Plan Review Details - Permit 06120229
Plan Review Stops For Permit 06120229
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-01-05 Cont ID  
Sent By adarroug Date 2007-01-05 Time 12:26 Rev Time 0.00
Received By adarroug Date 2007-01-05 Time 12:26 Sent To M
Notes
2007-01-05 12:26:48TO "HMOSER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-12-12 Cont ID  
Sent By tgordon Date 2006-12-12 Time 09:21 Rev Time 0.00
Received By tgordon Date 2006-12-08 Time 09:26 Sent To  
Notes
2006-12-08 09:27:08TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-01-06 Cont ID  
Sent By hmoser Date 2007-01-06 Time 07:16 Rev Time 0.00
Received By hmoser Date 2007-01-06 Time 07:16 Sent To  
Notes
2007-01-06 07:18:31PASS PRIVISO
 PLEASE REFER TO SECTION 601.4 BALANCED RETURN AIR FBC
 (M) 2004
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-12-12 Cont ID  
Sent By tgordon Date 2006-12-12 Time 09:22 Rev Time 0.25
Received By tgordon Date 2006-12-12 Time 09:21 Sent To  
Notes
2006-12-12 09:34:39*** DENIED ***
 1) THE WRONG PLANS WERE SUBMITTED WITH THE PERMIT
 APPLICATION PLANS WERE FOR 15510 OCEAN BREEZE LANE,
 WELLINGTON. PLEASE SUBMIT CORRECT PLANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.