Plan Review Details - Permit 06120319
Plan Review Stops For Permit 06120319
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2007-03-15 Cont ID  
Sent By lursu Date 2007-03-15 Time 14:17 Rev Time 0.00
Received By lursu Date 2007-03-14 Time 15:51 Sent To  
Notes
2007-03-15 14:18:19PERMIT WAS ASSIGNED TO UNIT 400 AS ON THE SITE PLANS .
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2007-01-09 Cont ID  
Sent By lursu Date 2007-01-09 Time 09:11 Rev Time 0.00
Received By lursu Date 2007-01-09 Time 09:11 Sent To  
Notes
2007-01-09 09:12:04PLEASE EXPLAININ WHICH UNIT NUMBER THE JOB SITE IS
 LOCATED ON THE 4TH FLOOR.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]
2007-01-07 18:21:38NEEDS UNIT/SUITE, ALSO WITH 06120320

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-11-01 Cont ID  
Sent By jwitmer Date 2007-11-01 Time 11:42 Rev Time 3.77
Received By jwitmer Date 2007-11-01 Time 10:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-09-04 Cont ID  
Sent By jwitmer Date 2007-09-04 Time 07:17 Rev Time 0.77
Received By jwitmer Date 2007-09-04 Time 07:01 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-08-27 Cont ID  
Sent By jwitmer Date 2007-08-27 Time 15:07 Rev Time 0.00
Received By jwitmer Date 2007-08-27 Time 15:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-06-27 Cont ID  
Sent By jwitmer Date 2007-06-27 Time 15:18 Rev Time 0.77
Received By jwitmer Date 2007-06-27 Time 15:18 Sent To  
Notes
2007-06-27 15:19:11SEE PERMIT 06120320 FOR 3RD FLOOR PERMIT.
 H PISKURA HAS THRESHOLD INSPECTION PLAN & SPECIAL
 INSPECTOR AGRREMENT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-03-30 Cont ID  
Sent By jwitmer Date 2007-03-30 Time 13:49 Rev Time 2.22
Received By jwitmer Date 2007-03-30 Time 13:49 Sent To  
Notes
2007-03-30 14:24:40BUILDING PLAN REVIEW
 PERMIT: 06120319
 ADD: 222 LAKEVIEW AVE 4TH FLOOR
 CONT: PASS INTERNATIONAL
 TEL: (561)706-7201
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE
 IS NULL & VOID.
 NOTE: 713.13(6)THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3A)2ND REQUEST, THE MEP AND FS SHEETS ARE STILL
 MISSING THE CERTIFICATE OF AUTHORIZATION FOR ASSOCIATED
 SPACE DESIGN.
 481.219 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL
 SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 3 B-C)OK
  
 3D) 2ND REQUEST, BUILDING FEATURES, TYPE OF
 CONSTRUCTION, TYPE I UNPROTECTED, SPRINKLERED. PLEASE
 SEE
 TABLE 503, TYPE I BUILDINGS ARE EITHER AOR B FOR
 ALLOWABLE STORIES. RESPONCE WAS WE ARE NOT ADDING ANY
 STORIES.
 WHILE THIS IS TRUE NO STORIES ARE BEING ADDED THE
 AMOUNT OF FIRE SAFING BUILT INTO THE BUILDING IS
 DETERMINED IF THE BUILDING EXCEEDS A CERTIAN LIMIT IN
 FT. TABLE 503
 WHILW A TYPE IB BUILDING IS LIMITED TO 160' A TYPE IA
 BUILDING IS UNLIMITED IN HEIGTH. TABLE 601 PROVIDES THE
 DIFFERENCE IN FIRE RATINGS BETWEEN A TYPE IA OR A IB.
 PLEASE PROVIDE FOOTAGE IN HEIGTH, SO THE CORRECT FIRE
 SAFING REQUIREMENTS WILL BE MEET IN THE NEW FLOOR DECK
 AREA.
  
 4)2ND REQUEST,A7.041 DETAIL# 1 PANTRY, THE
 ELEVATIONS FAIL TO SHOW COMPLIANCE
 FOR A FORWARD APPROACH. THE DOORS FLOORAND SHELVING
 WOULD NEED TO BE REMOVED
 TO ALLOW FOR THE FORWARD APPROACH USAGE.
 T SINKS:
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES
 (760 MM BY 1219 MM) COMPLYING WITH
 SECTION 11-4.2.4 SHALL BE PROVIDED IN FRONT OF A SINK
 TO ALLOW FORWARD APPROACH. THE CLEAR
 FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE
 SINK.
  
 5) 2ND REQUEST, THE WORK TO BE INCLUDED IN THIS PERMIT
 , ADDITIONAL JOIST 4TH FLOOR WILL REQUIRE A THRESHOLD
 INSPECTOR ONSITE DURING THIS PORTION OF WORK.
 WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 NOTE: 3 SETS OF THE THRESHOLD INSPECTION PLAN WILL BE
 RQUIRED AS WELL ASSETS OF PLANS, "THRESHOLD
 BUILDING".
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
 .

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-16 Cont ID  
Sent By jwitmer Date 2007-01-16 Time 14:01 Rev Time 2.22
Received By jwitmer Date 2007-01-16 Time 14:01 Sent To  
Notes
2007-01-16 14:07:54BUILDING PLAN REVIEW
 PERMIT: 06120319
 ADD: 222LAKEVIEW4TH FLOOR
 CONT: PASS INTERNATIONAL
 TEL: (954)421-9000X113
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
  
 3) SHEET A0.00
  
 3A)ARCHITECTURAL SHEETS ASD, AKERMAN SENTERFITTARE
 MISSING THE CERTIFICATE OF AUTHORIZATION. 481.219 F.S.
 CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL
 SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
  
 3B) ARCHITECT STEVEN D. YANCEY IS MISSING PRINTED
 NAME:
 ) 61G1-16.004FL. ADMIN. CODE.PLANS
 PREPARED BY A REGISTERED ARCHITECT SHALL
 INCLUDE A TITLE BLOCK WHICH MUST:
 - STATE THE FIRM NAME, ADDRESS AND
 TELEPHONE NUMBER
 - STATE THE FIRM LICENSE NUMBER
 - STATE PROJECT NAME OR IDENTIFICATION
 - STATE DATE PREPARED
 - INCLUDE AN ORIGINAL SIGNATURE AND
 DATED SEAL
 X - INCLUDE THE PRINTED NAME OF THE
 ARCHITECT SEALING THE PLANS
  
 3C) APPLICABLE BUILDING CODE: PLANS INDICATE PBC
 AMENDMENTS PLEASE DELETE,
 INTHE 2004 FBC THE ONLY LOCAL AMENDMENTS ARE CHAPTER
 (1) ADMINISTRATION- CITY OF WEST PALM BEACH .
  
 3D) BUILDING FEATURES, TYPE OF CONSTRUCTION, TYPE I
 UNPROTECTED, SPRINKLERED. PLEASE SEE TABLE 503 TYPE I
 BUILDING COLUMN A & B FOR ALLOWABLE STORIES.
  
 4) A7.041 DETAIL# 1 PANTRY, THE ELEVATIONS FAIL TO SHOW
 COMPLIANCE FOR A FORWARD APPROACH. SINKS:
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES
 (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4
 SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD
 APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN
 ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19
 INCHES (485 MM) UNDERNEATH THE SINK
  
 5) SHEET A9.042 INDICATES THEUSE OF A DOOR TYPE "D"
 WHICH HAS A VIEW PANEL , PLEASE NOTE REQUIREMENTS FOR
 SAFETY GLAZING.
 2406.3 HAZARDOUS LOCATIONS.
 THE FOLLOWING SHALL BE CONSIDERED SPECIFIC HAZARDOUS
 LOCATIONS REQUIRING SAFETY GLAZING MATERIALS:
 1.GLAZING IN SWINGING DOORS .
  
 6)SHEET S-2;
 6A)PLANS ARE SEALED BUT NOT SIGNED.
 PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 6B)CODES AND STANDARDS: INDICATE DESIGNED TO THE 2001
 FBC, PLEASE CORRECT.
  
 7) THE WORK TO BE INCLUDED IN THIS PERMIT , ADDITIONAL
 JOIST 4TH FLOOR WILL REQUIRE A THRESHOLD INSPECTOR
 ONSITE DURING THIS PORTION OF WORK.
 WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 STRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE
 ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE
 OF A BUILDING PERMIT FOR THE
 CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURL INSPECTION
 PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE
 BUILDING CAN BE ADEQUATELY INSPECTED FORCOMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2008-02-04 Cont ID  
Sent By dpalmer Date 2008-02-04 Time 11:13 Rev Time 0.00
Received By dpalmer Date 2008-02-04 Time 11:13 Sent To PC
Notes
2008-02-04 11:13:49REV #7

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2007-10-19 Cont ID  
Sent By dpalmer Date 2007-10-19 Time 13:21 Rev Time 0.00
Received By dpalmer Date 2007-10-19 Time 09:15 Sent To  
Notes
2007-10-19 13:21:35REVISION, DECREASED SCOPE OF WORK.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-08-31 Cont ID  
Sent By dpalmer Date 2007-08-31 Time 11:54 Rev Time 0.00
Received By dpalmer Date 2007-08-31 Time 11:54 Sent To B
Notes
2007-08-31 11:55:59** NEW SHEETS INSERTED INTO SET, STAMPED AND SENT OT
 BUILDING AS THERE ARE TWO NEW SHEETS FROM THE
 ARCHITECT.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2007-08-29 Cont ID  
Sent By dpalmer Date 2007-08-29 Time 07:40 Rev Time 0.00
Received By dpalmer Date 2007-08-29 Time 07:40 Sent To B
Notes
2007-08-29 10:51:252007-08-29 10:51:25
 SPOKE TO GORDAN SCOTT AND MR. LON CARTER (ENGINEER OF
 RECORD).
 NEW PLANS ARE BEING BROUGHT UP FOR INSERTTING INTO THE
 SETS.
 WALLS WILL NEED TO BE MOVED WHICH WILL REQUIRE NEW *A*
 SHEETS.
  
 ON HOLD.
2007-08-29 07:41:422007-08-29 07:41:42
 ** DENIED 5TH REVIEW **
  
 1) NOTE: PLEASE SEE PREVIOUS NOTE #2 WHICH REQUESTED TO
 MEET SEVERAL SECTIONS OF THE CODE FOR CLEARANCES OF THE
 TRANSFORMER(S) AND DISCONNECTS. BY SIMPLY PLACING A
 NOTE ON THE PLANS WHICH STATES *DISCONNECTS AND
 TRANSFORMER(S) WILL BE RELOCATED* DOES NOT SHOW CODE
 COMPLIANCE AS REQUIRED ON PLANS.
 PLEASE SUBMIT PLANS SHOWING NEW LOCATION(S) MEETING THE
 *MINIMUM* CODE. THIS OFFICE HAS ONLY REQUESTED THE
 MINIMUM CODE FROM THE FIRST REVIEW FOR THIESE SAME
 ITEMS. FBC 106.1.1, 106.1.2, 106.3.5.1.2.
 FLORIDA ADMINISTRATIVE CODE 61G15-33.003 (2)(D) PLEASE
 KNOW THAT ONCE THE LOCATION(S) MEETS 110.26, 240.24,
 240.21, 450.9, 450.13 ETC THE PERMIT CAN BE ISSUED.
  
 ** A CALL WILL BE PLACED TO THE ENGINEER'S OFFICE ONE
 UNDER NORMAL BUSINESS HOURS TO TRY AND RESOLVE THE
 ISSUE.
  
 ** PLANS ARE BEING ROUTED TO THE BUILDING REVIEWER AS A
 NEW ARCHITECTURAL SHEET WAS INSERTED INTO PLANS.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-07-31 Cont ID  
Sent By dpalmer Date 2007-07-31 Time 18:36 Rev Time 0.00
Received By dpalmer Date 2007-07-31 Time 17:53 Sent To  
Notes
2007-07-31 18:37:51*** UNSAT 4TH REVIEW ***
  
 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED
 DO NOT CORRELATE WITH THE PLANS FOR THE METHOD OF
 CONTROL. PLEASE SEE THESE ARE STILL BEING ENTERED AS
 *MANUAL ON/OFF* WHEN THEY ARE AUTOMATED/OCCUPANCY TYPE
 DEVICES ON PLANS.
 PLEASE COORDINATE. 13-415.1.AB.1.1, 13-415.1.A,
 13-415.2.
 PLEASE CLARIFY METHOD AND HOW THIS CAN BE USED FOR
 SCOPE OF WORK AS SHOWN. PLEASE CLARIFY LIGHTING POWER
 DENSITIES AS REQUESTED ON THE PREVIOUS THREE REVIEWS.
 THE RESPONSE LETTER DOES NOT ADDRESS OR MENTION THESE
 ITEMS???
 PLEASE SEE THESE ARE TO BE SIGNED BY THE ENGINEER OF
 RECORD WITH SIGNATURE AS ON FILE AND RECOGNIZED BY THIS
 OFFICE. PLEASE SEE THESE ARE NOT THE SAME AS THE PLANS
 OR PREVIOUS SUBMITTED ENERGY CALCULATIONS.
 13-103.1.1.1, FS471.025
  
 2) NOTE: PLEASE SEE THE PLANS HAVE NOT CHANGED FOR THE
 LOCATIONS OF DISCONNECTS. PLEASE SEE THE TRANSFORMER
 T1A WHICH IS BEING SHOWN IN SOME KIND OF CLOSET. THIS
 SAME CLOSET CONTAINS TWO SMALL RECTANGLES WHICH ARE NOT
 LABELED AS DISCONNECTS. AS THESE COULD NOT BE LOCATED
 AT ANY OTHER LOCATION ON PLANS, IT IS BEING ASSUMED
 THESE ARE THE SAME DISCONNECTS IN THIS SAME *CLOSET*.
 PLEASE SEE THESE DO NOT MEET 110.26, 240.24, 408.7 ETC
 AS PREVIOUSLY STATED IN PREVIOUS REVIEWS.
 ** ALL SERVICE EQUIPMENT NEW OR EXISTING WILL BE
 REQUIRED TO MEET THE MINIMUM REQUIRED BY CODE**
  
 **DOCUMENTATION HAS BEEN SENT TO THE CHIEF ELECTRICAL
 INSPECTOR FOR FIELD INSPECTION AND CORRECTION NOTICED
 TO BE ISSUED TO OWNER/JOBSITE AS/IF NEEDED.
  
 3) NOTE: PLANS AND SUPPORTING DOCUMENTS ARE BEING
 RETAINED BY THIS OFFICE DUE TO REPEAT CODE COMPLIANT
 COMMENTS PER FS 553.80(2)(B). AT THIS TIME A FEE OF
 $9,732.00 MAY BE ASSESSED DUE TO THE REPEAT COMMENTS
 FOR CODE COMPLIANCE. THE CODE COMMENTS WILL GO UNDER
 PIER REVIEW.
 THE FEE IS REQUIRED UNDER FLORIDA STATUTESAND WILL BE
 DUE BEFORE NEXT RESUB OF PLANS MAY BE DONE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-06-08 Cont ID  
Sent By dpalmer Date 2007-06-08 Time 09:56 Rev Time 0.00
Received By dpalmer Date 2007-06-08 Time 08:28 Sent To  
Notes
2007-06-08 09:56:28*** UNSAT 3RD ***
  
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEWS STILL
 ARE IN NEED OF ADDRESSING ALONE WITH SOME NEW COMMENTS
 DUE TO CHANGES MADE ON PLANS AND DOCUMENTS SUBMITTED.
  
 1) NOTE: PLEASE SEE THE PERMIT APPLICATION STILL
 INDICATES SCOPE OF WORK WHICH IS NOT THE SAME AS PLANS.
 THE PERMIT APPLICATION STATES *DESCRIBE PROJECT IN
 DETAIL* IF THE PERMIT APPLICATION STATES THE ENTIRE 4TH
 FLOOR IS BEING BUILD OUT FOR TENANT, THEN PLANS WILL BE
 REQUIRED TO BE REVISED TO SHOW CODE COMPLIANCE FOR THE
 ENTIRE FLOOR.
 PLEASE COORDINATE WITH ONE OR THE OTHER.
 PLEASE SEE THE PERMIT APPLICATION PACKAGE AS SUBMITTED
 DOES CONTAIN PAPERWORK AND DOCUMENTATION WHICH IS FROM
 THE THIRD FLOOR BUILD OUT WORK AND ANOTHER PERMIT.
 PLEASE COORDINATE ALL DOCUMENTS, PLANS, AND PAPERWORK.
 FBC 106.3.5.1.2
  
 2) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS NOW
 SUBMITTED DO NOT COORDINATE WITH THE SUBMITTED PLANS.
 PLEASE SEE THE NUMBER OF LIGHTING FIXTURES, THE
 WATTAGE, TYPES AND CONTROLS FOR SUCH FIXTURES DOES NOT
 MATCH WITH PLANS.
 PLEASE ADJUST.
 PLEASE SEE LEGEND AS THIS DOES NOT INDICATE ANY
 AUTOMATED TYPE DEVICE. THE TIMES ARE NOT STATED. THE
 PLANS DO NOT INDICATE DEVICES FOR NEW.
 PLEASE SEE13-101, 13-415.1.ABC.1.1, .1.2,
 13-415.1.AB.1.1, 13-415.2 HOW IS METHOD A ABLE TO BE
 SUED FOR THE SQ FT AS SHOWN AND FOR SCOPE OF WORK,
 PLEASE
 PLEASE SEE THE ENERGY CALCULATIONS WILL REQUIRE TO BE
 SIGNED BY *OWNER AGENT* AS INDICATED ON SHEET
 2.
  
 3) NOTE: PLEASE SEE SHEET E0.1 WHICH INDICATES A 2005
 FBC?
 PLEASE SEE NO YEARS INDICATE FOR ELECTRICAL CODE
 NFPA-70 OR LIFE SAFETY CODE NFPA-101. THESE SHOULD BE:
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70 (NEC).
 2003 NFPA-101
  
 4) NOTE: PLEASE SEE THE NEW DISCONNECTS ADDED FOR THE
 TAPPED CONDUCTORS TO PANEL L AND L1 DO NOT APPEAR ON
 PLANS AND LOCATIONS OF THESE CAN NOT BE VERIFIED FOR
 CODE COMPLIANCE OF 240.21, 110.26, 240.24 ETC
 PLEASE SHOW.
 FBC106.1.21
  
 5) NOTE: PLEASE SEE NO CHANGES OR NOTES HAVE BEEN ADDED
 FOR EXISTING AS SHOWN ELECTRICAL EQUIPMENT WHICH DOES
 NOT MEET 110.26,408.7, 240.24, 450.9,450.11,450.13 ETC
 ** PERMIT WILL NOT BE ISSUED.
 THE LOCATION OF THESE PANELS AND TRANSFORMER(S) WILL BE
 REQUIRED TO MEET CODE. IF PLANS AND PERMIT FOR SCOPE OF
 WORK DOES NOT COMMENCE WITHIN 60 DAYS FROM THIS REVIEW
 DATE FOR CORRECTION, A NOTICE WILL BE ISSUED ON-SITE
 FOR VIOLATIONS AND SCOPE OF WORK WILL BE REQUIRED ON A
 SEPARATE PERMIT WHETHER OR NOT BUILD OUT IS DONE TO
 ALLEVIATE ANY FURTHER ACTION FOR DISCONNECT OF SERVICE
 UTILITIES.
 ** AN ELECTRICAL CONTRACTOR MAY APPLY FOR THIS WORK
 SEPARATELY TO BEGIN. PLEASE CONTACT THIS OFFICE IF THIS
 OPTION IS TAKEN.
 AS THIS IS NOT ONLY A LIFE SAFETY HAZARD BUT AS WELL AS
 A FIRE HAZARD FOR LIFE AND PROPERTY, NO EXCEPTIONS TO
 ANY EXISTING NON-CODE COMPLIANCE WILL BE GRANTED.
 THIS IS FOR ANY OF THE TRANSFORMER(S), PANEL(S), AND
 DISCONNECT(S) LOCATIONS.
  
 ** PLEASE KNOW AT THIS TIME AS SOME OF THE INSTALLATION
 IS NOT CLEAR, THERE MAY BE COMMENTS IF THE INSTALLATION
 CHANGES AND/OR PERMIT APPLICATION CHANGES.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-03-11 Cont ID  
Sent By dpalmer Date 2007-03-11 Time 10:08 Rev Time 0.00
Received By dpalmer Date 2007-03-10 Time 18:52 Sent To  
Notes
2007-03-11 10:10:08** UNSAT 2ND REVIEW **
  
  
  
 222 LAKEVIEW
 4THFLOOR BUILD-OUT/REMODEL\
  
 ** PLEASE SEE SOME COMMENTS ARE THE SAME AND SOME ARE
 NEW DUE TO CHANGES IN PLANS.
  
  
 1) NOTE: PLEASE SEE MISSING COMPLETE INFORMATION FOR A
 TITLE BLOCK FOR THE ARCHITECT OF RECORD AND FIRM.
 PLEASE SEE MISSING CERTIFICATE OF AUTHORIZATION NUMBER
 ALSO KNOW AS FIRM LICENSE NUMBER.
 PLEASE SEE MISSING THE PRINTED NAME AND LICENSE NUMBER
 FOR ARCHITECT.
 FLORIDA ADMINISTRATIVE CODE 61G1-16.004, FLORIDA
 STATUTES 481.219
 **THIS IS NOT A COMMENT RELATED TO KAMM CONSULTING,
 HOWEVER TITLE BLOCKS ARE REQUIRED FOR ALL SHEETS PER
 ABOVE AND WHETHER OR NOT COMMENT IS MADE BY ANY OTHER
 TRADE.
  
 2) NOTE: PERMIT APPLICATION HAS NOT BEEN ADJUSTED.
 PLEASE CLARIFY PERMIT APPLICATION HAS APPLIED FOR NEW
 TENANT BUILD OUT, HOWEVER PLANS DO NOT CORRELATE WITH
 THIS.
  
 3) NOTE:PLEASE KNOW ANY NEW ROOM LIGHTING AND
 CONTROLS SHALL COMPLY WITH THIS SECTION. 13-415.
 PLEASE KNOW THE ENTIRE FLOOR DOES NOT HAVE BE BROUGHT
 UP TO CURRENT CODES, HOWEVER THE NEW ROOMS/LIGHTS AND
 CONTROLS WILL BE REQUIRED. THIS CAN BE DONE BY SINGLE
 DEVICES IN THESE ROOMS/AREAS.
 PLEASE ALSO KNOW THAT THE LIGHTING POWER DENSITIES FOR
 EACH OF THE NEW ROOMS SHALL COMPLY WITH THE MAXIMUM
 LIGHTING AS PERMITTED IN THE TABLES. PLEASE SEE MISSING
 LIGHTING CONTROL FOR ALL PER 13-415.1.ABC.1.1, .1.2,
 AND .1.3.NEW AREAS AND ROOMS. PLEASE SEE OVER RIDES
 DEVICES FOR THESE AREAS ALSO DEPENDING ON IF"SYSTEM"
 OR "DEVICES" ARECHOSEN.
 PLEASE SEE THE SYMBOL LEGEND FOR ALL DEVICES SHALL
 INDICATE ALL MAXIMUM TIMES FOR DEVICES. (30MINS FOR
 OCCUPANCY SENSOR TYPE AND 4HRS MAX FOR TIMER TYPE)
 PLEASE SEE ROOMS AND AREAS WHICH DO NOT INDICATE ANY OF
 THE DEVICES FOR AUTOMATED CONTROL.
 PLEASE SEE ALL AREAS CONTAIN FLOOR TO CEILING HEIGHT
 PARTITIONS SHALL CONTAIN DEVICE(S) FOR CONTROL. (PLEASE
 SEE STORAGE)
 PLEASE SEE 13-415.2, 13-415.2.ABC.1 FOR MISSING MAXIMUM
 PERMITTED LIGHTING POWER DENSITIES.
  
 4) NOTE: PLEASE PLACE A NOTE ON PLANS/SHEET E2.1 TO
 CLOSET AREA TO BE BROUGHT UP TO CODE FOR MINIMUM
 CLEARANCES AS STATED IN THE SECTIONS OF THE CODE NOTED
 BELOW. PLEASE KNOW THIS WILL BE A CONDITION OF ISSUANCE
 AND PLEASE KNOW NO ROUGH ELECTRICAL INSPECTIONS WILL BE
 DONE UNTIL REVISIONS OR SEPARATE PERMIT IS SUBMITTED
 FOR CHANGES.ONCE NOTE IS ON PLANS, A HOLD WILL BE
 PLACED ON INSPECTIONS.
 PLEASE SEE THE PANELSHV, LV1 AND LV2 WHICH DO NOT
 SEEM TO MEET 110.26 FOR PANEL HV AND TRANSFORMER.
 PLEASE VERIFY THIS AND KNOW THAT IF THIS WALL IS
 ACTUALLY INSTALLED IN FRONT OF THE PANEL/EQUIPMENT AS
 SHOWN, THIS WILL BE REQUIRED TO MEET 110.26/450.9,
 450.13 ETC
  
 5) NOTE: PLEASE SEE PLANS HAVE BEEN REVISED TO SHOW THE
 TRANSFORMER "T1A" DIRECTLY IN A CLOSET WHEN PREVIOUSLY
 SHOWN IN THE MIDDLE OF THE CONFERENCE ROOM. PLEASE SEE
 PANELS *L* AND L1* DO NOT SEEM TO MEET THE TAP
 CONDUCTOR RULE FOR DISTANCE IN THE LENGTH OF
 CONDUCTORS. PLEASE SEE 240.21C.
 PLEASE ALSO SEE MINIMUM CLEARANCES REQUIRED FOR
 TRANSFORMER.
 THIS IS A FIRE/LIFE SAFETY HAZARD.
 PLEASE ALSO VERIFY LOCATION FOR TAPS ON A TRANSFORMER
 PER 240.21C. PLEASE ADJUST PLANS AND VERIFY THE ACTUAL
 INSTALLATION.
  
  
 13) NOTE:** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDEDSHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.PLEASE KNOW ONLY
 ONE SET OF THE OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-03-10 18:53:062007-03-10 18:53:06
 IN ELEC FOR REVIEW

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-01-07 Cont ID  
Sent By dpalmer Date 2007-01-07 Time 19:44 Rev Time 0.00
Received By dpalmer Date 2007-01-07 Time 19:09 Sent To  
Notes
2007-01-07 19:44:05** UNSAT **
  
  
 222 LAKEVIEW
 4THFLOOR BUILD-OUT/REMODEL
  
  
 1) NOTE: PLEASE SEE MISSING ADDRESS INFORMATION FROM
 TITLE BLOCKS. PLEASE SEE THE SUITE/UNIT NUMBER IS BEING
 SHOWN, HOWEVER NOT THE ADDRESS/ LOCATION.
 FAC 61G1-16.004, FAC61G15-23.002
  
 2) NOTE: PLEASE SEE MISSING COMPLETE INFORMATION FOR A
 TITLE BLOCK FOR THE ARCHITECT OF RECORD AND FIRM.
 PLEASE SEE MISSING CERTIFICATE OF AUTHORIZATION NUMBER
 ALSO KNOW AS FIRM LICENSE NUMBER.
 PLEASE SEE MISSING THE PRINTED NAME AND LICENSE NUMBER
 FOR ARCHITECT.
 FLORIDA ADMINISTRATIVE CODE 61G1-16.004, FLORIDA
 STATUTES 481.219
 **THIS IS NOT A COMMENT RELATED TO KAMM CONSULTING,
 HOWEVER TITLE BLOCKS ARE REQUIRED FOR ALL SHEETS PER
 ABOVE AND WHETHER OR NOT COMMENT IS MADE BY ANY OTHER
 TRADE.
  
 3) NOTE: PLEASE LIST THE FOLLOWING MINIMUM CODES
 RELEVANT TO THIS PROJECT AND DESIGN.
 2005 NFPA-72, 2005 NFPA-70, 2003 NFPA-101
 PLEASE ADJUST THE ARCHITECTURAL SHEETS AS WELL AS THE
 ELECTRICAL SHEETS.
 PLEASE SEE AS THE PERMIT WAS APPLIED FOR AFTER DECEMBER
 8TH, 2006 THE 2006 REVISIONS TO THE 2004 FBC AND THE
 2005 NATIONAL ELECTRICAL CODE WAS ADOPTED BY THE STATE
 OF FLORIDA.
 PLEASE ADJUST CODES ON PLANS.
  
 4) NOTE: PLEASE CLARIFY PERMIT APPLICATION HAS APPLIED
 FOR NEW TENANT BUILD OUT, HOWEVER PLANS DO NOT
 CORRELATE WITH THIS. PLEASE CLARIFY AS THE NEXTTWO
 COMMENTS MAY APPLY FOR FLOOR OR FOR NEW ROOMS AS
 SHOWN.
  
 5) NOTE: PLEASE SEE MISSING LIGHTING CONTROL FOR ALL
 PER 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE SEE
 MISSING CONTROLS FOR COMMON AREAS. PLEASE SEE OVER
 RIDES DEVICES FOR THESE AREAS ALSO DEPENDING ON
 "SYSTEM" OR DEVICES CHOSEN. PLEASE SEE THE SYMBOL
 LEGEND FOR ALL DEVICES SHALL INDICATE ALL MAXIMUM TIMES
 FOR DEVICES. (30MINS FOR OCCUPANCY SENSOR TYPE AND 4HRS
 MAX FOR TIMER TYPE)
 PLEASE SEE ROOMS AND AREAS WHICH DO NOT INDICATE ANY OF
 THE DEVICES FOR AUTOMATED CONTROL.
 PLEASE PROVIDE SCHEDULING FOR ANY PROPOSED SYSTEM.
 PLEASE SEE ALL AREAS CONTAIN FLOOR TO CEILING HEIGHT
 PARTITIONS SHALL CONTAIN DEVICE(S) FOR CONTROL. (PLEASE
 SEE STORAGE)
 PLEASE SEE 13-415.2, 13-415.2.ABC.1 FOR MISSING MAXIMUM
 PERMITTED LIGHTING POWER DENSITIES.
 PLEASE ALSO SEE 13-415.AB.1 FOR MISSING ENERGY
 CALCULATIONS REQUIRED FOR NEW TENANT BUILD-OUT.
 ** PLEASE SUBMIT THE ABOVE. AS THERE ARE ITEMS NOT YET
 SUBMITTED, A REVIEW OF SAID SYSTEM/DEVICES ETC CAN NOT
 BE FULLY ACCOMPLISHED AT THIS TIME.
  
 6) NOTE: PLEASE PROVIDE A DETAIL ON ALL EMERGENCY
 AND/OR EXIT LIGHTING WIRED AHEAD OF ANY OVER RIDE
 CONTROL DEVICES PER 700.12E. PLEASE SEE A
 CLOUDED/HIGHLIGHTED NOTE MAY ALSO BE DONE. THIS AHJ HAS
 BEEN HAVING MANY INSTANCES WHERE EMERGENCY AND EXIT
 LIGHTS ARE BEING WIRED ON THE LOAD SIDE OF OC/ TIMER
 DEVICES.
  
 6) NOTE: PLEASE INDICATE ALL CONTINUOUS LOADS AT 125%.
 215.3, 230.42 ETC.
 FBC 106.1.2 ADMIN SECTION.
  
 7) NOTE: PLEASE KNOW EITHER AT THIS POINT OR BEFORE
 FINAL, A REVISION FOR ALL CIRCUITS TO SPECIFIC ROOMS
 AND AREAS WILL BE REQUIRED. (LIGHTING CIRCUITS ETC.)
 408.4.
  
  
 8) NOTE: PLEASE SEE THE PANELSHV, LV1 AND LV2 WHICH
 DO NOT SEEM TO MEET 110.26 FOR PANEL HV AND
 TRANSFORMER. PLEASE VERIFY THIS AND KNOW THAT IF THIS
 WALL IS ACTUALLY INSTALLED IN FRONT OF THE
 PANEL/EQUIPMENT AS SHOWN, THIS WILL BE REQUIRED TO MEET
 110.26/450.9, 450.13 ETC
  
 9) NOTE: PLEASE SEE THE RISER SHEET CONTAINS A BOX WITH
 NOTES FROM 9/25/01? PLEASE UPDATE NOTE.
 PLEASE SEE THIS NOTE #3 IN THIS BOX SHOW A NOTATION FOR
 A NEW BREAKER TO COME FROM THE EXISTING "H" PANEL TO
 FEED PANEL "H1" WHICH ON RISER IS SHOWN AS NEW, YET
 THIS PANEL SCHEDULE FOR "H1" INDICATES THIS PANEL AS
 A120/208V PANEL AND IS BEING FED FROM H WHICH IS
 277/480V.
 PLEASE SEE RISER AND PLANS DO NOT SHOW ANY
 TRANSFORMER.
 PLEASE SEE 450.3, 450.9, 450.13B, 240.21C ETC PLEASE
 CORRELATE PLANS AND ADJUST.
  
 10) NOTE: PLEASE SEE PLANS APPEAR TO SHOW TRANSFORMER
 "T1A" DIRECTLY IN THE MIDDLE OF THE CONFERENCE ROOM.
 PLEASE SEE 450.13B AS THIS UNIT IS A 75 KVA TRANSFORMER
 AND IF ABOVE CEILING IT WILL BE REQUIRED TO BE
 RELOCATED BELOW CEILING. THIS IS A FIRE/LIFE SAFETY
 HAZARD AND THE CODE EVEN WHEN THE BUILDING WAS BUILT
 DID NOT ALLOW THIS INSTALLATION AS SHOWN. PLEASE ALSO
 VERIFY LOCATION FOR TAPS ON A TRANSFORMER PER 240.21C.
 PLEASE ADJUST PLANS AND VERIFY THE ACTUAL
 INSTALLATION.
  
  
 11) NOTE: PLEASE SEE THE LOW VOLTAGE AUDIO/VISUAL PLANS
 SUBMITTED MAY ONLY BE PART OF THE PERMITTED RECORD SET
 OF PLANS IF BEING DONE BY THE ELECTRICAL SUB
 CONTRACTOR. AS THESE SHEETS SEEM TO INDICATE A SEPARATE
 LV SOUND/AUDIO VISUAL CONTRACTOR, THESE SHALL BE
 SUBMITTED UNDER A SEPARATE PERMIT APPLICATION. PLEASE
 KNOW IN EITHER CASE ALL PLANS ARE REQUIRED TO BE
 SIGNED, DATED PRINTED NAME ETC FOR THE PERSON TAKING
 RESPONSIBILITY OF SUCH PLANS.
 FBC 106.1.2, FS 481/471, FAC 61G15-23.002, FAC
 61G1-16.004 ETC
  
 12) NOTE: PLEASE SEE "S" SHEET IN BOTH SETS ARE NOT
 SIGNED AND DATED BY THE ENGINEER OF RECORD. SHEETS DO
 CONTAIN THE RAISED SEAL.
 PLEASE SEE FS 471.025, FAC 61G15-23.002
 THIS IS ONLY NOTED AND SHOULD ALSO BE IN NOTES FROM THE
 BUILDING REVIEWER.
  
 13) NOTE:** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDEDSHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.PLEASE KNOW ONLY
 ONE SET OF THE OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2007-10-31 Cont ID  
Sent By mawillia Date 2007-10-31 Time 10:40 Rev Time 0.00
Received By mawillia Date 2007-10-31 Time 10:08 Sent To  
Notes
2007-10-31 10:40:05*****APPROVED*****
  
  
 REVISED PLAN SHEETS A6.04, FA2.1, AND FS2.1 WERE
 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-08-15 Cont ID  
Sent By mawillia Date 2007-08-15 Time 17:02 Rev Time 0.00
Received By mawillia Date 2007-08-15 Time 16:53 Sent To  
Notes
2007-08-15 17:00:45****PROVISO*****
  
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED;HOWEVER, THE APPROPIATE PLAN SHEETS
 WILL BE FIRE-STAMPED WHEN ALL PLANREVIEWERS HAVE BEEN
 SATISFIED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-06-29 Cont ID  
Sent By mawillia Date 2007-06-29 Time 11:12 Rev Time 0.00
Received By mawillia Date 2007-06-29 Time 11:00 Sent To  
Notes
2007-06-29 11:05:14****PROVISO*****
  
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED;HOWEVER, THE APPROPIATE PLAN SHEETS
 WILL BE FIRE-STAMPED WHEN ALL PLANREVIEWERS HAVE BEEN
 SATISFIED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-04-02 Cont ID  
Sent By mawillia Date 2007-04-02 Time 13:23 Rev Time 0.00
Received By mawillia Date 2007-04-02 Time 12:40 Sent To  
Notes
2007-04-02 13:23:02****UNSAT*****
  
  
 PLEASE ADDRESS FOLLOWING COMMENT TAKEN FROM PREVIOUS
 FIRE PLAN REVIEW:
  
  
  
  
 5.ON SHEET FA2.1, FIRE ALARM NOTE #17, DELETE
 SUPERVISORY SIGNAL ONLY - INSERT GENERAL FIRE ALARM
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-02-07 Cont ID  
Sent By mawillia Date 2007-02-07 Time 19:11 Rev Time 0.00
Received By mawillia Date 2007-02-07 Time 19:11 Sent To  
Notes
2007-02-07 19:19:41*****DENIED*****
  
  
 1.THE COMPLETE ADDRESS OF WHERE THE SCOPE OF WORK
 WILL BE CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.
  
 2.ON SHEET A0.00, MAKE THE FOLLOWING CHANGES TO THE
 CODE ANALYSIS SECTION:I.AUTHORITIES CONSTRUCTION
 SERVICES DEPARTMENT - CITY OF WEST PALM BEACH
 561-805-6700;FIRE MARSHAL - MIKE CARSILLO
 561-804-4724II. APPLICABLE BUILDING CODES
 ELIMINATE NFPA 2003 CODES W/FLORIDA AMENDMENTS, INSERT
 FLORIDA FIRE PREVENTION CODE 2004
  
 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD
 TO GENERAL DEMOLITION NOTES, SHEET AD1.03
  
 4.DO THE TENANT ENTRY DOORS (AS REFERRED TO ON SHEET
 A9.032) LEAD TO AN EXIT ACCESS CORRIDOR?IF SO, THESE
 DOORS SHALL BE FIRE RATED AS PER NFPA 80.
  
 5.ON SHEET FA0.1, FIRE ALARM NOTE #17, DELETE
 SUPERVISORY SIGNAL ONLY - INSERT GENERAL FIRE ALARM
  
 6.PROVIDE A LAYOUT OF THE FIRE SPRINKLER SYSTEM. WILL
 THEY NEED TO BE ALTERED OR MODIFIED DUE TO THE SCOPE OF
 WORK?
  
 7.BUILDINGS OR PORTIONS OF BUILDINGS SHALL BE
 PERMITTED TO BE OCCUPIED DURING CONSTRUCTION, REPAIR,
 ALTERATIONS, OR ADDITIONS ONLY WHERE REQUIRED MEANS OF
 EGRESS AND REQUIRED FIRE PROTECTION
 FEATURES ARE IN PLACE AND CONTINUOUSLY MAINTAINED FOR
 THE PORTION OCCUPIED OR WHERE ALTERNATIVE LIFE SAFETY
 MEASURES ACCEPTABLE TO THE AUTHORITY HAVING
 JURISDICTION ARE IN PLACE.
  
 8.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF
 NEW BUILDING MATERIALS & SUPPLIES SHALL NOT HINDER OR
 INTERFERE WITH ACCESS TO OR EXIT FROM FLOOR AND/OR
 BUILDING (INCLUDING FIRE LANES).
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-02-01 Cont ID  
Sent By adarroug Date 2008-02-01 Time 09:26 Rev Time 0.00
Received By adarroug Date 2008-02-01 Time 09:25 Sent To E
Notes
2008-02-01 09:26:19TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-09-28 Cont ID  
Sent By adarroug Date 2007-09-28 Time 16:48 Rev Time 0.00
Received By adarroug Date 2007-09-28 Time 16:48 Sent To  
Notes
2007-10-18 16:19:55TO "COMM" BD#39
2007-09-28 16:48:43WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-08-28 Cont ID  
Sent By adarroug Date 2007-08-28 Time 14:36 Rev Time 0.00
Received By adarroug Date 2007-08-28 Time 14:36 Sent To E
Notes
2007-08-28 14:36:56TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-07-18 Cont ID  
Sent By adarroug Date 2007-07-18 Time 13:21 Rev Time 0.00
Received By adarroug Date 2007-07-18 Time 13:21 Sent To  
Notes
2007-07-27 11:59:22TO "COMM" BD#34
2007-07-18 13:21:44WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-05-15 Cont ID  
Sent By adarroug Date 2007-05-15 Time 11:22 Rev Time 0.00
Received By adarroug Date 2007-05-15 Time 11:22 Sent To  
Notes
2007-06-01 15:14:47TO "COMM" BD#49
2007-05-15 11:22:58WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-05 Cont ID  
Sent By adarroug Date 2007-03-05 Time 11:55 Rev Time 0.00
Received By adarroug Date 2007-03-05 Time 11:55 Sent To  
Notes
2007-03-08 11:47:15TO "COMM" BD#17
2007-03-05 11:55:23WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-07 Cont ID  
Sent By mawillia Date 2007-02-07 Time 19:11 Rev Time 0.00
Received By mawillia Date 2006-12-12 Time 18:58 Sent To  
Notes
2007-01-07 18:22:102007-01-07 18:22:10
 TO COMM BOARD #9
2006-12-12 18:58:42WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-10-25 Cont ID  
Sent By tgordon Date 2007-10-25 Time 10:53 Rev Time 0.35
Received By tgordon Date 2007-10-25 Time 10:53 Sent To  
Notes
2007-10-25 10:54:32REVISION TO MECH. PLANS PEGE M2.1 AND M5.1.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-07-30 Cont ID  
Sent By tgordon Date 2007-07-30 Time 14:19 Rev Time 0.25
Received By tgordon Date 2007-07-30 Time 14:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-06-14 Cont ID  
Sent By tgordon Date 2007-06-14 Time 13:52 Rev Time 0.25
Received By tgordon Date 2007-06-14 Time 13:52 Sent To  
Notes
2007-06-14 13:54:17*** DENIED ***
 1) MECHANICAL PLANS ARE OK AT THIS TIME, SEE ELECTRICAL
 REVIEW NOTES AND PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-03-14 Cont ID  
Sent By tgordon Date 2007-03-14 Time 09:18 Rev Time 0.30
Received By tgordon Date 2007-03-14 Time 09:18 Sent To  
Notes
2007-03-14 09:27:53*** DENIED ***
 1) AS NOTED IN LAST REVIEW 1-8-07.INFORMATION MISSING
 IN TITLE BLOCK FOR ARCHITECTURAL FIRM (ASSOCIATED SPACE
 DESIGN INC.) SEE FAC 61G1-16.004 TITLE BLOCK (2).
  
 *** A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT. ("JOB ADDRESS"
 SEE CITY WPB AMEND. 106.1.1).
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-01-08 Cont ID  
Sent By tgordon Date 2007-01-08 Time 14:34 Rev Time 0.30
Received By tgordon Date 2007-01-08 Time 14:34 Sent To  
Notes
2007-01-08 14:36:00*** DENIED ***
 1) SEE ELECTRICAL REVIEW NOTE # 2, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 6 Status P Date 2007-11-01 Cont ID  
Sent By kstevens Date 2007-11-01 Time 15:58 Rev Time 0.00
Received By kstevens Date 2007-11-01 Time 15:58 Sent To  
Notes
2007-11-01 15:58:50REVISION OK--SHT P2.1

Review Stop P PLUMBING
Rev No 5 Status P Date 2007-08-22 Cont ID  
Sent By kstevens Date 2007-08-22 Time 08:33 Rev Time 0.00
Received By kstevens Date 2007-08-22 Time 08:33 Sent To  
Notes
2007-08-22 08:35:25 
  
  
 PASSED/PROVISO
  
 WATER HAMMER ARRESTOR SHALL BE LOCATED NEAR THE
 FIXTURE, NOT IN THE CEILING.--BREAK ROOM INDICATES
 A WATER COOLER ON SHT A3.04 AND A DRINKING FOUNTAIN ON
 SHT P2.1. THESE HAVE BEEN ADDED TO THE ONE OUTSIDE THE
 GANG BATHS.

Review Stop P PLUMBING
Rev No 4 Status F Date 2007-08-20 Cont ID  
Sent By kstevens Date 2007-08-20 Time 18:06 Rev Time 0.00
Received By kstevens Date 2007-08-20 Time 18:02 Sent To  
Notes
2007-08-20 18:09:01DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
 (COMMENT NUMBERS TO REMAIN THE SAME)
 ********FROM PREVIOUS REVIEWS:
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
 A. OK
 B. OK
 C. OK
 D. OK
 E. OK
  
 7. SHOW THE FIXTURES REQUIRED BY SECTION 1004.1.3
 (BLDG) & 403.1 MINIMUM FACILITIES. INDICATE ON THE
 FLOOR PLAN THE DRINKING FOUNTAINS. SECTION 106.1.1.
 ****NO RESPONSE. NOT ADDRESSED.
 ******RESPONSE NOTED, BUT TABLE 403.1 REQUIRES 3
 DRINKING FOUNTAINS, AND ONLY ONE IS INDICATED. PLEASE
 SHOW ALL 3 DRINKING FOUNTAINS REQUIRED.
 *********RESPONSE NOTED, BUT 3 DRINKING FOUNTAINS ARE
 REQUIRED AND ONLY ONE WAS ADDED. AS THERE WAS ONLY ONE
 DRINKING FOUNTAIN INDICATED TO BEGIN WITH, THE ADDED
 ONE ONLY BRINGS THE TOTAL UP TO TWO. PLEASE INDICATE
 THREE DRINKING FOUNTAINS AS REQUIRED.
  
 8. OK
  
 ********NEW COMMENT********
  
 1B. SHT P2.1 THE WATER HAMMER ARRESTOR AT THE DRINKING
 FOUNTAIN SHALL BE LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING AS SHOWN. PDI-WH
 201 AND MANUF. INSTALLATION INSTRUCTIONS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-06-18 Cont ID  
Sent By kstevens Date 2007-06-18 Time 08:22 Rev Time 0.00
Received By kstevens Date 2007-06-16 Time 17:29 Sent To  
Notes
2007-06-18 08:25:25DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
 (COMMENT NUMBERS TO REMAIN THE SAME)
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
 A. OK
 B. OK
 C. OK
 D. OK
 E. OK
  
 7. SHOW THE FIXTURES REQUIRED BY SECTION 1004.1.3
 (BLDG) & 403.1 MINIMUM FACILITIES. INDICATE ON THE
 FLOOR PLAN THE DRINKING FOUNTAINS. SECTION 106.1.1.
 ****NO RESPONSE. NOT ADDRESSED.
 ******RESPONSE NOTED, BUT TABLE 403.1 REQUIRES 3
 DRINKING FOUNTAINS, AND ONLY ONE IS INDICATED. PLEASE
 SHOW ALL 3 DRINKING FOUNTAINS REQUIRED.
  
 8. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-03-19 Cont ID  
Sent By kstevens Date 2007-03-19 Time 07:57 Rev Time 0.00
Received By kstevens Date 2007-03-19 Time 07:57 Sent To  
Notes
2007-03-19 08:07:29DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
 (COMMENT NUMBERS TO REMAIN THE SAME)
  
 1. OK
 2. OK
  
 3. ALL ARCHITECTURAL SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING:THE FIRM LICENSE
 NUMBER & THE PRINTED NAME OF THE PERSON SEALING THE
 DOCUMENT. FAC 61G1-16.004(2)(6) & FS 481.219,
 481.2055.
 ****NO RESPONSE, THE PRINTED NAME HAS BEEN INDICATED,
 BUT THE CA# AS INDICATED ON THE PLANS IS SHOWN AS
 ANOTHER BUSINESS NAME IN THE STATE DBPR WEBSITE. SEE
 ATTACHED SHEET.
  
 4. OK
 5. OK
  
 6. SHTS A1.04 & A7.041 DETAIL 1. THE BREAK ROOMSINK
 SHALL COMPLY WITH SECTION 11-4.24 AND ALL SUBSECTIONS.
 SHOW THE FOLLOWING:
 A. OK
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.5 CLEAR FLOOR SPACE. FORWARD APPROACH
 EXTENDING A MAXIMUM 19" UNDERNEATH THE SINK IS
 REQUIRED. CABINET DOORS ARE NOT APPROVED.
 D. 11-4.24.6 EXPOSED PIPES & SURFACES
 E. 11-4.24.7 FAUCETS
 ****NO RESPONSE, THE SINK DEPTH IS NOT SHOWN. THE
 CABINET DOORS ARE STILL SHOWN ON ELEVATION 1 SHT
 A-7.041. EXPOSED PIPES & SURFACES NOT ADDRESSED.
 INDICATE FAUCET TYPE. (INDICATING ADA COMPLIANT FAUCET
 IS NOT ENOUTH INFORMATION).
  
 7. SHOW THE FIXTURES REQUIRED BY SECTION 1004.1.3
 (BLDG) & 403.1 MINIMUM FACILITIES. INDICATE ON THE
 FLOOR PLAN THE DRINKING FOUNTAINS. SECTION 106.1.1.
 ****NO RESPONSE. NOT ADDRESSED.
  
 8. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-01-24 Cont ID  
Sent By kstevens Date 2007-01-24 Time 15:05 Rev Time 0.00
Received By kstevens Date 2007-01-24 Time 15:05 Sent To  
Notes
2007-01-25 08:32:06DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT A.000 CODE ANALYSIS #1 INDICATES THE AUTHORITY
 AS PALM BEACH COUNTY. THE AUTHORITY FOR THIS ADDRESS IS
 THE CITY OF WEST PALM BEACH. #2 INDICATES THE FIRE
 MARSHALL AS ROBERT PRUSIECKI. HE HAS RETIRED AND THE
 NEW FIRE MARSHALL IS MIKE CARCILLO.PLEASE UPDATE THE
 INFORMATION ON THE PLANS. SECTION 106.1.1.
  
 2. SHT A.000 APPLICABLE BUILDING CODES INDICATES PBC
 AMENDMENTS. THIS SHALL BE CHANGED TO WPB AMENDMENTS.
 SECTION 106.1.1.
  
 3. ALL ARCHITECTURAL SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING:THE FIRM LICENSE
 NUMBER & THE PRINTED NAME OF THE PERSON SEALING THE
 DOCUMENT. FAC 61G1-16.004(2)(6) & FS 481.219,
 481.2055.
  
 4. SHT S-2 THE ENGINEER SHALL SIGN/DATE SEALED PLANS.
 FAC 61G15-23.002(2) & FS 471.025.
  
 5. SHT AD1.04 GENERAL DEMOLITION NOTES 0.1.4 INDICATES
 PLUMBING TO BE REMOVED 1/2" BEHIND THE FINISH FACE OF
 THE SURFACE. IN THE REMOVAL OF ANY PART OF THE DRAINAGE
 SYSTEM, DEAD ENDS ARE PROHIBITED. ALL DEMO'D PIPING
 SHALL BE CAPPED AND INSPECTED PRIOR TO COVERING PER
 SECTION 704.5. PLEASE INDICATE ON THE DEMO PLANS.
  
 6. SHTS A1.04 & A7.041 DETAIL 1. THE BREAK ROOMSINK
 SHALL COMPLY WITH SECTION 11-4.24 AND ALL SUBSECTIONS.
 SHOW THE FOLLOWING:
 A. 11-4.24.3 KNEE CLEARANCE
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.5 CLEAR FLOOR SPACE. FORWARD APPROACH
 EXTENDING A MAXIMUM 19" UNDERNEATH THE SINK IS
 REQUIRED. CABINET DOORS ARE NOT APPROVED.
 D. 11-4.24.6 EXPOSED PIPES & SURFACES
 E. 11-4.24.7 FAUCETS
  
 7. SHOW THE FIXTURES REQUIRED BY SECTION 1004.1.3
 (BLDG) & 403.1 MINIMUM FACILITIES. INDICATE ON THE
 FLOOR PLAN THE DRINKING FOUNTAINS. SECTION 106.1.1.
  
 8. SHT P2.1 DOMESTIC WATER ISOMETRIC. THE WATER HAMMER
 ARRESTORS SHALL BE LOCATED NEAR THE FIXTURES, IN AN
 "EFFECTIVE RANGE", NOT IN THE CEILING AS SHOWN. PDI-WH
 201 AND MANUF. INSTALLATION INSTRUCTIONS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved