Plan Review Details - Permit 06120129
Plan Review Stops For Permit 06120129
Review Stop AD ADDRESSING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2007-04-16 Cont ID  
Sent By lursu Date 2007-04-16 Time 15:01 Rev Time 0.00
Received By lursu Date 2007-04-16 Time 15:01 Sent To  
Notes
2007-04-16 15:05:50THE COPY OF THE RECORDED UNITY OF TITLE FOR THESE THREE
 PARCELS WITH THE CORRECT OWNER INFORMATION MUST BE
 SUBMITTED TO THE ADDRESSING SECTION ( SEE BELOW INFO)
 .
 THE SITE ADDRESS OF THE PROJECT IS ASSIGNED AS 2918
 BROADWAY WITH THE
 PARCEL CONTROL NUMBER = 74 43 43 09 05 021 0100 .
 THE REVISED SITE PLANS AND PERMIT APPLICATIONS MUST
 CONTAIN THE SITE ADDRESS ASSIGNED.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2007-01-17 Cont ID  
Sent By lursu Date 2007-01-17 Time 15:39 Rev Time 0.00
Received By lursu Date 2007-01-17 Time 15:39 Sent To  
Notes
2007-01-17 15:41:22THE UNITY OF TITLE MUST BE RECORDED FOR THESE THREE
 PARCELS INVOLVED IN THIS PROJECT .
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-08-08 Cont ID  
Sent By shill Date 2007-08-08 Time 08:25 Rev Time 0.00
Received By shill Date 2007-07-31 Time 10:38 Sent To  
Notes
2007-08-08 08:26:18****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
 1-8.) ADDRESSED.
  
 9.)FROM 1ST AND 2ND REVIEWS, ADDRESS THE ISSUE OF
 ROOF HEIGHT (36FT8IN SHOWN ON SHEET A5.1 WITH SHINGLE
 ROOF), A7.1 SHOWS TILE, TILE PRODUCT APPROVAL
 SUBMITTED.PLEASE COORDINATE PLANS WITH PRODUCT
 APPROVAL SUBMITTED AND ADDRESS THE HEIGHT LIMITATION
 WITH EITHER ENGINEERING OR ALTERNATE PRODUCT APPROVALS
 IF AVAILABLE.THE ELEVATIONS SUCH AS A5.1 SHOW
 SHINGLES, BUT OVERHANG SOFFIT DETAIL A7.1 SHOWS TILE.
  
 10.)ADDRESSED.
  
 11.)OCCUPANCY (FBC TABLE 302.3.2) AND TENANT (FBC708)
 SEPARATIONS REQUIRED.HORIZONTAL AND VERTICAL
 SEPARATION IS NOT SHOWN BETWEEN THE GARAGE AND LIVING
 SPACE (OCCUPANCY SEPARATION, SEE ALSO FBC406).A 1
 HOUR DOOR WAS ADDED BUT THAT WALL SHOULD ALSO BE NOTED
 ON THE PLAN AS A 1 HOUR WALL. A7.1 SHOWS A 1HOUR
 HORIZONTAL FLOOR/CEILING ASSEMBLY BUT NOTHING ON THE
 PLAN INDICATES WHERE THE 1HOUR IS REQUIRED OTHER THAN
 THE STATEMENT "OCCUPANCY SEPARATION A1.0".PLANS
 SHOULD CLEARLY SHOW ALL REQUIRED FIRE RESISTANCE.
  
 **REVISED 10/24/07**TENANT SEPARATION NOT REQUIRED
 BETWEEN UNIT GARAGE AND COMMON AREA**OCCUPANCY
 SEPARATION IS REQUIRED BETWEEN UNIT AND GARAGE,
 HORIZONTAL AND VERTICAL **
  
 12.)THIS ITEM FROM FIRST REVIEW WAS ADDRESSED WITH A
 NOTE STATING THAT ALL PRODUCTS WILL BE IMPACT ALONG
 WITH IMPACT RATED PRODUCT APPROVALS.SEE A2.1 AND
 OTHER SHEETS, FLOOR PLAN NOTES, ITEM 5, STILL STATES
 THAT HURRICANE SHUTTERS ARE REQUIRED.PLEASE REMOVE
 THE NOTE IF YOU DO NOT INTEND TO INSTALL HURRICANE
 SHUTTERS.SOME DOOR PRODUCT APPROVALS SUBMITTED WERE
 FOR NONIMPACT PRODUCTS.PLEASE SEE FIRST REVIEW IN
 REGARDS TO USE OF REMOVABLE HURRICANE SHUTTERS ON
 COMMERCIAL BUILDINGS.
  
 13.)ADDRESSED.
  
 14.)SEE FBC406, FBC311.3.THE GARAGES AND ACCESS TO
 THE INDIVIDUAL GARAGE SPACES ACT AS A PARKING GARAGE.
 OCCUPANCY SEPARATION REQUIRED FBC302.3.2, BOTH
 HORIZONTAL AND VERTICAL.PENETRATIONS AND DUCTS ARE TO
 BE PROTECTED, FBC716, FBC712.
  
 REQUIRED HORIZONTAL AND VERTICAL SEPARATION IS NOT
 CLEAR ON THE PLAN, SEE OTHER COMMENTS.
  
 A DETAIL IS SHOWN ON A7.1, BUT THIS IS FOR CONCRETE
 FLOOR/WALL, THE GARAGE CEILING/FLOOR ASSEMBLY IS WOOD
 TRUSS.CONFIRM THAT THERE WILL BE NO REQUIREMENT FOR A
 CEILING/FLOOR FIRE RATED PENETRATION DETAIL WITHIN THE
 UNITS.
  
 15.)ADDRESSED.
  
 16.)THE PARKING GARAGE VENTILATION TO BE IN
 COMPLIANCE WITH FLORIDA BUILDING CODE, MECHANICAL AS
 PER FBC406.4.2.THE PLANS SHOW NATURAL VENTILATION FOR
 THE UNIT GARAGES, BUT THIS SHOULD BE TO THE OUTSIDE.
 THE NATURAL VENTILATION IS SHOWN VENTING TO THE PARKING
 GARAGE.NO VENTILATION SHOWN FOR THE ENCLOSED PARKING
 GARAGE AREA ON THE MECHANICAL PLAN.SL1, SITE
 LIGHTING, SHOWS EXHAUST FANS BUT NO FIRE DAMPER AT THE
 1 HOUR FLOOR CEILING ASSEMBLY.NOTE STATES THAT IT IS
 TO BE DESIGNED TO SMB2004 (PLEASE EXPLAIN WHAT THIS IS)
 AND ASHRAE62; DESIGN INTENT NOT CLEAR.IT IS NOT CLEAR
 WHY THIS INFORMATION WOULD BE SHOWN ON THIS SHEET AS
 THE TWO REVIEWERS WHO REQUESTED THIS INFORMATION,
 MECHANICAL AND BUILDING, DO NOT TYPICALLY REIVEW SITE
 LIGHTING, AND IT IS NOT CLEAR HOW MECHANICAL
 VENTILATION IS RELATED TO SITE LIGHTING.PLEASE MOVE
 THIS INFORMATION TO THE APPROPRIATE (MECHANICAL)
 SECTION IN THE PLANS.
  
 17-20.) ADDRESSED.
  
 21.) SEE FIRST REVIEW REGARDING HANDRAIL EXTENSIONS,
 FBC1009.11.5.ALSO SEE STAIR LANDING REQUIREMENTS,
 FBC1009.4, DOOR LANDING REQUIREMENT, FBC1008.1.5,
 FBC1008.1.4.I WAS UNABLE TO LOCATE EXCEPTIONS FOR R2
 OCCUPANCY.
  
 22.)ADDRESSED.HOWEVER, SEE OTHER COMMENTS REGARDING
 OCCUPANCY SEPARATION WHICH WOULD REQUIRE A PROTECTED
 OPENING IN THIS LOCATION (INTERIOR GARAGE DOOR).
  
 23.)FIRST AND SECOND REVIEWS REQUESTED BUILDING AREA
 BY OCCUPANCY TO DETERMINE COMPLIANCE WITH FBC TABLE
 503.A TOTAL SF AREA PER FLOOR WAS PROVIDED AS R2,
 WITH A TOTAL WHICH INCLUDES THE THREE SF AREAS PER
 FLOOR.A FOURTH NUMBER WAS PROVIDED, ABOVE THE TOTAL
 LINE BUT NOT INCLUDED IN THE TOTAL, APPARENTLY TO SHOW
 THAT THE AREA EXCEEDS CODE COMPLIANCE.HOWEVER, FEES
 ARE ASSESSED BASED ON OCCUPANCY DECLARED (AND ARE
 HIGHER FOR THE R2 DECLARED THAN S2).FEES WILL BE
 ASSESSED ON OCCUPANCY DECLARED BY ARCHITECT.EITHER
 REVISE TO SEPARATE R2 AND S2 ON FIRST FLOOR, OR FEES
 WILL BE ASSESSED ON THE HIGHER R2 OCCUPANCY.
  
 IF DESIGNER ELECTS TO KEEP AREA CALCULATIONS AS IS,
 PLEASE MOVE THE S2 NUMBER BELOW THE TOTAL.IT IS NOT
 READILY APPARENT AS TO HOW YOU ARRIVE AT THE TOTAL OF
 66,400 WHEN YOU HAVE FOUR NUMBERS ABOVE IT BUT ARE
 TOTALING ONLY THREE.
  
 AREA INCREASE CALCULATIONS SHOULD GIVE EACH ELEVATION A
 WEIGHTED VALUE.ARCHITECT DECLARES THE EAST ELEVATION
 ON A1.2 AS 20FT, BUT IN THE CALCULATION GIVES IT A
 VALUE OF 30FT.WITH THE WEIGHTED VALUE, ALLOWABLE AREA
 IS 26,600 PER FLOOR FOR R2 (NOT 28,000 PER PLAN A1.2).
 AREAS DECLARED APPEAR CODE COMPLIANT (LESS THAN 26,600
 ALLOWED PER FLOOR) BUT PLEASE REVISE THE CALCULATION.
  
 PLEASE ALSO NOTE THAT ARCHITECT IS DECLARING OPEN SPACE
 OF 20FT ON THE EAST SIDE, BUT SHEET A5.2 STATES THAT
 THERE IS 25FT6IN TO THE PROPERTY LINE.HOW CAN THE
 OPEN SPACE (INCLUDING THE ENTIRE STREET) BE LESS THAN
 DISTANCE TO CENTERLINE OF THE ROAD?PLEASE RESOLVE
 INCONSISTENCIES.
  
 24-29.) ADDRESSED.
  
 29.)STRUCTURAL ELEMENTS ARE TO COMPLY WITH FBC TABLE
 601.SHOW CALCULATED FIRE RESISTANCE OR LISTED
 ASSEMBLY.
  
 2ND REVIEW; 2 HOUR WALL REQUIRED FOR EXTERIOR WALLS,
 BUT THIS IS NOT NOTED ANYWHERE ON THE PLAN OTHER THAN
 THE DETAIL.PLEASE NOTE ON THE SITE PLAN,
 ARCHITECTURAL DETAILS.
  
 3RD REVIEW; PARTIALLY ADDRESSED BY PUTTING A NOTE ON
 SHEET A1.0 AND WAS NOT INCLUDED ON THE SITE PLAN OR
 ARCHITECTURALS.SHEET A1.0 STATES THAT THERE IS A 1
 HOUR OCCUPANCY SEPARATION, BUT NONE SHOWN BETWEEN S2
 AND R2; SEE OTHER COMMENTS.FIRE RESISTANCE IS ALSO
 NOT SHOWN BETWEEN TENANTS, SEE DETAIL B A8.3.SEE
 OTHER COMMENTS; PLEASE CLEARLY SHOW REQUIRED FIRE
 RESISTANCE RATING NOT ONLY TO SHOW CODE COMPLIANCE BUT
 ALSO FOR COORDINATION IN THE FIELD.SEE ALSO ITEM 52.
  
  
 30-44.) ADDRESSED.
  
 45.)S1.0, 3 N GOVERNING CODE HAS BEEN REVISED BUT
 STATES 2006 AMENDMENTS.BASED ON APPLICATION DATE AND
 GOVERNING CODE DECLARED BY ARCHITECT, THIS SHOULD STATE
 2005 AMENDMENTS.2006 AMENDMENTS BECAME EFFECTIVE
 DECEMBER 8, 2006 AND APPLICATION DATE IS DECEMBER 6,
 2006.
  
 46-48.) ADDRESSED.
  
 49.)PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER
 OF RECORD, FBC*106.3.3.
  
 REGARDING THE PRODUCT APPROVALS SUBMITTED:
  
 FL19 IS EXPIRED, FAC9B72, WWW.FLORIDABUILDING.ORG AND
 THE DOORS DO NOT MEET THE WORST CASE PRESSURES ON
 A5.3.
  
 A2.3 DOOR 1 IS SHOWN AS DOUBLE DOORS AND AS OHD, A5.3
 SCHEDULE SHOWS A SINGLE DOOR.CHECK AND CORRELATE ALL
 DOORS.
  
 GLAZED DOUBLE DOOR PRODUCT APPROVAL STAPLED ONTO THE
 BACK OF THE MULLION PRODUCT APPROVAL IS FOR NON IMPACT
 AND DOES NOT MEET WORST CASE PRESSURES.
  
 THE DOUBLE GLAZED (REVIEWED BY DOR) HAVE SPEC SHEETS
 WHICH DO NOT CORRELATE WITH THE PRODUCT YOU INDICATE
 YOU ARE USING.ALSO THE ONE SHEET WHICH SHOWS THAT
 THIS PRODUCT IS IMPACT AND COMPLIANT FOR PRESSURES IS
 DATED 4/28/2005 REVISION, AFTER THE PRINTING OF THE
 EXPIRED PRODUCT APPROVAL 3/11/04.IT APPEARS THAT THE
 PAPERWORK IS NOT FROM THIS PRODUCT APPROVAL.PLEASE
 OBTAIN CURRENT FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 WITH EVALUATION REPORTS AND INSTALLATION INSTRUCTIONS
 WHICH CAN BE VERIFIED ON THE INTERNET. (APPLIES TO ALL
 PRODUCTS)
  
 FL8228 SUBMITTED IS PENDING APPROVAL.
  
 FOR PRODUCTS WITH ONLY A MIAMIDADE SUBMITTED, PROVIDE
 FLORIDA STATE OR LOCAL PRODUCT APPROVAL.
  
 ***REMOVED*** (FOR THE ROLLING DOOR, PROVIDE
 INFORMATION IN REGARDS TO THE FIRE RESISTANCE OF THIS
 DOOR. - NOT REQUIRED 10/24/07)
  
 06-302.03, THE EVALUATION REPORT IS INCOMPLETE.
  
 NO OPAQUE SINGLE DOOR SHOWN ON THE PLAN.PLEASE
 CORRELATE. THE PRODUCT APPROVAL IS FOR NON IMPACT, ALL
 PRODUCTS TO BE IMPACT RATED PER ARCHITECT.
  
 BARREL TILE PRODUCT APPROVAL SUBMITTED.IT IS NOT
 CLEAR IF YOU ARE USING SHINGLES, TILE, OR BOTH.PLANS
 SHOW BOTH IN THE SAME LOCATION. PLEASE REVISE PLAN AND
 SUBMIT REQUIRED PRODUCT APPROVALS.
  
 NEW COMMENTS:
  
 50.)AS YOU ARE NOT USING NFPA13 SYSTEM, PLEASE SHOW
 COMPLIANCE WITH FBC TABLE 1015.1, TRAVEL DISTANCE
 (175FT).YOU MAY SHOW WORST CASE (END UNITS) RATHER
 THAN EACH INDIVIDUAL UNIT.
  
 51.)M3 SHOWS A BALCONY ON THE 2ND FLOOR AT THE
 CORNER, A3.2 SHOWS WINDOW TYPE B.PLEASE COORDINATE.
  
 52.)SHEET M3, A 4INCH DRYER DUCT 2ND FLOOR WAS ADDED.
 THIS IS A 2HR WALL; PLEASE ADDRESS.
  
 53.)IMPACT FEES ARE STAMPED FOR 41,302 SF.THE 2ND
 AND 3RD FLOORS TOTAL 43,189, SO INCLUDING THE LIVING
 PORTION OF THE FIRST FLOOR SHOULD BE GREATER THAN
 43,189.PLEASE CLARIFY WHY IMPACT FEES WERE PAID FOR
 AN AREA LESS THAN SQUARE FOOT AREA DECLARED BY
 ARCHITECT.
  
 53.)SEE ATTACHED FS553.80(2)(B).

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-04-29 Cont ID  
Sent By shill Date 2007-04-29 Time 13:05 Rev Time 0.00
Received By shill Date 2007-04-29 Time 13:05 Sent To  
Notes
2007-04-29 13:47:47****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO
 PERMIT PICKUP, FS713.13.
  
 2.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY
 PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.THE PLANS
 MUST BE STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.PLEASE CALL 561-233-5025 FOR MORE
 INFORMATION.
  
 3.)RADON FEES HAVE BEEN ADDED FS553.721.THIS MAY BE
 ADJUSTED AFTER EXACT BUILDING SIZE IS DETERMINED.
  
 4.) FBC* 109.3.7RESIDENT INSPECTOR. SUBMIT INSPECTOR
 RESUME' AND LICENSE DOCUMENTS TO HAROLD PISKURA,
 DIRECTOR OF THE RESIDENT INSPECTOR PROGRAM.A RESIDENT
 INSPECTOR PROGRAM IS REQUIRED, ON THIS PROJECT, DUE TO
 ONE OR MORE OF THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQFT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN OR METHODS
 OF CONSTRUCTION
  
 ALSO, PLEASE ARRANGE WITH HAROLD PISKURA (INSPECTION
 SERVICES MANAGER - TEL:
 561 805 6711), A MEETING INVOLVING THE OWNER, RESIDENT
 INSPECTOR, JOB INSPECTOR, CONTRACTOR AND ENGINEER. THIS
 MUST BE DONE PRIOR TO PERMIT ISSUANCE.THREE ORIGINAL
 SETS OF ALL DOCUMENTS ARE REQUIRED FOR PERMITTING.
  
 2ND REVIEW ? THREE SETS OF PLANS SUBMITTED, ONLY TWO
 SETS OF SUPPORTING DOCUMENTATION SUBMITTED.THREE SETS
 OF ALL DOCUMENTS REQUIRED, SEE FIRST REVIEW.
  
 5.)ADDRESSED.
  
 6.)ALL INFORMATION REQUIRED BY FAC61G16-23.002 IS
 REQUIRED TO BE ON EACH SHEET SEALED BY THE ENGINEER
 (CERTIFICATE OF AUTHORIZATION).
  
 2ND REVIEW - THIS WAS DONE ON THE PLANS BUT NOT ON THE
 CALCS.
 7-8.)ADDRESSED.
  
 9.)DECLARE MEAN ROOF HEIGHT, FBC CHAPTER 5..NOTE
 THAT THE SHINGLE PRODUCT APPROVAL IS LIMITED TO A MRH
 OF LESS THAN 33 FEET.PLEASE CONTACT ME TO DISCUSS IF
 THIS IS AN ISSUE.
  
 2ND REVIEW ? MRH IS GREATER THAN 33?.SUBMIT COMPLIANT
 PRODUCT APPROVALS.
  
 10.)ADDRESSED.
  
 11.)SHEET A1.0 REFERS TO OCCUPANCY SEPARATION; IS
 THIS REFERRING TO TENANT SEPARATION?
  
 2ND REVIEW ? OCCUPANCY SEPARATION ALSO REQUIRED, AS
 WELL AS EXTERIOR WALL FIRE RATING REQUIREMENT.SEE
 OTHER COMMENTS AND INCLUDE ON A1.0.
  
 12-13.)ADDRESSED.
  
 14.)SEE FBC406, FBC311.3.THE GARAGES AND ACCESS TO
 THE INDIVIDUAL GARAGE SPACES ACT AS A PARKING GARAGE.
 OCCUPANCY SEPARATION REQUIRED FBC302.3.2, BOTH
 HORIZONTAL AND VERTICAL.PENETRATIONS AND DUCTS TO BE
 PROTECTED, FBC716, FBC712.
  
 2ND REVIEW ? THE RESPONSE LETTER STATES THAT ?ALTERNATE
 METHOD? IS TO BE USED.WHAT ALTERNATE METHOD?WHERE
 IN THE CODE IS THIS ALLOWED?THIS COMMENT WAS NOT
 PROPERLY ADDRESSED ON THE PLAN.
  
 15.)ADDRESSED.
  
 16.)THE PARKING GARAGE VENTILATION TO BE IN
 COMPLIANCE WITH FLORIDA BUILDING CODE, MECHANICAL.
  
 16.)NFPA 13 SYSTEM REQUIRED AS PARKING GARAGE IS NOT
 A RESIDENTIAL OCCUPANCY, SEE NFPA 13R 1.1, NFPA 101.
 ALSO SEE FBC504.2, NFPA 13 SYSTEM REQUIRED IF YOU ARE
 USING AREA MODIFICATIONS FOR SPRINKLED BUILDINGS.
  
 2ND REVIEW ? THE RESPONSE LETTER STATES THIS IS NOT
 NEEDED.HOWEVER, NFPA 13 SYSTEM WILL BE REQUIRED IF
 YOU USE SPRINKLERS FOR AREA INCREASES.SEE OTHER
 COMMENTS.
  
 17.)A5.2, DESIGNER HAS NOT PROVIDED CALCULATIONS IN
 REGARDS TO OPENINGS FOR THE REAR ELEVATION FBC704.8.
 NOTE THAT DISTANCE IS TO BE MEASURED TO THE CENTER OF
 THE ALLEY FOR DISTANCE TO ASSUMED PROPERTY LINE.
  
 2ND REVIEW ? NOT PROPERLY ADDRESSED.ARCHITECT STATES
 THAT 75% IS ALLOWED, 26.28% PROVIDED.THIS IS FOR
 PROTECTED OPENINGS.UNPROTECTED OPENINGS ARE LIMITED
 TO 26.28%.DISTANCE TO PROPERTY LINE IS 11?, SHOULD BE
 USING DISTANCE TO ASSUMED PROPERTY LINE WHICH APPEARS
 TO BE APPROX 26?.
  
 RIGHT SIDE ELEVATION, A1.2, APPEARS TO BE 35? TO
 ASSUMED PROPERTY LINE.UNLIMITED OPENINGS ALLOWED.IT
 IS NOT CLEAR WHY YOU HAVE INCLUDED THIS CALCULATION.
  
 18-23.) ADDRESSED.
  
 23.)DECLARE TOTAL BUILDING SIZE.SHOW COMPLIANCE
 WITH FBC TABLE 503.SHOW AREA INCREASE CALCULATIONS ON
 THE PLAN.PLEASE SEE DEFINITION OF BUILDING AREA, TO
 INCLUDE AREA INCLUDED WITHIN THE HORIZONTAL PROJECTION
 OF THE FLOOR ABOVE (FIRST FLOOR AREA COVERED BY
 BALCONIES ON SECOND FLOOR TO BE INCLUDED).DECLARE
 TOTAL SQUARE FOOT AREA FOR EACH OCCUPANCY
 CLASSIFICATION.
  
 2ND REVIEW ? OVERALL DIMENSIONS S1.1 ARE 228?7X104?4,
 WHICH WOULD BE OVER 23,000 SF, BUT YOU DECLARED MUCH
 LESS FOR EACH FLOOR.SEE DEFINITION OF BUILDING AREA,
 FBC 502. ALSO ARCHITECT STATES IN THE CALCULATIONS THAT
 AREA INCREASE IS 28000 SF WITHOUT SPRINKLERS, BUT
 STATES THAT 48,000 IS ALLOWED.AREA INCREASES FOR
 SPRINKLERS REQUIRES NFPA13 SYSTEM, FBC 504.2.
  
 24.)ADDRESSED.
  
 25.)WIND DESIGN CRITERIA ON CALCULATIONS PREPARED BY
 RICARDO DIAZ, PE STATES EXPOSURE C BUT THE CALCULATIONS
 WERE RUN USING EXPOSURE B.SHEET S1.0 ALSO DECLARES
 EXPOSURE B.
  
 2ND REVIEW ? REMOVE OLD SHEETS AND REPLACE WITH NEW
 SHEETS.
  
 26.)CALCULATIONS WERE DONE USING ASCE7-05.SEE
 FBC35, ASCE7-02 IS THE CORRECT STANDARD.
  
 2ND REVIEW ? REMOVE OLD SHEETS AND REPLACE WITH NEW
 SHEETS.
  
 27.)THE AGREEMENT FOR UNITY OF TITLE IS NOT SIGNED BY
 ALL PARTIES AND OWNER ON THE UNITY OF TITLE IS NOT THE
 OWNER OF RECORD (CLERK?S OFFICE).THIS ISSUE IS
 REQUIRED TO BE RESOLVED PRIOR TO PERMIT ISSUANCE.THE
 PROPOSED IMPROVEMENT CROSSES THE PROPERTY LINE WHICH
 WOULD NOT BE ALLOWED WITHOUT A FIREWALL, FBC CHAPTER
 6.
  
 28.)ADDRESSED.
  
 29.)STRUCTURAL ELEMENTS ARE TO COMPLY WITH FBC TABLE
 601.SHOW CALCULATED FIRE RESISTANCE OR LISTED
 ASSEMBLY.
  
 2ND REVIEW ? 2 HOUR WALL REQUIRED FOR EXTERIOR WALLS,
 BUT THIS IS NOT NOTED ANYWHERE ON THE PLAN OTHER THAN
 THE DETAIL.PLEASE NOTE ON THE SITE PLAN,
 ARCHITECTURAL DETAILS.
  
 30-36.) ADDESSED.
  
 37.)PROVIDE A DETAIL FOR U301, A7.1.
  
 2ND REVIEW ? I BELIEVE THIS WAS ADDRESSED, BUT THE NEW
 DETAIL IS NOT LABELED WITH ASSEMBLY NUMBER OR FIRE
 RATING.
  
 38-44.) ADDRESSED.
  
 NEW COMMENTS:
  
 45.)S1.0, 3 N REFERS TO FBC 2001.OTHER ASTM AND ACI
 REFERENCES ARE EXPIRED.CHECK ALL.
  
 46.)THERE ARE THREE CONFLICTS/INCONSISTENCIES BETWEEN
 THE SOILS (WHICH ENGINEER REFERS TO ON S1.0) AND THE
 SOILS ENGINEER RECOMMENDATIONS.THEY ARE AS FOLLOWS:
  
 A. S1.1 SPECS 6ML VAPOR BARRIER, SOILS RECOMMENDS 10ML
 MINIMUM.
  
 B. S5, WF16 IS 16INCH FOOTING, SOILS RECOMMENDS 24INCH
 MINIMUM.THE DESIGN OF COLUMNS ON EITHER SIDE OF THIS
 VERY SHORT FOOTING UNDER THE GARAGE DOOR IS NOTED.
  
 C. ENGINEER REFERS TO THE FOUNDATION CONDITIONS.
 NOWHERE ON THE PLAN DOES IT MENTION THE EXCAVATION
 REQUIREMENT.PLEASE CONFIRM THAT THIS REPORT HAS BEEN
 ADDRESSED.
  
 47.)A1.2, TRASH COMPACTOR GATES SWING OVER THE PUBLIC
 WAY, FBC3202.2.
  
 48.)A5.2, ?LEFT ELEVATION? IS ON THE RIGHT ON A1.
 THE LONG SIDES ARE LABELED ?FRONT? AND ?REAR? BUT BOTH
 HAVE UNIT ENTRANCES AND FACE STREETS.
  
 49.)PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER
 OF RECORD, FBC*106.3.3.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-22 Cont ID  
Sent By shill Date 2007-01-22 Time 15:57 Rev Time 0.00
Received By shill Date 2007-01-17 Time 10:14 Sent To  
Notes
2007-01-22 15:58:50****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO
 PERMIT PICKUP, FS713.13.
  
 2.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY
 PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.THE PLANS
 MUST BE STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.PLEASE CALL 561-233-5025 FOR MORE
 INFORMATION.
  
 3.)RADON FEES HAVE BEEN ADDED FS553.721.THIS MAY BE
 ADJUSTED AFTER EXACT BUILDING SIZE IS DETERMINED.
  
 4.) FBC* 109.3.7RESIDENT INSPECTOR. SUBMIT INSPECTOR
 RESUME' AND LICENSE DOCUMENTS TO HAROLD PISKURA,
 DIRECTOR OF THE RESIDENT INSPECTOR PROGRAM.A RESIDENT
 INSPECTOR PROGRAM IS REQUIRED, ON THIS PROJECT, DUE TO
 ONE OR MORE OF THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQFT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN OR METHODS
 OF CONSTRUCTION
  
 ALSO, PLEASE ARRANGE WITH HAROLD PISKURA (INSPECTION
 SERVICES MANAGER - TEL:
 561 805 6711), A MEETING INVOLVING THE OWNER, RESIDENT
 INSPECTOR, JOB INSPECTOR, CONTRACTOR AND ENGINEER. THIS
 MUST BE DONE PRIOR TO PERMIT ISSUANCE.THREE ORIGINAL
 SETS OF ALL DOCUMENTS ARE REQUIRED FOR PERMITTING.
  
 5.)AS DISCUSSED, ARCHITECT IS TO APPLY FOR
 CERTIFICATE OF AUTHORIZATION FOR DAVID LAWRENCE
 ARCHITECTURE INC., FS481.219(2).THE CORPORATION NAME
 IS NOT TO APPEAR ON DRAWINGS UNTIL APPROVED BY THE
 FLORIDA BOARD OF ARCHITECTS AND AN ARCHITECT BUSINESS
 NUMBER ASSIGNED.IF ARCHITECT BUSINESS NAME IS USED,
 THE COFA NUMBER IS TO APPEAR ON EACH SHEET
 FAC61G1-16.002,003.
  
 6.)ALL INFORMATION REQUIRED BY FAC61G16-23.002 IS
 REQUIRED TO BE ON EACH SHEET SEALED BY THE ENGINEER
 (CERTIFICATE OF AUTHORIZATION).
  
 7.)HYDRAULIC CALCS ARE REQUIRED TO HAVE ALL
 INFORMATION REQUIRED BY FAC61G16-23.002 (TITLE BLOCK
 INFORMATION FOR THE ENGINEER).
  
 8.)SHEET A1.0, PLANS STATE THAT THE BUILDINGS MUST
 COMPLY WITH FBC1606; THIS IS THE SECTION FOR DEAD
 LOADS, NOT WIND LOADS.PLEASE REVISE.
  
 9.)DECLARE MEAN ROOF HEIGHT, FBC CHAPTER 5..NOTE
 THAT THE SHINGLE PRODUCT APPROVAL IS LIMITED TO A MRH
 OF LESS THAN 33 FEET.PLEASE CONTACT ME TO DISCUSS IF
 THIS IS AN ISSUE.
  
 10.)INCLUDE 2005 AMENDMENTS IN GOVERNING CODE.THERE
 WAS A CODE AMENDMENT EFFECTIVE DECEMBER 8, 2006 (PERMIT
 APPLICATION DATE IS PRIOR TO THIS DATE).
  
 11.)SHEET A1.0 REFERS TO OCCUPANCY SEPARATION; IS
 THIS REFERRING TO TENANT SEPARATION?
  
 12.)A2.1 FLOOR PLAN NOTES STATES THAT HURRICANE
 SHUTTERS ARE TO BE INSTALLED.SEE ATTACHED POLICY IN
 REGARDS TO IMPACT PROTECTION ON COMMERCIAL BUILDINGS.
 PRODUCT APPROVALS SUBMITTED ARE FOR LARGE MISSILE
 IMPACT RATED PRODUCTS.PLEASE ADDRESS CONFLICT.IF
 YOUR INTENT IS TO USE SHUTTERS, NOTE THAT REMOVABLE
 SHUTTERS ARE PERMITTED ON THE FIRST FLOOR ONLY AND MUST
 BE APPROVED BY THE BUILDING OFFICIAL.PLEASE CONTACT
 ME IF THIS IS YOUR INTENT.
  
 13.)NOTE THAT THE UNITS ARE CALLED TOWNHOMES.THEY
 DO NOT MEET THE FLORIDA STATUTE DEFINITION OF A
 TOWNHOUSE.THIS COMMENT DOES NOT NEED TO BE
 ADDRESSED; INFORMATIONAL ONLY.OCCUPANCY
 CLASSIFICATION FOR THE RESIDENTIAL AREA IS NOTED AS
 DECLARED, R2.
  
 14.)SEE FBC406, FBC311.3.THE GARAGES AND ACCESS TO
 THE INDIVIDUAL GARAGE SPACES ACT AS A PARKING GARAGE.
 OCCUPANCY SEPARATION REQUIRED FBC302.3.2, BOTH
 HORIZONTAL AND VERTICAL.PENETRATIONS AND DUCTS TO BE
 PROTECTED, FBC716, FBC712.
  
 15.)PROVIDE EGRESS FROM THE PARKING GARAGE AREA ON
 THE FIRST FLOOR.
  
 16.)THE PARKING GARAGE VENTILATION TO BE IN
 COMPLIANCE WITH FLORIDA BUILDING CODE, MECHANICAL.
  
 16.)NFPA 13 SYSTEM REQUIRED AS PARKING GARAGE IS NOT
 A RESIDENTIAL OCCUPANCY, SEE NFPA 13R 1.1, NFPA 101.
 ALSO SEE FBC504.2, NFPA 13 SYSTEM REQUIRED IF YOU ARE
 USING AREA MODIFICATIONS FOR SPRINKLED BUILDINGS.
  
 17.)A5.2, DESIGNER HAS NOT PROVIDED CALCULATIONS IN
 REGARDS TO OPENINGS FOR THE REAR ELEVATION FBC704.8.
 NOTE THAT DISTANCE IS TO BE MEASURED TO THE CENTER OF
 THE ALLEY FOR DISTANCE TO ASSUMED PROPERTY LINE.
  
 18.)A2.1, STAIRS SHOWS "VARIES" FOR TREADS.STAIRS
 ARE TO COMPLY WITH FBC1009.3.1, DIMENSIONAL UNIFORMITY.
 NOTE DESIGN CRITERIA FOR THE STAIRS (RANGE FOR RISER
 HEIGHT) ON THE PLAN.
  
 19.)A2.1, BATHROOM DOOR IS TO HAVE A 29INCH CLEAR
 OPENING, FBC11-11.1(1).
  
 20.)STAIRS ARE TO BE CONSTRUCTED SO THAT WATER WILL
 NOT ACCUMULATE ON THE WALKING SURFACE, FBC1009.5.2
 (ENTRY TO UNITS).
  
 21.)HANDRAIL EXTENSION REQUIRED FOR STAIRS AT UNIT
 ENTRIES, FBC1009.11.5.NOTE THAT THE EXCEPTION STATES
 "WITHIN DWELLING UNITS", THE ENTRY IS OUTSIDE OF THE
 DWELLING UNIT.
  
 22.)FBC13-603.1ABC.1, ADJACENT DOORS SHALL BE SOLID
 CORE, WOOD, OR INSULATED.UNIT C, DOORS 6 AND 9, ARE
 LOCATED IN THE ADJACENT WALL.
  
 23.)DECLARE TOTAL BUILDING SIZE.SHOW COMPLIANCE
 WITH FBC TABLE 503.SHOW AREA INCREASE CALCULATIONS ON
 THE PLAN.PLEASE SEE DEFINITION OF BUILDING AREA, TO
 INCLUDE AREA INCLUDED WITHIN THE HORIZONTAL PROJECTION
 OF THE FLOOR ABOVE (FIRST FLOOR AREA COVERED BY
 BALCONIES ON SECOND FLOOR TO BE INCLUDED).DECLARE
 TOTAL SQUARE FOOT AREA FOR EACH OCCUPANCY
 CLASSIFICATION.
  
  
 24.)ARDAMAN & ASSOCIATESBORING LOCATION PLAN STATES
 THAT THIS IS A TYPE III A FULLY SPRINKLED BUILDING.
 THIS IS IN CONFLICT WITH THE ARCHITECTURAL PLAN.
 BUILDING TYPE IS NOT NECESSARY ON THE SOILS REPORT BUT
 IF PROVIDED MUST BE CONSISTENT WITH THE PLANS.
  
 25.)WIND DESIGN CRITERIA ON CALCULATIONS PREPARED BY
 RICARDO DIAZ, PE STATES EXPOSURE C BUT THE CALCULATIONS
 WERE RUN USING EXPOSURE B.SHEET S1.0 ALSO DECLARES
 EXPOSURE B.
  
 26.)CALCULATIONS WERE DONE USING ASCE7-05.SEE
 FBC35, ASCE7-02 IS THE CORRECT STANDARD.
  
 27.)THE AGREEMENT FOR UNITY OF TITLE IS NOT SIGNED BY
 ALL PARTIES AND OWNER ON THE UNITY OF TITLE IS NOT THE
 OWNER OF RECORD (CLERK?S OFFICE).THIS ISSUE IS
 REQUIRED TO BE RESOLVED PRIOR TO PERMIT ISSUANCE.THE
 PROPOSED IMPROVEMENT CROSSES THE PROPERTY LINE WHICH
 WOULD NOT BE ALLOWED WITHOUT A FIREWALL, FBC CHAPTER
 6.
  
  
 28.)A1.2, THE DISTANCE OF THE BUILDING FROM THE
 PROPERTY LINE IS LESS THAN 30FT (MEASURE TO CENTER LINE
 OF THE ALLEY).ONE HOUR WALL REQUIRED, FBC602. PROVIDE
 A DETAIL.
  
 29.)STRUCTURAL ELEMENTS ARE TO COMPLY WITH FBC TABLE
 601.SHOW CALCULATED FIRE RESISTANCE OR LISTED
 ASSEMBLY.
  
 30.)WINDOW O, HORIZONTAL ROLLER, HAS A DESIGN
 PRESSURE OF -53.72.SEE THE CHART ON SHEET 1 OF 6 OF
 THE PRODUCT APPROVAL, GLASS TYPES A & C ARE NOT
 COMPLIANT FOR THIS SIZE.PLEASE CIRCLE ON THE PRODUCT
 APPROVAL WHICH PRODUCT YOU WILL BE INSTALLING.
  
 31.)SEE SHEET 3 OF 11 OF THE SINGLE HUNG PRODUCT
 APPROVAL.NOT ALL GLASS OPTIONS ARE COMPLIANT FOR
 DESIGN PRESSURES ON A5.3.PLEASE INDICATE WHICH
 PRODUCT YOU WILL INSTALL.
  
 32.)SEE SHEET 5 OF 13 OF THE CASEMENT WINDOW PRODUCT
 APPROVAL.NOT ALL GLASS OPTIONS ARE COMPLIANT FOR
 DESIGN PRESSURES ON A5.3.PLEASE INDICATE WHICH
 PRODUCT YOU WILL INSTALL.
  
 33.)A5.3, ENTRY DOOR 10 IS SHOWN AS 3?0 ON THE DOOR
 SCHEDULE, 2.67 WIDTH ON DOOR PRESSURES.PLEASE
 ADDRESS.
  
 34.)DESIGN PRESSURE REQUIREMENT FOR DOORS 5 AND 6
 EXCEED PRODUCT LIMITATION, SEE THERMATRU PRODUCT
 APPROVAL, SHEET 1.NOTE THAT THE DOOR PRESSURES APPEAR
 TO HAVE BEEN CALCULATED FROM A SINGLE DOOR, BUT CAN BE
 DONE USING THE ENTIRE OPENING (DOUBLE DOOR WITH
 TRANSOM).
  
 35.)THE DOOR PRODUCT APPROVAL SUBMITTED DOES NOT
 INCLUDE THE TRANSOM ABOVE.PLEASE ADDRESS WITH A
 DETAIL AND PRODUCT APPROVALS FOR MULLIONS, FIXED GLASS
 WINDOW OR SUBMIT A PRODUCT APPROVAL WHICH INCLUDES THE
 USE OF A TRANSOM.
  
 36.)A5.3, ENTRY OVERHANG TYPE 1, DOES NOT SHOW THE
 1X2 WHICH IS TYPICALLY INSTALLED UNDER THE DRIP EDGE TO
 PREVENT THE FASCIA BOARD FROM ROTTING.THIS IS SHOWN
 GRAPHICALLY ON ENTRY OVERHANG TYPE 2.YOUR USE OF A PT
 FASCIA IS NOTED; HOWEVER, SINCE A MIAMIDADE NOA WAS
 SUBMITTED FOR THE ROOF SHINGLES, THE SHINGLES ARE TO BE
 INSTALLED IN ACCORDANCE WITH RAS115, RAS111, AND
 FBC1517.6.2.2.PLEASE ADDRESS.
  
 37.)PROVIDE A DETAIL FOR U301, 2 A7.1.
  
 38.)S1.0 REFERS TO DESIGN LOAD REQUIREMENTS FOR ONE
 AND TWO FAMILY DWELLINGS.THIS IS MULTIFAMILY, R2, NOT
 ONE AND TWO FAMILY DWELLINGS, R3.SEE FBC TABLE
 1607.1, 27 RESIDENTIAL AND FBC 310.SEE ALSO
 REQUIREMENTS FOR STAIRS.
  
 39.)S3 SHEATHING NOTES SPECIFIES 4INCH FOR CORNERS ON
 GABLE ENDS.THIS ROOF IS A HIP ROOF, 4 INCH IS
 REQUIRED FOR ZONE 3 REGARDLESS OF ROOF TYPE.
  
 40.)S5 WINDOW NOTES SPECIFICATIONS REFER TO 120 MPH,
 CITY OF WEST PALM BEACH IS IN THE 140MPH WIND ZONE.
  
 41.)FIRE SPRINKLER NOTES REGARDING SPRINKLERS IN
 BATHROOMS IS FOR NFPA13R.THE SYSTEM IS TO COMPLY WITH
 NFPA13.
  
 42.)CIVILS AND ARCHITECTURALS DO NOT MATCH.PLEASE
 ADDRESS.
  
 43.)SIGN THE OWNER/AGENT LINE OF THE ENERGY CALC,
 FBC13-103.1.
  
 44.)IT APPEARS THAT THE GARAGE DOOR BLOCKS THE FIRE
 SPRINKLER HEAD.PLEASE ADDRESS.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-07-07 Cont ID  
Sent By dpalmer Date 2007-07-07 Time 09:45 Rev Time 0.00
Received By dpalmer Date 2007-07-07 Time 08:34 Sent To  
Notes
2007-07-12 16:27:042007-07-12 16:27:04
 THIRD SET RETURNED FROM ZONING. STAMPED ELECTRICAL
 SHEETS IN THIRD SET. STILL NEED TO ADDRESS L SHEETS
 COMMENT.
2007-07-07 09:46:032007-07-07 09:46:03
 ** TEMPORARY FAILED STATUS **
  
 1) NOTE: PLEASE SEE THE LANDSCAPE AND IRRIGATION SHEETS
 NEED TO BE SEALED WITH CORRECT SEAL AS REQUIRED PER FAC
 61G1-16.002.
 PLEASE KNOW A TIME CAN BE SET UP FOR THE LANDSCAPE
 ARCHITECT OF RECORD TO COME IN AND SIGN AND SEAL EACH
 OF THESE SHEETS IN EACH SET.
 ** PLEASE BE SURE TO SEE COMMENTS FROM OTHER TRADES
 (ZONING AND PLUMBING) AS ANY OF THEIR COMMENTS MAY
 AFFECT THE LANDSCAPE AND IR PLANS FOR NEEDED REVISIONS.
 IF THE PLANS NEED TO BE REVISED THERE IS NO NEED TO
 RE-SIGN AND SEAL SHEETS WITH NEW SEAL AT THIS TIME.
 THIS WOULD BE DONE ON NEW REVISED SHEETS.
  
 2) NOTE: PLEASE SEE THAT TWO SETS OF ELECTRICAL AND SL
 PLANS HAVE BEEN STAMPED AND PASSED FOR ELECTRICAL
 REVIEW.
 THE THIRD SET OF E AND SL SHEETS WILL BE STAMPED WHEN
 PLANS ARE BACK FROM ZONING.
  
 3) NOTE: REDLINED ON LOCATION ON PLANS FOR POSSIBLE
 210.52 WALL SPACE TO BE VIF. NO NEED TO CHANGE OR
 REVISE PLANS.
  
  
2007-07-07 08:34:332007-07-07 08:34:33
 IN ELEC FOR REVIEW. TWO SETS ONLY AS ZONING HAS ONE.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-04-14 Cont ID  
Sent By dpalmer Date 2007-04-14 Time 15:54 Rev Time 0.00
Received By dpalmer Date 2007-04-14 Time 12:47 Sent To  
Notes
2007-04-14 15:57:58 
 ** UNSAT2ND REVIEW**
  
 ** PLEASE SEE THAT ITEMS ARE FROM PREVIOUS REVIEW;
 HOWEVER MOST ARE NEW DUE TO CHANGES IN PLANS AND ITEMS
 WHICH ARE NEW TO PLANS SUBMITTED.
 NOW THAT THE CIRCUITING HAS FOR THE MOST PART BEEN
 COMPLETED ON PLANS, THERE ARE SOME NEW COMMENTS BASED
 ON CIRCUITS AS SHOWN.
  
 ** PLEASE KNOW THAT IT IS MOST HELPFUL WHEN A RESPONSE
 LETTER OR COMMENTARY IS SUBMITTED FOR RESPONSE TO THE
 REVIEW COMMENTS AS PREVIOUSLY NOTED. THIS WILL HELP IN
 THE REVIEW PROCESS, HOWEVER NOT REQUIRED.
  
 ** PLEASE SEE ANY REFERENCES IN PLAN REVIEW NOTES TO
 CHAPTER 1 OF THE FBC ARE THAT WHICH IS ADOPTED BY THE
 CITY OF WEST PALM BEACH.
  
 1) NOTE: PLEASE SEE PLANS ARE STILL INDICATING
 TOWNHOUSE UNITS? PLEASE SEE BUILDING REVIEW COMMENTS AS
 THESE ARE NOT TRUE TOWNHOUSES BY DEFINITIONS.
 PLEASE SEE THAT IF THESE ARE INDEED FEE SIMPLE
 "TOWNHOUSES" AS PER FBC DEFINITIONS, PLEASE SEE
 REQUIREMENTS OF THE FBC AND ELECTRICAL CODE WHICH WOULD
 CHANGE MANY ITEMS IN THE DESIGN AND PLEASE KNOW
 SEPARATE PERMIT APPLICATIONS, PLANS AND FEES WOULD BE
 REQUIRED ON EACH FEE SIMPLE TOWNHOUSE. PLEASE SEE AS
 ALL UNITS ARE CONNECTED BY A COMMON AREA AND ONE
 BUILDING THIS DOES NOT SEEM POSSIBLE.
 PLEASE SEE COMMENTS FROM OTHER TRADES
 FBC ADMIN SECTION 106.1.2 FOR ADDITIONAL INFORMATION.
  
 2) NOTE:PLEASE SEE THAT THIS IS THE SAME COMMENT FROM
 PREVIOUS REVIEW AND NO CHANGES HAVE BEEN MADE. PLEASE
 KNOW THAT THIS WAS STATED AS BEING REQUIRED WHETHER OR
 NOT COMMENT IS MADE BY ANY OTHER TRADE.
 PLEASE SEE MISSING INFORMATION ON THE TITLE BLOCKS FOR
 THE LANDSCAPE SHEETS AS REQUIRED PER FLORIDA
 ADMINISTRATIVE CODE 61G1-16.004, AND FLORIDA STATUTES
 481.319.
 PLEASE SEE MISSING CERTIFICATE OF AUTHORIZATION NUMBER,
 PRINTED NAME, PRINTED LICENSE NUMBER ETC.
 PLEASE SEE 481.221 AS PLANS ARE REQUIRED TO BE SIGNED
 WITH LEGAL SIGNATURE AND DATED.
 THIS COMMENT IS REQUIRED WHETHER OR NOT COMMENT IS MADE
 BY ANY OTHER TRADE.
  
 3) NOTE: PLEASE SEE FBC CHAPTER 13.
 PLEASE SEE ANY "HOUSE" ROOMS WITH LIGHTING WILL REQUIRE
 AUTOMATIC SHUT OFF OF LIGHTING PER 13-415.1.ABC.1.1,
 .1.2, AND .1.3. THESE ROOMS ON PLANS DO NOT INDICATE
 ANY LIGHTING? PLEASE CLARIFY.
  
 4) NOTE: PLEASE SEE THAT AS FAR AS THIS REVIEW HAS
 TAKEN PLACE, THIS PREVIOUS NOTE IS STILL APPLICABLE.
 PLEASE SEE FBC ADMIN SECTION 109.3.6, 109.3.6.4.4
 WHICH REQUIRES THE STATEMENT FOR THRESHOLD PROJECTS ON
 ALL ARCH AND ENG SHEETS.
 " TO THE BEST OF THE ARCHITECT'S /OR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER
 633 OF THE FLORIDA STATUTES".
 THIS IS REQUIRED FOR EACH DESIGN PROFESSIONAL ON
 PLANS.
  
 5) NOTE:PLEASE SEE THE NOTES ALSO STATED BY THE
 BUILDING REVIEWER AS PREVIOUSLY NOTED AS IT SEEMS A FA
 SYSTEM OF SOME TYPE IS REQUIRED FOR THE PARKING GARAGE
 AREA. PLEASE KNOW THAT EVEN IF A SYSTEM IS GOING TO BE
 UNDER A SEPARATE PERMIT, THE BASE BUILDING PLANS SHALL
 INDICATE THE BASE INTENT IN DESIGN FOR LIFE SAFETY. FBC
 106.3.5.1.2. PLEASE SEE COMMENTS WITH RESPECT TO SMOKE
 ALARM DEVICES IN UNITS.
  
 PLEASE CLARIFY THE TYPE FIRE PROTECTION BEING INSTALLED
 FOR BUILDING. PLEASE SEE ARCHITECTURAL SHEETS REFERENCE
 A 13R , HOWEVER PLEASE SEE NFPA-72 11-5.1.1, 11.8.3.
 PLEASE SEE NFPA-72 DEFINITIONS AS PLANS CALL FOR SD FOR
 SMOKE DETECTORS THIS IS OK, HOWEVER PLEASE KNOW IF
 THESE ARE INDEED SMOKE DETECTORS AS DEFINED IN NFPA72,
 THESE WOULD BE DEVICES WHICH ONLY DETECT AND WOULD
 SIGNAL TO OTHER ALARM/HORN DEVICES. NO ALARM HORN
 DEVICES ARE SHOWN. PLEASE INDICATE IF PART OF A FUTURE
 LV FA SYSTEM.
  
 6) NOTE: PLEASE SEE THAT THE CIRCUITING IS MISSING FROM
 SEVERAL OF THE SMOKE ALARM DEVICES ON PLANS. PLEASE SEE
 THAT ON THE UNITS WHICH DO INDICATE CIRCUITS, THE PLANS
 INDICATE AS MANY AS 3,4 OR MORE CIRCUITS FOR THE SAME
 SMOKE ALARMS WHICH ARE REQUIRED TO BE WIRED *IN-LINE*
 PER NFPA-72 11.5.1.1.1. PLEASE KNOW AS THESE DEVICES
 ARE WIRED INLINE AND IF ON MORE THAN ONE CIRCUIT AND/OR
 PHASE THIS WOULD SEND 240V TO UNITS AS THEY ARE ALL
 INTERCONNECTED. PLEASE COMPLETE CIRCUITING FOR THE
 DEVICES WHICH ARE MISSING CIRCUITING AND PLEASE ADJUST
 CIRCUITING SO THAT ALL *S* DEVICES ARE WIRED TO THE
 SAME CIRCUIT.
  
 7) NOTE: PLEASE BE SURE THE *S*/SMOKE ALARM DEVICES
 ARE WIRED TO ONE OF THE EXISTING ARC FAULT CIRCUITS AS
 REQUIRED PER 210.12 OF THE NEC. (SOME OF THE CIRCUITS
 AS SHOWN ON SOME OF THE DEVICES AT THIS TIME ARE NOT
 ARC FAULT CIRCUITS AS NOTED ON PANEL SCHEDULE)
 PLEASE INDICATE THE CIRCUITS ON PANEL SCHEDULE WHICH
 WILL CONTAIN THE AFCI BREAKERS. THIS MAY BE DONE WITH
 AN ASTERISK WHICH CORRELATES TO NOTE BELOW PANEL
 SCHEDULE OR BY SOME OTHER MEANS.
 PLEASE SEE NOTE # 17 BELOW AS THIS WAS NOTED ON
 PREVIOUS REVIEW.
  
 8) NOTE:PLEASE SEE THIS NOTE REMAINS AS NO NOTES, OR
 DETAIL WAS PROVIDED TO MEET THIS PREVIOUS NOTE. THE
 SECTION OF CODE GIVEN WAS INCORRECT HOWEVER THE CORRECT
 SECTION WAS GIVEN TO THE ENGINEER OVER A PHONE MEETING
 AFTER THE INITIAL REVIEW.
 PLEASE SEE THE CORRECTED SECTION HAS BEEN INSERTED.
 THE SECTION GIVEN WAS FOR THE DESIGNER TO CERIFY THE
 ENERGY CALCULATIONS WHICH WAS CORRECT ALSO.
 PLEASE SEE FBC 2004 13-606.1.ABC.1.2.4 WHICH REQUIRES
 THE TYPE OF RECESSED LIGHTS TO BE INSTALLED. PLEASE
 NOTE ON PLANS ACCORDINGLY AND INDICATE FIXTURES.
  
 9) NOTE:THIS NOTE WILL REMAIN AS THE NOTE #5 ABOVE IS
 NOT CLEAR AT THIS TIME. THE MINIMUM LEVELS FOR DEVICE
 IN GARAGE AREA WILL BE REQUIRED TO BE INDICATED.
 PLEASE SEE FBC 2004 11-4.28.2, .3(4). PLEASE STATE ALL
 MINIMUM LEVELS AS REQUIRED FOR ALL AREAS WHICH MAY
 CONTAIN ANY FIRE HORN/STROBE DEVICES. AS IT IS NOT
 KNOWN AT THIS TIME OF ANY FIRE ALARM PANEL WILL BE
 REQUIRED FOR THE GARAGE OR BUILDING, PLEASE BE AWARE OF
 THE SECTIONS GIVEN IN ORDER TO INDICATE THE LEVELS AS
 REQUIRED IF A FA SYSTEM IS INSTALLED. 11-4.28.1. PLEASE
 BE SURE TO SEE SECTIONS GIVEN FOR STROBE AND HORN
 DEVICES FROM THE FBC AND PLEASE ALSO SEE NFPA-72.
 PLEASE KNOW THAT THE FBC CHAPTER 11 REQUIREMENTS ARE
 MORE STRINGENT AND THE MORE STRINGENT SHALL APPLY.
  
 10) NOTE: THIS NOTE WILL REMAIN FROM PREVIOUS REVIEW AS
 CONTROLS ETC ARE NOT CLEAR AT THIS TIME OR SHOWN ON
 ELECTRICAL PLANS.
 PLEASE SEE THAT SENSE THIS GARAGE SEEMS TO BE
 CONSIDERED AN ENCLOSED GARAGE PLEASE SEE THAT THERE MAY
 BE OTHER ELECTRICAL DEVICES WHICH MAY BE REQUIRED FOR
 CO SENSORS ETC. TO BE SHOWN AS PART OF ANY LV
 SYSTEMS/DEVICES ETC.
 THIS IS ONLY NOTED.
  
 11) NOTE: PLEASE SEE AS THIS IS ONE BUILDING; PLEASE
 SEE 230.2 AS THE PROPOSED SERVICES ARE NOT GRANTED AS
 SHOWN ON PLANS. PLEASE SEE THE SIZE OF THE SERVICES DO
 NOT EXCEED THE RATINGS FOR 2K AMPS FOR THE ADDITIONAL
 SERVICE.
 PLANS AT THIS TIME ARE SHOWING AS MANY AS FOUR
 SERVICES. PLEASE SEE AT THIS TIME ONLY TWO SERVICES
 WILL BE GRANTED BY SPECIAL PERMISSION. THIS MAY BE DONE
 BY ONE MAIN FOR EACH AND FEEDING A MLO METER*-CENTER OR
 SERVICE WHICH WOULD CONTAIN THE MAIN AS PART OF THE
 METER-CENTER. ONE WILL BE PERMITTED AT EACH SIDE OF THE
 BUILDING AS SHOWN.
 PLEASE SEE THAT SIGNAGE NOTES WILL BE REQUIRED ON PLANS
 FOR CORRECT SIGNS TO BE INSTALLED PER 230.2E. PLEASE
 KNOW THAT ALL SIGNS SHALL HAVE LETTERING A MINIMUM OF
 1INCH WITH A CONTRASTING BACKGROUND.
 PLEASE REVISE SERVICE RISER DIAGRAM FOR GROUPING OF
 MAINS AND SERVICES.
 PLEASE SEE OTHER COMMENTS WITH RESPECT TO LOAD
 CALCULATIONS.
 PLEASE REVISE RISER DIAGRAM.
  
 12) NOTE: PLEASE SEE 250.50, 250.104 ETC FOR MISSING
 ATTACHMENTS FOR THE FIRE SPRINKLER LINE.
  
 13) NOTE:PLEASE SEE AS NEW CIRCUITS ARE NOW SHOWN ON
 PLANS, PLEASE SEE 210.52B1, 210.11C1, AND 220.16 AS THE
 DINING ROOM RECEPTACLES ARE TO BE ON ONE OR MORE OF THE
 SMALL APPLIANCE CIRCUITS. THESE CIRCUITS MUST BE
 FIGURED AT 1500VA MINIMUM (1000VA SHOWN), MAY NOT FEED
 ANY OTHER DEVICES WHICH ARE OUTSIDE THE DINING
 DESIGNATED AREAS.
 PLEASE ALSO SEE SOME PLANS WHICH INDICATE THE DINING
 CIRCUIT AS CIRCUIT #25 DOES NOT SHOW ON PANEL SCHEDULE
 AS THE PANEL SCHEDULE IS SHOWN INDICATING A *SPARE*
 WITH A 1000VALOAD DESIGNATED.
 PLEASE SEE UNIT B, C AND D AS THIS SCENARIO EXIST.
 PLEASE SEE THIS WAS NOTED ON NOTE #25 ON PREVIOUS
 REVIEW.
  
 14) NOTE:PLEASE SEE SOME AREAS OF ROOMS DO NOT SEEM
 TO MEET 210.52 FOR RECEPTACLE SPACING. PLEASE SEE SOME
 UNITS WHICH RAIL AREAS ARE ACTUALLY PART OF THE ROOMS.
 PLEASE ALSO SEE DINING ROOM WALLS WHICH ARE MISSING
 DEVICES. PLEASE SEE UNITS A, B, C AND D.
 NOTE #27 PREVIOUS REVIEW
  
 15) NOTE: PLEASE SEE SOME AREAS WHICH A RECEPTACLE
 DEVICE SEEMS TO BE SHOWN TO MEET 210.52H FOR HALLWAYS,
 YET THIS DEVICE IS ACTUALLY LOCATED IN WHAT WOULD BE AN
 EGRESS PATH AND WOULD CREATE A TRIPPING HAZARD. PLEASE
 SEE PLANS FOR ALTERNATE LOCATIONS WHICH ARE PERHAPS ON
 OPPOSITE WALLS; SOME ARE THE POWDER ROOM WALLS ETC
 WHICH WOULD BE PERMITTED.
 PLEASE SEE SOME REDLINED AREAS ON PLANS. PLEASE KNOW
 THIS CAN BE GONE OVER ON THE PHONE AS LONG AS A SET OF
 PLANS ARE STILL LOCATED IN THIS OFFICE.
 NOTE #27 PREVIOUS REVIEW.
  
 16) NOTE: PLEASE SEE PANELS SCHEDULE FOR ALL UNITS
 WHICH CONTAIN A WHIRLPOOL TUB, HOWEVER THE LOAD
 CALCULATIONS DO NOT INDICATE THIS LOAD OF THIS JACUZZI
 TUB. PLEASE COORDINATE UNIT PANEL SCHEDULE AND REVISED
 LOAD CALCULATIONS.
 FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION.
 NEC 680.71, 408.4.
  
 17) NOTE: PLEASE LIST THE REQUIRED ARC FAULT PROTECTED
 CIRCUITS ON THE PANEL SCHEDULE. PLEASE KNOW THE NOTE ON
 PLANS IS NOT ENOUGH AT THIS TIME. PLEASE SEE THIS CAN
 BE DONE WITH AN * AT EACH CIRCUIT TO THIS NOTE ONCE ALL
 CIRCUITING IS PLACED ON PLANS. PLEASE BE SURE TO SEE
 NOTE PERTAINING TO SMOKE ALARM/DETECTORS DEVICES AND
 WHICH TYPE WILL BE INSTALLED. THIS WILL AFFECT THE
 CIRCUITING AND INDICATION OF THE REQUIRED AFCI
 PROTECTION.
 2002 NEC 210.12
  
 18) NOTE: PLEASE SEE THAT NOW LOAD CALCULATIONS HAVE
 BEEN SUBMITTED, PLEASE SEE NOTES PERTAINING TO
 ADDITIONAL SERVICES. PLEASE SEE THE LOAD SHOWN FOR
 PANEL HP IS SHOWN AS ONE LOAD ON LOAD CALCULATIONS AND
 A DIFFERENT LOAD ON PANEL SCHEDULE.
 PLEASE ALSO SEE THIS PANEL IS BEING SHOWN WITH 42POLES,
 YET THE PANEL SCHEDULE INFORMATION INDICATES ONLY
 30POLES.
 PLEASE CORRELATE THE ABOVE.
 FBC 106.1.2, 106.3.5.1.2
  
 19) NOTE: PLEASE SEE THERE ARE SEVERAL ELECTRICAL
 DEVICES ON PLANS WHICH DO NOT INDICATE ANY CIRCUITING.
 PLEASE SEE MASTER BATH GFI'S UNIT A, COMMON HALLS,
 BEDROOMS ETC FOR UNIT C, AND SOME OTHERS IN OTHER
 UNITS.
 PLEASE SEE NOTE PERTAINING TO CIRCUITING OF SMOKE
 ALARMS, DINING AND OTHER DEVICES.
 408.4, 310.16, 240.4.
 FBC 106.3.1.2, 106.1.2
  
 20) NOTE: PLEASE SEE THIS NOTE FROM PREVIOUS REVIEW.
 PLEASE SEE THE DEVICE HEIGHTS ARE SHOWN , HOWEVER
 INSTALLATION AND NOTES AS THIS IS REQUIRED PER FHAR
 24CFR 100.205 SHOULD BE INDICATE ON PLANS AS THE
 INSTALLATION OF DEVICES FOR OTHER CLEARANCES ETC ARE
 REQUIRED.
 AS NOTED ON PREVIOUS REVIEW*
 PLEASE INDICATE ALL DEVICE HEIGHTS. PLEASE SEE IF THIS
 IS GOING TO BE A MULTI-FAMILY BUILDING AS SHOWN, PLEASE
 SEE FHAR 24CFR100.205 FOR FIRST FLOOR AT A MINIMUM.
 PLEASE KNOW IF ANY VERTICAL ACCESSIBILITY IS INSTALLED,
 THEN THESE DEVICE HEIGHTS AND LOCATIONS SHALL BE FOR
 ALL FLOORS OR FLOORS THAT THE VERTICAL ACCESS IS
 PROVIDED.
 (15INCHES MIN FOR RECEPTS, 48INCHES MAX FOR SWITCHES,
 ETC).
  
 21) NOTE:PLEASE SEE 13-413.1ABC.1 OF THE 2004 FBC.
 PLEASE INDICATE THE VOLTAGE DROP FOR FEEDERS/BRANCH
 CIRCUITS. THIS CAN BE DONE IN A WORST CASE SCENARIO.
 THIS WAS NOT NOTED IN PREVIOUS REVIEW AND IS A NEW
 COMMENT.
  
 22) NOTE: PLEASE SEE SOME SHEETS ARE NOW SHOWING AN
 ADDRESS OF 2918 AND MANY SHEETS IN THE SET DO NOT
 INDICATE ANY ADDRESS OF PROJECT AT ALL.
 PLEASE SEE THE ADDRESSING REVIEWER'S COMMENTS AND
 PLEASE SEE OUR COMPUTER SYSTEM FOR THIS PCN IS STILL
 INDICATING 2900. PLEASE BE SURE NOT TO MAKE ANY CHANGES
 UNTIL THE FINAL ADDRESS HAS BEEN ISSUED BY THE
 ADDRESSING REVIEWER.
 PLEASE SEE THAT THE ADDRESS FOR THIS PROJECT SHALL BE
 PLACED ON THE TITLE BLOCKS. PLEASE KNOW AT THIS TIME,
 THIS IS A MULTI-FAMILY SINGLE BUILDING WITH THE ADDRESS
 OF 2900 BROADWAY.
 THIS IS NOT AND HAS NOT BEEN SUBMITTED AS TOWNHOUSES,
 OR CONDO'S.
 FAC 61G15-23.002, FAC 61G1-16.004
  
 23) NOTE: PLEASE SEE THE HOUSE PANEL INDICATES *ALLEY
 LIGHTS*, YET THESE CIRCUITS AND LIGHTING COULD NOT BE
 LOCATED ON PLANS.
 IF THESE ARE SITE LIGHTING POLES, PLEASE BE SURE TO
 SUBMIT THE REQUIRED WIND LOAD CALCULATIONS AND
 INFORMATION FOR BUILDING REVIEW.
 IF THESE ARE NOT POLES PLEASE INDICATE ON PLANS. ARE
 THE LIGHTS ON BACK OF BUILDING ACTUALLY THES LIGHTS,
 ONLY THE CIRCUITING IS NOT SHOWN??
 PLEASE CLARIFY.
 FBC 106.1.2
  
 24) NOTE: PLEASE SEE THE ATTACHED COPY OF FS
 553.80(2)(B) WITH RESPECT TO REPEAT COMMENTS. THIS IS
 ONLY GIVEN AS A NOTICE AT THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-01-07 Cont ID  
Sent By dpalmer Date 2007-01-07 Time 17:52 Rev Time 0.00
Received By dpalmer Date 2007-01-07 Time 14:00 Sent To  
Notes
2007-01-07 17:52:04** UNSAT **
  
 ** PLEASE SEE THESE ARE COMMENTS BASED ON THE PLANS
 SUBMITTED. PLEASE SEE THAT THERE MAY BE COMMENTS ON THE
 NEXT REVIEW WHICH MAY BE NEW AS SOME INFORMATION AS
 SHOWN ON THESE PLANS WILL BE CHANGING SYSTEMS.
  
 ** PLEASE SEE ANY REFERENCES IN PLAN REVIEW NOTES TO
 CHAPTER 1 OF THE FBC ARE THAT WHICH IS ADOPTED BY THE
 CITY OF WEST PALM BEACH.
  
 1) NOTE: PLEASE SEE PLANS ARE BEING SUBMITTED AND
 LABELED AS TOWNHOUSE UNITS, HOWEVER PLEASE SEE IF THESE
 ARE INDEED FEE SIMPLE "TOWNHOUSES" AS PER FBC
 DEFINITIONS, PLEASE SEE REQUIREMENTS OF THE FBC AND
 ELECTRICAL CODE WHICH WOULD CHANGE MANY ITEMS IN THE
 DESIGN AND PLEASE KNOW SEPARATE PERMIT APPLICATIONS,
 PLANS AND FEES WOULD BE REQUIRED ON EACH FEE SIMPLE
 TOWNHOUSE. PLEASE SEE AS ALL UNITS ARE CONNECTED BY A
 COMMON AREA AND ONE BUILDING THIS DOES NOT SEEM
 POSSIBLE.
 PLEASE KNOW THE PLANS AS SUBMITTED IS FOR ONE BUILDING
 AND PLEASE SEE COMMENTS FOR ELECTRICAL SERVICE(S) AS
 SUBMITTED.
 PLEASE CORRELATE SITE SURVEY PLANS WITH THAT OF THE
 SITE CIVIL PLANS. PLEASE SEE THERE ARE TWO COMPLETELY
 DIFFERENT LAYOUTS FOR THE PROPOSED BUILDING AND SITE.
 TH SITE SURVEY DIFFER FROM THE "A" SHEETS AND OTHER
 PLANS.
 PLEASE SEE COMMENTS FROM OTHER TRADES
 FBC ADMIN SECTION 106.1.2 FOR ADDITIONAL INFORMATION.
  
 2) NOTE: PLEASE SEE MISSING INFORMATION ON THE TITLE
 BLOCKS FOR THE LANDSCAPE SHEETS AS REQUIRED PER FLORIDA
 ADMINISTRATIVE CODE 61G1-16.004, AND FLORIDA STATUTES
 481.219.
 PLEASE SEE MISSING CERTIFICATE OF AUTHORIZATION NUMBER,
 PRINTED NAME, PRINTED LICENSE NUMBER ETC.
 PLEASE SEE 481.221 AS PLANS ARE REQUIRED TO BE SIGNED
 WITH LEGAL SIGNATURE AND DATED.
 THIS COMMENT IS REQUIRED WHETHER OR NOT COMMENT IS MADE
 BY ANY OTHER TRADE.
  
 3) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.1AB.1 FOR
 MISSING ENERGY CALCULATIONS FOR "HOUSE" CONNECTED
 POWER.
 PLEASE ALSO SEE 13-415.2 FOR PERFORMANCE CALCULATIONS
 FOR "HOUSE".
 PLEASE SEE ANY "HOUSE" ROOMS WITH LIGHTING WILL REQUIRE
 AUTOMATIC SHUT OFF OF LIGHTING PER 13-415.1.ABC.1.1,
 .1.2, AND .1.3.
  
 4) NOTE: PLEASE SE POSSIBLE BUILDING REVIEW COMMENTS IF
 THIS BUILDING IS CONSIDERED A THRESHOLD BUILDING OR
 THAT WHICH WILL REQUIRE A SPECIAL INSPECTOR. PLEASE SEE
 FS 553.71(7), FBC ADMIN SECTION 109.3.6 PLEASE KNOW IF
 THIS BUILDING IS EITHER ONE, THREE SETS OF PLANS WILL
 BE REQUIRED FOR PROJECT.
  
 5) NOTE: PLEASE SEE FBC ADMIN SECTION 109.3.6,
 109.3.6.4.4 WHICH REQUIRES THE STATEMENT FOR THRESHOLD
 PROJECTS ON ALL ARCH AND ENG SHEETS.
 " TO THE BEST OF THE ARCHITECT'S /OR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER
 633 OF THE FLORIDA STATUTES".
 THIS IS REQUIRED FOR EACH DESIGN PROFESSIONAL ON
 PLANS.
  
 6) NOTE: PLEASE CLARIFY THE TYPE FIRE PROTECTION BEING
 INSTALLED FOR BUILDING. PLEASE SEE ARCHITECTURAL SHEETS
 REFERENCE A 13R , HOWEVER PLEASE SEE NFPA-72 11-5.1.1,
 11.8.3. PLEASE SEE NFPA-72 DEFINITIONS AS PLANS CALL
 FOR SD FOR SMOKE DETECTORS THIS IS OK, HOWEVER PLEASE
 KNOW IF THESE ARE INDEED SMOKE DETECTORS AS DEFINED IN
 NFPA72, THESE WOULD BE DEVICES WHICH ONLY DETECT AND
 WOULD SIGNAL TO OTHER ALARM/HORN DEVICES. NO ALARM HORN
 DEVICES ARE SHOWN. PLEASE INDICATE IF PART OF A FUTURE
 LV FA SYSTEM.
 PLEASE KNOW AS PER SECTIONS GIVEN IF THESE ARE INDEED
 DEVICES WHICH DETECT AND ALSO SOUND AN ALARM, THEN THEY
 WOULD BE LABELED AS SA FOR SMOKE ALARMS.
 PLEASE KNOW AS OF OCT 06 IT CAME TO OUR ATTENTION AT
 THE SOUTHERN SECTION MEETING FROM NFPA THAT IF UNITS
 ARE INDEED DEVICES WHICH DETECT AND SOUND AN ALARM,
 PLANS SHOULD SHOW THEM AS SA'S AND THIS IS NOT NEW
 CODE. THIS HAS BEEN AN ACCEPTED METHOD IN THE PAST TO
 SHOW SD FOR BOTH HOWEVER ALL PLANS SINCE OCT 06 SHOULD
 BE CHANGING IF AND WHERE APPLICABLE.
 IF PART OF A LV FIRE/SECURITY SYSTEM PLEASE INDICATE AS
 SUCH. PLEASE SHOW DEVICES THEN FOR SOUNDING. PLEASE
 ALSO SEE MISSING SMOKE DETECTION/ SMOKE ALARM DEVICE IN
 UNIT "C" FIRST FLOOR.
  
 7) NOTE: PLEASE SEE FBC 2004 13-103.1.1.1 WHICH
 REQUIRES THE TYPE OF RECESSED LIGHTS TO BE INSTALLED.
 PLEASE NOTE ON PLANS ACCORDINGLY AND INDICATE
 FIXTURES.
  
 13) NOTE: PLEASE SEE FBC 2004 11-4.28.2, .3(4). PLEASE
 STATE ALL MINIMUM LEVELS AS REQUIRED FOR ALL AREAS
 WHICH MAY CONTAIN ANY FIRE HORN/STROBE DEVICES. AS IT
 IS NOT KNOWN AT THIS TIME OF ANY FIRE ALARM PANEL WILL
 BE REQUIRED FOR THE GARAGE OR BUILDING, PLEASE BE AWARE
 OF THE SECTIONS GIVEN IN ORDER TO INDICATE THE LEVELS
 AS REQUIRED IF A FA SYSTEM IS INSTALLED. 11-4.28.1
 PLEASE BE SURE TO SEE SECTIONS GIVEN FOR STROBE AND
 HORN DEVICES FROM THE FBC AND PLEASE ALSO SEE NFPA-72.
 PLEASE KNOW THAT THE FBC CHAPTER 11 REQUIREMENTS ARE
 MORE STRINGENT AND THE MORE STRINGENT SHALL APPLY.
  
 8) NOTE: PLEASE BE SURE PLANS REFLECT THE CODES IN
 WHICH THE DESIGN IS UNDER AND PERMITTED UNDER. PLEASE
 LIST THE FOLLOWING AT A MINIMUM FOR ELECTRICAL SHEETS
 AND ARCHITECTURAL SHEETS.
 2002 NFPA-70 (NEC), 2002-NFPA-72 NATIONAL FIRE ALARM
 CODE AND 2003 NFPA-101 LIFE SAFETY CODE.
 ** PLEASE KNOW FOR INFORMATIONAL PURPOSE, AS OF
 DECEMBER 8TH, 2006 THE STATE OF FLORIDA ADOPTED THE
 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70(
 NEC). AS THIS PROJECT WAS SUBMITTED FOR PERMIT BEFORE
 THIS DATE, THIS PROJECT IS UNDER THE PREVIOUS CODES AS
 STATED ABOVE. (NOTED FOR INFORMATION ONLY)
  
 9) NOTE: PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR ALL
 EGRESS PATHS UNDER NORMAL LIGHTING LEVELS AND UNDER
 EMERGENCY LIGHTING LEVELS TO THE PUBLIC RIGHT OF WAY
 OUT AND AWAY FROM BUILDING.
 PLEASE SEE NFPA-101 7.8 AND 7.9 AS BATTERY BACK UP
 LIGHTS OF SOME KIND WILL BE REQUIRED FOR EGRESS OUT OF
 THE GARAGE AREA.
 PLEASE SEE 700.12E FOR CIRCUITING .
 FBC 106.1.2 ADMIN SECTION.
 REVIEW FOR COMPLIANCE OF THIS CAN NOT BE DONE AT THIS
 TIME.
  
 10) NOTE: PLEASE PROVIDE MORE INFORMATION FOR FAIL SAFE
 OPERATION OF THE ELECTRICAL GATES AS SHOWN ON PLANS.
 PLANS NOTE IN MANY LOCATIONS THAT THE GATES SHALL
 AUTOMATICALLY OPEN IN THE EVENT OF POWER FAILURE;
 HOWEVER THERE ARE TWO SCENARIOS WHICH NEED TO BE
 ADDRESSED.
 A) PLEASE INDICATE HOW GATES WILL OPEN UNDER POWER
 FAILURE. (BATTERY BACK UP? ETC)
 B) PLEASE KNOW THAT IN AN EMERGENCY AND POWER IS STILL
 ON, THE OCCUPANTS SHALL BE ABLE TO EGRESS FROM THIS
 AREA OF THE STRUCTURE WITHOUT ANY IMPEDANCE FROM
 DEVICES WHICH MAY FAIL OR DELAY EGRESS IN ANY FASHION.
 PLEASE SEE NFPA-101 7.2, MORE SPECIFICALLY: 7.2.1.5.1
 DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM THE
 EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
  
 7.2.1.5.2 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR
 OPERATION FROM THE EGRESS SIDE.
 THERE ARE NUMEROUS OTHER CODE SECTIONS, HOWEVER ONLY
 NOTED A COUPLE.
 PLEASE SEE REVIEW NOTES FROM THE FIRE MARSHAL AND
 BUILDING REVIEWER WHICH MAY ALSO ADDRESS THIS COMMENT.
 PLEASE KNOW THAT MORE INFORMATION IS REQUIRED FOR THIS
 WHETHER OR NOT COMMENT IS MADE SPECIFICALLY BY OTHER
 TRADES.
 THIS WILL AFFECT THE ELECTRICAL PLANS AND ALONG WITH
 NOTES ON POSSIBLE "A" SHEETS.
  
 11) NOTE: PLEASE SEE THAT SENSE THIS GARAGE SEEMS TO BE
 CONSIDERED AN ENCLOSED GARAGE PLEASE SEE THAT THERE MAY
 BE OTHER ELECTRICAL DEVICES WHICH MAY BE REQUIRED FOR
 CO SENSORS ETC. TO BE SHOWN AS PART OF ANY LV
 SYSTEMS/DEVICES ETC.
 THIS IS ONLY NOTED.
  
 12) NOTE: PLEASE SEE AS THIS IS ONE BUILDING; PLEASE
 SEE 230.2 AS THE PROPOSED SERVICES ARE NOT GRANTED AS
 SHOWN ON PLANS. PLEASE REVISE SERVICE RISER DIAGRAM FOR
 GROUPING OF MAINS AND SERVICES.
 PLEASE SEE PLANS DO NOT CORRELATE WITH RISER AT THIS
 TIME; PLEASE SEE EACH UNIT SHOWS AN ELECTRICAL METER AT
 EACH UNIT WHICH IS NOT PERMITTED.
 PLEASE SEE OTHER COMMENTS WITH RESPECT TO LOAD
 CALCULATIONS.
 PLEASE REVISE RISER DIAGRAM.
  
 13) NOTE: PLEASE SEE 250.50, 250.104 ETC FOR MISSING
 ATTACHMENTS FOR THE FOOTER STEEL AND FIRE SPRINKLER
 LINES.
  
 14) NOTE: PLEASE SHOW ALL ROOMS AND AREA DESIGNATIONS
 ON PLANS. PLEASE COMPLETE ALL CIRCUITING ON PLANS AND
 CORRELATE WITH THE PANEL SCHEDULES SUBMITTED. PLEASE
 SEE THERE ARE SOME ITEMS WHICH CAN NOT BE REVIEWED FOR
 CODE COMPLIANCE AT THIS TIME DUE TO THIS INFORMATION
 NOT SHOWN.
 NEC 408.4, 310.16, 240.4 ETC.
 FBC 106.1.2, 106.3.5.1.2 ADMIN SECTIONS.
  
 15) NOTE: PLEASE SUBMIT PANEL SCHEDULES SPECIFIC TO
 EACH UNIT. THESE CAN NOT BE TYPICAL FOR A, B AND D AS
 SUBMITTED AS SOME OF THESE UNITS DO NOT CONTAIN
 ELECTRICAL APPLIANCES AS NOTED ON PANEL SCHEDULE(S) AND
 SOME UNITS DO NOT CONTAIN THE SAME ELECTRICAL POWER
 REQUIREMENTS FOR THE FOLLOWING LISTED IN NOTES TO COME.
 PLEASE KNOW ALL CIRCUITING AND IDENTIFICATION ON PANELS
 NEEDS TO BE SPECIFIC TO ROOMS AND AREAS IN WHICH THEY
 FEED.
 IE: LIVING RM LTS,BEDRM RECEPTS , DINING RM, ETC.
 408.4, 310.16,
 FBC 106.1.2, 106.3.5.1.2
  
 16) NOTE: PLEASE SEE MECHANICAL PLANS WHICH INDICATE
 LOADS FOR THE AHU WITH LESS OF A LOAD THAN THAT SHOWN
 ON THE PANEL SCHEDULES AND LOAD CALCULATIONS
 SUBMITTED.
 PLEASE CORRELATE ALL OVER CURRENT PROTECTION DEVICES
 WITH EACH. AS NOTED ABOVE IN NOTE #15, EACH PANEL SHALL
 BE SPECIFIC AS THE CU'S CONTAIN DIFFERENT OVER CURRENT
 PROTECTION FOR EACH UNIT. PLEASE ALSO SEE THE OVER
 PROTECTION FOR BOTH THE AHU'S AND THE CU'S SHALL
 CORRELATE WITH THE PANEL SCHEDULES.
 424.3B, 240.4, 310.16 ETC.
  
 17) NOTE: PLEASE SEE PANELS SCHEDULE FOR ALL UNITS
 INDICATE A WHIRLPOOL TUB, HOWEVER THE PLANS DO NOT SHOW
 THE SAME OR CONTAIN ELECTRICAL GFI'S AT THE TUB
 LOCATIONS?
 PLEASE CORRELATE EACH UNIT WITH PANEL SCHEDULE TO BE
 SUBMITTED FOR EACH UNIT.
 FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION.
 NEC 680.71
  
 18) NOTE: PLEASE SEE THE LOAD SHOWN ON THE PANEL
 SCHEDULE FOR THE GARAGE DOOR OPENER DOES NOT CORRELATE
 WITH THE LOAD CALCULATIONS. PLEASE CORRELATE. 408.4,
 220.31
  
 19) NOTE: PLEASE SEE BOTH THE DISHWASHER AND DISPOSAL
 ARE BEING FED TO THE SAME RECEPTACLE DEVICE/YOKE WHICH
 IS OK AND A TYPICAL INSTALLATION; HOWEVER PLEASE SEE
 210.4(A)&(B) AS THESE SHALL BE FED FROM THE SAME
 BREAKER WHICH WOULD BE A 2-POLE BREAKER. NO HANDLE TIES
 ARE PERMITTED. THE OTHER SCENARIO WOULD BE TO INSTALL
 TWO INDIVIDUAL SINGLE RECEPTACLES.
 PLEASE VERIFY THIS AS THE LOADS SHOWN FOR EACH UNIT
 SEEM TO EXCEED THAT OF A STANDARD 15A RATED DEVICE.
 MUST BE 20A RATED. PLEASE VERIFY 210.21(B)(2) AND
 (B)(3).
  
 20) NOTE: PLEASE LIST THE REQUIRED ARC FAULT PROTECTED
 CIRCUITS ON THE PANEL SCHEDULE. PLEASE KNOW THE NOTE ON
 PLANS IS NOT ENOUGH AT THIS TIME. PLEASE SEE THIS CAN
 BE DONE WITH AN * AT EACH CIRCUIT TO THIS NOTE ONCE ALL
 CIRCUITING IS PLACED ON PLANS. PLEASE BE SURE TO SEE
 NOTE PERTAINING TO SMOKE ALARM/DETECTORS DEVICES AND
 WHICH TYPE WILL BE INSTALLED. THIS WILL AFFECT THE
 CIRCUITING AND INDICATION OF THE REQUIRED AFCI
 PROTECTION.
 2002 NEC 210.12
  
 21) NOTE: PLEASE SEE PLANS CONTAIN A NOTE THAT STATE
 ALL EXTERIOR LIGHT FIXTURES SHALL BE RATED FOR "DAMP
 LOCATION"?? PLEASE KNOW THAT ANY FIXTURES OUTSIDE SHALL
 BE LISTED FOR "WET LOCATIONS".
 110.3, 90.4
  
 22) NOTE: PLEASE SEE MISSING THE REQUIRED GFI FOR SOME
 CONDENSING UNITS PER 210.63, 210.8A3 (UNIT "C").
  
 23) NOTE: PLEASE SEE SUBMIT COMPLETE LOAD CALCULATIONS
 FOR SERVICE. 220..3, 220.10, 220.11, 220.13 AND 220.32
 ETC
 PLEASE KNOW DEPENDING ON THE NEW SERVICE AND LOAD,
 CONSIDERATION OF 230.2 WILL BE REVIEWED, HOWEVER PLEASE
 KNOW AT THIS TIME THE FOUR SERVICES AS SHOWN WILL NOT
 BE GRANTED IN EITHER CASE AND ANY SERVICES GRANTED FOR
 THIS SINGLE BUILDING WILL STILL REQUIRE MAINS TO BE
 GROUPED AS PREVIOUSLY NOTED ABOVE.
  
 24) NOTE: PLEASE SEE 210.52D FOR UNIT "A" MASTER BATH
 WHICH WILL REQUIRE THE ADDITION OF ONE ADDITIONAL GFI
 RECEPT OR MOVE THE ONE SHOWN BETWEEN THE TWO LAVATORIES
 AS SHOWN. PLEASE KNOW THE CROSSING OVER A SINK/LAVATORY
 IS NOT PERMITTED IN ORDER TO PLUG IN ANY APPLIANCE FOR
 USE.
  
 25) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.16 OR
 DINING ROOMS AND AREAS OF THE LIKE. AS NOTED ABOVE,
 REVIEW FOR CIRCUITING OF THIS AREA CAN NOT BE DONE AT
 THIS TIME.
  
 26) NOTE: PLEASE INDICATE ALL DEVICE HEIGHTS. PLEASE
 SEE IF THIS IS GOING TO BE A MULTI-FAMILY BUILDING AS
 SHOWN, PLEASE SEE FHAR 24CFR100.205 FOR FIRST FLOOR AT
 A MINIMUM. PLEASE KNOW IF ANY VERTICAL ACCESSIBILITY IS
 INSTALLED, THEN THESE DEVICE HEIGHTS AND LOCATIONS
 SHALL BE FOR ALL FLOORS OR FLOORS THAT THE VERTICAL
 ACCESS IS PROVIDED.
 (15INCHES MIN FOR RECEPTS, 48INCHES MAX FOR SWITCHES,
 ETC).
  
 27) NOTE: PLEASE SEE 210.52 FOR AREAS FOR REQUIRED
 RECEPTS WHICH ARE MISSING ON PLANS. PLEASE SEE UNIT "C"
 ETC.
 PLEASE ALSO SEE OTHER AREAS PER 210.52H FOR HALLWAYS
 WHICH MAY HAVE A WALL SPACE 10FT OR MORE.
 ** PLEASE KNOW ANY ROOMS WHICH CONTAIN RAILINGS MAY BE
 REQUIRED TO CONTAIN RECEPTACLES ALONG THESE RAILINGS AS
 RAILS ARE CONSIDERED WALL SPACE.
 PLEASE SEE ONE SET OF PLANS ARE REDLINED FOR LOCATIONS
 WHICH ARE MISSING DEVICES WITHIN 6FT OF DOOR, 2FT OR
 MORE OF WALL SPACE AND HALLWAYS AS NOTED.
  
 28) NOTE: PLEASE SEE SOME DEVICES WHICH APPEAR TO BE
 3-WAY; DO NOT CONTAIN THE SWITCH WITH THE 3-WAY
 DESIGNATION. PLEASE VERIFY ALL. (UNIT "C").
  
 29) NOTE: SEE SOME UNITS SHOW WHAT APPEARS TO BE A
 STACK WASHER DRYER, HOWEVER NOTATION FOR SUCH ON PLANS
 AND PANEL SCHEDULES COULD NOT BE FOUND.
 PLEASE LIST. 408.4.
 FBC 106.1.2
  
 30) NOTE: PLEASE CORRELATE THE LOADS FOR THE RANGE.
 PANEL SCHEDULE SHOWS 10KW AND THE LOAD CALCULATIONS
 INDICATE 10KW?
 310.16, 408.4, 240.4, 220.19
  
 31) NOTE: PLEASE SEE LIGHT AND RECEPT ON THE "C" UNITS
 2ND FLOOR WHICH SEEMS TO BE LOCATED TOO FAR OVER AND
 PAST THE RAIL AREA OR NEXT BUILDING LOCATION.
 IF THE GFI IS THAT FOR THE CU AS NOTED IN NOTE #22
 ABOVE, DISREGARD NOTE #22 AND RELOCATE.
  
 32) NOTE: PLEASE COMPLETE RISER DIAGRAM WITH ALL
 FEEDERS TO UNITS AND CORRELATE WITH THE OVER CURRENT
 PROTECTION DEVICES OF THAT FOR EACH UNIT.
 215.5, 310.16, 240.4 ETC.
 FBC 106.1.2, 106.3.5.1.2
  
 33) NOTE: PLEASE INDICATE THE EQUIPMENT GROUNDING
 CONDUCTORS FROM MAINS TO EACH UNIT PER 250.122.
 250.24B, 250.110, ETC.
  
 34) NOTE: PLEASE SEE THAT THE ADDRESS FOR THIS PROJECT
 SHALL BE PLACED ON THE TITLE BLOCKS. PLEASE KNOW AT
 THIS TIME, THIS IS A MULTI-FAMILY SINGLE BUILDING WITH
 THE ADDRESS OF 2900 BROADWAY.
 THIS IS NOT AND HAS NOT BEEN SUBMITTED AS TOWNHOUSES,
 OR CONDO'S.
 FAC 61G15-23.002, FAC 61G1-16.004
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-01-07 14:00:56IN ELEC FOR REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2007-08-08 Cont ID  
Sent By rchokshi Date 2007-08-08 Time 13:25 Rev Time 0.00
Received By rchokshi Date 2007-08-08 Time 13:25 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2007-04-20 Cont ID  
Sent By rchokshi Date 2007-04-20 Time 14:21 Rev Time 0.00
Received By rchokshi Date 2007-04-20 Time 13:47 Sent To  
Notes
2007-04-20 14:21:35PLEASE PROVIDE FOLLOWING INFO:
  
 1. PLEASE SHOW STANDARDS NOTES OF CITY OF WPB ON
 DRAWINGSFOR SIDEWALK WIDTH , ITS SLOPE, DRIVEWAY,
 PARKING, HANDICAP PARKING, PAINTPER CITY CODES ETC.,,
 MUST MEET PER ADA,,ETC.,
 2. DUMPSTER: IN YOUR RESPOSE LETTER( YOU DO NOT HAVE
 THE DATE ON THE LETTER), YOU SAID "SEE SITE PLAN SHEET
 A2.1" WE CAN NOT FIND IT ON SHEET A2.1.SO,PLEASE
 SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE DETAILS PER
 CITY OF WPB, &LOCATION ON DWG, LOCATION MUST BE
 ACCESSIBLE FOR PICKUP TRUCK.
 3. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD ,
 SIDEWALK ELEVATION MUST MEET FL BLDG CODE, PLEASE SHOW
 ON THE DRAWINGS & SHOW CALCULATION USING WHICH FLOOD
 ZONE, 100 YEAR FOOD, 25 YEAR FLOOD, ETC, ETC. .
 4. PLEASE SHOW CALCULATION FOR LENGTH OF THE
 EXFILTRATION TRENCH.
 5.PLEASE SHOW STORM WATER QUALITY CALCULATIONS, WHAT
 CRITERIA YOU ASSUMEDFOR RUNOFF CAL.,, LIKE 1" OVER
 ENTIRE SITE OR2.5"CRITERIA, ?PERVIOUS AREA, LIKE
 GREEN, LAKES, ETC,IMPERVIOUS AREA CAL.,
 6.PLEASE SHOW ON DRAWINGS:WHAT IS THE SITE
 AREA,PERVIOUS/IMPERVIOUS AREAS.GREEN, LAKE AREA ETC
 YOU ARE DEVELOPING FOR THIS PROJECT ONLY ?
 7. HOW YOU CONNECT TO THE STORM WATER PIPES IN YOUR
 SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER PIPES
 AROUND YOUR SITE SO, WE CANSEE THE BEST PIPE TO
 CONNECT WITH THE STORM WATERFROM ALL OTHER STORM
 WATER PIPES. PLEASE SHOW DETAIL OF THE CONTROL
 STRUCTURES WITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC CALS OF EXFILTRATION TRENCH LENGTH?
 8. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED.
 9. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN. NOT CLEAR FROM YOUR
 RESPONSE. MAY BE YOU WANT TO SHOW IN THE GENERAL SITE
 PLAN.
  
 PLEASE RESPOND EACH ITEM IN DETAIL IN A MEMO & ON
 DRAWINGS WITH REVISIONS TO EXPEDITE YOUR PERMITTING
 PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-01-26 Cont ID  
Sent By rchokshi Date 2007-01-26 Time 09:35 Rev Time 0.00
Received By rchokshi Date 2007-01-26 Time 09:12 Sent To  
Notes
2007-01-26 09:34:51PLEASE PROVIDE FOLLOWING INFO:
  
 1. PLEASE SHOW STANDARDS NOTES OF CITY OF WPB ON
 DRAWINGSFOR SIDEWALK WIDTH , ITS SLOPE, DRIVEWAY,
 PARKING, HANDICAP PARKING, PAINTPER CITY CODES ETC.,,
 MUST MEET PER ADA,,ETC.,
 2. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 3. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD ,
 SIDEWALK ELEVATION MUST MEET FL BLDG CODE, PLEASE SHOW
 ON THE DRAWINGS.
 4. PLEASE PROVIDE A COPY OF SFWMD PERMIT,GEOTECH
 REPORT
 5.PLEASE SHOW STORM WATER CALCULATIONS, WHAT CRITERIA
 YOU ASSUMEDFOR RUNOFF CAL.,, LIKE 1" OVER ENTIRE SITE
 OR2.5"CRITERIA, ?PERVIOUS AREA, LIKE GREEN,
 LAKES, ETC,IMPERVIOUS AREA CAL.,
 6. WHAT IS THE SITE AREA, YOU ARE DEVELOPING FOR THIS
 PROJECT ONLY ? SO, WE CAN CHECK PERVIOUS, IMPERVIOUS
 CAL.
 7. HOW YOU CONNECT TO THE STORM WATER PIPES IN YOUR
 SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER PIPES
 AROUND YOUR SITE SO, WE CANSEE THE BEST PIPE TO
 CONNECT WITH THE STORM WATERFROM ALL OTHER STORM
 WATER PIPES. PLEASE SHOW DETAIL OF THE CONTROL
 STRUCTURES WITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC CALS OF EXFILTRATION TRENCH LENGTH?
 8. POLLUTION PREVENTION DETAILS,CLOTHES USED FOR SILT
 ETC., PLANS SHOWING SILT FENCE AROUND THE SITE
 9. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED
 10. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN.
  
 PLEASE RESPOND EACH ITEM IN DETAIL IN A MEMO & ON
 DRAWINGS WITH REVISIONS TO EXPEDITE YOUR PERMITTING
 PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-08-09 Cont ID  
Sent By mawillia Date 2007-08-09 Time 15:22 Rev Time 0.00
Received By mawillia Date 2007-08-09 Time 14:46 Sent To  
Notes
2007-08-09 15:19:42*****PROVISO*****
  
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED;HOWEVER THE APPROPIATE PLAN SHEETS TO
 BE FIRE-STAMPED WHEN ALL PLAN REVIEWERS HAVE BEEN
 SATISFIED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-05-01 Cont ID  
Sent By mawillia Date 2007-05-01 Time 19:14 Rev Time 0.00
Received By mawillia Date 2007-05-01 Time 18:33 Sent To  
Notes
2007-05-01 19:09:07*****UNSAT*****
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
  
  
 08.INDICATE THE LOCATION OF THE FIRE HYDRANT(S) IN
 THE VICINITY OF THE SITE.BE ADVISED THAT IF THE
 HYDRANT(S) IS GREATER THAN 500 FEET, AN ADDITIONAL
 HYDRANT SHALL BE REQUIRED.UNABLE TO VERIFY HYRANTS,
 DUE TO THE SMALLNESS OF THE FIRE HYDRANT VICINITY MAP.
 PLEASE SHOW NEAREST HYDRANTS ON PLAN SHEET WITH THE
 DISTANCE TO THE PROPERTY
  
 10.IN ADDITION TO THE EXTERIOR ELEVATION DETAILS ON
 SHEET A5.1 AND A5.2, SPECIFY ELEVATIONS AS NORTH, EAST,
 WEST, AND SOUTH.ON SHEET STILL UNCLEAR AS TO REAR,
 LEFT, AND RIGHT ELEVATION
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-02-09 Cont ID  
Sent By mawillia Date 2007-02-09 Time 15:34 Rev Time 0.00
Received By mawillia Date 2007-02-09 Time 15:19 Sent To  
Notes
2007-02-09 16:29:33*****DENIED*****
  
  
 01.THE COMPLETE AND/OR ACTUAL ADDRESS OF THE PROJECT
 SITE SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED PLAN
 SHEET.
  
 02.NFPA 101-2003 EDITION AND THE FLORIDA FIRE
 PREVENTION CODE SHALL BE REFERENCED.
  
 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 04.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL
 NOT HINDER OR INTERFERE WITH EMERGENCY ACCESS RESPONSE
 TO THE SAID PROPERTY OR VICINITY THEREOF (INCLUDING
 FIRE HYDRANTS AND FIRE LANES).
  
 05.ALL PAVEMENT ROAD SYSTEMS SHALL BE CAPABLE OF
 SUPPORTING 32 TONS FOR FIRE APPARATUS/EQUIPMENT.
  
 06. FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN
 UNOBSTRUCTED WIDTH OF NOT LESS THAN 20 FEET AND AN
 UNOBSTRUCTED VERTICAL CLEARANCE OF NOT LESS THAN 13
 FEET 6 INCHES.
  
 07.LANDSCAPING SHALL NOT OBSTRUCT OR INTERFERE WITH
 FIRE PROTECTION EQUIPMENT.PROPER CLEARANCES SHALL BE
 MAINTAINED AT ALL TIMES.
  
 08.INDICATE THE LOCATION OF THE FIRE HYDRANT(S) IN
 THE VICINITY OF THE SITE.BE ADVISED THAT IF THE
 HYDRANT(S) IS GREATER THAN 500 FEET, AN ADDITIONAL
 HYDRANT SHALL BE REQUIRED.
  
 09.ON THE APPROPIATE EXTERIOR ELEVATION, SHOW/DISPLAY
 THE NUMERICAL ADDRESS FOR THE BUILDINGS TO BE VISIBLE
 FROM BROADWAY AVENUE.ONCE EMERGENCY RESPONDERS ARE
 INSIDE OF THE COMPLEX, HOW ARE BUILDINGS DISTINGUISHED
 FROM EACH OTHER.
  
 10.IN ADDITION TO THE EXTERIOR ELEVATION DETAILS ON
 SHEET A5.2 AND A5.2, SPECIFY ELEVATIONS AS NORTH, EAST,
 WEST, AND SOUTH.
  
 11.PLEASE INDICATE IF THIS BUILDING WILL BE EQUIPPED
 WITH A FIRE ALARM SYSTEM.BE ADVISED THAT SMOKE
 DETECTORS, AS LEGENDED ON SHEET E-1, ARE TIED INTO A
 FIRE ALARM SYSTEM.SMOKE ALARMS ON THE OTHER HAND ARE
 NOT TIED INTO A FIRE ALARM SYSTEM.
  
 12.ON SHEET FS-6, PLEASE BE ADVISED THAT A 2 1/2"
 SINGLE INLET FIRE DEPARTMENT CONNECTION W/CHECK VALVE
 WILL BE REQUIRED.
  
 13.ON SHEET FS-6, THE FIRE SPRINKLER SYSTEM IS TO BE
 MONITORED.IT SHALL BE PROVIDED WITH AN APPROVED ALARM
 INITIATION DEVICE THAT OPERATES WHEN THE FLOW OF WATER
 IS EQUAL OR GREATER THAN THAT FROM A SINGLE AUTOMATIC
 SPRINKLER.
  
 14.IN REFERENCE TO THE HYDRAULIC CALCULATIONS THAT
 WERE SUBMITTED:3RD FLOOR UNIT-A SYSTEM 4, 3RD FLOOR
 UNIT-B SYSTEM 1, 3RD FLOOR UNIT-C SYSTEM 2, ALL SHOW AN
 UNACCEPTABLE SAFETY MARGIN.AS PER WPBFR, A SAFETY
 MARGIN OF AT LEAST 5.0 PSI IS REQUIRED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-06-20 Cont ID  
Sent By adarroug Date 2007-06-20 Time 10:55 Rev Time 0.00
Received By adarroug Date 2007-06-20 Time 10:55 Sent To  
Notes
2007-07-05 13:04:117/5/07--PLANS WERE TAKEN FROM REVIEW AND BROUGHT IN
 TODAY(SEE FRONT SCREEN NOTES) TO "COMM" BD#29/PLANS ON
 RACK--4 ROLLS AND PAPERWORK
2007-06-20 10:55:48WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-24 Cont ID  
Sent By adarroug Date 2007-03-24 Time 17:11 Rev Time 0.00
Received By adarroug Date 2007-03-24 Time 17:10 Sent To  
Notes
2007-03-24 17:11:12TO "COMM" BD#38

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-09 Cont ID  
Sent By mawillia Date 2007-02-09 Time 15:17 Rev Time 0.00
Received By mawillia Date 2006-12-06 Time 11:08 Sent To  
Notes
2007-01-03 07:44:55TO COMM BOAR #43, 1/3 DVP
2006-12-06 11:08:45WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-08-01 Cont ID  
Sent By rregueir Date 2007-08-01 Time 19:56 Rev Time 0.00
Received By rregueir Date 2007-08-01 Time 15:32 Sent To  
Notes
2007-08-01 19:56:083RD REVIEW: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. OK
  
 2. OK
  
 3. A) NATURAL VENTILATION IS NOT AN AVAILABLE OPTION IN
 THIS APPLICATION. FBC,M 402.1 REQUIRES OPENINGS TO THE
 OUTDOORS. THE DWELLING UNIT GARAGE DOORS OPEN TO AN
 ENCLOSED PARKING GARAGE AREA WHICH DOES NOT QUALIFY AS
 OUTDOORS.
  
 B) THE VENTILATION REQUIREMENTS FOR GARAGES, SEPARATE
 FOR EACH DWELLING UNIT, IN ACCORDANCE WITH TABLE 403.3,
 IS 100 CFM PER CAR. IN THIS CASE, EACH GARAGE WOULD
 REQUIRE 200 CFM OF OUTDOOR AIR. THE COMMON GARAGE AREA
 WILL REQUIRE 1.5 CFM PER SQ.FT OF FLOOR AREA.
 RECIRCULATION OF AIR FROM THIS SPACE IS PROHIBITED PER
 FBC,M TABLE 403.3 NOTE (B). AS SUCH, THE INDIVIDUAL
 DWELLING UNIT GARAGES ARE REQUIRED TO COMMUNICATE
 DIRECTLY WITH THE OUTDOORS FOR THEIR REQUIRED 200 CFM
 OF OUTDOOR AIR.
  
 C) THE COMMON GARAGE AREA VENTILATION SYSTEM MAY RUN
 INTERMITTENTLY IF IT IS DESIGNED IN ACCORDANCE WITH
 FBC,M SEC. 404.
  
 4. THIS COMMENT IS NOW ENCOMPASSED IN COMMENT #3.
  
 5. OK
  
 6. OK
  
 7. THE BALANCED RETURN EXCEPTIONS TO FBC,M 601.4 STILL
 HAVE NOT BEEN MET. NOTE THAT UNDER EXCEPTION #3 ALL
 SUPPLY INTO THE MASTER SUITE SHALL BE INCLUDED.
 EXAMPLE: UNIT A MASTER SUITE ISFED BY A 10X8 DUCT WHICH
 IS 80 SQ.IN. A 10" FLEX (RETURN JUMPER AS SOWN ON PLAN)
 IS 78.5 SQ.IN. IT IS SMALLER THAN THE SUPPLY WHEN THE
 EXCEPTION REQUIRES IT TO BE 1 1/2 TIMES LARGER THAN THE
 SUPPLY. IN ADDITION, THE RETURN FROM THE MASTER AND
 BEDROOM 2 IS BEING CARRIED BY ONE 10X10 DUCT, WHICH IS
 100 SQ.IN. WITH 80 SQ.IN. SUPPL FEEDING THE MASTER AND
 50 SQ.IN. FEEDING BEDROOM 2 (8" ROUND SUPPLY), THAT IS
 A TOTAL OF 130 SQ.IN. OF SUPPLY BEING RETURNED BY A 100
 SQ. IN. JUMPER. THIS DOES NOT QUALIFY AS BALANCED
 RETURN EVEN IF THE EXCEPTIONS TO 601.4 ARE NOT CLAIMED.
 PROVIDE BALANCED RETURN FROM ALL HABITABLE ROOMS AS
 REQUIRED BY FBC,M 601.4.
  
 COMMENTS 8 THROUGH 10 ARE OK.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-04-21 Cont ID  
Sent By rregueir Date 2007-04-21 Time 13:40 Rev Time 0.00
Received By rregueir Date 2007-04-21 Time 11:17 Sent To  
Notes
2007-04-21 13:39:27-------2ND REVIEW: DENIED--------
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PERVIOUS COMMENTS FOR THE PURPOSE OF CONTINUITY.
  
 1. OK
  
 2. OK
  
 3. PLEASE SHOW MEANS OF MECHANICAL EXHAUST FOR GARAGE
 ON MECHANICAL PLANS. FBC,M 403.3, FBC 106.1.1
  
 4. OK PENDING RESPONSE TO COOMENT #3.
  
 5. IF YOU CHOOSE TO LEAVE THESE NOTES ON PLAN, THOSE
 ELEMENTS WILL BE REQUIRED TO BE INSTALLED AT ROUGH
 INSPECTION. CONSULT MANUFACTURER'S INSTALLATION
 ISTRUCTIONS TO SEE IF ANOTHER METHOD OF VIBRATION
 ISOLATION IS AVAILABLE.
  
 6. OK
  
 7. THIS ISSUE WAS NOT ADDRESSED. IF RETURN TRANSFERS
 ARE NOT REDESIGNED TO MEET THE EXCEPTIONS UNDER FBC,M
 601.4, A FIELD TEST WILL BE REQUIRED AT FINAL
 INSPECTION TO DETERMINE IF BALANCED RETURN HAS BEEN
 ACHIEVED WITH A PRESSURE DIFFERENTIAL OF 0.01" WC OR
 LESS.
  
 8. OK
  
 9. OK
  
 10. (A) PER DETAIL ON M-5, IS IT THE INTENT OF THE
 DESIGNER TO HAVE A COMBINATION OF 4" ROUND, 10X3 AND
 6X3 ROOF JACKS? DETAIL INDICATES SIZE OF ROOF JACK IS
 TO MATCH SIZE OF EXHAUST DUCT GOING TO ROOF.
 (B) THIS TYPE OF ROOF JACK WILL NOT WORK FOR DRYER
 EXHAUST. SCREENS ARE PROHIBITED AND BACKDRAFT DAMPER IS
 REQUIRED PER FBC,M 504.4. PROVIDE DETAIL FOR DRYER
 EXHAUST TERMINATION IN ACCORDANCE WITH THIS SECTION.
 (C) PG M-3: CLOTHES DRYERS ARE TO BE EXHAUSTED IN
 ACCORDANCE WITH DRYER MANUFACTURER'S INSTALLATION
 INSTRUCTIONS PER FBC,M 504.1. VERIFY WITH INSTRUCTIONS
 THAT 6X3 DUCT IS AN ACCEPTABLE ALTERNATIVE TO 4" ROUND
 DUCT AND THAT SQUARE 90 DEGREE ELBOWS ARE ACCEPTABLE IN
 LEIU OF 4" ROUND RADIUS 90 DEGREE ELBOWS. PROVIDE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS TO SHOW
 COMPLIANCE IF THIS TYPE OF DUCT IS TO BE USED.
  
  
 REVIEWED BY:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-03-12 Cont ID  
Sent By rregueir Date 2007-01-25 Time 14:22 Rev Time 0.00
Received By rregueir Date 2007-01-23 Time 14:17 Sent To  
Notes
2007-01-29 14:27:34----------------DENIED-----------------
  
 1.PAGE M1, UNIT A 3RD FLOOR: PLAN SHOWS WASHER/DRYER IN
 CLOSET WITH AIR HANDLER. CLOTHES WASHERS, CLOTHES
 DRYERS SHALL NOT BE LOCATED IN MECHANICAL CLOSETS USED
 AS RETURN AIR PLENUMS PER FBC SEC. 13-610.1.ABC.3.7
  
 2.PAGE M1, UNIT A 3RD FLOOR: PLAN SHOWS 10X3 EXHAUST
 DUCT IN A/C CLOSET. FOR PURPOSES OF CONTAMINATION
 PREVENTION, EXHAUST DUCTS UNDER POSITIVE PRESSURE SHALL
 NOT EXTEND INTO OR PASS THROUGH DUCTS OR PLENUMS PER
 FBC,M 601.3
  
 3.GARAGE EXHAUST FANS ARE CALLED FOR ON EF SCHEDULE.
 FANS ALONG WITH DUCTS AND DISCHARGE LOCATIONS ARE NOT
 SHOWN ON MECHANICAL PLAN.
  
 4.FAN SCHEDULE SHOWS EF 3 (GARAGE) TO BE CONTROLLED BY
 A TIME CLOCK. THIS FAN SHOULD RUN CONTINUOUS PER FBC,M
 T403.3
  
 5.FAN SCHEDULE: NOTES 1,2 DO NOT USUALLY APPLY TO
 'RESIDENTIAL' TYPE CEILING MOUNTED EXHAUST FANS. IS THE
 INTENT TO HAVE THESE ITEMS INSTALLED ON BATHROOM
 EXHAUST FANS?
  
 6.FAN SCHEDULE SHOWS THREE DIFFERENT FAN TYPES. FANS
 ARE NOT IDENTIFIED BY TYPE ON MECHANICAL PLANS. PLEASE
 INDICATE ON PLAN WHICH TYPE OF FAN GOES IN EACH
 LOCATION.
  
 7.FBC,M 601.4 REQUIRES BALANCED RETURN IN ALL HABITABLE
 ROOMS. A PRESSURE DIFFERENTIAL OF .01" WC OR LESS IS
 REQUIRED UNLESS RETURNS ARE DESIGNED TO MEET THE
 EXCEPTIONS AS STATED IN THIS SECTION. IF RETURNS ARE
 NOT DESIGNED TO THESE EXCEPTIONS, A FIELD TEST WILL BE
 REQUIRED AT FINAL INSPECTION TO DETERMINE IF PRESSURE
 DIFFERENTIAL IS CODE COMPLIANT.
  
 8.HVAC SPECIFICATIONS NOTE # 19 CITES 2001 FBC(M) TABLE
 403.3. PLEASE REFERENCE 2004 FBC(M). ALSO TABLE 403.3
 DOES NOT RELATE TO CONDENSATE OVERFLOW PROTECTION.
 PLEASE CLARIFY (307.2.3 RELATES TO CONDENSATE
 DISPOSAL/OVERFLOW PROTECTION)
  
 9.HVAC SPECIFICATIONS NOTE #24 INDICATES FRESH AIR
 DAMPERS TO BE CONTROLLED BY T-STAT. AHU SCHEDULE STATES
 MECHANICAL FRESH AIR IS NOT REQUIRED. PLEASE CLARIFY.
  
 10. PLEASE PROVIDE DETAIL SHOWING BATH AND DRYER
 EXHAUST TERMINATIONS AT ROOF.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL OR EMAIL:
 RONALD J REGUEIRO
 561-805-6734
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-07-18 Cont ID  
Sent By kstevens Date 2007-07-18 Time 07:26 Rev Time 0.00
Received By kstevens Date 2007-07-18 Time 07:25 Sent To  
Notes
2007-07-18 11:16:59DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
 ********FROM PREVIOUS REVIEWS:********
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
 9. OK
 10. OK
 11. OK
 12. OK
 13. OK
 14. OK
 15. OK
  
 16. SHTS IR-1, LP-1 & LP-2 LANDSCAPE ARCHITECT LICENSE
 IS NULL & VOID PER DBPR WESITE. (SEE ATTACHED SHEET).
 ONE SET OF SHEETS SHALL BE RETAINED FOR POSSIBLE REVIEW
 BY THE STATE LANDSCAPE ARCHITECTURAL BOARD AS THIS SEAL
 HAS BEEN NULL & VOID SINCE 11/30/95.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE SEAL USED IS NOT
 APPROVED. PER FAC 61G1-16.002 THE SEAL SHALL BE 2" IN
 DIAMETER. PLEASE RESEAL THE PLANS.
  
 17. OK
 18. OK
  
 ***********NEW COMMENTS***********
  
 1B. OK
 2B. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-05-02 Cont ID  
Sent By kstevens Date 2007-05-02 Time 17:17 Rev Time 0.00
Received By kstevens Date 2007-05-02 Time 17:17 Sent To  
Notes
2007-05-02 17:57:03DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. ALL ARCHITECTURAL SHEETS. THE FIRM LICENSE NUMBER,
 (CERTIFICATE OF AUTHORIZATION), IS REQUIRED IN THE
 TITLE BLOCK OF EACH SHEET. FAC 61G1-16.004(2) & FS
 481.219, 481.2055.
 ****NO RESPONSE, NOT ADDRESSED.
  
 2. SHT A3.4 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS. SHOW THE SQUARE FOOTAGE OF EACH
 AREA AS WELL AS 1/2 AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS. ALSO INDICATE ANY AREA OF A ROOF
 THAT DRAINS FROM ABOVE IF APPLICABLE. SECTIONS 1106 &
 1107 WITH ALL SUBSECTIONS.
 ****NO RESPONSE, NOT ADDRESSED.
  
 3. SHT A3.4 DETAIL 4, SECONDARY DRAINS SHALL BE A
 MINIMUM 2" HIGHER THAN THE MAIN DRAIN. AS SHOWN THEY
 ARE ONLY ABOUT 3/4" ABOVE THE MAIN DRAINS. THIS IS
 REQUIRED SO THAT THE SECONDARY DRAINS WILL NOT DRAIN
 STORM WATER UNLESS THERE IS A BLOCKAGE IN THE PRIMARY
 DRAINS.--SUBMIT A DETAIL SHOWING THE ELEVATION AT
 THE FLOOR AT THE PATIO DOOR, AND INDICATE THE ELEVATION
 OF THE PRIMARY DRAIN AND THE SECONDARY DRAIN. SECTION
 106.1.1.
 ****NO RESPONSE, NOT ADDRESSED.
  
 4. SHT A3.5 SHOWS 6" OVERFLOW DRAINS CONNECTING TO
 MANHOLES. SECTION 1107.2 REQUIRES THE DISCHARGE TO BE
 ABOVE GRADE IN AN OBSERVABLE LOCATION. PLEASE CHANGE
 TERMINATION POINT FOR THE OVERFLOW DRAINS.--ONE 7"
 DOWNSPOUT DOES NOT SHOW THE PIPING TO THE MANHOLE.
 PLEASE SHOW ALL PIPING. SECTION 106.1.1.
 ****NO RESPONSE, NOT ADDRESSED.
  
 5. SHTS A4.1 & A5.1. SHT A4.1 SHOWS THE GUTTER TO BE
 CONTINUOUS AROUND THE INSIDE OF THE BLDG ROOF EXCEPT AT
 THE CHIMNEYS. SHT A5.1 ONLY SHOWS THE GUTTER AT THE
 MAIN ROOF SECTIONS, AND NO GUTTER AT THE HIP ROOF
 SECTIONS. ALSO NO DOWNSPOUTS ARE INDICATED AT THE HIP
 ROOF SECTIONS. PLEASE CLARIFY. SECTION 106.1.1. ****NO
 RESPONSE, NOT ADDRESSED.
  
 6. OK
  
 7. SHT P-1 THE SANITARY PARTIAL RISER DIAGRAMS DO NOT
 REFLECT THE FLOOR PLAN IN MANY INSTANCES. ALL OFFSETS
 SHALL BE SHOWN ON THE RISER DIAGRAM, SOME EXTRA PIPING
 IS SHOWN, SOME FIXTURE BRANCH LINES ARE NOT SHOWN.--
 THE AUTOMATIC CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR A DRAINAGE STACK A MINIMUM
 OF 3" IN DIAMETER. SECTION 406.3.-- SEE RED LINE
 NOTES ON ONE SET OF PLUMBING PLANS. SECTION 106.1.1.
 ****NO RESPONSE. PARTAL RISER 2ND FLOOR DOES NOT
 REFLECT THE NEW FLOOR PLAN, NOR DOES THE 3RD FLOORM/B
 TUB. SEE RED LINE CORRECTIONS.--SHOW ALL VENT
 PIPING AND WATER PIPING ON THE FLOOR PLAN TO REFLECT
 THE RISER DIAGRAMS. VENT OFFSETS ARE NOT SHOWN ON THE
 FLOOR PLAN.--THE WATER RISER DIAGRAM DOES NOT SHOW
 THE WATER PIPING & WATER HAMMER ARRESTOR FOR THE REF.
 WITH ICE MAKER NOR IS IT SHOWN ON THE FLOOR PLAN.
  
 8. SHT P-2 THE SANITARY PARTIAL RISER DIAGRAMS DO NOT
 REFLECT THE FLOOR PLAN IN MANY INSTANCES. ALL OFFSETS
 SHALL BE SHOWN ON THE RISER DIAGRAM, SOME EXTRA PIPING
 IS SHOWN, SOME FIXTURE BRANCH LINES ARE NOT SHOWN, THE
 VENT & SANT LINES ARE CROSSED FROM FLOOR TO FLOOR.--
 THE AUTOMATIC CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR A DRAINAGE STACK A MINIMUM
 OF 3" IN DIAMETER. SECTION 406.3.-- SEE RED LINE
 NOTES ON ONE SET OF PLUMBING PLANS. SECTION 106.1.1.
 ****NO RESPONSE. OFFSET FROM THE POWDER ROOM TO BATH #2
 IS NOT SHOWN ON THE FLOOR PLAN, AND THE RISER INDICATES
 THE RISER GOING IN THE WRONG DIRECTION.--RISERS
 FROM THE 1ST FLOOR BY BATH#3 TO THE 2ND FLOOR BY THE
 POWDER ROOM ARE CROSSED.--PARTIAL RISER TO BATH #2
 DOES NOT REFLECT THE FLOOR PLAN.--THE WATER LINE &
 WATER HAMMER ARRESTOR TO THE ICE MAKER IN THE REF IS
 NOT SHOWN ON THE WATER RISER NOR ON THE FLOOR PLAN.--
 SHOW ALL VENT OFFSETS AND WATER PIPING ON THE FLOOR
 PLAN.
  
 9. SHT P-3 THE SANITARY PARTIAL RISER DIAGRAMS DO NOT
 REFLECT THE FLOOR PLAN IN MANY INSTANCES. ALL OFFSETS
 SHALL BE SHOWN ON THE RISER DIAGRAM, SOME EXTRA PIPING
 IS SHOWN, SOME FIXTURE BRANCH LINES ARE NOT SHOWN, BATH
 2 INDICATES A TUB ON THE RISER, BUT SHOWS A SHOWER ON
 THE FLOOR PLAN. THE KITCHEN SHOWS A 3" TO THE 3RD
 FLOOR. PLEASE INDICATE WHERE THIS LINE IS TERMINATING.
 --THE AUTOMATIC CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR A DRAINAGE STACK A MINIMUM
 OF 3" IN DIAMETER. SECTION 406.3.-- SEE RED LINE
 NOTES ON ONE SET OF PLUMBING PLANS. SECTION 106.1.1.
 ****NO RESPONSE. PARTIAL RISERS FOR THE 3RD FLOOR NEED
 TO IDENTIFY VENTS WHEN REVENTING FROM ONE RISER TO
 ANOTHER.--NO WATER LINE OR WATER HAMMER ARRESTOR
 FOR THE ICE MAKER IN THE REF SHOWN ON THE RISER NOR ON
 THE FLOOR PLAN.--PARTIAL WATER TO THE DISH WASHER
 SHOW COLD WATER SUPPLY. HOT WATER REQUIRED.--SHOW
 VENTS AND WATER SUPPLY PIPING ON THE FLOOR PLAN.
  
 10. SHT P-4 THE SANITARY PARTIAL RISER DIAGRAMS DO NOT
 REFLECT THE FLOOR PLAN IN MANY INSTANCES. ALL OFFSETS
 SHALL BE SHOWN ON THE RISER DIAGRAM, SOME EXTRA PIPING
 IS SHOWN, SOME FIXTURE BRANCH LINES ARE NOT SHOWN. THE
 VENT FROM THE FIRST FLOOR, BATHROOM 3 IS NOT SHOWN ON
 THE FLOOR PLAN OF THE SECOND FLOOR. --THE
 AUTOMATIC CLOTHES WASHER FIXTURE DRAIN SHALL CONNECT TO
 A BRANCH DRAIN OR A DRAINAGE STACK A MINIMUM OF 3" IN
 DIAMETER. SECTION 406.3.-- SEE RED LINE NOTES ON ONE
 SET OF PLUMBING PLANS. SECTION 106.1.1.
 ****NO RESPONSE. OFFSETS OF THE VENTS ARE NOT SHOWN ON
 THE FLOOR PLAN.--IDENTIFY WHERE ALL REVENT PIPING
 IS CONNECTING TO.--MASTER BATH RISER DOES NOT
 REFLECT THE FLOOR PLAN.--PARTIAL WATER RISER 2ND
 FLOOR DOES NOT REFLECT THE FLOOR PLAN.--1ST FLOOR
 PIPING SHOWS EXTRA UNDERGROUND PIPING. PLEASE CLARIFY.
 --SHOW ALL VENT PIPING & WATER PIPING ON THE FLOOR
 PLAN.--IDENTIFY THE RISER THAT THE W/M AND M/BATH
 CONNECT TO ON THE FLOOR PLAN 2ND FLOOR.
  
 11. SUBMIT A WATER RISER DIAGRAM FOR EACH TYPE OF UNIT.
 SHOW ALL PIPE SIZES, VALVES AND WATER HAMMER ARRESTORS
 REQUIRED BY SECTION 604.9. (ICE MAKERS, DISHWASHERS, &
 WASH MACHINES). SECTION 106.3.5.1.3(3)(13).
 ****NO PIPING SHOWN ON THE FLOOR PLAN OR RISER DIAGRAMS
 FOR THE ICE MAKERS IN THE REF'S.
  
 12. SUBMIT A STORM RISER DIAGRAM FOR THE PRIMARY
 DRAINAGE AND SECONDARY DRAINAGE SYSTEMS. SHOW ALL PIPE
 SIZES, OFFSETS, AND INDICATE SQUARE FOOTAGE BEING
 DRAINED.SECTION 106.3.5.1.3(7)(13).
 ****NO RESPONSE, NOT ADDRESSED.
  
 13. OK.
  
 14. SHT P-5 WATER HEATER DETAIL. PLEASE INDICATE THE
 TERMINATION POINT FOR THE EMERGNECY PAN DRAIN AND THE
 T/P RELIEF DISCHARGE LINE. SECTIONS 504.6.1 & 504.7.2.
 ****MORE INFORMATION IS REQUIRED ON THE DETAIL. IT
 SHOWS A 4" HOUSE KEEPING PAD, THE THE DRAIN LINES
 APPEAR TO DROP DOWN TO THE GARAGE FLOOR. PLEASE
 INDICATE HOW THIS WILL COMPLY WITH THE CODE SECTIONS
 FOR THESE LINES TO BE 6" ABOVE GRADE AND NOT HAVE ANY
 TRAPPED SECTIONS PER SECTIONS 504.6.1 & 504.7.2. SUBMIT
 AN ISOMETRIC FOR EACH TYPICAL P/T & PAN DRAIN LINE.
  
 15. SHT IR-1 THE CONTROLLER AND THE RAIN SENSOR LOCTION
 ARE REQUIRED ON THE PLAN. SECTION 106.1.1.--THE
 BACKFLOW PREVENTOR SHALL BE INSTALLED BYA LICENCED
 PLUMBING CONTRACTOR.--A SEPARATE IRRIGATION PERMIT
 IS REQUIRED. SECTION 105.1.
 ****NO RESPONSE, NOT ADDRESSED.
  
 16. SHTS IR-1, LP-1 & LP-2 LANDSCAPE ARCHITECT LICENSE
 IS NULL & VOID PER DBPR WESITE. (SEE ATTACHED SHEET).
 ONE SET OF SHEETS SHALL BE RETAINED FOR POSSIBLE REVIEW
 BY THE STATE LANDSCAPE ARCHITECTURAL BOARD AS THIS SEAL
 HAS BEEN NULL & VOID SINCE 11/30/95.
 ****NO RESPONSE, NOT ADDRESSED.
  
 17. SHTS IR-1, LP-1 & LP-2THE LANDSCAPE FIRM LICENSE
 NUMBER AS WELL AS THE PRINTED NAME OF THE PERSON
 SEALING THE DOCUMENT SHALL BE IN THE TITLE BLOCK OF
 EACH SHEET. FAC 61G1-16.004(2)(6) & FS 481.2055. ****NO
 RESPONSE, NOT ADDRESSED.
  
  
 18. THE MANHOLES, TRENCH DRAINS, STORM DRAINS AND
 RELATED PIPING SHALL BE DESIGNED BY THE BUILDING
 ENGINEER, AND INSTALLED BY THE PLUMBING CONTRACTOR AS
 THIS IS WITHIN THE FOOTPRINT OF THE BUILDING. THE CIVIL
 ENGINEER, AND THE SITE CONTRACTOR CAN ONLY DESIGN AND
 INSTALL UP TO FIVE FEET OF THE BUILDING STRUCTURE. FS
 489.
 (INFORMATIONAL)
  
 ***********NEW COMMENTS***********
  
 1B. SHTS LP-1, LP-2 & IR-1 THE LANDSCAPE FIRM LICENSE
 NUMBER PER FLA STATE DBPR WEBSITE IN IN APPLICANT
 STATUS. (SEE ATTACHED SHEET). AS SUCH THESE PLANS CAN
 NOT BE APPROVED.--WHEN APPROVED SHEETS ARE
 SUBMITTED, THE DATE THE SEAL AND SIGNATURE OF THE
 LANDSCAPE ARCHITECT ARE AFFIXED TO THE PLANS, THE DATE
 SHALL BE ALSO AFFIXED BELOW THE SIGNATURE. FAC
 61G1-16.004(5) & FS 481.2055.
  
 2B. COMPLETE RISERS FROM THE HORIZONTAL BUILDING
 ISOMETRIC DIAGRAM TO THE VTRSHALL BE SUBMITTED AS
 PARTIAL RISER DIAGRAMS ARE HARD TO FOLLOW AND NOT ALL
 INFORMATION REQUIRED ON THE PARTIAL RISERS IS BEING
 SUBMITTED SUCH AS OFFSETS, VENTING, REVENTING ETC.
 SECTION 106.3.5.1.3. THE RISER DIAGRAMS SHALL REFLECT
 THE PIPING ON THE FLOOR PLAN. SECTION 106.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-02-03 Cont ID  
Sent By kstevens Date 2007-02-03 Time 09:50 Rev Time 0.00
Received By kstevens Date 2007-02-02 Time 18:58 Sent To  
Notes
2007-02-03 12:58:40DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL ARCHITECTURAL SHEETS. THE FIRM LICENSE NUMBER,
 (CERTIFICATE OF AUTHORIZATION), IS REQUIRED IN THE
 TITLE BLOCK OF EACH SHEET. FAC 61G1-16.004(2) & FS
 481.219, 481.2055.
  
 2. SHT A3.4 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS. SHOW THE SQUARE FOOTAGE OF EACH
 AREA AS WELL AS 1/2 AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS. ALSO INDICATE ANY AREA OF A ROOF
 THAT DRAINS FROM ABOVE IF APPLICABLE. SECTIONS 1106 &
 1107 WITH ALL SUBSECTIONS.
  
 3. SHT A3.4 DETAIL 4, SECONDARY DRAINS SHALL BE A
 MINIMUM 2" HIGHER THAN THE MAIN DRAIN. AS SHOWN THEY
 ARE ONLY ABOUT 3/4" ABOVE THE MAIN DRAINS. THIS IS
 REQUIRED SO THAT THE SECONDARY DRAINS WILL NOT DRAIN
 STORM WATER UNLESS THERE IS A BLOCKAGE IN THE PRIMARY
 DRAINS.--SUBMIT A DETAIL SHOWING THE ELEVATION AT
 THE FLOOR AT THE PATIO DOOR, AND INDICATE THE ELEVATION
 OF THE PRIMARY DRAIN AND THE SECONDARY DRAIN. SECTION
 106.1.1.
  
 4. SHT A3.5 SHOWS 6" OVERFLOW DRAINS CONNECTING TO
 MANHOLES. SECTION 1107.2 REQUIRES THE DISCHARGE TO BE
 ABOVE GRADE IN AN OBSERVABLE LOCATION. PLEASE CHANGE
 TERMINATION POINT FOR THE OVERFLOW DRAINS.--ONE 7"
 DOWNSPOUT DOES NOT SHOW THE PIPING TO THE MANHOLE.
 PLEASE SHOW ALL PIPING. SECTION 106.1.1.
  
 5. SHTS A4.1 & A5.1. SHT A4.1 SHOWS THE GUTTER TO BE
 CONTINUOUS AROUND THE INSIDE OF THE BLDG ROOF EXCEPT AT
 THE CHIMNEYS. SHT A5.1 ONLY SHOWS THE GUTTER AT THE
 MAIN ROOF SECTIONS, AND NO GUTTER AT THE HIP ROOF
 SECTIONS. ALSO NO DOWNSPOUTS ARE INDICATED AT THE HIP
 ROOF SECTIONS. PLEASE CLARIFY. SECTION 106.1.1.
  
 6. ALL PLUMBING, MECHANICAL, ELECTRICAL & SL SHEETS.
 THE ENGINEERS SEAL SHALL IMPRESS THE REQUIRED
 INFORMATION ON EACH SHEET. MANY SHEETS ONLY SHOW A
 PORTION OF REQUIRED INFORMATION. PLEASE MAKE SURE ALL
 INFORMATION REQUIRED BY FAC 61G15-23.001(1)(2),
 61G15-23.002(1)(2) AND FS 471.025 IS IMPRESSED ON EACH
 SHEET WHEN SEALING THE PLANS.
  
 7. SHT P-1 THE SANITARY PARTIAL RISER DIAGRAMS DO NOT
 REFLECT THE FLOOR PLAN IN MANY INSTANCES. ALL OFFSETS
 SHALL BE SHOWN ON THE RISER DIAGRAM, SOME EXTRA PIPING
 IS SHOWN, SOME FIXTURE BRANCH LINES ARE NOT SHOWN.--
 THE AUTOMATIC CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR A DRAINAGE STACK A MINIMUM
 OF 3" IN DIAMETER. SECTION 406.3.-- SEE RED LINE
 NOTES ON ONE SET OF PLUMBING PLANS. SECTION 106.1.1.
  
 8. SHT P-2 THE SANITARY PARTIAL RISER DIAGRAMS DO NOT
 REFLECT THE FLOOR PLAN IN MANY INSTANCES. ALL OFFSETS
 SHALL BE SHOWN ON THE RISER DIAGRAM, SOME EXTRA PIPING
 IS SHOWN, SOME FIXTURE BRANCH LINES ARE NOT SHOWN, THE
 VENT & SANT LINES ARE CROSSED FROM FLOOR TO FLOOR.--
 THE AUTOMATIC CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR A DRAINAGE STACK A MINIMUM
 OF 3" IN DIAMETER. SECTION 406.3.-- SEE RED LINE
 NOTES ON ONE SET OF PLUMBING PLANS. SECTION 106.1.1.
  
 9. SHT P-3 THE SANITARY PARTIAL RISER DIAGRAMS DO NOT
 REFLECT THE FLOOR PLAN IN MANY INSTANCES. ALL OFFSETS
 SHALL BE SHOWN ON THE RISER DIAGRAM, SOME EXTRA PIPING
 IS SHOWN, SOME FIXTURE BRANCH LINES ARE NOT SHOWN, BATH
 2 INDICATES A TUB ON THE RISER, BUT SHOWS A SHOWER ON
 THE FLOOR PLAN. THE KITCHEN SHOWS A 3" TO THE 3RD
 FLOOR. PLEASE INDICATE WHERE THIS LINE IS TERMINATING.
 --THE AUTOMATIC CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR A DRAINAGE STACK A MINIMUM
 OF 3" IN DIAMETER. SECTION 406.3.-- SEE RED LINE
 NOTES ON ONE SET OF PLUMBING PLANS. SECTION 106.1.1.
  
 10. SHT P-4 THE SANITARY PARTIAL RISER DIAGRAMS DO NOT
 REFLECT THE FLOOR PLAN IN MANY INSTANCES. ALL OFFSETS
 SHALL BE SHOWN ON THE RISER DIAGRAM, SOME EXTRA PIPING
 IS SHOWN, SOME FIXTURE BRANCH LINES ARE NOT SHOWN. THE
 VENT FROM THE FIRST FLOOR, BATHROOM 3 IS NOT SHOWN ON
 THE FLOOR PLAN OF THE SECOND FLOOR. --THE
 AUTOMATIC CLOTHES WASHER FIXTURE DRAIN SHALL CONNECT TO
 A BRANCH DRAIN OR A DRAINAGE STACK A MINIMUM OF 3" IN
 DIAMETER. SECTION 406.3.-- SEE RED LINE NOTES ON ONE
 SET OF PLUMBING PLANS. SECTION 106.1.1.
  
 11. SUBMIT A WATER RISER DIAGRAM FOR EACH TYPE OF UNIT.
 SHOW ALL PIPE SIZES, VALVES AND WATER HAMMER ARRESTORS
 REQUIRED BY SECTION 604.9. (ICE MAKERS, DISHWASHERS, &
 WASH MACHINES). SECTION 106.3.5.1.3(3)(13).
  
 12. SUBMIT A STORM RISER DIAGRAM FOR THE PRIMARY
 DRAINAGE AND SECONDARY DRAINAGE SYSTEMS. SHOW ALL PIPE
 SIZES, OFFSETS, AND INDICATE SQUARE FOOTAGE BEING
 DRAINED.SECTION 106.3.5.1.3(7)(13).
  
 13. SHT P-5CONDENSATE RISER DIAGRAM. THE CONDENSATE
 SHALL HAVE A RELIEF VENT, (RETURN BEND), INSTALLED AS
 THE CONDENSATE EXITS THE BUILDING.
  
 14. SHT P-5 WATER HEATER DETAIL. PLEASE INDICATE THE
 TERMINATION POINT FOR THE EMERGNECY PAN DRAIN AND THE
 T/P RELIEF DISCHARGE LINE. SECTIONS 504.6.1 & 504.7.2.
  
 15. SHT IR-1 THE CONTROLLER AND THE RAIN SENSOR LOCTION
 ARE REQUIRED ON THE PLAN. SECTION 106.1.1.--THE
 BACKFLOW PREVENTOR SHALL BE INSTALLED BYA LICENCED
 PLUMBING CONTRACTOR.--A SEPARATE IRRIGATION PERMIT
 IS REQUIRED. SECTION 105.1.
  
 16. SHTS IR-1, LP-1 & LP-2 LANDSCAPE ARCHITECT LICENSE
 IS NULL & VOID PER DBPR WESITE. (SEE ATTACHED SHEET).
 ONE SET OF SHEETS SHALL BE RETAINED FOR POSSIBLE REVIEW
 BY THE STATE LANDSCAPE ARCHITECTURAL BOARD AS THIS SEAL
 HAS BEEN NULL & VOID SINCE 11/30/95.
  
 17. SHTS IR-1, LP-1 & LP-2THE LANDSCAPE FIRM LICENSE
 NUMBER AS WELL AS THE PRINTED NAME OF THE PERSON
 SEALING THE DOCUMENT SHALL BE IN THE TITLE BLOCK OF
 EACH SHEET. FAC 61G1-16.004(2)(6) & FS 481.2055.
  
 18. THE MANHOLES, TRENCH DRAINS, STORM DRAINS AND
 RELATED PIPING SHALL BE DESIGNED BY THE BUILDING
 ENGINEER, AND INSTALLED BY THE PLUMBING CONTRACTOR AS
 THIS IS WITHIN THE FOOTPRINT OF THE BUILDING. THE CIVIL
 ENGINEER, AND THE SITE CONTRACTOR CAN ONLY DESIGN AND
 INSTALL UP TO FIVE FEET OF THE BUILDING STRUCTURE. FS
 489.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 4 Status F Date 2008-03-18 Cont ID  
Sent By eschneid Date 2008-02-12 Time 08:20 Rev Time 0.00
Received By eschneid Date 2008-02-12 Time 08:20 Sent To  
Notes
2008-03-18 08:21:24FAILED
  
 APPLICANT HAS SATISFIED CONDITION #5 - FDOT PERMIT.
 FINAL ROW PERMIT WILL BE REQUIRED PRIOR TO THE ACTUAL
 RELOCATION OF THE STREET CLOSURE.SEE HISTORY BELOW:
  
 2/12/08 FDOT GRANTS CONCEPTUAL APPROVAL TO RELOCATE THE
 STREET CLOSURES, WHICH SATISFIES P&Z COMMENT. 2/4/08
 DAVID LAWRENCE, ARCHITECT, NOTIFIES ERIC SCHNEIDER,
 P&Z, THAT FDOT WILL NOT PROCESS THE ROW PERMIT W/O CITY
 SIGN-OFF.
  
 ALL OTHER COMMENTS FROM JULY 11, 2007 REVIEW STILL
 APPLY.

Review Stop Z ZONING
Rev No 3 Status F Date 2007-07-11 Cont ID  
Sent By eschneid Date 2007-07-11 Time 16:38 Rev Time 0.00
Received By eschneid Date 2007-07-11 Time 16:38 Sent To  
Notes
2007-07-11 16:45:30FAILED
  
 1) THE PLANS WILL BE REQUIRED TO CONFORM TO THE CITY
 COMMISSION?S STREET CLOSURE RELOCATION PLAN.THE
 STREET CLOSURES AT 28TH AND 29TH STREET SHALL BE
 RELOCATED TO THE MID-BLOCK LOCATION (EAST OF THE
 PROJECT ENTRANCE).RELOCATED STREET CLOSURE LOCATIONS
 SHALL BE SHOWN ON THE PLANS.NOTE THAT PLANS FOR THE
 RELOCATED STREET CLOSURE DESIGN WILL NEED TO BE
 APPROVED BY THE CITY COMMISSION (JULY 16) AND
 CONSTRUCTED BY THE DEVELOPER.PLEASE SUBMIT THE CITY
 RIGHT-OF-WAY PERMIT APPROVING THE CONSTRUCTION OF THE
 RELOCATED STREET CLOSURES. (PARTIAL REPEAT)
  
 2) PROVIDE THE RECORDED PUBLIC ACCESS EASEMENT FOR THAT
 PORTION OF THE SIDEWALK LOCATED ON THE SITE ALONG
 BROADWAY AVENUE AND FOR THE SIDEWALK ALONG THE ALLEY.
 THE EASEMENT LANGUAGE SHALL BE APPROVED BY THE OFFICE
 OF THE CITY ATTORNEY PRIOR TO RECORDATION. (REPEAT)
  
 3) PROVIDE THE RECORDED PERPETUAL MAINTENANCE AGREEMENT
 FOR THE REBUILT, PAVERED ALLEY.THE MAINTENANCE
 AGREEMENT LANGUAGE SHALL BE APPROVED BY THE OFFICE OF
 THE CITY ATTORNEY PRIOR TO RECORDATION. (REPEAT)
  
 4) BMUD REQUIRES THAT SIDEWALKS ALONG BROADWAY BE A
 MINIMUM OF 8 FEET IN CLEAR WIDTH.THE SITE PLAN
 (SIGNED AND SEALED 6/26/07) AND THE CIVIL PLANS
 (REVISION 6/25/07, SIGNED AND SEALED 6/27/07) APPROVED
 WITH THE FOUNDATION PERMIT SHOW THIS STANDARD BEING
 MET, BUT THE PLANS SUBMITTED WITH THIS PERMIT DO NOT
 ADDRESS THE COMMENT.
  
 5) AN APPROVED FDOT ACCESS CONNECTION PERMIT TO MOVE
 THE 29TH STREET CLOSURE IS REQUIRED. (REPEAT)
  
 6) THE APPROVED ELEVATIONS DESIGNATE THIS AS A
 MEDITERRANEAN STYLE BUILDING WITH A BARREL TILE ROOF.
 SOME PAGES/DETAILS HAVE BEEN CORRECTED (EX. SHEET
 A7.1), BUT THERE ARE STILL REFERENCES TO ASPHALT
 SHINGLES (SHEETS A5.1 AND A5.2) AND THE ENTRY OVERHANG
 DETAILS (SHEET A5.3) SHOW SHINGLES NOT TILE.(PARTIAL
 REPEAT)
  
 7) BONDS WILL BE REQUIRED FOR ALL IMPROVEMENTS IN THE
 RIGHTS-OF-WAY. (REPEAT)
  
 8) THE CONSTRUCTION STAGING PLAN APPEARS WELL THOUGHT
 OUT.PLEASE PROVIDE DETAILS OF THE TEMPORARY BARRIERS.
 THESE SHALL NOT ALLOW ANY TRAFFIC TO FLOW THROUGH TO
 THE NEIGHBORHOOD WHILE THE NEW CLOSURES ARE BEING
 RECONSTRUCTED.ADDITIONALLY, PLEASE SUBMIT FOR
 REQUIRED PERMITS TO PREPARE THE CONSTRUCTION STAGING
 AREAS.
  
 9) PLEASE NOTE THAT THE LANDSCAPE REQUIRED IN THE
 STREET CLOSURES IS TO BE SABAL PALMS PER THE COMMISSION
 APPROVED STREET CLOSURE PLAN.
  
 10) PLEASE REVISE SHEETS LP-1 AND LP-2 TO INCORPORATE
 THE REDLINE NOTES MADE BY ALAN BARATTA, LANDSCAPE
 PLANNER (561) 822-1462, ON ONE OF THE PERMIT SUBMITTAL
 SETS.CONTACT HIM DIRECTLY FOR ANY CLARIFICATION.
  
 CONTACT ERIC SCHNEIDER (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-04-05 Cont ID  
Sent By eschneid Date 2007-04-05 Time 14:39 Rev Time 0.00
Received By eschneid Date 2007-04-05 Time 14:39 Sent To  
Notes
2007-04-05 14:44:01FAILED
  
 1) THE PLANS WILL BE REQUIRED TO CONFORM TO THE CITY
 COMMISSION?S STREET CLOSURE RELOCATION PLAN.
 COMPACTORS W/ENCLOSURES ARE TO BE LOCATED ON THE SOUTH
 SIDE OF THE BUILDING.THE STREET CLOSURES AT 28TH AND
 29TH STREET SHALL BE RELOCATED TO THE MID-BLOCK
 LOCATION (EAST OF THE PROJECT ENTRANCE).RELOCATED
 STREET CLOSURE LOCATIONS SHALL BE SHOWN ON THE PLANS.
 NOTE THAT PLANS FOR THE RELOCATED STREET CLOSURE DESIGN
 WILL NEED TO BE APPROVED BY THE CITY COMMISSION AND
 CONSTRUCTED BY THE DEVELOPER.
  
 2) SUPPLY A RECORDED UNITY OF TITLE FOR THE ENTIRE SITE
 TO THE PLANNING AND ZONING DEPARTMENT.
  
 3) PROVIDE THE RECORDED PUBLIC ACCESS EASEMENT FOR THAT
 PORTION OF THE SIDEWALK LOCATED ON THE SITE ALONG
 BROADWAY AVENUE AND FOR THE SIDEWALK ALONG THE ALLEY.
 THE EASEMENT LANGUAGE SHALL BE APPROVED BY THE OFFICE
 OF THE CITY ATTORNEY PRIOR TO RECORDATION.
  
 4) PROVIDE THE RECORDED PERPETUAL MAINTENANCE AGREEMENT
 FOR THE REBUILT, PAVERED ALLEY.THE MAINTENANCE
 AGREEMENT LANGUAGE SHALL BE APPROVED BY THE OFFICE OF
 THE CITY ATTORNEY PRIOR TO RECORDATION.
  
 5) PROVIDE PROOF THAT THE PROVISION OF ORDINANCE NOS.
 3994-06 AND 3995-06 REQUIRING NORTHWOOD SG, LLC, OR ANY
 SUCCESSOR DEVELOPER OF THE TOWNHOUSE PROJECTS, TO POST
 A BOND TO THE CITY IN THE AMOUNT DETERMINED BY THE
 DIRECTOR OF ENGINEERING SERVICES TO COVER THE COSTS
 ASSOCIATED WITH THE INSTALLATION OF ALL REQUIRED STREET
 SIGNS, TRAFFIC CONTROL SIGNS AND ROAD STRIPING HAS BEEN
 MET.
  
 6) PROVIDE THE PLANS SHOWING HOW THE UTILITY LINES IN
 THE ALLEY WILL BE BURIED UNDERGROUND, TO INCLUDE THE
 LOCATION OF THE REMAINING ABOVE GROUND UTILITY POLES.
  
 7) THE ALLEY NAME IS ?OLD NORTHWOOD LANE.?
  
 8) BMUD REQUIRES THAT SIDEWALKS ALONG BROADWAY BE A
 MINIMUM OF 8 FEET IN CLEAR WIDTH.PROVIDE A DETAIL OF
 THE F-CURB ALONG BROADWAY AVENUE FOR VERIFICATION OF
 THE DIMENSIONS SHOWN ON THE SIMONS AND WHITE CIVIL
 PLANS.PLEASE NOTE THAT THE GUTTER MAY NOT BE COUNTED
 AS PART OF THE SIDEWALK WIDTH.
  
 9) AN APPROVED FDOT ACCESS CONNECTION PERMIT TO MOVE
 THE 29TH STREET CLOSURE IS REQUIRED.
  
 10) PROVIDE THE COMPACTOR ENCLOSURE TRANSITION AT
 SIDEWALK AND STREET LEVEL.THE COMPACTOR IS TO BE AT
 STREET LEVEL.THE ADJACENT SIDEWALK WILL NEED TO BE
 SHOWN SLOPING DOWN TO THE RECESS ADJACENT TO THE
 COMPACTOR ENCLOSURE OPENING.
  
 11) THE APPROVED ELEVATIONS DESIGNATE THIS AS A
 MEDITERRANEAN STYLE BUILDING WITH A BARREL TILE ROOF.
 THE SUBMITTED SOFFIT DETAIL (SHEET A7.1) AS WELL AS
 OTHER DETAILS SHOW A SHINGLE ROOF.THE ROOF IS TO BE
 BARREL TILE IN KEEPING WITH THE ELEVATIONS AND
 RENDERINGS SHOWN IN THE COUNTLESS NEIGHBORHOOD MEETINGS
 AND BEFORE THE CITY COMMISSION.
  
 12) BONDS WILL BE REQUIRED FOR ALL IMPROVEMENTS IN THE
 RIGHTS-OF-WAY.
  
 13) A CONSTRUCTION STAGING PLAN IS REQUIRED.THE PLAN
 SHALL INCLUDE HOW THE CONSTRUCTION TRAFFIC WILL BE KEPT
 OUT OF THE OLD NORTHWOOD NEIGHBORHOOD, WHERE WORKER
 PARKING WILL TAKE PLACE, AND THE CONSTRUCTION PHASING,
 ESPECIALLY HOW THE STREET CLOSURES WILL BE RELOCATED IN
 RELATIONSHIP TO THE CONSTRUCTION OF THE BUILDING.
  
 14) THE PLANS SHALL SHOW THE SIDEWALK ADJACENT TO THE
 ALLEY CONTINUING TO 28TH AND 29TH STREETS CROSSINGS.
  
 CONTACT ERICSCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-01-19 Cont ID  
Sent By eschneid Date 2007-01-19 Time 14:29 Rev Time 0.00
Received By eschneid Date 2007-01-11 Time 11:49 Sent To  
Notes
2007-01-19 14:30:54FAILED
  
 1) THE PLANS WILL BE REQUIRED TO CONFORM TO THE CITY
 COMMISSION?S STREET CLOSURE RELOCATION PLAN.THIS WILL
 BE DETERMINED AT THE WORKSHOP ON FEBRUARY 5, 2007.
  
 2) THE SURVEY SHALL SHOW ALL OF THE EXISTING
 IMPROVEMENTS IN THE ALLEY ADJACENT TO THE RESIDENCES ON
 THE EAST SIDE OF THE ALLEY (EX. FENCES, LANDSCAPE,
 ETC.).
  
 3) SUPPLY A RECORDED UNITY OF TITLE FOR THE ENTIRE SITE
 TO THE PLANNING AND ZONING DEPARTMENT.
  
 4) PROVIDE THE RECORDED PUBLIC ACCESS EASEMENT FOR THAT
 PORTION OF THE SIDEWALK LOCATED ON THE SITE.THE
 EASEMENT LANGUAGE SHALL BE APPROVED BY THE OFFICE OF
 THE CITY ATTORNEY PRIOR TO RECORDATION.
  
 5) PROVIDE THE RECORDED PERPETUAL MAINTENANCE AGREEMENT
 FOR THE REBUILT, PAVERED ALLEY.THE MAINTENANCE
 AGREEMENT LANGUAGE SHALL BE APPROVED BY THE OFFICE OF
 THE CITY ATTORNEY PRIOR TO RECORDATION.
  
 6) PROVIDE PROOF THAT THE PROVISION OF ORDINANCE NOS.
 3994-06 AND 3995-06 REQUIRING NORTHWOOD SG, LLC, OR ANY
 SUCCESSOR DEVELOPER OF THE TOWNHOUSE PROJECTS, TO POST
 A BOND TO THE CITY IN THE AMOUNT DETERMINED BY THE
 DIRECTOR OF ENGINEERING SERVICES TO COVER THE COSTS
 ASSOCIATED WITH THE INSTALLATION OF ALL REQUIRED STREET
 SIGNS, TRAFFIC CONTROL SIGNS AND ROAD STRIPING HAS BEEN
 MET.
  
 7) PROVIDE THE PLANS SHOWING HOW THE UTILITY LINES IN
 THE ALLEY WILL BE BURIED UNDERGROUND, TO INCLUDE THE
 LOCATION OF THE REMAINING ABOVE GROUND UTILITY POLES.
  
 8) PROVIDE THE DETAILS FOR THE REBUILT, PAVERED ALLEY.
  
 9) BMUD REQUIRES THAT SIDEWALKS ALONG BROADWAY BE A
 MINIMUM OF 8 FEET IN CLEAR WIDTH.THE SIMONS AND WHITE
 CIVIL PLANS SHOW THE SIDEWALK ALONG BROADWAY AT 5 FEET
 WIDE AND ONLY 2 FEET ON THE SITE FOR A TOTAL WIDTH OF
 ONLY 7 FEET.
  
 10) THE SITE/LANDSCAPE AND CIVIL PLANS SHALL AGREE.
 THE FOLLOWING ITEMS DO NOT MATCH ON THE DIFFERING
 PLANS:
  
 A) LAYOUT OF THE COMPACTOR AND ADJOINING SIDEWALK.
  
 B) MAILBOX LOCATION MISSING ON SIMMONS AND WHITE
 PLANS.
  
 C) STABILIZED AND PLANTING AREA ALONG THE ALLEY -
 REQUIRED 5 FOOT WIDE STABILIZED AREA AND 4 FOOT WIDE
 PLANTING AREA.ONLY 8 FEET 7 INCH TOTAL SHOWN ON
 SHEETS 2 AND 3 OF 11 OF SIMONS AND WHITE PLANS, WHERE 9
 FEET ARE REQUIRED.SIMONS AND WHITE PLAN SHEET 5 OF 11
 SHOWS THE CORRECT 9 FOOT WIDTH IN THE SECTION DIAGRAM.
  
 11) PROVIDE THE COMPACTOR SPECS/DETAIL AND A DETAIL
 SHOWING THE COMPACTOR BIN CURBING AT STREET LEVEL.
  
 12) THE APPROVED ELEVATIONS DESIGNATE THIS AS A
 MEDITERRANEAN STYLE BUILDING WITH A BARREL TILE ROOF.
 THE SUBMITTED ELEVATIONS SHOW A SHINGLE ROOF.PLEASE
 NOTE THAT THE BARREL TILE IS CORRECTLY SHOWN ON
 ARCHITECTURAL SHEETS A8.2 AND A8.3.
  
 13) THE REAR ELEVATION NEEDS TO VERIFY THE MINIMUM 25%
 GLAZING REQUIREMENT IS MET.
  
 14) THE LANDSCAPE PLANS NEED TO SHOW PIGEON PLUM TREES
 AS ORIGINALLY APPROVED.THE LIVE OAKS ARE TOO LARGE A
 SPECIES FOR THE 4 FOOT WIDE LANDSCAPE STRIP AND TOO
 CLOSE TO THE FACE OF THE BUILDING TO ENSURE LONG TERM
 HEALTHY GROWTH.
  
 15) PROVIDE DETAILS OF THE 5 FOOT STABILIZED AREA.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.