APPLIED PESTICIDES,
 BAITING SYSTEMS, AND PESTICIDES APPLIED TO WOOD, OR
 OTHER APPROVED METHODS OF TERMITE PROTECTION LABELED
 FOR USE AS A PREVENTATIVE TREATMENT TO NEW
 CONSTRUCTION. SEE SECTION 202 , REGISTERED TERMITICIDE.
 UPON COMPLETION OF THE APPLICATION OF THE TERMITE
 PROTECTIVE TREATMENT, A CERTIFICATE OF COMPLIANCE SHALL
 BE ISSUED TO THE BUILDING DEPARTMENT BY THE LICENSED
 PEST CONTROL COMPANY THAT CONTAINS THE FOLLOWING
 STATEMENT: ?THE BUILDING HAS RECEIVED A COMPLETE
 TREATMENT FOR THE PREVENTION OF SUBTERRANEAN TERMITES.
 TREATMENT IS IN ACCORDANCE WITH RULES AND LAWS
 ESTABLISHED BY THE FLORIDA DEPARTMENT OF AGRICULTURE
 AND CONSUMER SERVICES.?
  
 11) SHEET F-1 STRUCTURAL NOTE# 4, PLANS INDICATE
 ANCHORING HARDWARE TO MEET THE MINIMUM STANDARDS FOR
 ACI 318-05. PLEASE PROVIDE HOW THE
 PREFAB WILL BE ATTACHED TO THE FOUNDATION. 106.1.2*.
  
 12)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 12A) WINDOWS- SINGLE HUNG
 12B) WINDOWS- GLASS BLOCK
 12C) EXTERIOR DOORS SOLID OR GLAZED
 12D) ROLL UP DOORS
 12E) ROOFING ASSEMBLIES
  
 13)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 14) SPEAKING WITH ARCHITECT STEVEN BRUH THE
 MANUFACTURING COMPANY HAS APPLIED FOR DCA APPROVAL BUT
 HAS NOT RECEIVED SUCH APPROVAL AT THIS TIME. THE CITY
 HAS REVIEWED WHAT THEY WILL REQUIRE FOR A SITE SPECIFIC
 REQUIREMENTS FOR ROYAL CONCRETE CONCEPTS, INC. REQUIRED
 SUBMITTALS:
  
 1) ALL REQUIRED SUBMITTALS FOR THE STRUCTURE ALONG WITH
 ENGINEERED PLANS, SHOP DRAWINGS INCLUDING ENGINEERING
 CALCULATIONS.
 2) LETTER FROM A LICENSED THRESHOLD INSPECTOR STATING
 THAT AN INSPECTION WILL BE MADE AT THE MANUFACTURES
 SITE OF THE JOB SPECIFIC COMPONENTS TO VERIFY
 CONSTRUCTION COMPLIANCE OF THE COMPONENTS WITH THE
 ENGINEERED DESIGN.
  
 DURING CONSTRUCTION SUBMITTALS:
 THREE SETS OF PLANS, DOCUMENTS, REPORTS , PRODUCT
 APPROVALS AND SUBMITTALS.
 1) CERTIFICATE OF COMPLIANCE AFFADAVIT FROM THE
 THRESHOLD INSPECTOR THAT, TO THE BEST OF HIS/ HER
 KNOWLEDGE AND BELIEF, THE OFF-SITE CONSTRUCTION
 COMPONENTS OUTLINED HEREIN AND INSPECTED UNDER HIS/ HER
 AUTHORITY HAVE BEEN COMPLETED IN CONFORMANCE WITH THE
 APPROVED PLANS, SHOP DRAWINGS AND ENGINEERING.ALSO,
 PLEASE ARRANGE WITH HAROLD PISKURA (INSPECTION SERVICES
 MANAGER - TEL:
 561 805 6711), A MEETING INVOLVING THE
 THRESHOLD INSPECTOR, JOB INSPECTOR, CONTRACTOR AND
 ENGINEER.
  
 15A) TABLE 602 REQUIREMENTS FOR EXTERIOR WALLS BASED ON
 FIRE SEPERATION DISTANCE, PLEASE PROVIDE THE DISTANCES
 FROM THE EXISTING STRUCTURES ALSO ON THIS SAME LOT. IT
 APPEARS THE STRUCTURES MAY BE CLOSER THAN 20'-0", THIS
 WILL AFFECT AN ASSUMED PROPERTY LINE BETWEEN BUILDINGS
 ON THE SAME LOT.503.1.3, TABLE 601,602,704.8. 715.3 AND
 715.4. IF ASSUMING NO FIRE SEPERATION IS REQUIRED
 BETWEEN BUILDINGS, (ASSUMED ONE LARGE BUILDING) PROVIDE
 THE TOTAL SQUARE FOOTAGE OF ADJACENT BUILDINGS
 FOOTPRINT.
  
 15B) PLANS INDICATE THE CONCRETE THICKNESSOF THE
 WALLS LTO BE 2" THICK, IF FIRE RESISTANCE WILL BE
 REQUIRED BETWEEN BUILDINGS PLEASE PROVIDE THE
 EQUIVALENT THICKNESS OF PRECAST CONCRETE WALL, SEE
 TABLE 721.2.1.1 OR 721.2.1.1.4.(RIBBED OR UNDULATING
 SURFACES).
  
 16) SHEET S-3 INDICATES A STEEL BEAM IN SECTIONS A-A NO
 MENTION AS TO SIZE OR WEIGHT OF BEAM? 106.1.2.*
 ADMINISTRATIVE CODE.
  
 17) THERE IS NO DBA OR CERTIFICATE OF AUTHORIZATION FOR
 BRUH-HOSEIN-RUPP AT DPBR.) 481.219 F.S.CERTIFICATE
 OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL
 SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 18) SHEET S-3 VARIOUS SECTIONS SHOW A 3/4" =1'-0",
 WRONG SCALE DETAIL# 3 AND SECTION A-A.BEFORE A
 PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 .NOTE : ADDITIONAL COMMENTS MAY APPEAR ON THE NEXT
 REVIEW DUE TO COMMENT RESPONSE OR ADDITIONAL NEW
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2007-08-22 Cont ID  
Sent By dpalmer Date 2007-08-22 Time 15:44 Rev Time 0.00
Received By dpalmer Date 2007-08-22 Time 15:44 Sent To PC
Notes
2007-08-22 15:46:32** REVISED E-1 STATE APPROVAL STAMPED.
 ** REVISEDENERGY CALCULATIONS TO COORDINATE WITH
 PLANS.

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2007-08-10 Cont ID  
Sent By dpalmer Date 2007-08-10 Time 16:36 Rev Time 0.00
Received By dpalmer Date 2007-08-10 Time 15:29 Sent To PC
Notes
2007-08-10 16:39:49** DENIED **
  
  
 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS
 SUBMITTED DO NOT MATCH WITH THE PLANS.
 PLEASE SEE THE 16 NEW FIXTURES WHICH WERE ADDED TO
 CALCULATIONS ARE ALL NOW SHOWN AT 13WATT COMPACT
 FLUORESCENT WHEN THE PLANS INDICATE THIS SAME FIXTURE
 AS 75WATT INCANDESCENT.
 PLEASE ADJUST ENERGY CALCULATIONS OR REVISE PLANS
 ACCORDINGLY.
 PLEASE SUBMIT EITHER REVISED CORRECTED AND COORDINATED
 PLANS TO THE STATE.
  
 THESE ARE TO BE REVIEWED BY THE STATE AND STAMPED.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CITY OF WEST PALM BEACH
 561-805-6717

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2007-07-07 Cont ID  
Sent By dpalmer Date 2007-07-07 Time 11:00 Rev Time 0.00
Received By dpalmer Date 2007-07-07 Time 10:54 Sent To PC
Notes
2007-07-07 11:02:07** UNSAT **
  
 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS STILL DO
 NOT CORRELATE AND MATCH WITH THE PLANS.
 PLEASE SEE THE NUMBER OF LUMINARIES, THE WATTAGE OF
 LUMINARIES AND THE TOTAL OF FIXTURES DO NOT CORRELATE
 WITH PLANS.
 THIS IS THE SAME COMMENT I HAVE STATED OVER ALL THE
 PREVIOUS REVIEWS.
 PLEASE KNOW COPIES OF PLANS AND ENERGY CALCULATIONS ARE
 BEING RETAINED AND CONTACT WITH DCA/ HWC (STATE OF
 FLORIDA) WILL BE MADE TO GO OVER THE ISSUES.
  
 PLEASE SEE FBC 13-415.1.A, 13-415.2
  
 *IF THERE ARE ANY QUESTIONS, PLEASE CONTACT THIS
 REVIEWER TO GO OVER COMMENTS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-07-07 Cont ID  
Sent By dpalmer Date 2007-07-07 Time 10:55 Rev Time 0.00
Received By dpalmer Date 2007-07-07 Time 10:08 Sent To PC
Notes
2007-07-07 10:55:25STAMPED SHEET E-2 ONLY .

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-06-21 Cont ID  
Sent By dpalmer Date 2007-06-21 Time 13:22 Rev Time 0.00
Received By dpalmer Date 2007-06-21 Time 12:14 Sent To  
Notes
2007-06-28 08:15:03DCA APPROVED MODULAR BUILDING , SITE PLAN REVIEWED FOR
 TABLE 602 & TABLE 704.8 WALL OPENINGS.
 FOUNDATION PERMIT: 07020510
 IMPACT FEES PAID$415.92
 RADON FEES4800 SQ FT
 NOC
2007-06-21 13:22:47**** NOTES ****
  
 1) NOTE: PLANS WHICH ARE STAMPED FROM DCA ARE FOR
 BUILDING. THERE IS A CONFLICT WITH CODE COMPLIANCE FOR
 SAID PLAN REVIEW OF ELECTRICAL PLANS AND ENERGY
 CALCULATIONS. CONTRACTOR IS SENDING PLANS BACK TO DCA
 ALONG WITH REVISED ENERGY CALCULATIONS AND WILL SUBMIT
 REVISED DCA PLANS AT A LATER DATE.
 DCA ELECTRICALPLANS ARE NOT STAMPED REVIEWED BY THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-06-08 Cont ID  
Sent By dpalmer Date 2007-06-08 Time 12:46 Rev Time 0.00
Received By dpalmer Date 2007-06-08 Time 12:11 Sent To  
Notes
2007-06-08 12:46:52 
 ** UNSAT 3RD REVIEW**
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEWS ALONG
 WITH A NEW NOTE BASED ON REVISED NOTES ON PLANS NEED TO
 BE ADDRESSED.
  
 1) NOTE:PLEASE SEE PREVIOUS NOTES WHICH REQUESTED THE
 MINIMUM LEVELS FOR FBC ADA LEVELS TO BE STATED ON
 PLANS. AS NOTED PREVIOUSLY THIS COULD BE SHOWN ON PLANS
 AND LEGEND. IT IS KNOWN THESE FIRE ALARM AND ANY FIRE
 SPRINKLERS WILL BE UNDER SEPARATE PERMITS, HOWEVER THE
 BASE PLANS ARE REQUIRED TO SHOW THE *MINIMUM*
 REQUIREMENTS FOR THIS.
 PLEASE SEE 11-4.28.1 FOR LOCATIONS, 11-4.28.2 AND .3(4)
 FOR LEVELS.
  
 2) NOTE: PLEASE SEE THE PREVIOUS SUBMITTED ENERGY
 CALCULATIONS HAD COMMENTS AS THEY NEEDED SOME
 COORDINATION WITH PLANS, HOWEVER THIS SUBMITTED PACKAGE
 DOES NOT CONTAIN ANY SUBMITTED ENERGY CALCULATIONS FOR
 REVIEW OF METHOD, COORDINATION ETC AS REQUIRED PER FBC
 13-415.AB.1.1.
 PLEASE KNOW AS THESE WERE NOT SUBMITTED, NO REVIEW OF
 THESE ITEMS CAN BE DONE.
  
 3) NOTE: PLEASE SEE THE REVISED NOTES ON E-1 NOW STATES
 IN *SPECIAL ENERGY EFFICIENT NOTES* , NOTE #5 THAT ALL
 INTERIOR LIGHTING IS GOING TO MEET 13-415.1.ABC.1.1,
 HOWEVER THE PLANS DO NOT SHOW THIS. THERE IS NOT SUCH
 DEVICES ON PLANS, NO CONTROLS, NO SCHEDULING, NO OVER
 RIDE TIMES ETC.
 PLEASE SEE CHAPTER 13 THIS SECTION AS STATED AND SEE
 PREVIOUS SUBMITTED PLANS FOR THIS SAME ITEM.
  
 ** EVEN IF PLANS ARE STAMPED BY THE STATE, IF THE PLANS
 DO NOT CORRELATE FOR CODE COMPLIANCE THEY CAN NOT BE
 ISSUED AND STAMPED.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-03-31 Cont ID  
Sent By dpalmer Date 2007-03-31 Time 12:02 Rev Time 0.00
Received By dpalmer Date 2007-03-31 Time 10:17 Sent To  
Notes
2007-04-16 15:28:032007-04-16 15:28:03
 *** NOTES ADDED.
  
 1) NOTE; PLEASE SEE NOTE #1 FROM REVIEW DATED 3/31/07
 HAS BEEN REMOVED AS THE ES-1 SHEET WAS LOCATED IN WITH
 THE CIVIL SHEETS.
 PLEASE BE SURE TO INSERT THE ES-1 SHEETS IN WITH THE
 ELECTRICAL PLANS. PLEASE SUBMIT STRUCTRUAL DETAIL FOR
 NEW CEILING HUNG TRANSFORMER.
 PLEASE CALRIFY THAT THE TRANSFORMER WILL NOT BE ABOVE
 ANY SUSPENDED CEILING ETC PER 450.13
2007-03-31 12:03:15 
  
 *** UNSAT 2ND REVIEW **
  
 ** PLEASE SEE SOME COMMENTS FORM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING AND SOME NEW COMMENTS BASED
 ON CHANGES ON PLANS.
  
  
 1) NOTE:
  
 2) NOTE: PLEASE SEE THE ENERGY CALCULATIONS DO NOT
 CORRELATE WITH THE ELECTRICAL PLANS SUBMITTED OR THE
 FIXTURES AS STATED ON LEGEND, WATTAGE ON FIXTURES, THE
 AMOUNT OF FIXTURES ETC.
 PLEASE COORDINATE THE USE, LIGHTING POWER DENSITIES AND
 METHOD OF CALCULATIONS BEING USED.
 PLEASE SEE THE INPUT DATA REPORT.
 PLEASE CLARIFY WHY PLANS CONTAIN NOTES FOR LIGHTING
 CONTROLS REQUIRED IF THE BUILDING IS OVER 5K SQ FT. IF
 THE BUILDING WHICH IS BEING SHOWN IS UNDER THE 5K,
 PLEASE DO NOT REFERENCE THESE CODE REQUIREMENTS UNLESS
 IT IS THE INTENTION AND DESIGN TO PROVIDE LIGHTING
 ENERGY EFFICIENT CONTROLS FOR AUTO-MATED SHUT OF
 LIGHTING.
 PLEASE SEE 13-415.1AB.1.1, 13-415.2
 PLEASE ALSO SEE 13-103.1.1.1 AS THE ENERGY CALCULATIONS
 SHALL BE SIGNED, DATED AND SEALED BY THE RESPONSIBLE
 DESIGNERS.
 PLEASE SEE THE CALCULATIONS SUBMITTED ARE PHOTOCOPIES
 OF SIGNED SHEETS.
  
 3) NOTE: PLEASE SEE THAT THE CODE SECTION REFLECTED FOR
 WIRING OF EMERGENCY/EXIT LIGHTS SHOULD BE 700.12E.
 PLEASE SEE THIS SEEMS TO HAVE BEEN A MISPRINT AND WOULD
 HAVE BEEN REDLINED IF THE PLANS WERE NOT COMING BACK
 FOR OTHER COMMENTS.
 PREVIOUS REVIEW NOTE:
  
 4) NOTE: PLEASE SEE THAT MINIMUM STROBES AND HORN
 LEVELS SHALL BE STATED ON PLANS FOR FBC 11-4.28.2,
 .3(4).
 THIS COMMENT WAS MADE ON PREVIOUS REVIEW AND NOT
 MINIMUM LEVELS ARE STATED FOR ADA COMPLIANCE. THIS CAN
 BE DONE ON THE SYMBOL LEGEND.
 ** PLEASE KNOW EVEN THOUGH THE FIRE ALARM WILL BE UNDER
 A SEPARATE PERMIT THIS IS REQUIRED ON THE PLANS AT THIS
 TIME.
 ** PLEASE ALSO KNOW THE SECURITY SYSTEM AS SHOWN WILL
 ALSO BE UNDER A SEPARATE PERMIT.
  
 5) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS IF
 THE SERVICE AS SHOWN IS BEING FED FROM AN EXISTING
 SERVICE.
 220, 215.3, 230.42
 PLEASE ALSO SEE THAT ALL CONTINUOUS LOADS SHALL BE
 SHOWN AT 125%. 215.3 AND 230.42.
  
 6) NOTE: PLEASE SEE *F*,*S* AND *WM* SHEETS CONTAIN A
 RAISED SEAL OVER A PHOTO-COPIED SIGNATURE FOR THE
 ENGINEER * MR. ALBERT KWAN*. THIS HAS BEEN DONE ON A
 REPETITIVE BASIS BY THE SAID DESIGNER ON SEVERAL
 PROJECTS WHICH HAVE BEEN SUBMITTED TO THIS JURISDICTION
 AND ON SEVERAL OCCASIONS THE NOTES HAVE BEEN ISSUED TO
 THIS ENGINEER THAT AN *ORIGINAL SIGNATURE* IS REQUIRED
 UNDER FLORIDA STATUTES 471.025 AND FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002.
 THE PREVIOUS SHEETS SUBMITTED WERE *PHOTO-COPIES* AND
 THE ONLY THING WHICH HAS CHANGED IS THE FACT THE
 PREVIOUS PLANS WITH THE PHOTO-COPIED SIGNATURE NOW HAS
 A RAISED SEAL OVER THE PHOTO-COPIED SIGNATURE.
 **PLEASE KNOW AT THIS TIME THESE SHEETS WILL BE
 RETAINED BY THIS OFFICE AND SENT TO THE FLORIDA BOARD
 OF PROFESSIONAL ENGINEERS FOR REVIEW.
  
 7) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A
 NOTICE AT THIS TIME.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-01-11 Cont ID  
Sent By dpalmer Date 2007-01-11 Time 08:36 Rev Time 0.00
Received By dpalmer Date 2007-01-11 Time 06:56 Sent To  
Notes
2007-01-11 08:37:20*** UNSAT **
  
 1) NOTE: PLEASE KNOW ALL OF THE FOLLOWING CODES SHALL
 BE STATED AS RELEVANT TO THE DESIGN AND PLANS. 2005
 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
 ** PLEASE ALSO KNOW AS PERMIT APPLICATION WAS SUBMITTED
 AFTER DECEMBER 7TH,2006, AS OF DECEMBER 8TH, 2006 THE
 2005 NEC BECAME ADOPTED BY THE STATE AS WELL AS THE
 2006 REVISIONS TO THE 2004 FBC.
  
 2) NOTE: PLEASE CLARIFY SERVICE AS SHOWN. PLEASE SEE
 RISER SHOWS THIS BEING FED FROM SERVICE BY OTHERS,
 HOWEVER NO INFORMATION WAS SUBMITTED FOR WHERE AND HOW
 THIS EXISTING SERVICE IS, LOAD, SIZE, ETC.PLEASE SEE
 SOME OF THE FOLLOWING COMMENTS WILL BE BASED ON WHETHER
 OR NOT THIS MDP IS A NEW SE MAIN OR A SUB PANEL.
 COMMENTS WILL BE ALSO BROUGHT UP IF FED ON THE LOAD
 SIDE OF AN EXISTING MAIN, THEN THE GROUNDING ELECTRODE
 SYSTEM AS SHOWN ON RISER WILL CHANGE. PLEASE SEE OTHER
 COMMENTS FOR CORRELATION OF SEVERAL OTHER ELECTRICAL
 ITEMS.
 FBC 106.1.2, 106.3.5.1.2
 NEC 2005
  
 3) NOTE: PLEASE SEE IF THIS IS A NEW SERVICEMAIN, A
 MAIN CIRCUIT BREAKER WILL BE REQUIRED IN THE MDP PER
 230.70, 230.71.
  
 4) NOTE: PLEASE SEE RISER SHOWS THIS PANEL AS BEING
 3-PHASE AND 1-PHASE? PLEASE ALSO SEE MDP WHICH IS THREE
 PHASE FOR BREAKERS TO EACH SUB PANEL, HOWEVER EACH SUB
 PANEL IS ONLY 1-PHASE?
 PLEASE SEE THE SPACE ALLOTTED FOR EACH SUB PANEL SHOWS
 ONLY 2-POLES BEING USED, YET PANEL SHOWS PHASES BEING
 3? PLEASE CORRELATE AS LOADS, SERVICE ETC CAN NOT BE
 CONFIRMED FOR COMPLIANCE AT THIS TIME.
 FBC 106.1.2, 106.3.5.1.2
 PLEASE SEE NEXT COMMENT ALSO.
  
 5) NOTE: PLEASE CORRELATE FEEDERS TO SUB PANELS. RISER
 SHOWS BOTH 4/0'S AND #3'S TO EACH?
 PLEASE SEE ONE SHOWS 3-PHASE FOR THE NUMBER OF FEEDERS
 AND THE OTHER SHOWS 1-PHASE FOR THE SAME. PLEASE SEE
 PANELS FOR EACH SUB PANEL ARE SHOWN AS 1-PHASE WITH A
 2-POLE 80AMP BREAKER OR 100A BREAKER. PLEASE ALSO KNOW
 THAT 4/0'S WILL NOT FIT INTO A 80AMP OR 100AMP
 BREAKERS.
 PLEASE CORRELATE ALL OF THE FEEDERS, THE PHASING, ETC
 PLEASE KNOW COMPLIANCE FOR MANY ITEMS CAN NOT BE
 REVIEWED AT THIS TIME DUE TO SOME COORDINATION ISSUES.
 FBC 106.1.2, 106.3.5.1.2,
 NEC 215.3, 215.5, 230, 310.16, 240.4 ETC
  
 6) NOTE: PLEASE SEE RISER MENTIONS 1 1/2INCH THWN,
 WHICH SEEMS TO BE A MISPRINT WHICH SHOULD READ CONDUIT
 INSTEAD, UNLESS THE CONDUIT IS THE 2INCH AS NOTED
 DIRECTLY ABOVE.
 FBC 106.1.2
  
 7) NOTE: PLEASE SEE 250.50 AND 250.32 FOR THIS
 STRUCTURE IS BEING FED FROM AN EXISTING SERVICE AND IS
 ON THE LOAD SIDE OF AN EXISTING MAIN. PLEASE SEE THE
 NEUTRAL AND THE GROUNDING ELECTRODE AT THIS DETACHED
 BUILDING SHALL NOT BE BONDED TOGETHER. IF THIS IS A NEW
 SERVICE THEN THE RISER WILL BE CHANGING BASED ON THE
 NEW SERVICE ENTRANCE CONDUCTORS WHICH WILL NOT CONTAIN
 AN EQUIPMENT GROUNDING CONDUCTOR.
 250.6, 250.24B
 PLEASE ALSO SEE MISSING FOOTER STEEL FROM GROUNDING
 RISER. MENTIONS BUILDING STEEL WHICH IS REQUIRED TO BE
 PART OF THE SYSTEM, HOWEVER FOOTER STEEL COULD NOT BE
 LOCATED.250.50
  
 8) NOTE: PLEASE CLARIFY THE OCCUPANCY SENSORS AS SHOWN.
 PLEASE SEE SOME ROOMS DO NOT CONTAIN THESE. PLEASE
 STATE THE TIMES.
 PLEASE INDICATE THAT THE EMERGENCY AND EXIT LIGHTS
 SHALL BE CONNECTED AHEAD OF THESE DEVICES. THIS AHJ HAS
 HAD NUMEROUS INSTANCES WHERE THE CONNECTION OF THE
 EMERGENCY AND EXIT LIGHTS ARE BEING DONE ON THE LOAD
 SIDE OF THESE OC DEVICES. PLEASE PROVIDE NOTE/DETAIL
 FOR THIS.
 700.12E.
  
 9) NOTE: PLEASE SEE THAT MINIMUM STROBES AND HORN
 LEVELS SHALL BE STATED ON PLANS FOR FBC 11-4.28.2,
 .3(4).
 ** PLEASE KNOW EVEN THOUGH THE FIRE ALARM WILL BE UNDER
 A SEPARATE PERMIT THIS IS REQUIRED ON THE PLANS AT THIS
 TIME.
 ** PLEASE ALSO KNOW THE SECURITY SYSTEM AS SHOWN WILL
 ALSO BE UNDER A SEPARATE PERMIT.
  
 10) NOTE: PLEASE CLARIFY TITLE BLOCK AND LICENSURE FOR
 FIR. PLEASE SEE A BRUH- HOSEIN-RUPP IS BEING SHOWN,
 HOWEVER LICENSURE IS STATED FOR ROYAL ARCHITECTURE. THE
 STATE DEPARTMENT OF BUSINESS AND PROFESSIONAL
 REGULATION?S WEBSITE DOES NOT CONTAIN ANY RELEVANT
 INFORMATION FOR OTHER NAMES RELATED TO THIS LICENSE AS
 SHOWN.
  
 11) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS IF
 THE SERVICE AS SHOWN IS BEING FED FROM AN EXISTING
 SERVICE.
 220, 215.3, 230.42
 PLEASE ALSO SEE THAT ALL CONTINUOUS LOADS SHALL BE
 SHOWN AT 125%. 215.3 AND 230.42.
  
  
 ** PLEASE KNOW AS THERE ARE SEVERAL UNANSWERED
 QUESTIONS WITH THE RISER/PANELS AND FEEDERS THERE MAY
 BE FURTHER COMMENTS ON NEXT REVIEW.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 3 Status N Date 2007-10-19 Cont ID  
Sent By rchokshi Date 2007-10-19 Time 15:18 Rev Time 0.00
Received By rchokshi Date 2007-10-19 Time 15:11 Sent To  
Notes
2007-10-19 15:18:04PASSED
  
 DAMON A. ROBLING, AIA OF ROBLING ARCHITECTURE CONST. ,
 INC.,SENT US ANE-MAIL ON10/17/07 @ 1:33PM
 EXPLAINING THAT NO CHANGES WERE MADE THAT AFFECTEDENG
 REVIEW. THIS E-MAIL IS STORED IN COMPUTER INBOX AND A
 COPY OF E-MAIL ATTACHED IN DRAWINGS.
  
 RASIK CHOKSHI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2007-04-06 Cont ID  
Sent By rchokshi Date 2007-04-06 Time 15:43 Rev Time 0.00
Received By rchokshi Date 2007-04-06 Time 15:43 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-02-02 Cont ID  
Sent By rchokshi Date 2007-02-02 Time 09:03 Rev Time 0.00
Received By rchokshi Date 2007-02-02 Time 09:00 Sent To  
Notes
2007-02-02 09:03:24PLEASE PROVIDE FOLLOWING INFO:
  
 1. PLEASE SHOW STANDARDS NOTES OF CITY OF WPB ON
 DRAWINGSFOR SIDEWALK WIDTH , ITS SLOPE, DRIVEWAY,
 PARKING, HANDICAP PARKING, PAINTPER CITY CODES ETC.,,
 MUST MEET PER ADA,,ETC.,
 2. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 3. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD ,
 SIDEWALK ELEVATION MUST MEET FL BLDG CODE, PLEASE SHOW
 ON THE DRAWINGS.
 4. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, GEO TECH
 REPORT.
 5.PLEASE SHOW STORM WATER CALCULATIONS, WHAT CRITERIA
 YOU ASSUMEDFOR RUNOFF CAL.,, LIKE 1" OVER ENTIRE SITE
 OR2.5"CRITERIA, ?PERVIOUS AREA, LIKE GREEN,
 LAKES, ETC,IMPERVIOUS AREA CAL.,
 6. WHAT IS THE SITE AREA, YOU ARE DEVELOPING FOR THIS
 PROJECT ONLY ? SO, WE CAN CHECK PERVIOUS, IMPERVIOUS
 CAL.
 7. HOW YOU CONNECT TO THE STORM WATER PIPES IN YOUR
 SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER PIPES
 AROUND YOUR SITE SO, WE CANSEE THE BEST PIPE TO
 CONNECT WITH THE STORM WATERFROM ALL OTHER STORM
 WATER PIPES. PLEASE SHOW DETAIL OF THE CONTROL
 STRUCTURES WITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC DID YOU USE EXFILTRATION TRENCH ?
 8. POLLUTION PREVENTION DETAILS,CLOTHES USED FOR SILT
 ETC., PLANS SHOWING SILT FENCE AROUND THE SITE
 9. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED 11.
 ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND YOUR
 SITE FOR STORM WATER DRAIN.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-06-22 Cont ID  
Sent By mawillia Date 2007-06-22 Time 10:20 Rev Time 0.00
Received By mawillia Date 2007-06-21 Time 13:59 Sent To  
Notes
2007-06-21 14:01:22*****APPROVED*****
 THE COMMENT FROM THE PREVIOUS FIRE PLAN REVIEWS HAS
 BEEN ADDRESSED ADDRESSED;PLAN SHEETS LS-1, A-5, AND
 E-1 STAMPED, INITIALED, AND DATED.
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2007-06-21 Cont ID  
Sent By mawillia Date 2007-06-21 Time 10:48 Rev Time 0.00
Received By mawillia Date 2007-06-21 Time 10:39 Sent To  
Notes
2007-06-21 10:47:27*****UNSAT*****
 THE FOLLOWING COMMENT TAKEN FROM THE PREVIOUS FIRE PLAN
 REVIEWS STILL NEEDS TO BE ADDRESSED:
  
  
  
 1.THE COMPLETE AND/OR ACTUAL ADDRESS OF WHERE THE
 SCOPE OF WORK IS TO BE CONDUCTED SHALL BE IN THE TITLE
 BLOCK OF EACH SUBMITTED PLAN SHEET.PLAN SHEETS T-1,
 LS-1, AND A-1 THRU A-6 HAVE 355 JEFFERSON AS THE
 NUMERICAL ADDRESS, WHEREAS SHEETS F-1, S-1 THRU S-4,
 WM-1, AND WM-2 HAVE 901 SOUTH FLAGLER DRIVE AS THE
 ADDRESS. WHICH ONE IS IT?
  
  
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-05-03 Cont ID  
Sent By mawillia Date 2007-05-03 Time 16:37 Rev Time 0.00
Received By mawillia Date 2007-05-03 Time 15:27 Sent To  
Notes
2007-05-03 16:37:24*****UNSAT*****
 THE FOLLOWING COMMENT TAKEN FROM THE PREVIOUS FIRE PLAN
 REVIEW STILL NEEDS TO BE ADDRESSED:
  
  
  
 1.THE COMPLETE AND/OR ACTUAL ADDRESS OF WHERE THE
 SCOPE OF WORK IS TO BE CONDUCTED SHALL BE IN THE TITLE
 BLOCK OF EACH SUBMITTED PLAN SHEET.PLAN SHEETS T-1,
 LS-1, AND A-1 THRU A-6 HAVE 355 JEFFERSON AS THE
 NUMERICAL ADDRESS, WHEREAS SHEETS F-1, S-1 THRU S-4,
 WM-1, AND WM-2 HAVE 901 SOUTH FLAGLER DRIVE AS THE
 ADDRESS. WHICH ONE IS IT?
  
  
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-02-08 Cont ID  
Sent By mawillia Date 2007-02-08 Time 10:44 Rev Time 0.00
Received By mawillia Date 2007-02-08 Time 10:44 Sent To  
Notes
2007-02-08 12:08:16*****DENIED*****
  
  
 1.THE COMPLETE AND/OR ACTUAL ADDRESS OF WHERE THE
 SCOPE OF WORK IS TO BE CONDUCTED SHALL BE IN THE TITLE
 BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 2.THE NFPA 101, 2003 EDITION AND THE FLORIDA FIRE
 PREVENTION CODE 2004 SHALL BE REFERENCED.
  
 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, AND
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 4.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS TO THE
 PROPERTY OR VICINITY THEREOF (INCLUDING FIRE LANES).
  
 5.WHAT IS THE OCCUPANCY CLASSIFICATION FOR THIS
 STRUCTURE?
  
 6.INDICATE THE NEAREST FIRE HYDRANT(S) IN THE
 VICINITY OF THE STRUCTURE.PLEASE BE ADVISED THAT IF
 THE DISTANCE IS GREATER THAN 500 FEET, AN ADDITIONAL
 HYDRANT MAY BE REQUIRED.
  
 7.SHOW/DISPLAY THE NUMERICAL ADDRESS ON THE EXTERIOR
 ELEVATION THAT FRONTS JEFFERSON ROAD.AS PER WEST PALM
 BEACH CODE, THE ADDRESS NUMBERS SHALL BE NO LESS THAN
 6" IN HEIGHT NAND 1" IN WIDTH.
  
 8.ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM AN AREA
 HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE
 PROVIDED WITH PANIC HARDWARE OR FIRE EXIT HARDWARE,
 UNLESS OTHERWISE THEY ARE DELAYED-EGRESS LOCKS OR
 ACCESS-CONTROLLED EGRESS LOCKS PERMITTED AND APPROVED
 BY THE AHJ.
  
 9.SINCE THE STRUCTURE WILL HAVE A FIRE ALARM AND/OR
 FIRE SPRINKLER SYSTEM, A LAYOUT OF EACH OF THESE FIRE
 PROTECTION SYSTEMS WILL BE SUBMITTED FOR REVIEW.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-08-27 Cont ID  
Sent By adarroug Date 2007-08-27 Time 14:15 Rev Time 0.00
Received By adarroug Date 2007-08-27 Time 14:15 Sent To P
Notes
2007-08-27 14:16:13TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-08-14 Cont ID  
Sent By adarroug Date 2007-08-14 Time 11:23 Rev Time 0.00
Received By adarroug Date 2007-08-14 Time 11:23 Sent To E
Notes
2007-08-14 11:23:48TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-08-02 Cont ID  
Sent By adarroug Date 2007-08-02 Time 13:04 Rev Time 0.00
Received By adarroug Date 2007-08-02 Time 13:04 Sent To E
Notes
2007-08-02 13:05:06TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-07-19 Cont ID  
Sent By adarroug Date 2007-07-19 Time 14:02 Rev Time 0.00
Received By adarroug Date 2007-07-19 Time 14:02 Sent To B
Notes
2007-07-19 14:02:21TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-07-05 Cont ID  
Sent By adarroug Date 2007-07-05 Time 10:28 Rev Time 0.00
Received By adarroug Date 2007-07-05 Time 10:28 Sent To E
Notes
2007-07-05 10:28:47TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-05-17 Cont ID  
Sent By adarroug Date 2007-05-17 Time 14:42 Rev Time 0.00
Received By adarroug Date 2007-05-17 Time 14:42 Sent To  
Notes
2007-06-05 14:32:58TO "COMM" BD#34
2007-05-17 14:42:52WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-25 Cont ID  
Sent By adarroug Date 2007-03-25 Time 13:52 Rev Time 0.00
Received By adarroug Date 2007-03-25 Time 13:52 Sent To  
Notes
2007-03-25 13:54:41TO "COMM" BD#57

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-08 Cont ID  
Sent By mawillia Date 2007-02-08 Time 10:44 Rev Time 0.00
Received By mawillia Date 2006-12-17 Time 12:38 Sent To  
Notes
2007-01-08 09:22:26TO "COMM" BD#12
2006-12-17 12:38:26WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2007-06-25 Cont ID  
Sent By tgordon Date 2007-06-21 Time 14:59 Rev Time 0.30
Received By tgordon Date 2007-06-21 Time 14:51 Sent To  
Notes
2007-06-21 14:59:26PLANS FOR MODULAR BUILDINGS. HAVE DCA STAMP ON THEM

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-06-14 Cont ID  
Sent By tgordon Date 2007-06-14 Time 14:19 Rev Time 0.20
Received By tgordon Date 2007-06-14 Time 14:19 Sent To  
Notes
2007-06-14 14:21:45*** DENIED ***
 1) SEE ELECTRICAL REVIEW NOTES, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-04-02 Cont ID  
Sent By tgordon Date 2007-04-02 Time 09:45 Rev Time 0.30
Received By tgordon Date 2007-04-02 Time 09:45 Sent To  
Notes
2007-04-02 09:47:38*** DENIED ***
 1) MECHANICAL PLANS ARE OK BUT SEE ELECTRICAL REVIEW
 NOTES 2 AND 6, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-01-09 Cont ID  
Sent By tgordon Date 2007-01-09 Time 10:14 Rev Time 0.45
Received By tgordon Date 2007-01-09 Time 10:14 Sent To  
Notes
2007-01-09 10:33:22*** DENIED ***
 1) PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC
 13-101.1.1.
  
 2) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR A/C
 SYSTEMS, A/C EQUIPMENT LISTING IS CALLING FOR 10.5 SEER
 EQUIPMENT BUT THE MINIMUM IS 13 SEER, PER 2004/ 06 REV.
 FBC 13-607.1.ABC.3.2.1.
  
 3) SEE PLANS PAGE M-1 A/C UNIT MOUNTING DETAIL,
 CONDENSER DRAIN NEEDS TO DISCHARGE A MINIMUM OF 12"
 FROM THE BUILDING, PER 2004 FBC 1503.6.
  
 4) SEE PLANS PAGE M-1 RETURN AIR TRANSFER DUCTS, 10"
 FROM ROOM 102 TO 103 NEEDS TO BE 14", 10" FROM ROOM 112
 TO 107 NEEDS TO BE 14", AND 10" FROM ROOM 107 TO 109
 NEEDS TO BE 18",
 BALANCED RETURN AIR MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-06-27 Cont ID  
Sent By kstevens Date 2007-06-27 Time 17:50 Rev Time 0.00
Received By kstevens Date 2007-06-27 Time 17:45 Sent To  
Notes
2007-06-27 17:52:14PASSED/PROVISO
  
 REVISIONS REQUIRED FOR COVER SHEET. (SEE FOLLOWING
 COMMENT)
 COVER SHEET INDICATES ADDRESS AT 901 S FLAGLER DR., BUT
 THE PERMIT NUMBER AND PROPERTY CONTROL NUMBER INDICATE
 THE ADDRESS AS 355 JEFFERSON RD. PLEASE CONTACT LILI
 URSA AT 822-1239 AND ASSURE THE CORRECT ADDRESS.
 ****RESPONSE NOTED, BUT THE ADDRESS HAS NOT CHANGED.
 THE ADDRESS ON THE APPLICATION IS NOT CORRECT PER THE
 REVIEW OF LILI URSA FROM ADDRESSING.
 ******NO RESPONSE/NOT ADDRESSED. NEW PREMIT APPLICATION
 NOW SHOWS 900 S. FLAGLER DR.

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-06-18 Cont ID  
Sent By kstevens Date 2007-06-18 Time 16:52 Rev Time 0.00
Received By kstevens Date 2007-06-18 Time 16:52 Sent To  
Notes
2007-06-18 16:57:59DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 11
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
 ******FROM PREVIOUS REVIEWS:
  
 1. COVER SHEET INDICATES ADDRESS AT 901 S FLAGLER DR.,
 BUT THE PERMIT NUMBER AND PROPERTY CONTROL NUMBER
 INDICATE THE ADDRESS AS 355 JEFFERSON RD. PLEASE
 CONTACT LILI URSA AT 822-1239 AND ASSURE THE CORRECT
 ADDRESS.
 ****RESPONSE NOTED, BUT THE ADDRESS HAS NOT CHANGED.
 THE ADDRESS ON THE APPLICATION IS NOT CORRECT PER THE
 REVIEW OF LILI URSA FROM ADDRESSING.
 ******NO RESPONSE/NOT ADDRESSED. NEW PREMIT APPLICATION
 NOW SHOWS 900 S. FLAGLER DR.
  
 2. OK
 3. OK
  
 4. SHT A-1 TYPICAL ACCESSIBLE RESTROOM DETAIL. SHOW THE
 FOLLOWING:
 A. 11-4.16.5 FLUSH CONTROLS
 ****NOT ADDRESSED
 ******NO RESPONSE/NOT ADDRESSED
 B. OK
 C. 11-4.19.5 FAUCETS
 ****NOT ADDRESSED
 ******NO RESPONSE/NOT ADDRESSED
  
 5. SUBMIT A DETAIL FOR THE SINKS IN ROOMS 103 & 104
 SHOWING COMPLIANCE WITH THE FOLLOWING.
 A. OK
 B. OK
 C. 11-4.24.4 SINK DEPTH
 ****NOT ADDRESSED
 ******NO RESPONSE/NOT ADDRESSED
 D. OK
 E. OK
 F. 11-4.24.7 FAUCETS
 ****NOT ADDRESSED
 ******NO RESPONSE/NOT ADDRESSED
  
 6. OK
 7. OK
 8. OK
 10. OK
 11. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 808-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-05-07 Cont ID  
Sent By kstevens Date 2007-05-07 Time 11:13 Rev Time 0.00
Received By kstevens Date 2007-05-07 Time 11:13 Sent To  
Notes
2007-05-07 11:38:13DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 11
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. COVER SHEET INDICATES ADDRESS AT 901 S FLAGLER DR.,
 BUT THE PERMIT NUMBER AND PROPERTY CONTROL NUMBER
 INDICATE THE ADDRESS AS 355 JEFFERSON RD. PLEASE
 CONTACT LILI URSA AT 822-1239 AND ASSURE THE CORRECT
 ADDRESS.
 ****RESPONSE NOTED, BUT THE ADDRESS HAS NOT CHANGED.
 THE ADDRESS ON THE APPLICATION IS NOT CORRECT PER THE
 REVIEW OF LILI URSA FROM ADDRESSING.
  
 2. CIVIL SHT 1 OF 2 STATES 1" BACKFLOW PREVENTOR. PER
 TABLE 603(D) THE BACKFLOW PREVENTOR ASSEMBLIES SHALL BE
 AT LEAST THE SAME SIZE AS THE LINE IN WHICH THEY ARE
 INSTALLED. THE WASTER SERVICE IS SHOWN AT 1-1/2".
 PLEASE PROVIDE THE APPROVED SIZE RPZV BACKFLOW.
 ****SHEETS HAVE BEEN DELETED. COMMENT WILL BE TAKEN
 CARE OF AT THE TIME OF INSPECTION.
  
 3. OK
  
 4. SHT A-1 TYPICAL ACCESSIBLE RESTROOM DETAIL. SHOW THE
 FOLLOWING:
 A. 11-4.16.5 FLUSH CONTROLS
 ****NOT ADDRESSED
 B. OK
 C. 11-4.19.5 FAUCETS
 ****NOT ADDRESSED
  
 5. SUBMIT A DETAIL FOR THE SINKS IN ROOMS 103 & 104
 SHOWING COMPLIANCE WITH THE FOLLOWING.
 A. OK
 B. OK
 C. 11-4.24.4 SINK DEPTH
 ****NOT ADDRESSED
 D. OK
 E. OK
 F. 11-4.24.7 FAUCETS
 ****NOT ADDRESSED
  
 6. OK
 7. OK
 8. OK
 10. OK
 11. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 808-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-02-03 Cont ID  
Sent By kstevens Date 2007-02-03 Time 17:32 Rev Time 0.00
Received By kstevens Date 2007-02-03 Time 17:31 Sent To  
Notes
2007-02-03 18:03:17DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 11
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. COVER SHEET INDICATES ADDRESS AT 901 S FLAGLER DR.,
 BUT THE PERMIT NUMBER AND PROPERTY CONTROL NUMBER
 INDICATE THE ADDRESS AS 355 JEFFERSON RD. PLEASE
 CONTACT LILI URSA AT 822-1239 AND ASSURE THE CORRECT
 ADDRESS.
  
 2. CIVIL SHT 1 OF 2 STATES 1" BACKFLOW PREVENTOR. PER
 TABLE 603(D) THE BACKFLOW PREVENTOR ASSEMBLIES SHALL BE
 AT LEAST THE SAME SIZE AS THE LINE IN WHICH THEY ARE
 INSTALLED. THE WASTER SERVICE IS SHOWN AT 1-1/2".
 PLEASE PROVIDE THE APPROVED SIZE RPZV BACKFLOW.
  
 3. THE BRUH-HOSEIN-RUPP PARTNERSHIP REQUIRES A
 CERTIFICATE OF AUTHORIZATION ON EACH SHEET THAT THE
 FIRM NAME IS SHOWN ON THE TITLE BLOCK. PLEASE PROVIDE
 ON EACH SHEET AS WELL AS ALL OTHER REQUIREMENTS OF FAC
 61G1-16.004 & FS 481.219, 481.2055.
  
 4. SHT A-1 TYPICAL ACCESSIBLE RESTROOM DETAIL. SHOW THE
 FOLLOWING:
 A. 11-4.16.5 FLUSH CONTROLS
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
  
 5. SUBMIT A DETAIL FOR THE SINKS IN ROOMS 103 & 104
 SHOWING COMPLIANCE WITH THE FOLLOWING.
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.3 KNEE CLEARANCE
 C. 11-4.24.4 SINK DEPTH
 D. 11-4.24.5 CLEAR FLOOR SPACE - SHALL EXTEND A
 MAXIMUM OF 19" UNDERNEATH THE SINK. (FIG 32). - CABINET
 DOORS NOT APPROVED IN THE CLEAR FLOOR SPACE.
 E. 11-4.24.6 EXPOSED PIPES & SURFACES
 F. 11-4.24.7 FAUCETS
  
 6. A DRINKING FOUNTAIN IS REQUIRED PER TABLE 403.1.
 PLEASE INDICATE THE LOCATION AND SUBMIT A DETAIL
 SHOWING COMPLIANCE WITH SECTION 11-4.15 AND ALL
 SUBSECTIONS AND SECTION 11-4.1.3(10)(A) PROVISIONS FOR
 THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING IS THE
 UNIT IS NOT A HI/LOW UNIT.
  
 7. SHT A-1 FINISH SCHEDULE FOR RESTROOMS 110 & 111.
 REMARKS INDICATE CERAMIC TILE TO 42" AFF. THE
 REQUIREMENT PER SECTION 1210.2 IS FOR THE SMOOTH, HARD,
 NONABSORBENT SURFACE TO BE INSTALLED UP TO 48". PLEASE
 CORRECT THE REMARKS.
  
 8. SHT M-1 SHOW THE FLOOR PLAN FOR THE SINK IN ROOM 104
 AS WELL AS THE SANITARY AND WATER RISER DIAGRAMS.--
 THE RISER DIAGRAM FOR THE SINK IN ROOM 103 DOES NOT
 MEET THE CODE REQUIREMENT THAT STATES THE WASH MACHINE
 SHALL CONNECT TO A BRANCH DRAIN OR STACK A MINIMUM OF
 3" IN DIAMETER. SHOW THE FUTURE STUB UP ON THE RISER.
 THE W/M WILL ALSO REQUIRE A VENT CONNECTION WHEN THE
 SANITARY IS CONNECTED IN THE FUTURE. SECTIONS 406.3 &
 901.2.1.
  
 10. SHT M-1, ALL WATER RISER DIAGRAMS. THE WATER HAMMER
 ARRESTORS SHALL BE LOCATED NEAR THE FIXTURES IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING AS INDICATED.
 PDI-WH 201 AND MANUF. INSTALLATION INSTRUCTIONS.
  
 11. A SEPARATE IRRIGATION PERMIT WILL BE REQUIRED.
 PLANS MAY BE SUBMITTED AT THE TIME OF APPLICATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 808-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2007-08-27 Cont ID  
Sent By jroach Date 2007-08-27 Time 13:14 Rev Time 0.00
Received By jroach Date 2007-08-27 Time 13:14 Sent To  
Notes
2007-08-27 13:15:218/27/07
  
 PASSED LANDSCAPE AS-BUILTS.
  
 JOHN ROACH, SENIOR PLANNER

Review Stop Z ZONING
Rev No 3 Status P Date 2007-06-18 Cont ID  
Sent By jroach Date 2007-06-18 Time 19:37 Rev Time 0.00
Received By jroach Date 2007-06-18 Time 19:37 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2007-04-04 Cont ID  
Sent By jroach Date 2007-04-04 Time 12:09 Rev Time 0.00
Received By jroach Date 2007-04-04 Time 12:09 Sent To  
Notes
2007-04-04 12:18:49***FAILED***
  
 1) PLEASE PROVIDE DOCUMENTATION THAT FP&L HAS NO
 OBJECTION TO THE PLANTING OF TREES/PALMS WITHIN THEIR
 EASEMENT.
  
 2) LANDSCAPE PLANS (DETAILS) REFERENCE TO
 SPECIFICATIONS.NO SPECIFICATIONS WERE PROVIDED (I.E.
 QUALITY, INSTALLATION, MAINTENANCE, GUYING AND STAKING,
 ETC.).
  
 3) PLEASE INCLUDE A SITE PLAN SHOWING THE LOCATION OF
 THE BUILDINGS, SETBACKS, ETC.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-01-25 Cont ID  
Sent By jroach Date 2007-01-25 Time 15:10 Rev Time 0.00
Received By jroach Date 2007-01-25 Time 15:10 Sent To  
Notes
2007-01-25 15:23:44***FAILED***
  
 1) SIGNED AND SEALED LANDSCAPE PLANS SHALL BE SUBMITTED
 WITH THE PERMIT APPLICATION.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT JOHN ROACH, SENIOR
 PLANNER, AT (561) 822-1435.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved