Plan Review Stops For Permit 06120319 |
Review Stop |
AD |
ADDRESSING |
Rev No |
2 |
Status |
P |
Date |
2007-03-15 |
|
|
Cont ID |
|
Sent By |
lursu |
Date |
2007-03-15 |
Time |
14:17 |
Rev Time |
0.00 |
Received By |
lursu |
Date |
2007-03-14 |
Time |
15:51 |
Sent To |
|
|
Notes |
2007-03-15 14:18:19 | PERMIT WAS ASSIGNED TO UNIT 400 AS ON THE SITE PLANS . | | | | LACRAMIOARA URSU | | MIS - GIS SUPPORT SPECIALIST | | CITY OF WEST PALM BEACH | | OFFICE:822-1239 | | FAX: 822-1249 | | E-MAIL:[email protected] |
|
|
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
F |
Date |
2007-01-09 |
|
|
Cont ID |
|
Sent By |
lursu |
Date |
2007-01-09 |
Time |
09:11 |
Rev Time |
0.00 |
Received By |
lursu |
Date |
2007-01-09 |
Time |
09:11 |
Sent To |
|
|
Notes |
2007-01-09 09:12:04 | PLEASE EXPLAININ WHICH UNIT NUMBER THE JOB SITE IS | | LOCATED ON THE 4TH FLOOR. | | | | LACRAMIOARA URSU | | MIS - GIS SUPPORT SPECIALIST | | OFFICE:822-1239 | | FAX: 822-1249 | | E-MAIL:[email protected] | 2007-01-07 18:21:38 | NEEDS UNIT/SUITE, ALSO WITH 06120320 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
6 |
Status |
P |
Date |
2007-11-01 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-11-01 |
Time |
11:42 |
Rev Time |
3.77 |
Received By |
jwitmer |
Date |
2007-11-01 |
Time |
10:18 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
P |
Date |
2007-09-04 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-09-04 |
Time |
07:17 |
Rev Time |
0.77 |
Received By |
jwitmer |
Date |
2007-09-04 |
Time |
07:01 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2007-08-27 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-08-27 |
Time |
15:07 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2007-08-27 |
Time |
15:07 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2007-06-27 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-06-27 |
Time |
15:18 |
Rev Time |
0.77 |
Received By |
jwitmer |
Date |
2007-06-27 |
Time |
15:18 |
Sent To |
|
|
Notes |
2007-06-27 15:19:11 | SEE PERMIT 06120320 FOR 3RD FLOOR PERMIT. | | H PISKURA HAS THRESHOLD INSPECTION PLAN & SPECIAL | | INSPECTOR AGRREMENT. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2007-03-30 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-03-30 |
Time |
13:49 |
Rev Time |
2.22 |
Received By |
jwitmer |
Date |
2007-03-30 |
Time |
13:49 |
Sent To |
|
|
Notes |
2007-03-30 14:24:40 | BUILDING PLAN REVIEW | | PERMIT: 06120319 | | ADD: 222 LAKEVIEW AVE 4TH FLOOR | | CONT: PASS INTERNATIONAL | | TEL: (561)706-7201 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | 2NDREVIEW | | ACTION: DENIED | | | | 1)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | BER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | 2 ) FL S S 713.13 | | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF | | THE COURT. | | NOTE: 713.13(2) | | IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS | | NOT ACTUALLYCOMMENCED | | WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE | | IS NULL & VOID. | | NOTE: 713.13(6)THE POSTING OF THE NOTICE OF | | COMMENCEMENT AT THE | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | 3A)2ND REQUEST, THE MEP AND FS SHEETS ARE STILL | | MISSING THE CERTIFICATE OF AUTHORIZATION FOR ASSOCIATED | | SPACE DESIGN. | | 481.219 F.S.CERTIFICATE OF | | AUTHORIZATION.THE TITLE BLOCK FOR ANY | | SHEET BEARING THE NAME OF AN ARCHITECT | | PRACTICING UNDER A FICTITIOUS NAME, A | | CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL | | SERVICES, SHALL INCLUDE | | THE CERTIFICATE OF AUTHORIZATION | | NUMBER.ADD THE NUMBER TO EACH SHEET. | | THIS MAY BE ADDED BY HAND. | | | | 3 B-C)OK | | | | 3D) 2ND REQUEST, BUILDING FEATURES, TYPE OF | | CONSTRUCTION, TYPE I UNPROTECTED, SPRINKLERED. PLEASE | | SEE | | TABLE 503, TYPE I BUILDINGS ARE EITHER AOR B FOR | | ALLOWABLE STORIES. RESPONCE WAS WE ARE NOT ADDING ANY | | STORIES. | | WHILE THIS IS TRUE NO STORIES ARE BEING ADDED THE | | AMOUNT OF FIRE SAFING BUILT INTO THE BUILDING IS | | DETERMINED IF THE BUILDING EXCEEDS A CERTIAN LIMIT IN | | FT. TABLE 503 | | WHILW A TYPE IB BUILDING IS LIMITED TO 160' A TYPE IA | | BUILDING IS UNLIMITED IN HEIGTH. TABLE 601 PROVIDES THE | | DIFFERENCE IN FIRE RATINGS BETWEEN A TYPE IA OR A IB. | | PLEASE PROVIDE FOOTAGE IN HEIGTH, SO THE CORRECT FIRE | | SAFING REQUIREMENTS WILL BE MEET IN THE NEW FLOOR DECK | | AREA. | | | | 4)2ND REQUEST,A7.041 DETAIL# 1 PANTRY, THE | | ELEVATIONS FAIL TO SHOW COMPLIANCE | | FOR A FORWARD APPROACH. THE DOORS FLOORAND SHELVING | | WOULD NEED TO BE REMOVED | | TO ALLOW FOR THE FORWARD APPROACH USAGE. | | T SINKS: | | 11-4.24.2 SINKS, HEIGHT. SINKS SHALL | | BE MOUNTED WITH THE COUNTER NO HIGHER | | THAN 34" ABOVE THE FINISH FLOOR. | | 11-4.24.3 KNEE CLEARANCE THAT IS AT | | LEAST 27" HIGH 30" WIDE, AND 19" DEEP | | SHALL BE PROVIDED UNDERNEATH SINKS. | | 11-4.24.5 CLEAR FLOOR SPACE. | | A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES | | (760 MM BY 1219 MM) COMPLYING WITH | | SECTION 11-4.2.4 SHALL BE PROVIDED IN FRONT OF A SINK | | TO ALLOW FORWARD APPROACH. THE CLEAR | | FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL | | EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE | | SINK. | | | | 5) 2ND REQUEST, THE WORK TO BE INCLUDED IN THIS PERMIT | | , ADDITIONAL JOIST 4TH FLOOR WILL REQUIRE A THRESHOLD | | INSPECTOR ONSITE DURING THIS PORTION OF WORK. | | WPB AMENDMENT 105.13.6. W.P.B. | | CONSTRUCTION SERVICES DEPARTMENT | | REQUEST FOR THRESHOLD BUILDINGS A | | SPECIAL INSPECTOR AS REQUIRED BY S. | | 553.79(5) FLORIDA STATUTES TO THE MIN- | | IMUM INSPECTIONS REQUIRED BY THIS CODE. | | CONTACT HAROLD PISKURA MANAGER OF THE | | SPECIAL INSPECTOR PROGRAM AT (561) | | 805-6711 FOR FURTHER INFORMATION BEFORE | | THE PERMIT MAY BE ISSUED. | | | | NOTE: 3 SETS OF THE THRESHOLD INSPECTION PLAN WILL BE | | RQUIRED AS WELL ASSETS OF PLANS, "THRESHOLD | | BUILDING". | | | | BUILDING PLAN REVIEW | | JIM WITMER C. B. O. | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | . |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2007-01-16 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-01-16 |
Time |
14:01 |
Rev Time |
2.22 |
Received By |
jwitmer |
Date |
2007-01-16 |
Time |
14:01 |
Sent To |
|
|
Notes |
2007-01-16 14:07:54 | BUILDING PLAN REVIEW | | PERMIT: 06120319 | | ADD: 222LAKEVIEW4TH FLOOR | | CONT: PASS INTERNATIONAL | | TEL: (954)421-9000X113 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | * WEST PALM BEACH AMENDMENTS | | | | 1STREVIEW | | ACTION: DENIED | | | | 1)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | BER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | 2 ) FL S S 713.13 | | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF | | THE COURT. | | NOTE: 713.13(2) | | IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS | | NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE | | RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: | | 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT | | THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 3) SHEET A0.00 | | | | 3A)ARCHITECTURAL SHEETS ASD, AKERMAN SENTERFITTARE | | MISSING THE CERTIFICATE OF AUTHORIZATION. 481.219 F.S. | | CERTIFICATE OF | | AUTHORIZATION.THE TITLE BLOCK FOR ANY | | SHEET BEARING THE NAME OF AN ARCHITECT | | PRACTICING UNDER A FICTITIOUS NAME, A | | CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL | | SERVICES, SHALL INCLUDE | | THE CERTIFICATE OF AUTHORIZATION | | NUMBER.ADD THE NUMBER TO EACH SHEET. | | THIS MAY BE ADDED BY HAND. | | | | | | 3B) ARCHITECT STEVEN D. YANCEY IS MISSING PRINTED | | NAME: | | ) 61G1-16.004FL. ADMIN. CODE.PLANS | | PREPARED BY A REGISTERED ARCHITECT SHALL | | INCLUDE A TITLE BLOCK WHICH MUST: | | - STATE THE FIRM NAME, ADDRESS AND | | TELEPHONE NUMBER | | - STATE THE FIRM LICENSE NUMBER | | - STATE PROJECT NAME OR IDENTIFICATION | | - STATE DATE PREPARED | | - INCLUDE AN ORIGINAL SIGNATURE AND | | DATED SEAL | | X - INCLUDE THE PRINTED NAME OF THE | | ARCHITECT SEALING THE PLANS | | | | 3C) APPLICABLE BUILDING CODE: PLANS INDICATE PBC | | AMENDMENTS PLEASE DELETE, | | INTHE 2004 FBC THE ONLY LOCAL AMENDMENTS ARE CHAPTER | | (1) ADMINISTRATION- CITY OF WEST PALM BEACH . | | | | 3D) BUILDING FEATURES, TYPE OF CONSTRUCTION, TYPE I | | UNPROTECTED, SPRINKLERED. PLEASE SEE TABLE 503 TYPE I | | BUILDING COLUMN A & B FOR ALLOWABLE STORIES. | | | | 4) A7.041 DETAIL# 1 PANTRY, THE ELEVATIONS FAIL TO SHOW | | COMPLIANCE FOR A FORWARD APPROACH. SINKS: | | 11-4.24.2 SINKS, HEIGHT. SINKS SHALL | | BE MOUNTED WITH THE COUNTER NO HIGHER | | THAN 34" ABOVE THE FINISH FLOOR. | | 11-4.24.3 KNEE CLEARANCE THAT IS AT | | LEAST 27" HIGH 30" WIDE, AND 19" DEEP | | SHALL BE PROVIDED UNDERNEATH SINKS. | | 11-4.24.5 CLEAR FLOOR SPACE. | | A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES | | (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4 | | SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD | | APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN | | ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19 | | INCHES (485 MM) UNDERNEATH THE SINK | | | | 5) SHEET A9.042 INDICATES THEUSE OF A DOOR TYPE "D" | | WHICH HAS A VIEW PANEL , PLEASE NOTE REQUIREMENTS FOR | | SAFETY GLAZING. | | 2406.3 HAZARDOUS LOCATIONS. | | THE FOLLOWING SHALL BE CONSIDERED SPECIFIC HAZARDOUS | | LOCATIONS REQUIRING SAFETY GLAZING MATERIALS: | | 1.GLAZING IN SWINGING DOORS . | | | | 6)SHEET S-2; | | 6A)PLANS ARE SEALED BUT NOT SIGNED. | | PLANS, SPECIFICATIONS, REPORTS OR | | OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND | | BEING FILED FOR PUBLIC | | RECORD SHALL HAVE THE SIGNATURE AND | | SEAL OF THE DESIGN PROFESSIONAL AFFIXED | | TO THE DOCUMENT. | | FL STATE STAT: 61G15-23.002 ENGINEERS | | FL ATATE STAT: 61G16.003 ARCHITECTS | | | | 6B)CODES AND STANDARDS: INDICATE DESIGNED TO THE 2001 | | FBC, PLEASE CORRECT. | | | | 7) THE WORK TO BE INCLUDED IN THIS PERMIT , ADDITIONAL | | JOIST 4TH FLOOR WILL REQUIRE A THRESHOLD INSPECTOR | | ONSITE DURING THIS PORTION OF WORK. | | WPB AMENDMENT 105.13.6. W.P.B. | | CONSTRUCTION SERVICES DEPARTMENT | | REQUEST FOR THRESHOLD BUILDINGS A | | SPECIAL INSPECTOR AS REQUIRED BY S. | | 553.79(5) FLORIDA STATUTES TO THE MIN- | | IMUM INSPECTIONS REQUIRED BY THIS CODE. | | CONTACT HAROLD PISKURA MANAGER OF THE | | SPECIAL INSPECTOR PROGRAM AT (561) | | 805-6711 FOR FURTHER INFORMATION BEFORE | | THE PERMIT MAY BE ISSUED. | | | | FL S. S. 553.71(7) " THRESHOLD | | BUILDING" MEANING ANY BUILDING WHICH IS | | GREATER THAN (3) STORIES OR 50 FT IN | | HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN | | CY CLASSIFICATION AS DEINED IN THE | | FLORIDA BUILDING CODE WHICH EXCEEDS | | 5,000 SQ FT IN AREA AND AN OCCUPANT | | CONTENT OF GREATER THAN 500 PERSONS. | | 105.13.1 THE ENFORCING AGENCY SHALL | | REQUIRE A SPECIAL INSPECTOR TO PERFORM | | STRUCTURAL INSPECTIONS ON A THRESHOLD | | BUILDING PURSUANT TO A STRUCTURAL | | INSPECTION PLAN PREPARED BY THE | | ENGINEER OF RECORD. THE STRUCTURAL | | INSPECTION PLAN MUST BE SUBMITTED TO THE | | ENFORCING AGENCY PRIOR TO THE ISSUANCE | | OF A BUILDING PERMIT FOR THE | | CONSTRUCTION OF A THRESHOLD BUILDING. | | THE PURPOSE OF THE STRUCTURL INSPECTION | | PLAN IS TO PROVIDE SPECIFIC INSPECTION | | PROCEDURES AND SCHEDULES SO THAT THE | | BUILDING CAN BE ADEQUATELY INSPECTED FORCOMPLIANCE | | WITH THE PERMITTED DOCUMENTS. | | | | BUILDING PLAN REVIEW | | JIM WITMER C. B. O. | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
8 |
Status |
P |
Date |
2008-02-04 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-02-04 |
Time |
11:13 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-02-04 |
Time |
11:13 |
Sent To |
PC |
|
Notes |
2008-02-04 11:13:49 | REV #7 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
7 |
Status |
P |
Date |
2007-10-19 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-10-19 |
Time |
13:21 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-10-19 |
Time |
09:15 |
Sent To |
|
|
Notes |
2007-10-19 13:21:35 | REVISION, DECREASED SCOPE OF WORK. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
6 |
Status |
P |
Date |
2007-08-31 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-08-31 |
Time |
11:54 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-08-31 |
Time |
11:54 |
Sent To |
B |
|
Notes |
2007-08-31 11:55:59 | ** NEW SHEETS INSERTED INTO SET, STAMPED AND SENT OT | | BUILDING AS THERE ARE TWO NEW SHEETS FROM THE | | ARCHITECT. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
F |
Date |
2007-08-29 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-08-29 |
Time |
07:40 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-08-29 |
Time |
07:40 |
Sent To |
B |
|
Notes |
2007-08-29 10:51:25 | 2007-08-29 10:51:25 | | SPOKE TO GORDAN SCOTT AND MR. LON CARTER (ENGINEER OF | | RECORD). | | NEW PLANS ARE BEING BROUGHT UP FOR INSERTTING INTO THE | | SETS. | | WALLS WILL NEED TO BE MOVED WHICH WILL REQUIRE NEW *A* | | SHEETS. | | | | ON HOLD. | 2007-08-29 07:41:42 | 2007-08-29 07:41:42 | | ** DENIED 5TH REVIEW ** | | | | 1) NOTE: PLEASE SEE PREVIOUS NOTE #2 WHICH REQUESTED TO | | MEET SEVERAL SECTIONS OF THE CODE FOR CLEARANCES OF THE | | TRANSFORMER(S) AND DISCONNECTS. BY SIMPLY PLACING A | | NOTE ON THE PLANS WHICH STATES *DISCONNECTS AND | | TRANSFORMER(S) WILL BE RELOCATED* DOES NOT SHOW CODE | | COMPLIANCE AS REQUIRED ON PLANS. | | PLEASE SUBMIT PLANS SHOWING NEW LOCATION(S) MEETING THE | | *MINIMUM* CODE. THIS OFFICE HAS ONLY REQUESTED THE | | MINIMUM CODE FROM THE FIRST REVIEW FOR THIESE SAME | | ITEMS. FBC 106.1.1, 106.1.2, 106.3.5.1.2. | | FLORIDA ADMINISTRATIVE CODE 61G15-33.003 (2)(D) PLEASE | | KNOW THAT ONCE THE LOCATION(S) MEETS 110.26, 240.24, | | 240.21, 450.9, 450.13 ETC THE PERMIT CAN BE ISSUED. | | | | ** A CALL WILL BE PLACED TO THE ENGINEER'S OFFICE ONE | | UNDER NORMAL BUSINESS HOURS TO TRY AND RESOLVE THE | | ISSUE. | | | | ** PLANS ARE BEING ROUTED TO THE BUILDING REVIEWER AS A | | NEW ARCHITECTURAL SHEET WAS INSERTED INTO PLANS. | | | | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
F |
Date |
2007-07-31 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-07-31 |
Time |
18:36 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-07-31 |
Time |
17:53 |
Sent To |
|
|
Notes |
2007-07-31 18:37:51 | *** UNSAT 4TH REVIEW *** | | | | 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED | | DO NOT CORRELATE WITH THE PLANS FOR THE METHOD OF | | CONTROL. PLEASE SEE THESE ARE STILL BEING ENTERED AS | | *MANUAL ON/OFF* WHEN THEY ARE AUTOMATED/OCCUPANCY TYPE | | DEVICES ON PLANS. | | PLEASE COORDINATE. 13-415.1.AB.1.1, 13-415.1.A, | | 13-415.2. | | PLEASE CLARIFY METHOD AND HOW THIS CAN BE USED FOR | | SCOPE OF WORK AS SHOWN. PLEASE CLARIFY LIGHTING POWER | | DENSITIES AS REQUESTED ON THE PREVIOUS THREE REVIEWS. | | THE RESPONSE LETTER DOES NOT ADDRESS OR MENTION THESE | | ITEMS??? | | PLEASE SEE THESE ARE TO BE SIGNED BY THE ENGINEER OF | | RECORD WITH SIGNATURE AS ON FILE AND RECOGNIZED BY THIS | | OFFICE. PLEASE SEE THESE ARE NOT THE SAME AS THE PLANS | | OR PREVIOUS SUBMITTED ENERGY CALCULATIONS. | | 13-103.1.1.1, FS471.025 | | | | 2) NOTE: PLEASE SEE THE PLANS HAVE NOT CHANGED FOR THE | | LOCATIONS OF DISCONNECTS. PLEASE SEE THE TRANSFORMER | | T1A WHICH IS BEING SHOWN IN SOME KIND OF CLOSET. THIS | | SAME CLOSET CONTAINS TWO SMALL RECTANGLES WHICH ARE NOT | | LABELED AS DISCONNECTS. AS THESE COULD NOT BE LOCATED | | AT ANY OTHER LOCATION ON PLANS, IT IS BEING ASSUMED | | THESE ARE THE SAME DISCONNECTS IN THIS SAME *CLOSET*. | | PLEASE SEE THESE DO NOT MEET 110.26, 240.24, 408.7 ETC | | AS PREVIOUSLY STATED IN PREVIOUS REVIEWS. | | ** ALL SERVICE EQUIPMENT NEW OR EXISTING WILL BE | | REQUIRED TO MEET THE MINIMUM REQUIRED BY CODE** | | | | **DOCUMENTATION HAS BEEN SENT TO THE CHIEF ELECTRICAL | | INSPECTOR FOR FIELD INSPECTION AND CORRECTION NOTICED | | TO BE ISSUED TO OWNER/JOBSITE AS/IF NEEDED. | | | | 3) NOTE: PLANS AND SUPPORTING DOCUMENTS ARE BEING | | RETAINED BY THIS OFFICE DUE TO REPEAT CODE COMPLIANT | | COMMENTS PER FS 553.80(2)(B). AT THIS TIME A FEE OF | | $9,732.00 MAY BE ASSESSED DUE TO THE REPEAT COMMENTS | | FOR CODE COMPLIANCE. THE CODE COMMENTS WILL GO UNDER | | PIER REVIEW. | | THE FEE IS REQUIRED UNDER FLORIDA STATUTESAND WILL BE | | DUE BEFORE NEXT RESUB OF PLANS MAY BE DONE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2007-06-08 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-06-08 |
Time |
09:56 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-06-08 |
Time |
08:28 |
Sent To |
|
|
Notes |
2007-06-08 09:56:28 | *** UNSAT 3RD *** | | | | | | ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEWS STILL | | ARE IN NEED OF ADDRESSING ALONE WITH SOME NEW COMMENTS | | DUE TO CHANGES MADE ON PLANS AND DOCUMENTS SUBMITTED. | | | | 1) NOTE: PLEASE SEE THE PERMIT APPLICATION STILL | | INDICATES SCOPE OF WORK WHICH IS NOT THE SAME AS PLANS. | | THE PERMIT APPLICATION STATES *DESCRIBE PROJECT IN | | DETAIL* IF THE PERMIT APPLICATION STATES THE ENTIRE 4TH | | FLOOR IS BEING BUILD OUT FOR TENANT, THEN PLANS WILL BE | | REQUIRED TO BE REVISED TO SHOW CODE COMPLIANCE FOR THE | | ENTIRE FLOOR. | | PLEASE COORDINATE WITH ONE OR THE OTHER. | | PLEASE SEE THE PERMIT APPLICATION PACKAGE AS SUBMITTED | | DOES CONTAIN PAPERWORK AND DOCUMENTATION WHICH IS FROM | | THE THIRD FLOOR BUILD OUT WORK AND ANOTHER PERMIT. | | PLEASE COORDINATE ALL DOCUMENTS, PLANS, AND PAPERWORK. | | FBC 106.3.5.1.2 | | | | 2) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS NOW | | SUBMITTED DO NOT COORDINATE WITH THE SUBMITTED PLANS. | | PLEASE SEE THE NUMBER OF LIGHTING FIXTURES, THE | | WATTAGE, TYPES AND CONTROLS FOR SUCH FIXTURES DOES NOT | | MATCH WITH PLANS. | | PLEASE ADJUST. | | PLEASE SEE LEGEND AS THIS DOES NOT INDICATE ANY | | AUTOMATED TYPE DEVICE. THE TIMES ARE NOT STATED. THE | | PLANS DO NOT INDICATE DEVICES FOR NEW. | | PLEASE SEE13-101, 13-415.1.ABC.1.1, .1.2, | | 13-415.1.AB.1.1, 13-415.2 HOW IS METHOD A ABLE TO BE | | SUED FOR THE SQ FT AS SHOWN AND FOR SCOPE OF WORK, | | PLEASE | | PLEASE SEE THE ENERGY CALCULATIONS WILL REQUIRE TO BE | | SIGNED BY *OWNER AGENT* AS INDICATED ON SHEET | | 2. | | | | 3) NOTE: PLEASE SEE SHEET E0.1 WHICH INDICATES A 2005 | | FBC? | | PLEASE SEE NO YEARS INDICATE FOR ELECTRICAL CODE | | NFPA-70 OR LIFE SAFETY CODE NFPA-101. THESE SHOULD BE: | | 2004 FBC W/ 2006 REVISIONS. | | 2005 NFPA-70 (NEC). | | 2003 NFPA-101 | | | | 4) NOTE: PLEASE SEE THE NEW DISCONNECTS ADDED FOR THE | | TAPPED CONDUCTORS TO PANEL L AND L1 DO NOT APPEAR ON | | PLANS AND LOCATIONS OF THESE CAN NOT BE VERIFIED FOR | | CODE COMPLIANCE OF 240.21, 110.26, 240.24 ETC | | PLEASE SHOW. | | FBC106.1.21 | | | | 5) NOTE: PLEASE SEE NO CHANGES OR NOTES HAVE BEEN ADDED | | FOR EXISTING AS SHOWN ELECTRICAL EQUIPMENT WHICH DOES | | NOT MEET 110.26,408.7, 240.24, 450.9,450.11,450.13 ETC | | ** PERMIT WILL NOT BE ISSUED. | | THE LOCATION OF THESE PANELS AND TRANSFORMER(S) WILL BE | | REQUIRED TO MEET CODE. IF PLANS AND PERMIT FOR SCOPE OF | | WORK DOES NOT COMMENCE WITHIN 60 DAYS FROM THIS REVIEW | | DATE FOR CORRECTION, A NOTICE WILL BE ISSUED ON-SITE | | FOR VIOLATIONS AND SCOPE OF WORK WILL BE REQUIRED ON A | | SEPARATE PERMIT WHETHER OR NOT BUILD OUT IS DONE TO | | ALLEVIATE ANY FURTHER ACTION FOR DISCONNECT OF SERVICE | | UTILITIES. | | ** AN ELECTRICAL CONTRACTOR MAY APPLY FOR THIS WORK | | SEPARATELY TO BEGIN. PLEASE CONTACT THIS OFFICE IF THIS | | OPTION IS TAKEN. | | AS THIS IS NOT ONLY A LIFE SAFETY HAZARD BUT AS WELL AS | | A FIRE HAZARD FOR LIFE AND PROPERTY, NO EXCEPTIONS TO | | ANY EXISTING NON-CODE COMPLIANCE WILL BE GRANTED. | | THIS IS FOR ANY OF THE TRANSFORMER(S), PANEL(S), AND | | DISCONNECT(S) LOCATIONS. | | | | ** PLEASE KNOW AT THIS TIME AS SOME OF THE INSTALLATION | | IS NOT CLEAR, THERE MAY BE COMMENTS IF THE INSTALLATION | | CHANGES AND/OR PERMIT APPLICATION CHANGES. | | | | * ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2007-03-11 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-03-11 |
Time |
10:08 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-03-10 |
Time |
18:52 |
Sent To |
|
|
Notes |
2007-03-11 10:10:08 | ** UNSAT 2ND REVIEW ** | | | | | | | | 222 LAKEVIEW | | 4THFLOOR BUILD-OUT/REMODEL\ | | | | ** PLEASE SEE SOME COMMENTS ARE THE SAME AND SOME ARE | | NEW DUE TO CHANGES IN PLANS. | | | | | | 1) NOTE: PLEASE SEE MISSING COMPLETE INFORMATION FOR A | | TITLE BLOCK FOR THE ARCHITECT OF RECORD AND FIRM. | | PLEASE SEE MISSING CERTIFICATE OF AUTHORIZATION NUMBER | | ALSO KNOW AS FIRM LICENSE NUMBER. | | PLEASE SEE MISSING THE PRINTED NAME AND LICENSE NUMBER | | FOR ARCHITECT. | | FLORIDA ADMINISTRATIVE CODE 61G1-16.004, FLORIDA | | STATUTES 481.219 | | **THIS IS NOT A COMMENT RELATED TO KAMM CONSULTING, | | HOWEVER TITLE BLOCKS ARE REQUIRED FOR ALL SHEETS PER | | ABOVE AND WHETHER OR NOT COMMENT IS MADE BY ANY OTHER | | TRADE. | | | | 2) NOTE: PERMIT APPLICATION HAS NOT BEEN ADJUSTED. | | PLEASE CLARIFY PERMIT APPLICATION HAS APPLIED FOR NEW | | TENANT BUILD OUT, HOWEVER PLANS DO NOT CORRELATE WITH | | THIS. | | | | 3) NOTE:PLEASE KNOW ANY NEW ROOM LIGHTING AND | | CONTROLS SHALL COMPLY WITH THIS SECTION. 13-415. | | PLEASE KNOW THE ENTIRE FLOOR DOES NOT HAVE BE BROUGHT | | UP TO CURRENT CODES, HOWEVER THE NEW ROOMS/LIGHTS AND | | CONTROLS WILL BE REQUIRED. THIS CAN BE DONE BY SINGLE | | DEVICES IN THESE ROOMS/AREAS. | | PLEASE ALSO KNOW THAT THE LIGHTING POWER DENSITIES FOR | | EACH OF THE NEW ROOMS SHALL COMPLY WITH THE MAXIMUM | | LIGHTING AS PERMITTED IN THE TABLES. PLEASE SEE MISSING | | LIGHTING CONTROL FOR ALL PER 13-415.1.ABC.1.1, .1.2, | | AND .1.3.NEW AREAS AND ROOMS. PLEASE SEE OVER RIDES | | DEVICES FOR THESE AREAS ALSO DEPENDING ON IF"SYSTEM" | | OR "DEVICES" ARECHOSEN. | | PLEASE SEE THE SYMBOL LEGEND FOR ALL DEVICES SHALL | | INDICATE ALL MAXIMUM TIMES FOR DEVICES. (30MINS FOR | | OCCUPANCY SENSOR TYPE AND 4HRS MAX FOR TIMER TYPE) | | PLEASE SEE ROOMS AND AREAS WHICH DO NOT INDICATE ANY OF | | THE DEVICES FOR AUTOMATED CONTROL. | | PLEASE SEE ALL AREAS CONTAIN FLOOR TO CEILING HEIGHT | | PARTITIONS SHALL CONTAIN DEVICE(S) FOR CONTROL. (PLEASE | | SEE STORAGE) | | PLEASE SEE 13-415.2, 13-415.2.ABC.1 FOR MISSING MAXIMUM | | PERMITTED LIGHTING POWER DENSITIES. | | | | 4) NOTE: PLEASE PLACE A NOTE ON PLANS/SHEET E2.1 TO | | CLOSET AREA TO BE BROUGHT UP TO CODE FOR MINIMUM | | CLEARANCES AS STATED IN THE SECTIONS OF THE CODE NOTED | | BELOW. PLEASE KNOW THIS WILL BE A CONDITION OF ISSUANCE | | AND PLEASE KNOW NO ROUGH ELECTRICAL INSPECTIONS WILL BE | | DONE UNTIL REVISIONS OR SEPARATE PERMIT IS SUBMITTED | | FOR CHANGES.ONCE NOTE IS ON PLANS, A HOLD WILL BE | | PLACED ON INSPECTIONS. | | PLEASE SEE THE PANELSHV, LV1 AND LV2 WHICH DO NOT | | SEEM TO MEET 110.26 FOR PANEL HV AND TRANSFORMER. | | PLEASE VERIFY THIS AND KNOW THAT IF THIS WALL IS | | ACTUALLY INSTALLED IN FRONT OF THE PANEL/EQUIPMENT AS | | SHOWN, THIS WILL BE REQUIRED TO MEET 110.26/450.9, | | 450.13 ETC | | | | 5) NOTE: PLEASE SEE PLANS HAVE BEEN REVISED TO SHOW THE | | TRANSFORMER "T1A" DIRECTLY IN A CLOSET WHEN PREVIOUSLY | | SHOWN IN THE MIDDLE OF THE CONFERENCE ROOM. PLEASE SEE | | PANELS *L* AND L1* DO NOT SEEM TO MEET THE TAP | | CONDUCTOR RULE FOR DISTANCE IN THE LENGTH OF | | CONDUCTORS. PLEASE SEE 240.21C. | | PLEASE ALSO SEE MINIMUM CLEARANCES REQUIRED FOR | | TRANSFORMER. | | THIS IS A FIRE/LIFE SAFETY HAZARD. | | PLEASE ALSO VERIFY LOCATION FOR TAPS ON A TRANSFORMER | | PER 240.21C. PLEASE ADJUST PLANS AND VERIFY THE ACTUAL | | INSTALLATION. | | | | | | 13) NOTE:** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | OLD/VOIDEDSHEETS AND ONLY INSERT NEW REVISED SHEETS | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.DO NOT | | LEAVE ANY OLD/VOIDED SHEETS IN SETS.PLEASE KNOW ONLY | | ONE SET OF THE OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | DELAYS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | 2007-03-10 18:53:06 | 2007-03-10 18:53:06 | | IN ELEC FOR REVIEW |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2007-01-07 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-01-07 |
Time |
19:44 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-01-07 |
Time |
19:09 |
Sent To |
|
|
Notes |
2007-01-07 19:44:05 | ** UNSAT ** | | | | | | 222 LAKEVIEW | | 4THFLOOR BUILD-OUT/REMODEL | | | | | | 1) NOTE: PLEASE SEE MISSING ADDRESS INFORMATION FROM | | TITLE BLOCKS. PLEASE SEE THE SUITE/UNIT NUMBER IS BEING | | SHOWN, HOWEVER NOT THE ADDRESS/ LOCATION. | | FAC 61G1-16.004, FAC61G15-23.002 | | | | 2) NOTE: PLEASE SEE MISSING COMPLETE INFORMATION FOR A | | TITLE BLOCK FOR THE ARCHITECT OF RECORD AND FIRM. | | PLEASE SEE MISSING CERTIFICATE OF AUTHORIZATION NUMBER | | ALSO KNOW AS FIRM LICENSE NUMBER. | | PLEASE SEE MISSING THE PRINTED NAME AND LICENSE NUMBER | | FOR ARCHITECT. | | FLORIDA ADMINISTRATIVE CODE 61G1-16.004, FLORIDA | | STATUTES 481.219 | | **THIS IS NOT A COMMENT RELATED TO KAMM CONSULTING, | | HOWEVER TITLE BLOCKS ARE REQUIRED FOR ALL SHEETS PER | | ABOVE AND WHETHER OR NOT COMMENT IS MADE BY ANY OTHER | | TRADE. | | | | 3) NOTE: PLEASE LIST THE FOLLOWING MINIMUM CODES | | RELEVANT TO THIS PROJECT AND DESIGN. | | 2005 NFPA-72, 2005 NFPA-70, 2003 NFPA-101 | | PLEASE ADJUST THE ARCHITECTURAL SHEETS AS WELL AS THE | | ELECTRICAL SHEETS. | | PLEASE SEE AS THE PERMIT WAS APPLIED FOR AFTER DECEMBER | | 8TH, 2006 THE 2006 REVISIONS TO THE 2004 FBC AND THE | | 2005 NATIONAL ELECTRICAL CODE WAS ADOPTED BY THE STATE | | OF FLORIDA. | | PLEASE ADJUST CODES ON PLANS. | | | | 4) NOTE: PLEASE CLARIFY PERMIT APPLICATION HAS APPLIED | | FOR NEW TENANT BUILD OUT, HOWEVER PLANS DO NOT | | CORRELATE WITH THIS. PLEASE CLARIFY AS THE NEXTTWO | | COMMENTS MAY APPLY FOR FLOOR OR FOR NEW ROOMS AS | | SHOWN. | | | | 5) NOTE: PLEASE SEE MISSING LIGHTING CONTROL FOR ALL | | PER 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE SEE | | MISSING CONTROLS FOR COMMON AREAS. PLEASE SEE OVER | | RIDES DEVICES FOR THESE AREAS ALSO DEPENDING ON | | "SYSTEM" OR DEVICES CHOSEN. PLEASE SEE THE SYMBOL | | LEGEND FOR ALL DEVICES SHALL INDICATE ALL MAXIMUM TIMES | | FOR DEVICES. (30MINS FOR OCCUPANCY SENSOR TYPE AND 4HRS | | MAX FOR TIMER TYPE) | | PLEASE SEE ROOMS AND AREAS WHICH DO NOT INDICATE ANY OF | | THE DEVICES FOR AUTOMATED CONTROL. | | PLEASE PROVIDE SCHEDULING FOR ANY PROPOSED SYSTEM. | | PLEASE SEE ALL AREAS CONTAIN FLOOR TO CEILING HEIGHT | | PARTITIONS SHALL CONTAIN DEVICE(S) FOR CONTROL. (PLEASE | | SEE STORAGE) | | PLEASE SEE 13-415.2, 13-415.2.ABC.1 FOR MISSING MAXIMUM | | PERMITTED LIGHTING POWER DENSITIES. | | PLEASE ALSO SEE 13-415.AB.1 FOR MISSING ENERGY | | CALCULATIONS REQUIRED FOR NEW TENANT BUILD-OUT. | | ** PLEASE SUBMIT THE ABOVE. AS THERE ARE ITEMS NOT YET | | SUBMITTED, A REVIEW OF SAID SYSTEM/DEVICES ETC CAN NOT | | BE FULLY ACCOMPLISHED AT THIS TIME. | | | | 6) NOTE: PLEASE PROVIDE A DETAIL ON ALL EMERGENCY | | AND/OR EXIT LIGHTING WIRED AHEAD OF ANY OVER RIDE | | CONTROL DEVICES PER 700.12E. PLEASE SEE A | | CLOUDED/HIGHLIGHTED NOTE MAY ALSO BE DONE. THIS AHJ HAS | | BEEN HAVING MANY INSTANCES WHERE EMERGENCY AND EXIT | | LIGHTS ARE BEING WIRED ON THE LOAD SIDE OF OC/ TIMER | | DEVICES. | | | | 6) NOTE: PLEASE INDICATE ALL CONTINUOUS LOADS AT 125%. | | 215.3, 230.42 ETC. | | FBC 106.1.2 ADMIN SECTION. | | | | 7) NOTE: PLEASE KNOW EITHER AT THIS POINT OR BEFORE | | FINAL, A REVISION FOR ALL CIRCUITS TO SPECIFIC ROOMS | | AND AREAS WILL BE REQUIRED. (LIGHTING CIRCUITS ETC.) | | 408.4. | | | | | | 8) NOTE: PLEASE SEE THE PANELSHV, LV1 AND LV2 WHICH | | DO NOT SEEM TO MEET 110.26 FOR PANEL HV AND | | TRANSFORMER. PLEASE VERIFY THIS AND KNOW THAT IF THIS | | WALL IS ACTUALLY INSTALLED IN FRONT OF THE | | PANEL/EQUIPMENT AS SHOWN, THIS WILL BE REQUIRED TO MEET | | 110.26/450.9, 450.13 ETC | | | | 9) NOTE: PLEASE SEE THE RISER SHEET CONTAINS A BOX WITH | | NOTES FROM 9/25/01? PLEASE UPDATE NOTE. | | PLEASE SEE THIS NOTE #3 IN THIS BOX SHOW A NOTATION FOR | | A NEW BREAKER TO COME FROM THE EXISTING "H" PANEL TO | | FEED PANEL "H1" WHICH ON RISER IS SHOWN AS NEW, YET | | THIS PANEL SCHEDULE FOR "H1" INDICATES THIS PANEL AS | | A120/208V PANEL AND IS BEING FED FROM H WHICH IS | | 277/480V. | | PLEASE SEE RISER AND PLANS DO NOT SHOW ANY | | TRANSFORMER. | | PLEASE SEE 450.3, 450.9, 450.13B, 240.21C ETC PLEASE | | CORRELATE PLANS AND ADJUST. | | | | 10) NOTE: PLEASE SEE PLANS APPEAR TO SHOW TRANSFORMER | | "T1A" DIRECTLY IN THE MIDDLE OF THE CONFERENCE ROOM. | | PLEASE SEE 450.13B AS THIS UNIT IS A 75 KVA TRANSFORMER | | AND IF ABOVE CEILING IT WILL BE REQUIRED TO BE | | RELOCATED BELOW CEILING. THIS IS A FIRE/LIFE SAFETY | | HAZARD AND THE CODE EVEN WHEN THE BUILDING WAS BUILT | | DID NOT ALLOW THIS INSTALLATION AS SHOWN. PLEASE ALSO | | VERIFY LOCATION FOR TAPS ON A TRANSFORMER PER 240.21C. | | PLEASE ADJUST PLANS AND VERIFY THE ACTUAL | | INSTALLATION. | | | | | | 11) NOTE: PLEASE SEE THE LOW VOLTAGE AUDIO/VISUAL PLANS | | SUBMITTED MAY ONLY BE PART OF THE PERMITTED RECORD SET | | OF PLANS IF BEING DONE BY THE ELECTRICAL SUB | | CONTRACTOR. AS THESE SHEETS SEEM TO INDICATE A SEPARATE | | LV SOUND/AUDIO VISUAL CONTRACTOR, THESE SHALL BE | | SUBMITTED UNDER A SEPARATE PERMIT APPLICATION. PLEASE | | KNOW IN EITHER CASE ALL PLANS ARE REQUIRED TO BE | | SIGNED, DATED PRINTED NAME ETC FOR THE PERSON TAKING | | RESPONSIBILITY OF SUCH PLANS. | | FBC 106.1.2, FS 481/471, FAC 61G15-23.002, FAC | | 61G1-16.004 ETC | | | | 12) NOTE: PLEASE SEE "S" SHEET IN BOTH SETS ARE NOT | | SIGNED AND DATED BY THE ENGINEER OF RECORD. SHEETS DO | | CONTAIN THE RAISED SEAL. | | PLEASE SEE FS 471.025, FAC 61G15-23.002 | | THIS IS ONLY NOTED AND SHOULD ALSO BE IN NOTES FROM THE | | BUILDING REVIEWER. | | | | 13) NOTE:** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | OLD/VOIDEDSHEETS AND ONLY INSERT NEW REVISED SHEETS | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.DO NOT | | LEAVE ANY OLD/VOIDED SHEETS IN SETS.PLEASE KNOW ONLY | | ONE SET OF THE OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | DELAYS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
5 |
Status |
P |
Date |
2007-10-31 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-10-31 |
Time |
10:40 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-10-31 |
Time |
10:08 |
Sent To |
|
|
Notes |
2007-10-31 10:40:05 | *****APPROVED***** | | | | | | REVISED PLAN SHEETS A6.04, FA2.1, AND FS2.1 WERE | | STAMPED, INITIALED, AND DATED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2007-08-15 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-08-15 |
Time |
17:02 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-08-15 |
Time |
16:53 |
Sent To |
|
|
Notes |
2007-08-15 17:00:45 | ****PROVISO***** | | | | | | ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE | | BEEN ADDRESSED;HOWEVER, THE APPROPIATE PLAN SHEETS | | WILL BE FIRE-STAMPED WHEN ALL PLANREVIEWERS HAVE BEEN | | SATISFIED. | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2007-06-29 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-06-29 |
Time |
11:12 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-06-29 |
Time |
11:00 |
Sent To |
|
|
Notes |
2007-06-29 11:05:14 | ****PROVISO***** | | | | | | ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE | | BEEN ADDRESSED;HOWEVER, THE APPROPIATE PLAN SHEETS | | WILL BE FIRE-STAMPED WHEN ALL PLANREVIEWERS HAVE BEEN | | SATISFIED. | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2007-04-02 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-04-02 |
Time |
13:23 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-04-02 |
Time |
12:40 |
Sent To |
|
|
Notes |
2007-04-02 13:23:02 | ****UNSAT***** | | | | | | PLEASE ADDRESS FOLLOWING COMMENT TAKEN FROM PREVIOUS | | FIRE PLAN REVIEW: | | | | | | | | | | 5.ON SHEET FA2.1, FIRE ALARM NOTE #17, DELETE | | SUPERVISORY SIGNAL ONLY - INSERT GENERAL FIRE ALARM | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2007-02-07 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-02-07 |
Time |
19:11 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-02-07 |
Time |
19:11 |
Sent To |
|
|
Notes |
2007-02-07 19:19:41 | *****DENIED***** | | | | | | 1.THE COMPLETE ADDRESS OF WHERE THE SCOPE OF WORK | | WILL BE CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH | | SUBMITTED PLAN SHEET. | | | | 2.ON SHEET A0.00, MAKE THE FOLLOWING CHANGES TO THE | | CODE ANALYSIS SECTION:I.AUTHORITIES CONSTRUCTION | | SERVICES DEPARTMENT - CITY OF WEST PALM BEACH | | 561-805-6700;FIRE MARSHAL - MIKE CARSILLO | | 561-804-4724II. APPLICABLE BUILDING CODES | | ELIMINATE NFPA 2003 CODES W/FLORIDA AMENDMENTS, INSERT | | FLORIDA FIRE PREVENTION CODE 2004 | | | | 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD | | TO GENERAL DEMOLITION NOTES, SHEET AD1.03 | | | | 4.DO THE TENANT ENTRY DOORS (AS REFERRED TO ON SHEET | | A9.032) LEAD TO AN EXIT ACCESS CORRIDOR?IF SO, THESE | | DOORS SHALL BE FIRE RATED AS PER NFPA 80. | | | | 5.ON SHEET FA0.1, FIRE ALARM NOTE #17, DELETE | | SUPERVISORY SIGNAL ONLY - INSERT GENERAL FIRE ALARM | | | | 6.PROVIDE A LAYOUT OF THE FIRE SPRINKLER SYSTEM. WILL | | THEY NEED TO BE ALTERED OR MODIFIED DUE TO THE SCOPE OF | | WORK? | | | | 7.BUILDINGS OR PORTIONS OF BUILDINGS SHALL BE | | PERMITTED TO BE OCCUPIED DURING CONSTRUCTION, REPAIR, | | ALTERATIONS, OR ADDITIONS ONLY WHERE REQUIRED MEANS OF | | EGRESS AND REQUIRED FIRE PROTECTION | | FEATURES ARE IN PLACE AND CONTINUOUSLY MAINTAINED FOR | | THE PORTION OCCUPIED OR WHERE ALTERNATIVE LIFE SAFETY | | MEASURES ACCEPTABLE TO THE AUTHORITY HAVING | | JURISDICTION ARE IN PLACE. | | | | 8.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF | | NEW BUILDING MATERIALS & SUPPLIES SHALL NOT HINDER OR | | INTERFERE WITH ACCESS TO OR EXIT FROM FLOOR AND/OR | | BUILDING (INCLUDING FIRE LANES). | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
7 |
Status |
N |
Date |
2008-02-01 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-02-01 |
Time |
09:26 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-02-01 |
Time |
09:25 |
Sent To |
E |
|
Notes |
2008-02-01 09:26:19 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2007-09-28 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-09-28 |
Time |
16:48 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-09-28 |
Time |
16:48 |
Sent To |
|
|
Notes |
2007-10-18 16:19:55 | TO "COMM" BD#39 | 2007-09-28 16:48:43 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2007-08-28 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-08-28 |
Time |
14:36 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-08-28 |
Time |
14:36 |
Sent To |
E |
|
Notes |
2007-08-28 14:36:56 | TO "DPALMER" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2007-07-18 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-07-18 |
Time |
13:21 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-07-18 |
Time |
13:21 |
Sent To |
|
|
Notes |
2007-07-27 11:59:22 | TO "COMM" BD#34 | 2007-07-18 13:21:44 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2007-05-15 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-05-15 |
Time |
11:22 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-05-15 |
Time |
11:22 |
Sent To |
|
|
Notes |
2007-06-01 15:14:47 | TO "COMM" BD#49 | 2007-05-15 11:22:58 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-03-05 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-03-05 |
Time |
11:55 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-03-05 |
Time |
11:55 |
Sent To |
|
|
Notes |
2007-03-08 11:47:15 | TO "COMM" BD#17 | 2007-03-05 11:55:23 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-02-07 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-02-07 |
Time |
19:11 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2006-12-12 |
Time |
18:58 |
Sent To |
|
|
Notes |
2007-01-07 18:22:10 | 2007-01-07 18:22:10 | | TO COMM BOARD #9 | 2006-12-12 18:58:42 | WAITING FOR "COMM" BD |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
5 |
Status |
P |
Date |
2007-10-25 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-10-25 |
Time |
10:53 |
Rev Time |
0.35 |
Received By |
tgordon |
Date |
2007-10-25 |
Time |
10:53 |
Sent To |
|
|
Notes |
2007-10-25 10:54:32 | REVISION TO MECH. PLANS PEGE M2.1 AND M5.1. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2007-07-30 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-07-30 |
Time |
14:19 |
Rev Time |
0.25 |
Received By |
tgordon |
Date |
2007-07-30 |
Time |
14:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
F |
Date |
2007-06-14 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-06-14 |
Time |
13:52 |
Rev Time |
0.25 |
Received By |
tgordon |
Date |
2007-06-14 |
Time |
13:52 |
Sent To |
|
|
Notes |
2007-06-14 13:54:17 | *** DENIED *** | | 1) MECHANICAL PLANS ARE OK AT THIS TIME, SEE ELECTRICAL | | REVIEW NOTES AND PLEASE CORRECT. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2007-03-14 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-03-14 |
Time |
09:18 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2007-03-14 |
Time |
09:18 |
Sent To |
|
|
Notes |
2007-03-14 09:27:53 | *** DENIED *** | | 1) AS NOTED IN LAST REVIEW 1-8-07.INFORMATION MISSING | | IN TITLE BLOCK FOR ARCHITECTURAL FIRM (ASSOCIATED SPACE | | DESIGN INC.) SEE FAC 61G1-16.004 TITLE BLOCK (2). | | | | *** A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR | | INTERIOR DESIGN DRAWINGS AND SPECIFICATION | | IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A | | MINIMUM, CONTAIN THE FOLLOWING INFORMATION: | | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. | | (2) FIRM LICENSE NUMBER. | | (3) NAME OR IDENTIFICATION OF PROJECT. ("JOB ADDRESS" | | SEE CITY WPB AMEND. 106.1.1). | | (4) DATE PREPARED. | | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. | | (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING | | THE DOCUMENT. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2007-01-08 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-01-08 |
Time |
14:34 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2007-01-08 |
Time |
14:34 |
Sent To |
|
|
Notes |
2007-01-08 14:36:00 | *** DENIED *** | | 1) SEE ELECTRICAL REVIEW NOTE # 2, PLEASE CORRECT. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
6 |
Status |
P |
Date |
2007-11-01 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-11-01 |
Time |
15:58 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-11-01 |
Time |
15:58 |
Sent To |
|
|
Notes |
2007-11-01 15:58:50 | REVISION OK--SHT P2.1 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
5 |
Status |
P |
Date |
2007-08-22 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-08-22 |
Time |
08:33 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-08-22 |
Time |
08:33 |
Sent To |
|
|
Notes |
2007-08-22 08:35:25 | | | | | | | PASSED/PROVISO | | | | WATER HAMMER ARRESTOR SHALL BE LOCATED NEAR THE | | FIXTURE, NOT IN THE CEILING.--BREAK ROOM INDICATES | | A WATER COOLER ON SHT A3.04 AND A DRINKING FOUNTAIN ON | | SHT P2.1. THESE HAVE BEEN ADDED TO THE ONE OUTSIDE THE | | GANG BATHS. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
F |
Date |
2007-08-20 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-08-20 |
Time |
18:06 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-08-20 |
Time |
18:02 |
Sent To |
|
|
Notes |
2007-08-20 18:09:01 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 BUILDING | | FBC-2004 CHAPTER 1 | | FBC-2004 CHAPTER 11 | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | FROM PREVIOUS REVIEW: | | (COMMENT NUMBERS TO REMAIN THE SAME) | | ********FROM PREVIOUS REVIEWS: | | | | 1. OK | | 2. OK | | 3. OK | | 4. OK | | 5. OK | | 6. OK | | A. OK | | B. OK | | C. OK | | D. OK | | E. OK | | | | 7. SHOW THE FIXTURES REQUIRED BY SECTION 1004.1.3 | | (BLDG) & 403.1 MINIMUM FACILITIES. INDICATE ON THE | | FLOOR PLAN THE DRINKING FOUNTAINS. SECTION 106.1.1. | | ****NO RESPONSE. NOT ADDRESSED. | | ******RESPONSE NOTED, BUT TABLE 403.1 REQUIRES 3 | | DRINKING FOUNTAINS, AND ONLY ONE IS INDICATED. PLEASE | | SHOW ALL 3 DRINKING FOUNTAINS REQUIRED. | | *********RESPONSE NOTED, BUT 3 DRINKING FOUNTAINS ARE | | REQUIRED AND ONLY ONE WAS ADDED. AS THERE WAS ONLY ONE | | DRINKING FOUNTAIN INDICATED TO BEGIN WITH, THE ADDED | | ONE ONLY BRINGS THE TOTAL UP TO TWO. PLEASE INDICATE | | THREE DRINKING FOUNTAINS AS REQUIRED. | | | | 8. OK | | | | ********NEW COMMENT******** | | | | 1B. SHT P2.1 THE WATER HAMMER ARRESTOR AT THE DRINKING | | FOUNTAIN SHALL BE LOCATED NEAR THE FIXTURE IN AN | | "EFFECTIVE RANGE" NOT IN THE CEILING AS SHOWN. PDI-WH | | 201 AND MANUF. INSTALLATION INSTRUCTIONS. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2007-06-18 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-06-18 |
Time |
08:22 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-06-16 |
Time |
17:29 |
Sent To |
|
|
Notes |
2007-06-18 08:25:25 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 BUILDING | | FBC-2004 CHAPTER 1 | | FBC-2004 CHAPTER 11 | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | FROM PREVIOUS REVIEW: | | (COMMENT NUMBERS TO REMAIN THE SAME) | | | | 1. OK | | 2. OK | | 3. OK | | 4. OK | | 5. OK | | 6. OK | | A. OK | | B. OK | | C. OK | | D. OK | | E. OK | | | | 7. SHOW THE FIXTURES REQUIRED BY SECTION 1004.1.3 | | (BLDG) & 403.1 MINIMUM FACILITIES. INDICATE ON THE | | FLOOR PLAN THE DRINKING FOUNTAINS. SECTION 106.1.1. | | ****NO RESPONSE. NOT ADDRESSED. | | ******RESPONSE NOTED, BUT TABLE 403.1 REQUIRES 3 | | DRINKING FOUNTAINS, AND ONLY ONE IS INDICATED. PLEASE | | SHOW ALL 3 DRINKING FOUNTAINS REQUIRED. | | | | 8. OK | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2007-03-19 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-03-19 |
Time |
07:57 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-03-19 |
Time |
07:57 |
Sent To |
|
|
Notes |
2007-03-19 08:07:29 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 BUILDING | | FBC-2004 CHAPTER 1 | | FBC-2004 CHAPTER 11 | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | FROM PREVIOUS REVIEW: | | (COMMENT NUMBERS TO REMAIN THE SAME) | | | | 1. OK | | 2. OK | | | | 3. ALL ARCHITECTURAL SHEETS. THE TITLE BLOCK MUST, AT A | | MINIMUM, CONTAIN THE FOLLOWING:THE FIRM LICENSE | | NUMBER & THE PRINTED NAME OF THE PERSON SEALING THE | | DOCUMENT. FAC 61G1-16.004(2)(6) & FS 481.219, | | 481.2055. | | ****NO RESPONSE, THE PRINTED NAME HAS BEEN INDICATED, | | BUT THE CA# AS INDICATED ON THE PLANS IS SHOWN AS | | ANOTHER BUSINESS NAME IN THE STATE DBPR WEBSITE. SEE | | ATTACHED SHEET. | | | | 4. OK | | 5. OK | | | | 6. SHTS A1.04 & A7.041 DETAIL 1. THE BREAK ROOMSINK | | SHALL COMPLY WITH SECTION 11-4.24 AND ALL SUBSECTIONS. | | SHOW THE FOLLOWING: | | A. OK | | B. 11-4.24.4 SINK DEPTH | | C. 11-4.24.5 CLEAR FLOOR SPACE. FORWARD APPROACH | | EXTENDING A MAXIMUM 19" UNDERNEATH THE SINK IS | | REQUIRED. CABINET DOORS ARE NOT APPROVED. | | D. 11-4.24.6 EXPOSED PIPES & SURFACES | | E. 11-4.24.7 FAUCETS | | ****NO RESPONSE, THE SINK DEPTH IS NOT SHOWN. THE | | CABINET DOORS ARE STILL SHOWN ON ELEVATION 1 SHT | | A-7.041. EXPOSED PIPES & SURFACES NOT ADDRESSED. | | INDICATE FAUCET TYPE. (INDICATING ADA COMPLIANT FAUCET | | IS NOT ENOUTH INFORMATION). | | | | 7. SHOW THE FIXTURES REQUIRED BY SECTION 1004.1.3 | | (BLDG) & 403.1 MINIMUM FACILITIES. INDICATE ON THE | | FLOOR PLAN THE DRINKING FOUNTAINS. SECTION 106.1.1. | | ****NO RESPONSE. NOT ADDRESSED. | | | | 8. OK | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2007-01-24 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-01-24 |
Time |
15:05 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-01-24 |
Time |
15:05 |
Sent To |
|
|
Notes |
2007-01-25 08:32:06 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 BUILDING | | FBC-2004 CHAPTER 1 | | FBC-2004 CHAPTER 11 | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | 1. SHT A.000 CODE ANALYSIS #1 INDICATES THE AUTHORITY | | AS PALM BEACH COUNTY. THE AUTHORITY FOR THIS ADDRESS IS | | THE CITY OF WEST PALM BEACH. #2 INDICATES THE FIRE | | MARSHALL AS ROBERT PRUSIECKI. HE HAS RETIRED AND THE | | NEW FIRE MARSHALL IS MIKE CARCILLO.PLEASE UPDATE THE | | INFORMATION ON THE PLANS. SECTION 106.1.1. | | | | 2. SHT A.000 APPLICABLE BUILDING CODES INDICATES PBC | | AMENDMENTS. THIS SHALL BE CHANGED TO WPB AMENDMENTS. | | SECTION 106.1.1. | | | | 3. ALL ARCHITECTURAL SHEETS. THE TITLE BLOCK MUST, AT A | | MINIMUM, CONTAIN THE FOLLOWING:THE FIRM LICENSE | | NUMBER & THE PRINTED NAME OF THE PERSON SEALING THE | | DOCUMENT. FAC 61G1-16.004(2)(6) & FS 481.219, | | 481.2055. | | | | 4. SHT S-2 THE ENGINEER SHALL SIGN/DATE SEALED PLANS. | | FAC 61G15-23.002(2) & FS 471.025. | | | | 5. SHT AD1.04 GENERAL DEMOLITION NOTES 0.1.4 INDICATES | | PLUMBING TO BE REMOVED 1/2" BEHIND THE FINISH FACE OF | | THE SURFACE. IN THE REMOVAL OF ANY PART OF THE DRAINAGE | | SYSTEM, DEAD ENDS ARE PROHIBITED. ALL DEMO'D PIPING | | SHALL BE CAPPED AND INSPECTED PRIOR TO COVERING PER | | SECTION 704.5. PLEASE INDICATE ON THE DEMO PLANS. | | | | 6. SHTS A1.04 & A7.041 DETAIL 1. THE BREAK ROOMSINK | | SHALL COMPLY WITH SECTION 11-4.24 AND ALL SUBSECTIONS. | | SHOW THE FOLLOWING: | | A. 11-4.24.3 KNEE CLEARANCE | | B. 11-4.24.4 SINK DEPTH | | C. 11-4.24.5 CLEAR FLOOR SPACE. FORWARD APPROACH | | EXTENDING A MAXIMUM 19" UNDERNEATH THE SINK IS | | REQUIRED. CABINET DOORS ARE NOT APPROVED. | | D. 11-4.24.6 EXPOSED PIPES & SURFACES | | E. 11-4.24.7 FAUCETS | | | | 7. SHOW THE FIXTURES REQUIRED BY SECTION 1004.1.3 | | (BLDG) & 403.1 MINIMUM FACILITIES. INDICATE ON THE | | FLOOR PLAN THE DRINKING FOUNTAINS. SECTION 106.1.1. | | | | 8. SHT P2.1 DOMESTIC WATER ISOMETRIC. THE WATER HAMMER | | ARRESTORS SHALL BE LOCATED NEAR THE FIXTURES, IN AN | | "EFFECTIVE RANGE", NOT IN THE CEILING AS SHOWN. PDI-WH | | 201 AND MANUF. INSTALLATION INSTRUCTIONS. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|