Plan Review Details - Permit 06120143
Plan Review Stops For Permit 06120143
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-02-16 Cont ID  
Sent By jgomez Date 2007-02-16 Time 11:14 Rev Time 0.50
Received By jgomez Date 2007-02-16 Time 11:14 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-02-08 Cont ID  
Sent By jgomez Date 2007-02-08 Time 13:12 Rev Time 0.50
Received By jgomez Date 2007-02-08 Time 13:12 Sent To  
Notes
2007-02-08 13:44:25BUILDING REVIEW CHECKLIST:
 1- THIS IS A CONCRETE BLOCK HOUSE. NEED TO USE CONCRETE
 BLOCK INSTALLATION SCHEDULE ON SHEET 7 OF 7 OF DRAWING
 05-420 SUBMITTED.REVISE INSTALLATION SCHEDULE AS
 REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-01-31 Cont ID  
Sent By jgomez Date 2007-01-31 Time 10:52 Rev Time 1.00
Received By jgomez Date 2007-01-31 Time 10:51 Sent To  
Notes
2007-01-31 11:04:40BUILDING REVIEW SECOND CHECKLIST:
  
 1- INSTALLATION SCHEDULE SUBMITTED SHOWS ANCHOR SPACING
 TO BE 13" O.C. FOR ALL PANELS.ACCORDING TO ANCHOR
 SCHEDULE ON SHEET 7 OF 7 OF DRAWING 05-420 THE ANCHOR
 SPACING FOR ANCHORS IN CONCRETE BLOCK SHALL BE LESS
 THAN 13' O.C. FOR PANELS SPANS GREATER THAN 72".
 REVISE INSTALLATION SCHEDULED AS REQUIRED.
  
 2- INSTALLATION SCHEDULE SUBMITTED SHOWS THAT SHUTTER
 GLASS SEPARATION IS NOT REQUIRED.ACCORDING TO TABLE 2
 ON SHEET 6 OF 7 OF DRAWING 05-420 THERE ISA MINIMUM
 GLASS SEPARATION THAT NEED TO BE MET. REVISE
 INSTALLATION SCHEDULE AS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-19 Cont ID  
Sent By jgomez Date 2007-01-19 Time 16:02 Rev Time 1.00
Received By jgomez Date 2007-01-19 Time 16:02 Sent To  
Notes
2007-01-19 16:40:32BUILDING REVIEW CHECKLIST:
 1- PROVIDE APPROVED PRODUCT APPROVAL AS REQUIRED BY DCA
 RULE 9B-72 FOR STORM SHUTTERS.DRAWINGS SUBMITTED ARE
 NOT AN APPROVED PRODUCT APPROVAL.
  
 2- SOME STORM PANELS EXCEED THE MAXIMUM PANEL SPAN AS
 ALLOWED BY TABLE 1 ON SHEET 3 OF 4 OF DRAWING NO
 05-421. REVISE AS REQUIRED FOR OPENINGS 18, 22 AND 23.
  
 3- SOME STORM PANELS EXCEED THE MINIMUM PANEL SPAN AS
 ALLOWED BY TABLE 2ON SHEET 3 OF 4 OF DRAWING NO
 05-421. REVISE AS REQUIRED FOR OPENINGS 3, 25, 26, 27
 AND 28.
  
 4- PERMIT VALUATION WAS UPDATEDAS REQUIRED BY SEC.
 108.3 CITY AMENDMENTS TO FBC 2004.OWES $29.42FOR
 ADDITIONAL PERMIT FEES.
  
 5- INSTALLATION SCHEDULE USED IS TOO OLD. PLEASE USE
 ATTACHED SAMPLE OF REVISED INSTALLATION SCHEDULE WHICH
 PROVIDES ALL REQUIRED INFORMATION FOR PLAN REVIEW. FILL
 IN ALL INFORMATION TO AVOID DELAYS. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-02-16 Cont ID  
Sent By adarroug Date 2007-02-16 Time 10:04 Rev Time 0.00
Received By adarroug Date 2007-02-16 Time 10:04 Sent To B
Notes
2007-02-16 10:05:12TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-02-08 Cont ID  
Sent By adarroug Date 2007-02-08 Time 08:50 Rev Time 0.00
Received By adarroug Date 2007-02-08 Time 08:50 Sent To B
Notes
2007-02-08 08:50:34TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-01-30 Cont ID  
Sent By adarroug Date 2007-01-30 Time 16:42 Rev Time 0.00
Received By adarroug Date 2007-01-30 Time 16:42 Sent To B
Notes
2007-01-30 16:42:25TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-19 Cont ID  
Sent By jgomez Date 2007-01-19 Time 16:49 Rev Time 0.00
Received By jgomez Date 2007-01-19 Time 09:39 Sent To  
Notes
2006-12-06 14:23:05TO "MSIC" BOX#1