Plan Review Details - Permit 06120129
Plan Review Stops For Permit 06120129 |
Review Stop |
AD |
ADDRESSING |
Rev No |
3 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
AD |
ADDRESSING |
Rev No |
2 |
Status |
F |
Date |
2007-04-16 |
|
|
Cont ID |
|
Sent By |
lursu |
Date |
2007-04-16 |
Time |
15:01 |
Rev Time |
0.00 |
Received By |
lursu |
Date |
2007-04-16 |
Time |
15:01 |
Sent To |
|
|
Notes |
2007-04-16 15:05:50 | THE COPY OF THE RECORDED UNITY OF TITLE FOR THESE THREE | | PARCELS WITH THE CORRECT OWNER INFORMATION MUST BE | | SUBMITTED TO THE ADDRESSING SECTION ( SEE BELOW INFO) | | . | | THE SITE ADDRESS OF THE PROJECT IS ASSIGNED AS 2918 | | BROADWAY WITH THE | | PARCEL CONTROL NUMBER = 74 43 43 09 05 021 0100 . | | THE REVISED SITE PLANS AND PERMIT APPLICATIONS MUST | | CONTAIN THE SITE ADDRESS ASSIGNED. | | | | LACRAMIOARA URSU | | MIS - GIS SUPPORT SPECIALIST | | CITY OF WEST PALM BEACH | | OFFICE:822-1239 | | FAX: 822-1249 | | E-MAIL:[email protected] |
|
|
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
F |
Date |
2007-01-17 |
|
|
Cont ID |
|
Sent By |
lursu |
Date |
2007-01-17 |
Time |
15:39 |
Rev Time |
0.00 |
Received By |
lursu |
Date |
2007-01-17 |
Time |
15:39 |
Sent To |
|
|
Notes |
2007-01-17 15:41:22 | THE UNITY OF TITLE MUST BE RECORDED FOR THESE THREE | | PARCELS INVOLVED IN THIS PROJECT . | | | | LACRAMIOARA URSU | | MIS - GIS SUPPORT SPECIALIST | | CITY OF WEST PALM BEACH | | OFFICE:822-1239 | | FAX: 822-1249 | | E-MAIL:[email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2007-08-08 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-08-08 |
Time |
08:25 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2007-07-31 |
Time |
10:38 |
Sent To |
|
|
Notes |
2007-08-08 08:26:18 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE | | FBC2004 | | | | 1-8.) ADDRESSED. | | | | 9.)FROM 1ST AND 2ND REVIEWS, ADDRESS THE ISSUE OF | | ROOF HEIGHT (36FT8IN SHOWN ON SHEET A5.1 WITH SHINGLE | | ROOF), A7.1 SHOWS TILE, TILE PRODUCT APPROVAL | | SUBMITTED.PLEASE COORDINATE PLANS WITH PRODUCT | | APPROVAL SUBMITTED AND ADDRESS THE HEIGHT LIMITATION | | WITH EITHER ENGINEERING OR ALTERNATE PRODUCT APPROVALS | | IF AVAILABLE.THE ELEVATIONS SUCH AS A5.1 SHOW | | SHINGLES, BUT OVERHANG SOFFIT DETAIL A7.1 SHOWS TILE. | | | | 10.)ADDRESSED. | | | | 11.)OCCUPANCY (FBC TABLE 302.3.2) AND TENANT (FBC708) | | SEPARATIONS REQUIRED.HORIZONTAL AND VERTICAL | | SEPARATION IS NOT SHOWN BETWEEN THE GARAGE AND LIVING | | SPACE (OCCUPANCY SEPARATION, SEE ALSO FBC406).A 1 | | HOUR DOOR WAS ADDED BUT THAT WALL SHOULD ALSO BE NOTED | | ON THE PLAN AS A 1 HOUR WALL. A7.1 SHOWS A 1HOUR | | HORIZONTAL FLOOR/CEILING ASSEMBLY BUT NOTHING ON THE | | PLAN INDICATES WHERE THE 1HOUR IS REQUIRED OTHER THAN | | THE STATEMENT "OCCUPANCY SEPARATION A1.0".PLANS | | SHOULD CLEARLY SHOW ALL REQUIRED FIRE RESISTANCE. | | | | **REVISED 10/24/07**TENANT SEPARATION NOT REQUIRED | | BETWEEN UNIT GARAGE AND COMMON AREA**OCCUPANCY | | SEPARATION IS REQUIRED BETWEEN UNIT AND GARAGE, | | HORIZONTAL AND VERTICAL ** | | | | 12.)THIS ITEM FROM FIRST REVIEW WAS ADDRESSED WITH A | | NOTE STATING THAT ALL PRODUCTS WILL BE IMPACT ALONG | | WITH IMPACT RATED PRODUCT APPROVALS.SEE A2.1 AND | | OTHER SHEETS, FLOOR PLAN NOTES, ITEM 5, STILL STATES | | THAT HURRICANE SHUTTERS ARE REQUIRED.PLEASE REMOVE | | THE NOTE IF YOU DO NOT INTEND TO INSTALL HURRICANE | | SHUTTERS.SOME DOOR PRODUCT APPROVALS SUBMITTED WERE | | FOR NONIMPACT PRODUCTS.PLEASE SEE FIRST REVIEW IN | | REGARDS TO USE OF REMOVABLE HURRICANE SHUTTERS ON | | COMMERCIAL BUILDINGS. | | | | 13.)ADDRESSED. | | | | 14.)SEE FBC406, FBC311.3.THE GARAGES AND ACCESS TO | | THE INDIVIDUAL GARAGE SPACES ACT AS A PARKING GARAGE. | | OCCUPANCY SEPARATION REQUIRED FBC302.3.2, BOTH | | HORIZONTAL AND VERTICAL.PENETRATIONS AND DUCTS ARE TO | | BE PROTECTED, FBC716, FBC712. | | | | REQUIRED HORIZONTAL AND VERTICAL SEPARATION IS NOT | | CLEAR ON THE PLAN, SEE OTHER COMMENTS. | | | | A DETAIL IS SHOWN ON A7.1, BUT THIS IS FOR CONCRETE | | FLOOR/WALL, THE GARAGE CEILING/FLOOR ASSEMBLY IS WOOD | | TRUSS.CONFIRM THAT THERE WILL BE NO REQUIREMENT FOR A | | CEILING/FLOOR FIRE RATED PENETRATION DETAIL WITHIN THE | | UNITS. | | | | 15.)ADDRESSED. | | | | 16.)THE PARKING GARAGE VENTILATION TO BE IN | | COMPLIANCE WITH FLORIDA BUILDING CODE, MECHANICAL AS | | PER FBC406.4.2.THE PLANS SHOW NATURAL VENTILATION FOR | | THE UNIT GARAGES, BUT THIS SHOULD BE TO THE OUTSIDE. | | THE NATURAL VENTILATION IS SHOWN VENTING TO THE PARKING | | GARAGE.NO VENTILATION SHOWN FOR THE ENCLOSED PARKING | | GARAGE AREA ON THE MECHANICAL PLAN.SL1, SITE | | LIGHTING, SHOWS EXHAUST FANS BUT NO FIRE DAMPER AT THE | | 1 HOUR FLOOR CEILING ASSEMBLY.NOTE STATES THAT IT IS | | TO BE DESIGNED TO SMB2004 (PLEASE EXPLAIN WHAT THIS IS) | | AND ASHRAE62; DESIGN INTENT NOT CLEAR.IT IS NOT CLEAR | | WHY THIS INFORMATION WOULD BE SHOWN ON THIS SHEET AS | | THE TWO REVIEWERS WHO REQUESTED THIS INFORMATION, | | MECHANICAL AND BUILDING, DO NOT TYPICALLY REIVEW SITE | | LIGHTING, AND IT IS NOT CLEAR HOW MECHANICAL | | VENTILATION IS RELATED TO SITE LIGHTING.PLEASE MOVE | | THIS INFORMATION TO THE APPROPRIATE (MECHANICAL) | | SECTION IN THE PLANS. | | | | 17-20.) ADDRESSED. | | | | 21.) SEE FIRST REVIEW REGARDING HANDRAIL EXTENSIONS, | | FBC1009.11.5.ALSO SEE STAIR LANDING REQUIREMENTS, | | FBC1009.4, DOOR LANDING REQUIREMENT, FBC1008.1.5, | | FBC1008.1.4.I WAS UNABLE TO LOCATE EXCEPTIONS FOR R2 | | OCCUPANCY. | | | | 22.)ADDRESSED.HOWEVER, SEE OTHER COMMENTS REGARDING | | OCCUPANCY SEPARATION WHICH WOULD REQUIRE A PROTECTED | | OPENING IN THIS LOCATION (INTERIOR GARAGE DOOR). | | | | 23.)FIRST AND SECOND REVIEWS REQUESTED BUILDING AREA | | BY OCCUPANCY TO DETERMINE COMPLIANCE WITH FBC TABLE | | 503.A TOTAL SF AREA PER FLOOR WAS PROVIDED AS R2, | | WITH A TOTAL WHICH INCLUDES THE THREE SF AREAS PER | | FLOOR.A FOURTH NUMBER WAS PROVIDED, ABOVE THE TOTAL | | LINE BUT NOT INCLUDED IN THE TOTAL, APPARENTLY TO SHOW | | THAT THE AREA EXCEEDS CODE COMPLIANCE.HOWEVER, FEES | | ARE ASSESSED BASED ON OCCUPANCY DECLARED (AND ARE | | HIGHER FOR THE R2 DECLARED THAN S2).FEES WILL BE | | ASSESSED ON OCCUPANCY DECLARED BY ARCHITECT.EITHER | | REVISE TO SEPARATE R2 AND S2 ON FIRST FLOOR, OR FEES | | WILL BE ASSESSED ON THE HIGHER R2 OCCUPANCY. | | | | IF DESIGNER ELECTS TO KEEP AREA CALCULATIONS AS IS, | | PLEASE MOVE THE S2 NUMBER BELOW THE TOTAL.IT IS NOT | | READILY APPARENT AS TO HOW YOU ARRIVE AT THE TOTAL OF | | 66,400 WHEN YOU HAVE FOUR NUMBERS ABOVE IT BUT ARE | | TOTALING ONLY THREE. | | | | AREA INCREASE CALCULATIONS SHOULD GIVE EACH ELEVATION A | | WEIGHTED VALUE.ARCHITECT DECLARES THE EAST ELEVATION | | ON A1.2 AS 20FT, BUT IN THE CALCULATION GIVES IT A | | VALUE OF 30FT.WITH THE WEIGHTED VALUE, ALLOWABLE AREA | | IS 26,600 PER FLOOR FOR R2 (NOT 28,000 PER PLAN A1.2). | | AREAS DECLARED APPEAR CODE COMPLIANT (LESS THAN 26,600 | | ALLOWED PER FLOOR) BUT PLEASE REVISE THE CALCULATION. | | | | PLEASE ALSO NOTE THAT ARCHITECT IS DECLARING OPEN SPACE | | OF 20FT ON THE EAST SIDE, BUT SHEET A5.2 STATES THAT | | THERE IS 25FT6IN TO THE PROPERTY LINE.HOW CAN THE | | OPEN SPACE (INCLUDING THE ENTIRE STREET) BE LESS THAN | | DISTANCE TO CENTERLINE OF THE ROAD?PLEASE RESOLVE | | INCONSISTENCIES. | | | | 24-29.) ADDRESSED. | | | | 29.)STRUCTURAL ELEMENTS ARE TO COMPLY WITH FBC TABLE | | 601.SHOW CALCULATED FIRE RESISTANCE OR LISTED | | ASSEMBLY. | | | | 2ND REVIEW; 2 HOUR WALL REQUIRED FOR EXTERIOR WALLS, | | BUT THIS IS NOT NOTED ANYWHERE ON THE PLAN OTHER THAN | | THE DETAIL.PLEASE NOTE ON THE SITE PLAN, | | ARCHITECTURAL DETAILS. | | | | 3RD REVIEW; PARTIALLY ADDRESSED BY PUTTING A NOTE ON | | SHEET A1.0 AND WAS NOT INCLUDED ON THE SITE PLAN OR | | ARCHITECTURALS.SHEET A1.0 STATES THAT THERE IS A 1 | | HOUR OCCUPANCY SEPARATION, BUT NONE SHOWN BETWEEN S2 | | AND R2; SEE OTHER COMMENTS.FIRE RESISTANCE IS ALSO | | NOT SHOWN BETWEEN TENANTS, SEE DETAIL B A8.3.SEE | | OTHER COMMENTS; PLEASE CLEARLY SHOW REQUIRED FIRE | | RESISTANCE RATING NOT ONLY TO SHOW CODE COMPLIANCE BUT | | ALSO FOR COORDINATION IN THE FIELD.SEE ALSO ITEM 52. | | | | | | 30-44.) ADDRESSED. | | | | 45.)S1.0, 3 N GOVERNING CODE HAS BEEN REVISED BUT | | STATES 2006 AMENDMENTS.BASED ON APPLICATION DATE AND | | GOVERNING CODE DECLARED BY ARCHITECT, THIS SHOULD STATE | | 2005 AMENDMENTS.2006 AMENDMENTS BECAME EFFECTIVE | | DECEMBER 8, 2006 AND APPLICATION DATE IS DECEMBER 6, | | 2006. | | | | 46-48.) ADDRESSED. | | | | 49.)PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER | | OF RECORD, FBC*106.3.3. | | | | REGARDING THE PRODUCT APPROVALS SUBMITTED: | | | | FL19 IS EXPIRED, FAC9B72, WWW.FLORIDABUILDING.ORG AND | | THE DOORS DO NOT MEET THE WORST CASE PRESSURES ON | | A5.3. | | | | A2.3 DOOR 1 IS SHOWN AS DOUBLE DOORS AND AS OHD, A5.3 | | SCHEDULE SHOWS A SINGLE DOOR.CHECK AND CORRELATE ALL | | DOORS. | | | | GLAZED DOUBLE DOOR PRODUCT APPROVAL STAPLED ONTO THE | | BACK OF THE MULLION PRODUCT APPROVAL IS FOR NON IMPACT | | AND DOES NOT MEET WORST CASE PRESSURES. | | | | THE DOUBLE GLAZED (REVIEWED BY DOR) HAVE SPEC SHEETS | | WHICH DO NOT CORRELATE WITH THE PRODUCT YOU INDICATE | | YOU ARE USING.ALSO THE ONE SHEET WHICH SHOWS THAT | | THIS PRODUCT IS IMPACT AND COMPLIANT FOR PRESSURES IS | | DATED 4/28/2005 REVISION, AFTER THE PRINTING OF THE | | EXPIRED PRODUCT APPROVAL 3/11/04.IT APPEARS THAT THE | | PAPERWORK IS NOT FROM THIS PRODUCT APPROVAL.PLEASE | | OBTAIN CURRENT FLORIDA STATE OR LOCAL PRODUCT APPROVAL | | WITH EVALUATION REPORTS AND INSTALLATION INSTRUCTIONS | | WHICH CAN BE VERIFIED ON THE INTERNET. (APPLIES TO ALL | | PRODUCTS) | | | | FL8228 SUBMITTED IS PENDING APPROVAL. | | | | FOR PRODUCTS WITH ONLY A MIAMIDADE SUBMITTED, PROVIDE | | FLORIDA STATE OR LOCAL PRODUCT APPROVAL. | | | | ***REMOVED*** (FOR THE ROLLING DOOR, PROVIDE | | INFORMATION IN REGARDS TO THE FIRE RESISTANCE OF THIS | | DOOR. - NOT REQUIRED 10/24/07) | | | | 06-302.03, THE EVALUATION REPORT IS INCOMPLETE. | | | | NO OPAQUE SINGLE DOOR SHOWN ON THE PLAN.PLEASE | | CORRELATE. THE PRODUCT APPROVAL IS FOR NON IMPACT, ALL | | PRODUCTS TO BE IMPACT RATED PER ARCHITECT. | | | | BARREL TILE PRODUCT APPROVAL SUBMITTED.IT IS NOT | | CLEAR IF YOU ARE USING SHINGLES, TILE, OR BOTH.PLANS | | SHOW BOTH IN THE SAME LOCATION. PLEASE REVISE PLAN AND | | SUBMIT REQUIRED PRODUCT APPROVALS. | | | | NEW COMMENTS: | | | | 50.)AS YOU ARE NOT USING NFPA13 SYSTEM, PLEASE SHOW | | COMPLIANCE WITH FBC TABLE 1015.1, TRAVEL DISTANCE | | (175FT).YOU MAY SHOW WORST CASE (END UNITS) RATHER | | THAN EACH INDIVIDUAL UNIT. | | | | 51.)M3 SHOWS A BALCONY ON THE 2ND FLOOR AT THE | | CORNER, A3.2 SHOWS WINDOW TYPE B.PLEASE COORDINATE. | | | | 52.)SHEET M3, A 4INCH DRYER DUCT 2ND FLOOR WAS ADDED. | | THIS IS A 2HR WALL; PLEASE ADDRESS. | | | | 53.)IMPACT FEES ARE STAMPED FOR 41,302 SF.THE 2ND | | AND 3RD FLOORS TOTAL 43,189, SO INCLUDING THE LIVING | | PORTION OF THE FIRST FLOOR SHOULD BE GREATER THAN | | 43,189.PLEASE CLARIFY WHY IMPACT FEES WERE PAID FOR | | AN AREA LESS THAN SQUARE FOOT AREA DECLARED BY | | ARCHITECT. | | | | 53.)SEE ATTACHED FS553.80(2)(B). |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2007-04-29 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-04-29 |
Time |
13:05 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2007-04-29 |
Time |
13:05 |
Sent To |
|
|
Notes |
2007-04-29 13:47:47 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE | | FBC2004 | | | | 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO | | PERMIT PICKUP, FS713.13. | | | | 2.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY | | PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.THE PLANS | | MUST BE STAMPED AND THE RECEIPT ATTACHED TO THE | | APPLICATION.PLEASE CALL 561-233-5025 FOR MORE | | INFORMATION. | | | | 3.)RADON FEES HAVE BEEN ADDED FS553.721.THIS MAY BE | | ADJUSTED AFTER EXACT BUILDING SIZE IS DETERMINED. | | | | 4.) FBC* 109.3.7RESIDENT INSPECTOR. SUBMIT INSPECTOR | | RESUME' AND LICENSE DOCUMENTS TO HAROLD PISKURA, | | DIRECTOR OF THE RESIDENT INSPECTOR PROGRAM.A RESIDENT | | INSPECTOR PROGRAM IS REQUIRED, ON THIS PROJECT, DUE TO | | ONE OR MORE OF THE FOLLOWING: | | - BUILDINGS/ADDITIONS OF TYPE I OR II | | CONSTRUCTION | | - ANY MAJOR STRUCTURAL ALTERATIONS | | - STRUCTURES IN WHICH THE CONCRETE | | DESIGN IS BASED ON COMPRESSIVE | | STRENGTH (F'C) IN EXCESS OF 3000 PSI | | - PILE DRIVING | | - BUILDINGS OVER 20,000 SQFT IN AREA | | - BUILDINGS OVER 2 STORIES IN HEIGHT | | - BUILDING/STRUCTURES OF UNUSUAL DESIGN OR METHODS | | OF CONSTRUCTION | | | | ALSO, PLEASE ARRANGE WITH HAROLD PISKURA (INSPECTION | | SERVICES MANAGER - TEL: | | 561 805 6711), A MEETING INVOLVING THE OWNER, RESIDENT | | INSPECTOR, JOB INSPECTOR, CONTRACTOR AND ENGINEER. THIS | | MUST BE DONE PRIOR TO PERMIT ISSUANCE.THREE ORIGINAL | | SETS OF ALL DOCUMENTS ARE REQUIRED FOR PERMITTING. | | | | 2ND REVIEW ? THREE SETS OF PLANS SUBMITTED, ONLY TWO | | SETS OF SUPPORTING DOCUMENTATION SUBMITTED.THREE SETS | | OF ALL DOCUMENTS REQUIRED, SEE FIRST REVIEW. | | | | 5.)ADDRESSED. | | | | 6.)ALL INFORMATION REQUIRED BY FAC61G16-23.002 IS | | REQUIRED TO BE ON EACH SHEET SEALED BY THE ENGINEER | | (CERTIFICATE OF AUTHORIZATION). | | | | 2ND REVIEW - THIS WAS DONE ON THE PLANS BUT NOT ON THE | | CALCS. | | 7-8.)ADDRESSED. | | | | 9.)DECLARE MEAN ROOF HEIGHT, FBC CHAPTER 5..NOTE | | THAT THE SHINGLE PRODUCT APPROVAL IS LIMITED TO A MRH | | OF LESS THAN 33 FEET.PLEASE CONTACT ME TO DISCUSS IF | | THIS IS AN ISSUE. | | | | 2ND REVIEW ? MRH IS GREATER THAN 33?.SUBMIT COMPLIANT | | PRODUCT APPROVALS. | | | | 10.)ADDRESSED. | | | | 11.)SHEET A1.0 REFERS TO OCCUPANCY SEPARATION; IS | | THIS REFERRING TO TENANT SEPARATION? | | | | 2ND REVIEW ? OCCUPANCY SEPARATION ALSO REQUIRED, AS | | WELL AS EXTERIOR WALL FIRE RATING REQUIREMENT.SEE | | OTHER COMMENTS AND INCLUDE ON A1.0. | | | | 12-13.)ADDRESSED. | | | | 14.)SEE FBC406, FBC311.3.THE GARAGES AND ACCESS TO | | THE INDIVIDUAL GARAGE SPACES ACT AS A PARKING GARAGE. | | OCCUPANCY SEPARATION REQUIRED FBC302.3.2, BOTH | | HORIZONTAL AND VERTICAL.PENETRATIONS AND DUCTS TO BE | | PROTECTED, FBC716, FBC712. | | | | 2ND REVIEW ? THE RESPONSE LETTER STATES THAT ?ALTERNATE | | METHOD? IS TO BE USED.WHAT ALTERNATE METHOD?WHERE | | IN THE CODE IS THIS ALLOWED?THIS COMMENT WAS NOT | | PROPERLY ADDRESSED ON THE PLAN. | | | | 15.)ADDRESSED. | | | | 16.)THE PARKING GARAGE VENTILATION TO BE IN | | COMPLIANCE WITH FLORIDA BUILDING CODE, MECHANICAL. | | | | 16.)NFPA 13 SYSTEM REQUIRED AS PARKING GARAGE IS NOT | | A RESIDENTIAL OCCUPANCY, SEE NFPA 13R 1.1, NFPA 101. | | ALSO SEE FBC504.2, NFPA 13 SYSTEM REQUIRED IF YOU ARE | | USING AREA MODIFICATIONS FOR SPRINKLED BUILDINGS. | | | | 2ND REVIEW ? THE RESPONSE LETTER STATES THIS IS NOT | | NEEDED.HOWEVER, NFPA 13 SYSTEM WILL BE REQUIRED IF | | YOU USE SPRINKLERS FOR AREA INCREASES.SEE OTHER | | COMMENTS. | | | | 17.)A5.2, DESIGNER HAS NOT PROVIDED CALCULATIONS IN | | REGARDS TO OPENINGS FOR THE REAR ELEVATION FBC704.8. | | NOTE THAT DISTANCE IS TO BE MEASURED TO THE CENTER OF | | THE ALLEY FOR DISTANCE TO ASSUMED PROPERTY LINE. | | | | 2ND REVIEW ? NOT PROPERLY ADDRESSED.ARCHITECT STATES | | THAT 75% IS ALLOWED, 26.28% PROVIDED.THIS IS FOR | | PROTECTED OPENINGS.UNPROTECTED OPENINGS ARE LIMITED | | TO 26.28%.DISTANCE TO PROPERTY LINE IS 11?, SHOULD BE | | USING DISTANCE TO ASSUMED PROPERTY LINE WHICH APPEARS | | TO BE APPROX 26?. | | | | RIGHT SIDE ELEVATION, A1.2, APPEARS TO BE 35? TO | | ASSUMED PROPERTY LINE.UNLIMITED OPENINGS ALLOWED.IT | | IS NOT CLEAR WHY YOU HAVE INCLUDED THIS CALCULATION. | | | | 18-23.) ADDRESSED. | | | | 23.)DECLARE TOTAL BUILDING SIZE.SHOW COMPLIANCE | | WITH FBC TABLE 503.SHOW AREA INCREASE CALCULATIONS ON | | THE PLAN.PLEASE SEE DEFINITION OF BUILDING AREA, TO | | INCLUDE AREA INCLUDED WITHIN THE HORIZONTAL PROJECTION | | OF THE FLOOR ABOVE (FIRST FLOOR AREA COVERED BY | | BALCONIES ON SECOND FLOOR TO BE INCLUDED).DECLARE | | TOTAL SQUARE FOOT AREA FOR EACH OCCUPANCY | | CLASSIFICATION. | | | | 2ND REVIEW ? OVERALL DIMENSIONS S1.1 ARE 228?7X104?4, | | WHICH WOULD BE OVER 23,000 SF, BUT YOU DECLARED MUCH | | LESS FOR EACH FLOOR.SEE DEFINITION OF BUILDING AREA, | | FBC 502. ALSO ARCHITECT STATES IN THE CALCULATIONS THAT | | AREA INCREASE IS 28000 SF WITHOUT SPRINKLERS, BUT | | STATES THAT 48,000 IS ALLOWED.AREA INCREASES FOR | | SPRINKLERS REQUIRES NFPA13 SYSTEM, FBC 504.2. | | | | 24.)ADDRESSED. | | | | 25.)WIND DESIGN CRITERIA ON CALCULATIONS PREPARED BY | | RICARDO DIAZ, PE STATES EXPOSURE C BUT THE CALCULATIONS | | WERE RUN USING EXPOSURE B.SHEET S1.0 ALSO DECLARES | | EXPOSURE B. | | | | 2ND REVIEW ? REMOVE OLD SHEETS AND REPLACE WITH NEW | | SHEETS. | | | | 26.)CALCULATIONS WERE DONE USING ASCE7-05.SEE | | FBC35, ASCE7-02 IS THE CORRECT STANDARD. | | | | 2ND REVIEW ? REMOVE OLD SHEETS AND REPLACE WITH NEW | | SHEETS. | | | | 27.)THE AGREEMENT FOR UNITY OF TITLE IS NOT SIGNED BY | | ALL PARTIES AND OWNER ON THE UNITY OF TITLE IS NOT THE | | OWNER OF RECORD (CLERK?S OFFICE).THIS ISSUE IS | | REQUIRED TO BE RESOLVED PRIOR TO PERMIT ISSUANCE.THE | | PROPOSED IMPROVEMENT CROSSES THE PROPERTY LINE WHICH | | WOULD NOT BE ALLOWED WITHOUT A FIREWALL, FBC CHAPTER | | 6. | | | | 28.)ADDRESSED. | | | | 29.)STRUCTURAL ELEMENTS ARE TO COMPLY WITH FBC TABLE | | 601.SHOW CALCULATED FIRE RESISTANCE OR LISTED | | ASSEMBLY. | | | | 2ND REVIEW ? 2 HOUR WALL REQUIRED FOR EXTERIOR WALLS, | | BUT THIS IS NOT NOTED ANYWHERE ON THE PLAN OTHER THAN | | THE DETAIL.PLEASE NOTE ON THE SITE PLAN, | | ARCHITECTURAL DETAILS. | | | | 30-36.) ADDESSED. | | | | 37.)PROVIDE A DETAIL FOR U301, A7.1. | | | | 2ND REVIEW ? I BELIEVE THIS WAS ADDRESSED, BUT THE NEW | | DETAIL IS NOT LABELED WITH ASSEMBLY NUMBER OR FIRE | | RATING. | | | | 38-44.) ADDRESSED. | | | | NEW COMMENTS: | | | | 45.)S1.0, 3 N REFERS TO FBC 2001.OTHER ASTM AND ACI | | REFERENCES ARE EXPIRED.CHECK ALL. | | | | 46.)THERE ARE THREE CONFLICTS/INCONSISTENCIES BETWEEN | | THE SOILS (WHICH ENGINEER REFERS TO ON S1.0) AND THE | | SOILS ENGINEER RECOMMENDATIONS.THEY ARE AS FOLLOWS: | | | | A. S1.1 SPECS 6ML VAPOR BARRIER, SOILS RECOMMENDS 10ML | | MINIMUM. | | | | B. S5, WF16 IS 16INCH FOOTING, SOILS RECOMMENDS 24INCH | | MINIMUM.THE DESIGN OF COLUMNS ON EITHER SIDE OF THIS | | VERY SHORT FOOTING UNDER THE GARAGE DOOR IS NOTED. | | | | C. ENGINEER REFERS TO THE FOUNDATION CONDITIONS. | | NOWHERE ON THE PLAN DOES IT MENTION THE EXCAVATION | | REQUIREMENT.PLEASE CONFIRM THAT THIS REPORT HAS BEEN | | ADDRESSED. | | | | 47.)A1.2, TRASH COMPACTOR GATES SWING OVER THE PUBLIC | | WAY, FBC3202.2. | | | | 48.)A5.2, ?LEFT ELEVATION? IS ON THE RIGHT ON A1. | | THE LONG SIDES ARE LABELED ?FRONT? AND ?REAR? BUT BOTH | | HAVE UNIT ENTRANCES AND FACE STREETS. | | | | 49.)PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER | | OF RECORD, FBC*106.3.3. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2007-01-22 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-01-22 |
Time |
15:57 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2007-01-17 |
Time |
10:14 |
Sent To |
|
|
Notes |
2007-01-22 15:58:50 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE | | FBC2004 | | | | 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO | | PERMIT PICKUP, FS713.13. | | | | 2.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY | | PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.THE PLANS | | MUST BE STAMPED AND THE RECEIPT ATTACHED TO THE | | APPLICATION.PLEASE CALL 561-233-5025 FOR MORE | | INFORMATION. | | | | 3.)RADON FEES HAVE BEEN ADDED FS553.721.THIS MAY BE | | ADJUSTED AFTER EXACT BUILDING SIZE IS DETERMINED. | | | | 4.) FBC* 109.3.7RESIDENT INSPECTOR. SUBMIT INSPECTOR | | RESUME' AND LICENSE DOCUMENTS TO HAROLD PISKURA, | | DIRECTOR OF THE RESIDENT INSPECTOR PROGRAM.A RESIDENT | | INSPECTOR PROGRAM IS REQUIRED, ON THIS PROJECT, DUE TO | | ONE OR MORE OF THE FOLLOWING: | | - BUILDINGS/ADDITIONS OF TYPE I OR II | | CONSTRUCTION | | - ANY MAJOR STRUCTURAL ALTERATIONS | | - STRUCTURES IN WHICH THE CONCRETE | | DESIGN IS BASED ON COMPRESSIVE | | STRENGTH (F'C) IN EXCESS OF 3000 PSI | | - PILE DRIVING | | - BUILDINGS OVER 20,000 SQFT IN AREA | | - BUILDINGS OVER 2 STORIES IN HEIGHT | | - BUILDING/STRUCTURES OF UNUSUAL DESIGN OR METHODS | | OF CONSTRUCTION | | | | ALSO, PLEASE ARRANGE WITH HAROLD PISKURA (INSPECTION | | SERVICES MANAGER - TEL: | | 561 805 6711), A MEETING INVOLVING THE OWNER, RESIDENT | | INSPECTOR, JOB INSPECTOR, CONTRACTOR AND ENGINEER. THIS | | MUST BE DONE PRIOR TO PERMIT ISSUANCE.THREE ORIGINAL | | SETS OF ALL DOCUMENTS ARE REQUIRED FOR PERMITTING. | | | | 5.)AS DISCUSSED, ARCHITECT IS TO APPLY FOR | | CERTIFICATE OF AUTHORIZATION FOR DAVID LAWRENCE | | ARCHITECTURE INC., FS481.219(2).THE CORPORATION NAME | | IS NOT TO APPEAR ON DRAWINGS UNTIL APPROVED BY THE | | FLORIDA BOARD OF ARCHITECTS AND AN ARCHITECT BUSINESS | | NUMBER ASSIGNED.IF ARCHITECT BUSINESS NAME IS USED, | | THE COFA NUMBER IS TO APPEAR ON EACH SHEET | | FAC61G1-16.002,003. | | | | 6.)ALL INFORMATION REQUIRED BY FAC61G16-23.002 IS | | REQUIRED TO BE ON EACH SHEET SEALED BY THE ENGINEER | | (CERTIFICATE OF AUTHORIZATION). | | | | 7.)HYDRAULIC CALCS ARE REQUIRED TO HAVE ALL | | INFORMATION REQUIRED BY FAC61G16-23.002 (TITLE BLOCK | | INFORMATION FOR THE ENGINEER). | | | | 8.)SHEET A1.0, PLANS STATE THAT THE BUILDINGS MUST | | COMPLY WITH FBC1606; THIS IS THE SECTION FOR DEAD | | LOADS, NOT WIND LOADS.PLEASE REVISE. | | | | 9.)DECLARE MEAN ROOF HEIGHT, FBC CHAPTER 5..NOTE | | THAT THE SHINGLE PRODUCT APPROVAL IS LIMITED TO A MRH | | OF LESS THAN 33 FEET.PLEASE CONTACT ME TO DISCUSS IF | | THIS IS AN ISSUE. | | | | 10.)INCLUDE 2005 AMENDMENTS IN GOVERNING CODE.THERE | | WAS A CODE AMENDMENT EFFECTIVE DECEMBER 8, 2006 (PERMIT | | APPLICATION DATE IS PRIOR TO THIS DATE). | | | | 11.)SHEET A1.0 REFERS TO OCCUPANCY SEPARATION; IS | | THIS REFERRING TO TENANT SEPARATION? | | | | 12.)A2.1 FLOOR PLAN NOTES STATES THAT HURRICANE | | SHUTTERS ARE TO BE INSTALLED.SEE ATTACHED POLICY IN | | REGARDS TO IMPACT PROTECTION ON COMMERCIAL BUILDINGS. | | PRODUCT APPROVALS SUBMITTED ARE FOR LARGE MISSILE | | IMPACT RATED PRODUCTS.PLEASE ADDRESS CONFLICT.IF | | YOUR INTENT IS TO USE SHUTTERS, NOTE THAT REMOVABLE | | SHUTTERS ARE PERMITTED ON THE FIRST FLOOR ONLY AND MUST | | BE APPROVED BY THE BUILDING OFFICIAL.PLEASE CONTACT | | ME IF THIS IS YOUR INTENT. | | | | 13.)NOTE THAT THE UNITS ARE CALLED TOWNHOMES.THEY | | DO NOT MEET THE FLORIDA STATUTE DEFINITION OF A | | TOWNHOUSE.THIS COMMENT DOES NOT NEED TO BE | | ADDRESSED; INFORMATIONAL ONLY.OCCUPANCY | | CLASSIFICATION FOR THE RESIDENTIAL AREA IS NOTED AS | | DECLARED, R2. | | | | 14.)SEE FBC406, FBC311.3.THE GARAGES AND ACCESS TO | | THE INDIVIDUAL GARAGE SPACES ACT AS A PARKING GARAGE. | | OCCUPANCY SEPARATION REQUIRED FBC302.3.2, BOTH | | HORIZONTAL AND VERTICAL.PENETRATIONS AND DUCTS TO BE | | PROTECTED, FBC716, FBC712. | | | | 15.)PROVIDE EGRESS FROM THE PARKING GARAGE AREA ON | | THE FIRST FLOOR. | | | | 16.)THE PARKING GARAGE VENTILATION TO BE IN | | COMPLIANCE WITH FLORIDA BUILDING CODE, MECHANICAL. | | | | 16.)NFPA 13 SYSTEM REQUIRED AS PARKING GARAGE IS NOT | | A RESIDENTIAL OCCUPANCY, SEE NFPA 13R 1.1, NFPA 101. | | ALSO SEE FBC504.2, NFPA 13 SYSTEM REQUIRED IF YOU ARE | | USING AREA MODIFICATIONS FOR SPRINKLED BUILDINGS. | | | | 17.)A5.2, DESIGNER HAS NOT PROVIDED CALCULATIONS IN | | REGARDS TO OPENINGS FOR THE REAR ELEVATION FBC704.8. | | NOTE THAT DISTANCE IS TO BE MEASURED TO THE CENTER OF | | THE ALLEY FOR DISTANCE TO ASSUMED PROPERTY LINE. | | | | 18.)A2.1, STAIRS SHOWS "VARIES" FOR TREADS.STAIRS | | ARE TO COMPLY WITH FBC1009.3.1, DIMENSIONAL UNIFORMITY. | | NOTE DESIGN CRITERIA FOR THE STAIRS (RANGE FOR RISER | | HEIGHT) ON THE PLAN. | | | | 19.)A2.1, BATHROOM DOOR IS TO HAVE A 29INCH CLEAR | | OPENING, FBC11-11.1(1). | | | | 20.)STAIRS ARE TO BE CONSTRUCTED SO THAT WATER WILL | | NOT ACCUMULATE ON THE WALKING SURFACE, FBC1009.5.2 | | (ENTRY TO UNITS). | | | | 21.)HANDRAIL EXTENSION REQUIRED FOR STAIRS AT UNIT | | ENTRIES, FBC1009.11.5.NOTE THAT THE EXCEPTION STATES | | "WITHIN DWELLING UNITS", THE ENTRY IS OUTSIDE OF THE | | DWELLING UNIT. | | | | 22.)FBC13-603.1ABC.1, ADJACENT DOORS SHALL BE SOLID | | CORE, WOOD, OR INSULATED.UNIT C, DOORS 6 AND 9, ARE | | LOCATED IN THE ADJACENT WALL. | | | | 23.)DECLARE TOTAL BUILDING SIZE.SHOW COMPLIANCE | | WITH FBC TABLE 503.SHOW AREA INCREASE CALCULATIONS ON | | THE PLAN.PLEASE SEE DEFINITION OF BUILDING AREA, TO | | INCLUDE AREA INCLUDED WITHIN THE HORIZONTAL PROJECTION | | OF THE FLOOR ABOVE (FIRST FLOOR AREA COVERED BY | | BALCONIES ON SECOND FLOOR TO BE INCLUDED).DECLARE | | TOTAL SQUARE FOOT AREA FOR EACH OCCUPANCY | | CLASSIFICATION. | | | | | | 24.)ARDAMAN & ASSOCIATESBORING LOCATION PLAN STATES | | THAT THIS IS A TYPE III A FULLY SPRINKLED BUILDING. | | THIS IS IN CONFLICT WITH THE ARCHITECTURAL PLAN. | | BUILDING TYPE IS NOT NECESSARY ON THE SOILS REPORT BUT | | IF PROVIDED MUST BE CONSISTENT WITH THE PLANS. | | | | 25.)WIND DESIGN CRITERIA ON CALCULATIONS PREPARED BY | | RICARDO DIAZ, PE STATES EXPOSURE C BUT THE CALCULATIONS | | WERE RUN USING EXPOSURE B.SHEET S1.0 ALSO DECLARES | | EXPOSURE B. | | | | 26.)CALCULATIONS WERE DONE USING ASCE7-05.SEE | | FBC35, ASCE7-02 IS THE CORRECT STANDARD. | | | | 27.)THE AGREEMENT FOR UNITY OF TITLE IS NOT SIGNED BY | | ALL PARTIES AND OWNER ON THE UNITY OF TITLE IS NOT THE | | OWNER OF RECORD (CLERK?S OFFICE).THIS ISSUE IS | | REQUIRED TO BE RESOLVED PRIOR TO PERMIT ISSUANCE.THE | | PROPOSED IMPROVEMENT CROSSES THE PROPERTY LINE WHICH | | WOULD NOT BE ALLOWED WITHOUT A FIREWALL, FBC CHAPTER | | 6. | | | | | | 28.)A1.2, THE DISTANCE OF THE BUILDING FROM THE | | PROPERTY LINE IS LESS THAN 30FT (MEASURE TO CENTER LINE | | OF THE ALLEY).ONE HOUR WALL REQUIRED, FBC602. PROVIDE | | A DETAIL. | | | | 29.)STRUCTURAL ELEMENTS ARE TO COMPLY WITH FBC TABLE | | 601.SHOW CALCULATED FIRE RESISTANCE OR LISTED | | ASSEMBLY. | | | | 30.)WINDOW O, HORIZONTAL ROLLER, HAS A DESIGN | | PRESSURE OF -53.72.SEE THE CHART ON SHEET 1 OF 6 OF | | THE PRODUCT APPROVAL, GLASS TYPES A & C ARE NOT | | COMPLIANT FOR THIS SIZE.PLEASE CIRCLE ON THE PRODUCT | | APPROVAL WHICH PRODUCT YOU WILL BE INSTALLING. | | | | 31.)SEE SHEET 3 OF 11 OF THE SINGLE HUNG PRODUCT | | APPROVAL.NOT ALL GLASS OPTIONS ARE COMPLIANT FOR | | DESIGN PRESSURES ON A5.3.PLEASE INDICATE WHICH | | PRODUCT YOU WILL INSTALL. | | | | 32.)SEE SHEET 5 OF 13 OF THE CASEMENT WINDOW PRODUCT | | APPROVAL.NOT ALL GLASS OPTIONS ARE COMPLIANT FOR | | DESIGN PRESSURES ON A5.3.PLEASE INDICATE WHICH | | PRODUCT YOU WILL INSTALL. | | | | 33.)A5.3, ENTRY DOOR 10 IS SHOWN AS 3?0 ON THE DOOR | | SCHEDULE, 2.67 WIDTH ON DOOR PRESSURES.PLEASE | | ADDRESS. | | | | 34.)DESIGN PRESSURE REQUIREMENT FOR DOORS 5 AND 6 | | EXCEED PRODUCT LIMITATION, SEE THERMATRU PRODUCT | | APPROVAL, SHEET 1.NOTE THAT THE DOOR PRESSURES APPEAR | | TO HAVE BEEN CALCULATED FROM A SINGLE DOOR, BUT CAN BE | | DONE USING THE ENTIRE OPENING (DOUBLE DOOR WITH | | TRANSOM). | | | | 35.)THE DOOR PRODUCT APPROVAL SUBMITTED DOES NOT | | INCLUDE THE TRANSOM ABOVE.PLEASE ADDRESS WITH A | | DETAIL AND PRODUCT APPROVALS FOR MULLIONS, FIXED GLASS | | WINDOW OR SUBMIT A PRODUCT APPROVAL WHICH INCLUDES THE | | USE OF A TRANSOM. | | | | 36.)A5.3, ENTRY OVERHANG TYPE 1, DOES NOT SHOW THE | | 1X2 WHICH IS TYPICALLY INSTALLED UNDER THE DRIP EDGE TO | | PREVENT THE FASCIA BOARD FROM ROTTING.THIS IS SHOWN | | GRAPHICALLY ON ENTRY OVERHANG TYPE 2.YOUR USE OF A PT | | FASCIA IS NOTED; HOWEVER, SINCE A MIAMIDADE NOA WAS | | SUBMITTED FOR THE ROOF SHINGLES, THE SHINGLES ARE TO BE | | INSTALLED IN ACCORDANCE WITH RAS115, RAS111, AND | | FBC1517.6.2.2.PLEASE ADDRESS. | | | | 37.)PROVIDE A DETAIL FOR U301, 2 A7.1. | | | | 38.)S1.0 REFERS TO DESIGN LOAD REQUIREMENTS FOR ONE | | AND TWO FAMILY DWELLINGS.THIS IS MULTIFAMILY, R2, NOT | | ONE AND TWO FAMILY DWELLINGS, R3.SEE FBC TABLE | | 1607.1, 27 RESIDENTIAL AND FBC 310.SEE ALSO | | REQUIREMENTS FOR STAIRS. | | | | 39.)S3 SHEATHING NOTES SPECIFIES 4INCH FOR CORNERS ON | | GABLE ENDS.THIS ROOF IS A HIP ROOF, 4 INCH IS | | REQUIRED FOR ZONE 3 REGARDLESS OF ROOF TYPE. | | | | 40.)S5 WINDOW NOTES SPECIFICATIONS REFER TO 120 MPH, | | CITY OF WEST PALM BEACH IS IN THE 140MPH WIND ZONE. | | | | 41.)FIRE SPRINKLER NOTES REGARDING SPRINKLERS IN | | BATHROOMS IS FOR NFPA13R.THE SYSTEM IS TO COMPLY WITH | | NFPA13. | | | | 42.)CIVILS AND ARCHITECTURALS DO NOT MATCH.PLEASE | | ADDRESS. | | | | 43.)SIGN THE OWNER/AGENT LINE OF THE ENERGY CALC, | | FBC13-103.1. | | | | 44.)IT APPEARS THAT THE GARAGE DOOR BLOCKS THE FIRE | | SPRINKLER HEAD.PLEASE ADDRESS. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2007-07-07 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-07-07 |
Time |
09:45 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-07-07 |
Time |
08:34 |
Sent To |
|
|
Notes |
2007-07-12 16:27:04 | 2007-07-12 16:27:04 | | THIRD SET RETURNED FROM ZONING. STAMPED ELECTRICAL | | SHEETS IN THIRD SET. STILL NEED TO ADDRESS L SHEETS | | COMMENT. | 2007-07-07 09:46:03 | 2007-07-07 09:46:03 | | ** TEMPORARY FAILED STATUS ** | | | | 1) NOTE: PLEASE SEE THE LANDSCAPE AND IRRIGATION SHEETS | | NEED TO BE SEALED WITH CORRECT SEAL AS REQUIRED PER FAC | | 61G1-16.002. | | PLEASE KNOW A TIME CAN BE SET UP FOR THE LANDSCAPE | | ARCHITECT OF RECORD TO COME IN AND SIGN AND SEAL EACH | | OF THESE SHEETS IN EACH SET. | | ** PLEASE BE SURE TO SEE COMMENTS FROM OTHER TRADES | | (ZONING AND PLUMBING) AS ANY OF THEIR COMMENTS MAY | | AFFECT THE LANDSCAPE AND IR PLANS FOR NEEDED REVISIONS. | | IF THE PLANS NEED TO BE REVISED THERE IS NO NEED TO | | RE-SIGN AND SEAL SHEETS WITH NEW SEAL AT THIS TIME. | | THIS WOULD BE DONE ON NEW REVISED SHEETS. | | | | 2) NOTE: PLEASE SEE THAT TWO SETS OF ELECTRICAL AND SL | | PLANS HAVE BEEN STAMPED AND PASSED FOR ELECTRICAL | | REVIEW. | | THE THIRD SET OF E AND SL SHEETS WILL BE STAMPED WHEN | | PLANS ARE BACK FROM ZONING. | | | | 3) NOTE: REDLINED ON LOCATION ON PLANS FOR POSSIBLE | | 210.52 WALL SPACE TO BE VIF. NO NEED TO CHANGE OR | | REVISE PLANS. | | | | | 2007-07-07 08:34:33 | 2007-07-07 08:34:33 | | IN ELEC FOR REVIEW. TWO SETS ONLY AS ZONING HAS ONE. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2007-04-14 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-04-14 |
Time |
15:54 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-04-14 |
Time |
12:47 |
Sent To |
|
|
Notes |
2007-04-14 15:57:58 | | | ** UNSAT2ND REVIEW** | | | | ** PLEASE SEE THAT ITEMS ARE FROM PREVIOUS REVIEW; | | HOWEVER MOST ARE NEW DUE TO CHANGES IN PLANS AND ITEMS | | WHICH ARE NEW TO PLANS SUBMITTED. | | NOW THAT THE CIRCUITING HAS FOR THE MOST PART BEEN | | COMPLETED ON PLANS, THERE ARE SOME NEW COMMENTS BASED | | ON CIRCUITS AS SHOWN. | | | | ** PLEASE KNOW THAT IT IS MOST HELPFUL WHEN A RESPONSE | | LETTER OR COMMENTARY IS SUBMITTED FOR RESPONSE TO THE | | REVIEW COMMENTS AS PREVIOUSLY NOTED. THIS WILL HELP IN | | THE REVIEW PROCESS, HOWEVER NOT REQUIRED. | | | | ** PLEASE SEE ANY REFERENCES IN PLAN REVIEW NOTES TO | | CHAPTER 1 OF THE FBC ARE THAT WHICH IS ADOPTED BY THE | | CITY OF WEST PALM BEACH. | | | | 1) NOTE: PLEASE SEE PLANS ARE STILL INDICATING | | TOWNHOUSE UNITS? PLEASE SEE BUILDING REVIEW COMMENTS AS | | THESE ARE NOT TRUE TOWNHOUSES BY DEFINITIONS. | | PLEASE SEE THAT IF THESE ARE INDEED FEE SIMPLE | | "TOWNHOUSES" AS PER FBC DEFINITIONS, PLEASE SEE | | REQUIREMENTS OF THE FBC AND ELECTRICAL CODE WHICH WOULD | | CHANGE MANY ITEMS IN THE DESIGN AND PLEASE KNOW | | SEPARATE PERMIT APPLICATIONS, PLANS AND FEES WOULD BE | | REQUIRED ON EACH FEE SIMPLE TOWNHOUSE. PLEASE SEE AS | | ALL UNITS ARE CONNECTED BY A COMMON AREA AND ONE | | BUILDING THIS DOES NOT SEEM POSSIBLE. | | PLEASE SEE COMMENTS FROM OTHER TRADES | | FBC ADMIN SECTION 106.1.2 FOR ADDITIONAL INFORMATION. | | | | 2) NOTE:PLEASE SEE THAT THIS IS THE SAME COMMENT FROM | | PREVIOUS REVIEW AND NO CHANGES HAVE BEEN MADE. PLEASE | | KNOW THAT THIS WAS STATED AS BEING REQUIRED WHETHER OR | | NOT COMMENT IS MADE BY ANY OTHER TRADE. | | PLEASE SEE MISSING INFORMATION ON THE TITLE BLOCKS FOR | | THE LANDSCAPE SHEETS AS REQUIRED PER FLORIDA | | ADMINISTRATIVE CODE 61G1-16.004, AND FLORIDA STATUTES | | 481.319. | | PLEASE SEE MISSING CERTIFICATE OF AUTHORIZATION NUMBER, | | PRINTED NAME, PRINTED LICENSE NUMBER ETC. | | PLEASE SEE 481.221 AS PLANS ARE REQUIRED TO BE SIGNED | | WITH LEGAL SIGNATURE AND DATED. | | THIS COMMENT IS REQUIRED WHETHER OR NOT COMMENT IS MADE | | BY ANY OTHER TRADE. | | | | 3) NOTE: PLEASE SEE FBC CHAPTER 13. | | PLEASE SEE ANY "HOUSE" ROOMS WITH LIGHTING WILL REQUIRE | | AUTOMATIC SHUT OFF OF LIGHTING PER 13-415.1.ABC.1.1, | | .1.2, AND .1.3. THESE ROOMS ON PLANS DO NOT INDICATE | | ANY LIGHTING? PLEASE CLARIFY. | | | | 4) NOTE: PLEASE SEE THAT AS FAR AS THIS REVIEW HAS | | TAKEN PLACE, THIS PREVIOUS NOTE IS STILL APPLICABLE. | | PLEASE SEE FBC ADMIN SECTION 109.3.6, 109.3.6.4.4 | | WHICH REQUIRES THE STATEMENT FOR THRESHOLD PROJECTS ON | | ALL ARCH AND ENG SHEETS. | | " TO THE BEST OF THE ARCHITECT'S /OR ENGINEER'S | | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE | | APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE | | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL | | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER | | 633 OF THE FLORIDA STATUTES". | | THIS IS REQUIRED FOR EACH DESIGN PROFESSIONAL ON | | PLANS. | | | | 5) NOTE:PLEASE SEE THE NOTES ALSO STATED BY THE | | BUILDING REVIEWER AS PREVIOUSLY NOTED AS IT SEEMS A FA | | SYSTEM OF SOME TYPE IS REQUIRED FOR THE PARKING GARAGE | | AREA. PLEASE KNOW THAT EVEN IF A SYSTEM IS GOING TO BE | | UNDER A SEPARATE PERMIT, THE BASE BUILDING PLANS SHALL | | INDICATE THE BASE INTENT IN DESIGN FOR LIFE SAFETY. FBC | | 106.3.5.1.2. PLEASE SEE COMMENTS WITH RESPECT TO SMOKE | | ALARM DEVICES IN UNITS. | | | | PLEASE CLARIFY THE TYPE FIRE PROTECTION BEING INSTALLED | | FOR BUILDING. PLEASE SEE ARCHITECTURAL SHEETS REFERENCE | | A 13R , HOWEVER PLEASE SEE NFPA-72 11-5.1.1, 11.8.3. | | PLEASE SEE NFPA-72 DEFINITIONS AS PLANS CALL FOR SD FOR | | SMOKE DETECTORS THIS IS OK, HOWEVER PLEASE KNOW IF | | THESE ARE INDEED SMOKE DETECTORS AS DEFINED IN NFPA72, | | THESE WOULD BE DEVICES WHICH ONLY DETECT AND WOULD | | SIGNAL TO OTHER ALARM/HORN DEVICES. NO ALARM HORN | | DEVICES ARE SHOWN. PLEASE INDICATE IF PART OF A FUTURE | | LV FA SYSTEM. | | | | 6) NOTE: PLEASE SEE THAT THE CIRCUITING IS MISSING FROM | | SEVERAL OF THE SMOKE ALARM DEVICES ON PLANS. PLEASE SEE | | THAT ON THE UNITS WHICH DO INDICATE CIRCUITS, THE PLANS | | INDICATE AS MANY AS 3,4 OR MORE CIRCUITS FOR THE SAME | | SMOKE ALARMS WHICH ARE REQUIRED TO BE WIRED *IN-LINE* | | PER NFPA-72 11.5.1.1.1. PLEASE KNOW AS THESE DEVICES | | ARE WIRED INLINE AND IF ON MORE THAN ONE CIRCUIT AND/OR | | PHASE THIS WOULD SEND 240V TO UNITS AS THEY ARE ALL | | INTERCONNECTED. PLEASE COMPLETE CIRCUITING FOR THE | | DEVICES WHICH ARE MISSING CIRCUITING AND PLEASE ADJUST | | CIRCUITING SO THAT ALL *S* DEVICES ARE WIRED TO THE | | SAME CIRCUIT. | | | | 7) NOTE: PLEASE BE SURE THE *S*/SMOKE ALARM DEVICES | | ARE WIRED TO ONE OF THE EXISTING ARC FAULT CIRCUITS AS | | REQUIRED PER 210.12 OF THE NEC. (SOME OF THE CIRCUITS | | AS SHOWN ON SOME OF THE DEVICES AT THIS TIME ARE NOT | | ARC FAULT CIRCUITS AS NOTED ON PANEL SCHEDULE) | | PLEASE INDICATE THE CIRCUITS ON PANEL SCHEDULE WHICH | | WILL CONTAIN THE AFCI BREAKERS. THIS MAY BE DONE WITH | | AN ASTERISK WHICH CORRELATES TO NOTE BELOW PANEL | | SCHEDULE OR BY SOME OTHER MEANS. | | PLEASE SEE NOTE # 17 BELOW AS THIS WAS NOTED ON | | PREVIOUS REVIEW. | | | | 8) NOTE:PLEASE SEE THIS NOTE REMAINS AS NO NOTES, OR | | DETAIL WAS PROVIDED TO MEET THIS PREVIOUS NOTE. THE | | SECTION OF CODE GIVEN WAS INCORRECT HOWEVER THE CORRECT | | SECTION WAS GIVEN TO THE ENGINEER OVER A PHONE MEETING | | AFTER THE INITIAL REVIEW. | | PLEASE SEE THE CORRECTED SECTION HAS BEEN INSERTED. | | THE SECTION GIVEN WAS FOR THE DESIGNER TO CERIFY THE | | ENERGY CALCULATIONS WHICH WAS CORRECT ALSO. | | PLEASE SEE FBC 2004 13-606.1.ABC.1.2.4 WHICH REQUIRES | | THE TYPE OF RECESSED LIGHTS TO BE INSTALLED. PLEASE | | NOTE ON PLANS ACCORDINGLY AND INDICATE FIXTURES. | | | | 9) NOTE:THIS NOTE WILL REMAIN AS THE NOTE #5 ABOVE IS | | NOT CLEAR AT THIS TIME. THE MINIMUM LEVELS FOR DEVICE | | IN GARAGE AREA WILL BE REQUIRED TO BE INDICATED. | | PLEASE SEE FBC 2004 11-4.28.2, .3(4). PLEASE STATE ALL | | MINIMUM LEVELS AS REQUIRED FOR ALL AREAS WHICH MAY | | CONTAIN ANY FIRE HORN/STROBE DEVICES. AS IT IS NOT | | KNOWN AT THIS TIME OF ANY FIRE ALARM PANEL WILL BE | | REQUIRED FOR THE GARAGE OR BUILDING, PLEASE BE AWARE OF | | THE SECTIONS GIVEN IN ORDER TO INDICATE THE LEVELS AS | | REQUIRED IF A FA SYSTEM IS INSTALLED. 11-4.28.1. PLEASE | | BE SURE TO SEE SECTIONS GIVEN FOR STROBE AND HORN | | DEVICES FROM THE FBC AND PLEASE ALSO SEE NFPA-72. | | PLEASE KNOW THAT THE FBC CHAPTER 11 REQUIREMENTS ARE | | MORE STRINGENT AND THE MORE STRINGENT SHALL APPLY. | | | | 10) NOTE: THIS NOTE WILL REMAIN FROM PREVIOUS REVIEW AS | | CONTROLS ETC ARE NOT CLEAR AT THIS TIME OR SHOWN ON | | ELECTRICAL PLANS. | | PLEASE SEE THAT SENSE THIS GARAGE SEEMS TO BE | | CONSIDERED AN ENCLOSED GARAGE PLEASE SEE THAT THERE MAY | | BE OTHER ELECTRICAL DEVICES WHICH MAY BE REQUIRED FOR | | CO SENSORS ETC. TO BE SHOWN AS PART OF ANY LV | | SYSTEMS/DEVICES ETC. | | THIS IS ONLY NOTED. | | | | 11) NOTE: PLEASE SEE AS THIS IS ONE BUILDING; PLEASE | | SEE 230.2 AS THE PROPOSED SERVICES ARE NOT GRANTED AS | | SHOWN ON PLANS. PLEASE SEE THE SIZE OF THE SERVICES DO | | NOT EXCEED THE RATINGS FOR 2K AMPS FOR THE ADDITIONAL | | SERVICE. | | PLANS AT THIS TIME ARE SHOWING AS MANY AS FOUR | | SERVICES. PLEASE SEE AT THIS TIME ONLY TWO SERVICES | | WILL BE GRANTED BY SPECIAL PERMISSION. THIS MAY BE DONE | | BY ONE MAIN FOR EACH AND FEEDING A MLO METER*-CENTER OR | | SERVICE WHICH WOULD CONTAIN THE MAIN AS PART OF THE | | METER-CENTER. ONE WILL BE PERMITTED AT EACH SIDE OF THE | | BUILDING AS SHOWN. | | PLEASE SEE THAT SIGNAGE NOTES WILL BE REQUIRED ON PLANS | | FOR CORRECT SIGNS TO BE INSTALLED PER 230.2E. PLEASE | | KNOW THAT ALL SIGNS SHALL HAVE LETTERING A MINIMUM OF | | 1INCH WITH A CONTRASTING BACKGROUND. | | PLEASE REVISE SERVICE RISER DIAGRAM FOR GROUPING OF | | MAINS AND SERVICES. | | PLEASE SEE OTHER COMMENTS WITH RESPECT TO LOAD | | CALCULATIONS. | | PLEASE REVISE RISER DIAGRAM. | | | | 12) NOTE: PLEASE SEE 250.50, 250.104 ETC FOR MISSING | | ATTACHMENTS FOR THE FIRE SPRINKLER LINE. | | | | 13) NOTE:PLEASE SEE AS NEW CIRCUITS ARE NOW SHOWN ON | | PLANS, PLEASE SEE 210.52B1, 210.11C1, AND 220.16 AS THE | | DINING ROOM RECEPTACLES ARE TO BE ON ONE OR MORE OF THE | | SMALL APPLIANCE CIRCUITS. THESE CIRCUITS MUST BE | | FIGURED AT 1500VA MINIMUM (1000VA SHOWN), MAY NOT FEED | | ANY OTHER DEVICES WHICH ARE OUTSIDE THE DINING | | DESIGNATED AREAS. | | PLEASE ALSO SEE SOME PLANS WHICH INDICATE THE DINING | | CIRCUIT AS CIRCUIT #25 DOES NOT SHOW ON PANEL SCHEDULE | | AS THE PANEL SCHEDULE IS SHOWN INDICATING A *SPARE* | | WITH A 1000VALOAD DESIGNATED. | | PLEASE SEE UNIT B, C AND D AS THIS SCENARIO EXIST. | | PLEASE SEE THIS WAS NOTED ON NOTE #25 ON PREVIOUS | | REVIEW. | | | | 14) NOTE:PLEASE SEE SOME AREAS OF ROOMS DO NOT SEEM | | TO MEET 210.52 FOR RECEPTACLE SPACING. PLEASE SEE SOME | | UNITS WHICH RAIL AREAS ARE ACTUALLY PART OF THE ROOMS. | | PLEASE ALSO SEE DINING ROOM WALLS WHICH ARE MISSING | | DEVICES. PLEASE SEE UNITS A, B, C AND D. | | NOTE #27 PREVIOUS REVIEW | | | | 15) NOTE: PLEASE SEE SOME AREAS WHICH A RECEPTACLE | | DEVICE SEEMS TO BE SHOWN TO MEET 210.52H FOR HALLWAYS, | | YET THIS DEVICE IS ACTUALLY LOCATED IN WHAT WOULD BE AN | | EGRESS PATH AND WOULD CREATE A TRIPPING HAZARD. PLEASE | | SEE PLANS FOR ALTERNATE LOCATIONS WHICH ARE PERHAPS ON | | OPPOSITE WALLS; SOME ARE THE POWDER ROOM WALLS ETC | | WHICH WOULD BE PERMITTED. | | PLEASE SEE SOME REDLINED AREAS ON PLANS. PLEASE KNOW | | THIS CAN BE GONE OVER ON THE PHONE AS LONG AS A SET OF | | PLANS ARE STILL LOCATED IN THIS OFFICE. | | NOTE #27 PREVIOUS REVIEW. | | | | 16) NOTE: PLEASE SEE PANELS SCHEDULE FOR ALL UNITS | | WHICH CONTAIN A WHIRLPOOL TUB, HOWEVER THE LOAD | | CALCULATIONS DO NOT INDICATE THIS LOAD OF THIS JACUZZI | | TUB. PLEASE COORDINATE UNIT PANEL SCHEDULE AND REVISED | | LOAD CALCULATIONS. | | FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION. | | NEC 680.71, 408.4. | | | | 17) NOTE: PLEASE LIST THE REQUIRED ARC FAULT PROTECTED | | CIRCUITS ON THE PANEL SCHEDULE. PLEASE KNOW THE NOTE ON | | PLANS IS NOT ENOUGH AT THIS TIME. PLEASE SEE THIS CAN | | BE DONE WITH AN * AT EACH CIRCUIT TO THIS NOTE ONCE ALL | | CIRCUITING IS PLACED ON PLANS. PLEASE BE SURE TO SEE | | NOTE PERTAINING TO SMOKE ALARM/DETECTORS DEVICES AND | | WHICH TYPE WILL BE INSTALLED. THIS WILL AFFECT THE | | CIRCUITING AND INDICATION OF THE REQUIRED AFCI | | PROTECTION. | | 2002 NEC 210.12 | | | | 18) NOTE: PLEASE SEE THAT NOW LOAD CALCULATIONS HAVE | | BEEN SUBMITTED, PLEASE SEE NOTES PERTAINING TO | | ADDITIONAL SERVICES. PLEASE SEE THE LOAD SHOWN FOR | | PANEL HP IS SHOWN AS ONE LOAD ON LOAD CALCULATIONS AND | | A DIFFERENT LOAD ON PANEL SCHEDULE. | | PLEASE ALSO SEE THIS PANEL IS BEING SHOWN WITH 42POLES, | | YET THE PANEL SCHEDULE INFORMATION INDICATES ONLY | | 30POLES. | | PLEASE CORRELATE THE ABOVE. | | FBC 106.1.2, 106.3.5.1.2 | | | | 19) NOTE: PLEASE SEE THERE ARE SEVERAL ELECTRICAL | | DEVICES ON PLANS WHICH DO NOT INDICATE ANY CIRCUITING. | | PLEASE SEE MASTER BATH GFI'S UNIT A, COMMON HALLS, | | BEDROOMS ETC FOR UNIT C, AND SOME OTHERS IN OTHER | | UNITS. | | PLEASE SEE NOTE PERTAINING TO CIRCUITING OF SMOKE | | ALARMS, DINING AND OTHER DEVICES. | | 408.4, 310.16, 240.4. | | FBC 106.3.1.2, 106.1.2 | | | | 20) NOTE: PLEASE SEE THIS NOTE FROM PREVIOUS REVIEW. | | PLEASE SEE THE DEVICE HEIGHTS ARE SHOWN , HOWEVER | | INSTALLATION AND NOTES AS THIS IS REQUIRED PER FHAR | | 24CFR 100.205 SHOULD BE INDICATE ON PLANS AS THE | | INSTALLATION OF DEVICES FOR OTHER CLEARANCES ETC ARE | | REQUIRED. | | AS NOTED ON PREVIOUS REVIEW* | | PLEASE INDICATE ALL DEVICE HEIGHTS. PLEASE SEE IF THIS | | IS GOING TO BE A MULTI-FAMILY BUILDING AS SHOWN, PLEASE | | SEE FHAR 24CFR100.205 FOR FIRST FLOOR AT A MINIMUM. | | PLEASE KNOW IF ANY VERTICAL ACCESSIBILITY IS INSTALLED, | | THEN THESE DEVICE HEIGHTS AND LOCATIONS SHALL BE FOR | | ALL FLOORS OR FLOORS THAT THE VERTICAL ACCESS IS | | PROVIDED. | | (15INCHES MIN FOR RECEPTS, 48INCHES MAX FOR SWITCHES, | | ETC). | | | | 21) NOTE:PLEASE SEE 13-413.1ABC.1 OF THE 2004 FBC. | | PLEASE INDICATE THE VOLTAGE DROP FOR FEEDERS/BRANCH | | CIRCUITS. THIS CAN BE DONE IN A WORST CASE SCENARIO. | | THIS WAS NOT NOTED IN PREVIOUS REVIEW AND IS A NEW | | COMMENT. | | | | 22) NOTE: PLEASE SEE SOME SHEETS ARE NOW SHOWING AN | | ADDRESS OF 2918 AND MANY SHEETS IN THE SET DO NOT | | INDICATE ANY ADDRESS OF PROJECT AT ALL. | | PLEASE SEE THE ADDRESSING REVIEWER'S COMMENTS AND | | PLEASE SEE OUR COMPUTER SYSTEM FOR THIS PCN IS STILL | | INDICATING 2900. PLEASE BE SURE NOT TO MAKE ANY CHANGES | | UNTIL THE FINAL ADDRESS HAS BEEN ISSUED BY THE | | ADDRESSING REVIEWER. | | PLEASE SEE THAT THE ADDRESS FOR THIS PROJECT SHALL BE | | PLACED ON THE TITLE BLOCKS. PLEASE KNOW AT THIS TIME, | | THIS IS A MULTI-FAMILY SINGLE BUILDING WITH THE ADDRESS | | OF 2900 BROADWAY. | | THIS IS NOT AND HAS NOT BEEN SUBMITTED AS TOWNHOUSES, | | OR CONDO'S. | | FAC 61G15-23.002, FAC 61G1-16.004 | | | | 23) NOTE: PLEASE SEE THE HOUSE PANEL INDICATES *ALLEY | | LIGHTS*, YET THESE CIRCUITS AND LIGHTING COULD NOT BE | | LOCATED ON PLANS. | | IF THESE ARE SITE LIGHTING POLES, PLEASE BE SURE TO | | SUBMIT THE REQUIRED WIND LOAD CALCULATIONS AND | | INFORMATION FOR BUILDING REVIEW. | | IF THESE ARE NOT POLES PLEASE INDICATE ON PLANS. ARE | | THE LIGHTS ON BACK OF BUILDING ACTUALLY THES LIGHTS, | | ONLY THE CIRCUITING IS NOT SHOWN?? | | PLEASE CLARIFY. | | FBC 106.1.2 | | | | 24) NOTE: PLEASE SEE THE ATTACHED COPY OF FS | | 553.80(2)(B) WITH RESPECT TO REPEAT COMMENTS. THIS IS | | ONLY GIVEN AS A NOTICE AT THIS TIME. | | | | * ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2007-01-07 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-01-07 |
Time |
17:52 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-01-07 |
Time |
14:00 |
Sent To |
|
|
Notes |
2007-01-07 17:52:04 | ** UNSAT ** | | | | ** PLEASE SEE THESE ARE COMMENTS BASED ON THE PLANS | | SUBMITTED. PLEASE SEE THAT THERE MAY BE COMMENTS ON THE | | NEXT REVIEW WHICH MAY BE NEW AS SOME INFORMATION AS | | SHOWN ON THESE PLANS WILL BE CHANGING SYSTEMS. | | | | ** PLEASE SEE ANY REFERENCES IN PLAN REVIEW NOTES TO | | CHAPTER 1 OF THE FBC ARE THAT WHICH IS ADOPTED BY THE | | CITY OF WEST PALM BEACH. | | | | 1) NOTE: PLEASE SEE PLANS ARE BEING SUBMITTED AND | | LABELED AS TOWNHOUSE UNITS, HOWEVER PLEASE SEE IF THESE | | ARE INDEED FEE SIMPLE "TOWNHOUSES" AS PER FBC | | DEFINITIONS, PLEASE SEE REQUIREMENTS OF THE FBC AND | | ELECTRICAL CODE WHICH WOULD CHANGE MANY ITEMS IN THE | | DESIGN AND PLEASE KNOW SEPARATE PERMIT APPLICATIONS, | | PLANS AND FEES WOULD BE REQUIRED ON EACH FEE SIMPLE | | TOWNHOUSE. PLEASE SEE AS ALL UNITS ARE CONNECTED BY A | | COMMON AREA AND ONE BUILDING THIS DOES NOT SEEM | | POSSIBLE. | | PLEASE KNOW THE PLANS AS SUBMITTED IS FOR ONE BUILDING | | AND PLEASE SEE COMMENTS FOR ELECTRICAL SERVICE(S) AS | | SUBMITTED. | | PLEASE CORRELATE SITE SURVEY PLANS WITH THAT OF THE | | SITE CIVIL PLANS. PLEASE SEE THERE ARE TWO COMPLETELY | | DIFFERENT LAYOUTS FOR THE PROPOSED BUILDING AND SITE. | | TH SITE SURVEY DIFFER FROM THE "A" SHEETS AND OTHER | | PLANS. | | PLEASE SEE COMMENTS FROM OTHER TRADES | | FBC ADMIN SECTION 106.1.2 FOR ADDITIONAL INFORMATION. | | | | 2) NOTE: PLEASE SEE MISSING INFORMATION ON THE TITLE | | BLOCKS FOR THE LANDSCAPE SHEETS AS REQUIRED PER FLORIDA | | ADMINISTRATIVE CODE 61G1-16.004, AND FLORIDA STATUTES | | 481.219. | | PLEASE SEE MISSING CERTIFICATE OF AUTHORIZATION NUMBER, | | PRINTED NAME, PRINTED LICENSE NUMBER ETC. | | PLEASE SEE 481.221 AS PLANS ARE REQUIRED TO BE SIGNED | | WITH LEGAL SIGNATURE AND DATED. | | THIS COMMENT IS REQUIRED WHETHER OR NOT COMMENT IS MADE | | BY ANY OTHER TRADE. | | | | 3) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.1AB.1 FOR | | MISSING ENERGY CALCULATIONS FOR "HOUSE" CONNECTED | | POWER. | | PLEASE ALSO SEE 13-415.2 FOR PERFORMANCE CALCULATIONS | | FOR "HOUSE". | | PLEASE SEE ANY "HOUSE" ROOMS WITH LIGHTING WILL REQUIRE | | AUTOMATIC SHUT OFF OF LIGHTING PER 13-415.1.ABC.1.1, | | .1.2, AND .1.3. | | | | 4) NOTE: PLEASE SE POSSIBLE BUILDING REVIEW COMMENTS IF | | THIS BUILDING IS CONSIDERED A THRESHOLD BUILDING OR | | THAT WHICH WILL REQUIRE A SPECIAL INSPECTOR. PLEASE SEE | | FS 553.71(7), FBC ADMIN SECTION 109.3.6 PLEASE KNOW IF | | THIS BUILDING IS EITHER ONE, THREE SETS OF PLANS WILL | | BE REQUIRED FOR PROJECT. | | | | 5) NOTE: PLEASE SEE FBC ADMIN SECTION 109.3.6, | | 109.3.6.4.4 WHICH REQUIRES THE STATEMENT FOR THRESHOLD | | PROJECTS ON ALL ARCH AND ENG SHEETS. | | " TO THE BEST OF THE ARCHITECT'S /OR ENGINEER'S | | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE | | APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE | | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL | | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER | | 633 OF THE FLORIDA STATUTES". | | THIS IS REQUIRED FOR EACH DESIGN PROFESSIONAL ON | | PLANS. | | | | 6) NOTE: PLEASE CLARIFY THE TYPE FIRE PROTECTION BEING | | INSTALLED FOR BUILDING. PLEASE SEE ARCHITECTURAL SHEETS | | REFERENCE A 13R , HOWEVER PLEASE SEE NFPA-72 11-5.1.1, | | 11.8.3. PLEASE SEE NFPA-72 DEFINITIONS AS PLANS CALL | | FOR SD FOR SMOKE DETECTORS THIS IS OK, HOWEVER PLEASE | | KNOW IF THESE ARE INDEED SMOKE DETECTORS AS DEFINED IN | | NFPA72, THESE WOULD BE DEVICES WHICH ONLY DETECT AND | | WOULD SIGNAL TO OTHER ALARM/HORN DEVICES. NO ALARM HORN | | DEVICES ARE SHOWN. PLEASE INDICATE IF PART OF A FUTURE | | LV FA SYSTEM. | | PLEASE KNOW AS PER SECTIONS GIVEN IF THESE ARE INDEED | | DEVICES WHICH DETECT AND ALSO SOUND AN ALARM, THEN THEY | | WOULD BE LABELED AS SA FOR SMOKE ALARMS. | | PLEASE KNOW AS OF OCT 06 IT CAME TO OUR ATTENTION AT | | THE SOUTHERN SECTION MEETING FROM NFPA THAT IF UNITS | | ARE INDEED DEVICES WHICH DETECT AND SOUND AN ALARM, | | PLANS SHOULD SHOW THEM AS SA'S AND THIS IS NOT NEW | | CODE. THIS HAS BEEN AN ACCEPTED METHOD IN THE PAST TO | | SHOW SD FOR BOTH HOWEVER ALL PLANS SINCE OCT 06 SHOULD | | BE CHANGING IF AND WHERE APPLICABLE. | | IF PART OF A LV FIRE/SECURITY SYSTEM PLEASE INDICATE AS | | SUCH. PLEASE SHOW DEVICES THEN FOR SOUNDING. PLEASE | | ALSO SEE MISSING SMOKE DETECTION/ SMOKE ALARM DEVICE IN | | UNIT "C" FIRST FLOOR. | | | | 7) NOTE: PLEASE SEE FBC 2004 13-103.1.1.1 WHICH | | REQUIRES THE TYPE OF RECESSED LIGHTS TO BE INSTALLED. | | PLEASE NOTE ON PLANS ACCORDINGLY AND INDICATE | | FIXTURES. | | | | 13) NOTE: PLEASE SEE FBC 2004 11-4.28.2, .3(4). PLEASE | | STATE ALL MINIMUM LEVELS AS REQUIRED FOR ALL AREAS | | WHICH MAY CONTAIN ANY FIRE HORN/STROBE DEVICES. AS IT | | IS NOT KNOWN AT THIS TIME OF ANY FIRE ALARM PANEL WILL | | BE REQUIRED FOR THE GARAGE OR BUILDING, PLEASE BE AWARE | | OF THE SECTIONS GIVEN IN ORDER TO INDICATE THE LEVELS | | AS REQUIRED IF A FA SYSTEM IS INSTALLED. 11-4.28.1 | | PLEASE BE SURE TO SEE SECTIONS GIVEN FOR STROBE AND | | HORN DEVICES FROM THE FBC AND PLEASE ALSO SEE NFPA-72. | | PLEASE KNOW THAT THE FBC CHAPTER 11 REQUIREMENTS ARE | | MORE STRINGENT AND THE MORE STRINGENT SHALL APPLY. | | | | 8) NOTE: PLEASE BE SURE PLANS REFLECT THE CODES IN | | WHICH THE DESIGN IS UNDER AND PERMITTED UNDER. PLEASE | | LIST THE FOLLOWING AT A MINIMUM FOR ELECTRICAL SHEETS | | AND ARCHITECTURAL SHEETS. | | 2002 NFPA-70 (NEC), 2002-NFPA-72 NATIONAL FIRE ALARM | | CODE AND 2003 NFPA-101 LIFE SAFETY CODE. | | ** PLEASE KNOW FOR INFORMATIONAL PURPOSE, AS OF | | DECEMBER 8TH, 2006 THE STATE OF FLORIDA ADOPTED THE | | 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70( | | NEC). AS THIS PROJECT WAS SUBMITTED FOR PERMIT BEFORE | | THIS DATE, THIS PROJECT IS UNDER THE PREVIOUS CODES AS | | STATED ABOVE. (NOTED FOR INFORMATION ONLY) | | | | 9) NOTE: PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR ALL | | EGRESS PATHS UNDER NORMAL LIGHTING LEVELS AND UNDER | | EMERGENCY LIGHTING LEVELS TO THE PUBLIC RIGHT OF WAY | | OUT AND AWAY FROM BUILDING. | | PLEASE SEE NFPA-101 7.8 AND 7.9 AS BATTERY BACK UP | | LIGHTS OF SOME KIND WILL BE REQUIRED FOR EGRESS OUT OF | | THE GARAGE AREA. | | PLEASE SEE 700.12E FOR CIRCUITING . | | FBC 106.1.2 ADMIN SECTION. | | REVIEW FOR COMPLIANCE OF THIS CAN NOT BE DONE AT THIS | | TIME. | | | | 10) NOTE: PLEASE PROVIDE MORE INFORMATION FOR FAIL SAFE | | OPERATION OF THE ELECTRICAL GATES AS SHOWN ON PLANS. | | PLANS NOTE IN MANY LOCATIONS THAT THE GATES SHALL | | AUTOMATICALLY OPEN IN THE EVENT OF POWER FAILURE; | | HOWEVER THERE ARE TWO SCENARIOS WHICH NEED TO BE | | ADDRESSED. | | A) PLEASE INDICATE HOW GATES WILL OPEN UNDER POWER | | FAILURE. (BATTERY BACK UP? ETC) | | B) PLEASE KNOW THAT IN AN EMERGENCY AND POWER IS STILL | | ON, THE OCCUPANTS SHALL BE ABLE TO EGRESS FROM THIS | | AREA OF THE STRUCTURE WITHOUT ANY IMPEDANCE FROM | | DEVICES WHICH MAY FAIL OR DELAY EGRESS IN ANY FASHION. | | PLEASE SEE NFPA-101 7.2, MORE SPECIFICALLY: 7.2.1.5.1 | | DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM THE | | EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. | | | | 7.2.1.5.2 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE | | OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR | | OPERATION FROM THE EGRESS SIDE. | | THERE ARE NUMEROUS OTHER CODE SECTIONS, HOWEVER ONLY | | NOTED A COUPLE. | | PLEASE SEE REVIEW NOTES FROM THE FIRE MARSHAL AND | | BUILDING REVIEWER WHICH MAY ALSO ADDRESS THIS COMMENT. | | PLEASE KNOW THAT MORE INFORMATION IS REQUIRED FOR THIS | | WHETHER OR NOT COMMENT IS MADE SPECIFICALLY BY OTHER | | TRADES. | | THIS WILL AFFECT THE ELECTRICAL PLANS AND ALONG WITH | | NOTES ON POSSIBLE "A" SHEETS. | | | | 11) NOTE: PLEASE SEE THAT SENSE THIS GARAGE SEEMS TO BE | | CONSIDERED AN ENCLOSED GARAGE PLEASE SEE THAT THERE MAY | | BE OTHER ELECTRICAL DEVICES WHICH MAY BE REQUIRED FOR | | CO SENSORS ETC. TO BE SHOWN AS PART OF ANY LV | | SYSTEMS/DEVICES ETC. | | THIS IS ONLY NOTED. | | | | 12) NOTE: PLEASE SEE AS THIS IS ONE BUILDING; PLEASE | | SEE 230.2 AS THE PROPOSED SERVICES ARE NOT GRANTED AS | | SHOWN ON PLANS. PLEASE REVISE SERVICE RISER DIAGRAM FOR | | GROUPING OF MAINS AND SERVICES. | | PLEASE SEE PLANS DO NOT CORRELATE WITH RISER AT THIS | | TIME; PLEASE SEE EACH UNIT SHOWS AN ELECTRICAL METER AT | | EACH UNIT WHICH IS NOT PERMITTED. | | PLEASE SEE OTHER COMMENTS WITH RESPECT TO LOAD | | CALCULATIONS. | | PLEASE REVISE RISER DIAGRAM. | | | | 13) NOTE: PLEASE SEE 250.50, 250.104 ETC FOR MISSING | | ATTACHMENTS FOR THE FOOTER STEEL AND FIRE SPRINKLER | | LINES. | | | | 14) NOTE: PLEASE SHOW ALL ROOMS AND AREA DESIGNATIONS | | ON PLANS. PLEASE COMPLETE ALL CIRCUITING ON PLANS AND | | CORRELATE WITH THE PANEL SCHEDULES SUBMITTED. PLEASE | | SEE THERE ARE SOME ITEMS WHICH CAN NOT BE REVIEWED FOR | | CODE COMPLIANCE AT THIS TIME DUE TO THIS INFORMATION | | NOT SHOWN. | | NEC 408.4, 310.16, 240.4 ETC. | | FBC 106.1.2, 106.3.5.1.2 ADMIN SECTIONS. | | | | 15) NOTE: PLEASE SUBMIT PANEL SCHEDULES SPECIFIC TO | | EACH UNIT. THESE CAN NOT BE TYPICAL FOR A, B AND D AS | | SUBMITTED AS SOME OF THESE UNITS DO NOT CONTAIN | | ELECTRICAL APPLIANCES AS NOTED ON PANEL SCHEDULE(S) AND | | SOME UNITS DO NOT CONTAIN THE SAME ELECTRICAL POWER | | REQUIREMENTS FOR THE FOLLOWING LISTED IN NOTES TO COME. | | PLEASE KNOW ALL CIRCUITING AND IDENTIFICATION ON PANELS | | NEEDS TO BE SPECIFIC TO ROOMS AND AREAS IN WHICH THEY | | FEED. | | IE: LIVING RM LTS,BEDRM RECEPTS , DINING RM, ETC. | | 408.4, 310.16, | | FBC 106.1.2, 106.3.5.1.2 | | | | 16) NOTE: PLEASE SEE MECHANICAL PLANS WHICH INDICATE | | LOADS FOR THE AHU WITH LESS OF A LOAD THAN THAT SHOWN | | ON THE PANEL SCHEDULES AND LOAD CALCULATIONS | | SUBMITTED. | | PLEASE CORRELATE ALL OVER CURRENT PROTECTION DEVICES | | WITH EACH. AS NOTED ABOVE IN NOTE #15, EACH PANEL SHALL | | BE SPECIFIC AS THE CU'S CONTAIN DIFFERENT OVER CURRENT | | PROTECTION FOR EACH UNIT. PLEASE ALSO SEE THE OVER | | PROTECTION FOR BOTH THE AHU'S AND THE CU'S SHALL | | CORRELATE WITH THE PANEL SCHEDULES. | | 424.3B, 240.4, 310.16 ETC. | | | | 17) NOTE: PLEASE SEE PANELS SCHEDULE FOR ALL UNITS | | INDICATE A WHIRLPOOL TUB, HOWEVER THE PLANS DO NOT SHOW | | THE SAME OR CONTAIN ELECTRICAL GFI'S AT THE TUB | | LOCATIONS? | | PLEASE CORRELATE EACH UNIT WITH PANEL SCHEDULE TO BE | | SUBMITTED FOR EACH UNIT. | | FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION. | | NEC 680.71 | | | | 18) NOTE: PLEASE SEE THE LOAD SHOWN ON THE PANEL | | SCHEDULE FOR THE GARAGE DOOR OPENER DOES NOT CORRELATE | | WITH THE LOAD CALCULATIONS. PLEASE CORRELATE. 408.4, | | 220.31 | | | | 19) NOTE: PLEASE SEE BOTH THE DISHWASHER AND DISPOSAL | | ARE BEING FED TO THE SAME RECEPTACLE DEVICE/YOKE WHICH | | IS OK AND A TYPICAL INSTALLATION; HOWEVER PLEASE SEE | | 210.4(A)&(B) AS THESE SHALL BE FED FROM THE SAME | | BREAKER WHICH WOULD BE A 2-POLE BREAKER. NO HANDLE TIES | | ARE PERMITTED. THE OTHER SCENARIO WOULD BE TO INSTALL | | TWO INDIVIDUAL SINGLE RECEPTACLES. | | PLEASE VERIFY THIS AS THE LOADS SHOWN FOR EACH UNIT | | SEEM TO EXCEED THAT OF A STANDARD 15A RATED DEVICE. | | MUST BE 20A RATED. PLEASE VERIFY 210.21(B)(2) AND | | (B)(3). | | | | 20) NOTE: PLEASE LIST THE REQUIRED ARC FAULT PROTECTED | | CIRCUITS ON THE PANEL SCHEDULE. PLEASE KNOW THE NOTE ON | | PLANS IS NOT ENOUGH AT THIS TIME. PLEASE SEE THIS CAN | | BE DONE WITH AN * AT EACH CIRCUIT TO THIS NOTE ONCE ALL | | CIRCUITING IS PLACED ON PLANS. PLEASE BE SURE TO SEE | | NOTE PERTAINING TO SMOKE ALARM/DETECTORS DEVICES AND | | WHICH TYPE WILL BE INSTALLED. THIS WILL AFFECT THE | | CIRCUITING AND INDICATION OF THE REQUIRED AFCI | | PROTECTION. | | 2002 NEC 210.12 | | | | 21) NOTE: PLEASE SEE PLANS CONTAIN A NOTE THAT STATE | | ALL EXTERIOR LIGHT FIXTURES SHALL BE RATED FOR "DAMP | | LOCATION"?? PLEASE KNOW THAT ANY FIXTURES OUTSIDE SHALL | | BE LISTED FOR "WET LOCATIONS". | | 110.3, 90.4 | | | | 22) NOTE: PLEASE SEE MISSING THE REQUIRED GFI FOR SOME | | CONDENSING UNITS PER 210.63, 210.8A3 (UNIT "C"). | | | | 23) NOTE: PLEASE SEE SUBMIT COMPLETE LOAD CALCULATIONS | | FOR SERVICE. 220..3, 220.10, 220.11, 220.13 AND 220.32 | | ETC | | PLEASE KNOW DEPENDING ON THE NEW SERVICE AND LOAD, | | CONSIDERATION OF 230.2 WILL BE REVIEWED, HOWEVER PLEASE | | KNOW AT THIS TIME THE FOUR SERVICES AS SHOWN WILL NOT | | BE GRANTED IN EITHER CASE AND ANY SERVICES GRANTED FOR | | THIS SINGLE BUILDING WILL STILL REQUIRE MAINS TO BE | | GROUPED AS PREVIOUSLY NOTED ABOVE. | | | | 24) NOTE: PLEASE SEE 210.52D FOR UNIT "A" MASTER BATH | | WHICH WILL REQUIRE THE ADDITION OF ONE ADDITIONAL GFI | | RECEPT OR MOVE THE ONE SHOWN BETWEEN THE TWO LAVATORIES | | AS SHOWN. PLEASE KNOW THE CROSSING OVER A SINK/LAVATORY | | IS NOT PERMITTED IN ORDER TO PLUG IN ANY APPLIANCE FOR | | USE. | | | | 25) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.16 OR | | DINING ROOMS AND AREAS OF THE LIKE. AS NOTED ABOVE, | | REVIEW FOR CIRCUITING OF THIS AREA CAN NOT BE DONE AT | | THIS TIME. | | | | 26) NOTE: PLEASE INDICATE ALL DEVICE HEIGHTS. PLEASE | | SEE IF THIS IS GOING TO BE A MULTI-FAMILY BUILDING AS | | SHOWN, PLEASE SEE FHAR 24CFR100.205 FOR FIRST FLOOR AT | | A MINIMUM. PLEASE KNOW IF ANY VERTICAL ACCESSIBILITY IS | | INSTALLED, THEN THESE DEVICE HEIGHTS AND LOCATIONS | | SHALL BE FOR ALL FLOORS OR FLOORS THAT THE VERTICAL | | ACCESS IS PROVIDED. | | (15INCHES MIN FOR RECEPTS, 48INCHES MAX FOR SWITCHES, | | ETC). | | | | 27) NOTE: PLEASE SEE 210.52 FOR AREAS FOR REQUIRED | | RECEPTS WHICH ARE MISSING ON PLANS. PLEASE SEE UNIT "C" | | ETC. | | PLEASE ALSO SEE OTHER AREAS PER 210.52H FOR HALLWAYS | | WHICH MAY HAVE A WALL SPACE 10FT OR MORE. | | ** PLEASE KNOW ANY ROOMS WHICH CONTAIN RAILINGS MAY BE | | REQUIRED TO CONTAIN RECEPTACLES ALONG THESE RAILINGS AS | | RAILS ARE CONSIDERED WALL SPACE. | | PLEASE SEE ONE SET OF PLANS ARE REDLINED FOR LOCATIONS | | WHICH ARE MISSING DEVICES WITHIN 6FT OF DOOR, 2FT OR | | MORE OF WALL SPACE AND HALLWAYS AS NOTED. | | | | 28) NOTE: PLEASE SEE SOME DEVICES WHICH APPEAR TO BE | | 3-WAY; DO NOT CONTAIN THE SWITCH WITH THE 3-WAY | | DESIGNATION. PLEASE VERIFY ALL. (UNIT "C"). | | | | 29) NOTE: SEE SOME UNITS SHOW WHAT APPEARS TO BE A | | STACK WASHER DRYER, HOWEVER NOTATION FOR SUCH ON PLANS | | AND PANEL SCHEDULES COULD NOT BE FOUND. | | PLEASE LIST. 408.4. | | FBC 106.1.2 | | | | 30) NOTE: PLEASE CORRELATE THE LOADS FOR THE RANGE. | | PANEL SCHEDULE SHOWS 10KW AND THE LOAD CALCULATIONS | | INDICATE 10KW? | | 310.16, 408.4, 240.4, 220.19 | | | | 31) NOTE: PLEASE SEE LIGHT AND RECEPT ON THE "C" UNITS | | 2ND FLOOR WHICH SEEMS TO BE LOCATED TOO FAR OVER AND | | PAST THE RAIL AREA OR NEXT BUILDING LOCATION. | | IF THE GFI IS THAT FOR THE CU AS NOTED IN NOTE #22 | | ABOVE, DISREGARD NOTE #22 AND RELOCATE. | | | | 32) NOTE: PLEASE COMPLETE RISER DIAGRAM WITH ALL | | FEEDERS TO UNITS AND CORRELATE WITH THE OVER CURRENT | | PROTECTION DEVICES OF THAT FOR EACH UNIT. | | 215.5, 310.16, 240.4 ETC. | | FBC 106.1.2, 106.3.5.1.2 | | | | 33) NOTE: PLEASE INDICATE THE EQUIPMENT GROUNDING | | CONDUCTORS FROM MAINS TO EACH UNIT PER 250.122. | | 250.24B, 250.110, ETC. | | | | 34) NOTE: PLEASE SEE THAT THE ADDRESS FOR THIS PROJECT | | SHALL BE PLACED ON THE TITLE BLOCKS. PLEASE KNOW AT | | THIS TIME, THIS IS A MULTI-FAMILY SINGLE BUILDING WITH | | THE ADDRESS OF 2900 BROADWAY. | | THIS IS NOT AND HAS NOT BEEN SUBMITTED AS TOWNHOUSES, | | OR CONDO'S. | | FAC 61G15-23.002, FAC 61G1-16.004 | | | | | | * ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | 2007-01-07 14:00:56 | IN ELEC FOR REVIEW. |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
3 |
Status |
P |
Date |
2007-08-08 |
|
|
Cont ID |
|
Sent By |
rchokshi |
Date |
2007-08-08 |
Time |
13:25 |
Rev Time |
0.00 |
Received By |
rchokshi |
Date |
2007-08-08 |
Time |
13:25 |
Sent To |
|
|
Notes |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
2 |
Status |
F |
Date |
2007-04-20 |
|
|
Cont ID |
|
Sent By |
rchokshi |
Date |
2007-04-20 |
Time |
14:21 |
Rev Time |
0.00 |
Received By |
rchokshi |
Date |
2007-04-20 |
Time |
13:47 |
Sent To |
|
|
Notes |
2007-04-20 14:21:35 | PLEASE PROVIDE FOLLOWING INFO: | | | | 1. PLEASE SHOW STANDARDS NOTES OF CITY OF WPB ON | | DRAWINGSFOR SIDEWALK WIDTH , ITS SLOPE, DRIVEWAY, | | PARKING, HANDICAP PARKING, PAINTPER CITY CODES ETC.,, | | MUST MEET PER ADA,,ETC., | | 2. DUMPSTER: IN YOUR RESPOSE LETTER( YOU DO NOT HAVE | | THE DATE ON THE LETTER), YOU SAID "SEE SITE PLAN SHEET | | A2.1" WE CAN NOT FIND IT ON SHEET A2.1.SO,PLEASE | | SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE DETAILS PER | | CITY OF WPB, &LOCATION ON DWG, LOCATION MUST BE | | ACCESSIBLE FOR PICKUP TRUCK. | | 3. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD , | | SIDEWALK ELEVATION MUST MEET FL BLDG CODE, PLEASE SHOW | | ON THE DRAWINGS & SHOW CALCULATION USING WHICH FLOOD | | ZONE, 100 YEAR FOOD, 25 YEAR FLOOD, ETC, ETC. . | | 4. PLEASE SHOW CALCULATION FOR LENGTH OF THE | | EXFILTRATION TRENCH. | | 5.PLEASE SHOW STORM WATER QUALITY CALCULATIONS, WHAT | | CRITERIA YOU ASSUMEDFOR RUNOFF CAL.,, LIKE 1" OVER | | ENTIRE SITE OR2.5"CRITERIA, ?PERVIOUS AREA, LIKE | | GREEN, LAKES, ETC,IMPERVIOUS AREA CAL., | | 6.PLEASE SHOW ON DRAWINGS:WHAT IS THE SITE | | AREA,PERVIOUS/IMPERVIOUS AREAS.GREEN, LAKE AREA ETC | | YOU ARE DEVELOPING FOR THIS PROJECT ONLY ? | | 7. HOW YOU CONNECT TO THE STORM WATER PIPES IN YOUR | | SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER PIPES | | AROUND YOUR SITE SO, WE CANSEE THE BEST PIPE TO | | CONNECT WITH THE STORM WATERFROM ALL OTHER STORM | | WATER PIPES. PLEASE SHOW DETAIL OF THE CONTROL | | STRUCTURES WITH ELEVATIONS, NOTCHES, BLEEDING | | ELEVATION, ETC CALS OF EXFILTRATION TRENCH LENGTH? | | 8. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH | | STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED. | | 9. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND | | YOUR SITE FOR STORM WATER DRAIN. NOT CLEAR FROM YOUR | | RESPONSE. MAY BE YOU WANT TO SHOW IN THE GENERAL SITE | | PLAN. | | | | PLEASE RESPOND EACH ITEM IN DETAIL IN A MEMO & ON | | DRAWINGS WITH REVISIONS TO EXPEDITE YOUR PERMITTING | | PROCESS | | | | RASIK CHOKSHI805-6723 |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
F |
Date |
2007-01-26 |
|
|
Cont ID |
|
Sent By |
rchokshi |
Date |
2007-01-26 |
Time |
09:35 |
Rev Time |
0.00 |
Received By |
rchokshi |
Date |
2007-01-26 |
Time |
09:12 |
Sent To |
|
|
Notes |
2007-01-26 09:34:51 | PLEASE PROVIDE FOLLOWING INFO: | | | | 1. PLEASE SHOW STANDARDS NOTES OF CITY OF WPB ON | | DRAWINGSFOR SIDEWALK WIDTH , ITS SLOPE, DRIVEWAY, | | PARKING, HANDICAP PARKING, PAINTPER CITY CODES ETC.,, | | MUST MEET PER ADA,,ETC., | | 2. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE | | DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION | | MUST BE ACCESSIBLE FOR PICKUP TRUCK. | | 3. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD , | | SIDEWALK ELEVATION MUST MEET FL BLDG CODE, PLEASE SHOW | | ON THE DRAWINGS. | | 4. PLEASE PROVIDE A COPY OF SFWMD PERMIT,GEOTECH | | REPORT | | 5.PLEASE SHOW STORM WATER CALCULATIONS, WHAT CRITERIA | | YOU ASSUMEDFOR RUNOFF CAL.,, LIKE 1" OVER ENTIRE SITE | | OR2.5"CRITERIA, ?PERVIOUS AREA, LIKE GREEN, | | LAKES, ETC,IMPERVIOUS AREA CAL., | | 6. WHAT IS THE SITE AREA, YOU ARE DEVELOPING FOR THIS | | PROJECT ONLY ? SO, WE CAN CHECK PERVIOUS, IMPERVIOUS | | CAL. | | 7. HOW YOU CONNECT TO THE STORM WATER PIPES IN YOUR | | SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER PIPES | | AROUND YOUR SITE SO, WE CANSEE THE BEST PIPE TO | | CONNECT WITH THE STORM WATERFROM ALL OTHER STORM | | WATER PIPES. PLEASE SHOW DETAIL OF THE CONTROL | | STRUCTURES WITH ELEVATIONS, NOTCHES, BLEEDING | | ELEVATION, ETC CALS OF EXFILTRATION TRENCH LENGTH? | | 8. POLLUTION PREVENTION DETAILS,CLOTHES USED FOR SILT | | ETC., PLANS SHOWING SILT FENCE AROUND THE SITE | | 9. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH | | STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED | | 10. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND | | YOUR SITE FOR STORM WATER DRAIN. | | | | PLEASE RESPOND EACH ITEM IN DETAIL IN A MEMO & ON | | DRAWINGS WITH REVISIONS TO EXPEDITE YOUR PERMITTING | | PROCESS | | | | RASIK CHOKSHI805-6723 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2007-08-09 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-08-09 |
Time |
15:22 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-08-09 |
Time |
14:46 |
Sent To |
|
|
Notes |
2007-08-09 15:19:42 | *****PROVISO***** | | | | | | THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE | | BEEN ADDRESSED;HOWEVER THE APPROPIATE PLAN SHEETS TO | | BE FIRE-STAMPED WHEN ALL PLAN REVIEWERS HAVE BEEN | | SATISFIED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2007-05-01 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-05-01 |
Time |
19:14 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-05-01 |
Time |
18:33 |
Sent To |
|
|
Notes |
2007-05-01 19:09:07 | *****UNSAT***** | | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE | | PLAN REVIEW STILL NEED TO BE ADDRESSED: | | | | | | | | 08.INDICATE THE LOCATION OF THE FIRE HYDRANT(S) IN | | THE VICINITY OF THE SITE.BE ADVISED THAT IF THE | | HYDRANT(S) IS GREATER THAN 500 FEET, AN ADDITIONAL | | HYDRANT SHALL BE REQUIRED.UNABLE TO VERIFY HYRANTS, | | DUE TO THE SMALLNESS OF THE FIRE HYDRANT VICINITY MAP. | | PLEASE SHOW NEAREST HYDRANTS ON PLAN SHEET WITH THE | | DISTANCE TO THE PROPERTY | | | | 10.IN ADDITION TO THE EXTERIOR ELEVATION DETAILS ON | | SHEET A5.1 AND A5.2, SPECIFY ELEVATIONS AS NORTH, EAST, | | WEST, AND SOUTH.ON SHEET STILL UNCLEAR AS TO REAR, | | LEFT, AND RIGHT ELEVATION | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2007-02-09 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-02-09 |
Time |
15:34 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-02-09 |
Time |
15:19 |
Sent To |
|
|
Notes |
2007-02-09 16:29:33 | *****DENIED***** | | | | | | 01.THE COMPLETE AND/OR ACTUAL ADDRESS OF THE PROJECT | | SITE SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED PLAN | | SHEET. | | | | 02.NFPA 101-2003 EDITION AND THE FLORIDA FIRE | | PREVENTION CODE SHALL BE REFERENCED. | | | | 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 04.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL | | NOT HINDER OR INTERFERE WITH EMERGENCY ACCESS RESPONSE | | TO THE SAID PROPERTY OR VICINITY THEREOF (INCLUDING | | FIRE HYDRANTS AND FIRE LANES). | | | | 05.ALL PAVEMENT ROAD SYSTEMS SHALL BE CAPABLE OF | | SUPPORTING 32 TONS FOR FIRE APPARATUS/EQUIPMENT. | | | | 06. FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN | | UNOBSTRUCTED WIDTH OF NOT LESS THAN 20 FEET AND AN | | UNOBSTRUCTED VERTICAL CLEARANCE OF NOT LESS THAN 13 | | FEET 6 INCHES. | | | | 07.LANDSCAPING SHALL NOT OBSTRUCT OR INTERFERE WITH | | FIRE PROTECTION EQUIPMENT.PROPER CLEARANCES SHALL BE | | MAINTAINED AT ALL TIMES. | | | | 08.INDICATE THE LOCATION OF THE FIRE HYDRANT(S) IN | | THE VICINITY OF THE SITE.BE ADVISED THAT IF THE | | HYDRANT(S) IS GREATER THAN 500 FEET, AN ADDITIONAL | | HYDRANT SHALL BE REQUIRED. | | | | 09.ON THE APPROPIATE EXTERIOR ELEVATION, SHOW/DISPLAY | | THE NUMERICAL ADDRESS FOR THE BUILDINGS TO BE VISIBLE | | FROM BROADWAY AVENUE.ONCE EMERGENCY RESPONDERS ARE | | INSIDE OF THE COMPLEX, HOW ARE BUILDINGS DISTINGUISHED | | FROM EACH OTHER. | | | | 10.IN ADDITION TO THE EXTERIOR ELEVATION DETAILS ON | | SHEET A5.2 AND A5.2, SPECIFY ELEVATIONS AS NORTH, EAST, | | WEST, AND SOUTH. | | | | 11.PLEASE INDICATE IF THIS BUILDING WILL BE EQUIPPED | | WITH A FIRE ALARM SYSTEM.BE ADVISED THAT SMOKE | | DETECTORS, AS LEGENDED ON SHEET E-1, ARE TIED INTO A | | FIRE ALARM SYSTEM.SMOKE ALARMS ON THE OTHER HAND ARE | | NOT TIED INTO A FIRE ALARM SYSTEM. | | | | 12.ON SHEET FS-6, PLEASE BE ADVISED THAT A 2 1/2" | | SINGLE INLET FIRE DEPARTMENT CONNECTION W/CHECK VALVE | | WILL BE REQUIRED. | | | | 13.ON SHEET FS-6, THE FIRE SPRINKLER SYSTEM IS TO BE | | MONITORED.IT SHALL BE PROVIDED WITH AN APPROVED ALARM | | INITIATION DEVICE THAT OPERATES WHEN THE FLOW OF WATER | | IS EQUAL OR GREATER THAN THAT FROM A SINGLE AUTOMATIC | | SPRINKLER. | | | | 14.IN REFERENCE TO THE HYDRAULIC CALCULATIONS THAT | | WERE SUBMITTED:3RD FLOOR UNIT-A SYSTEM 4, 3RD FLOOR | | UNIT-B SYSTEM 1, 3RD FLOOR UNIT-C SYSTEM 2, ALL SHOW AN | | UNACCEPTABLE SAFETY MARGIN.AS PER WPBFR, A SAFETY | | MARGIN OF AT LEAST 5.0 PSI IS REQUIRED. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2007-06-20 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-06-20 |
Time |
10:55 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-06-20 |
Time |
10:55 |
Sent To |
|
|
Notes |
2007-07-05 13:04:11 | 7/5/07--PLANS WERE TAKEN FROM REVIEW AND BROUGHT IN | | TODAY(SEE FRONT SCREEN NOTES) TO "COMM" BD#29/PLANS ON | | RACK--4 ROLLS AND PAPERWORK | 2007-06-20 10:55:48 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-03-24 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-03-24 |
Time |
17:11 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-03-24 |
Time |
17:10 |
Sent To |
|
|
Notes |
2007-03-24 17:11:12 | TO "COMM" BD#38 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-02-09 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-02-09 |
Time |
15:17 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2006-12-06 |
Time |
11:08 |
Sent To |
|
|
Notes |
2007-01-03 07:44:55 | TO COMM BOAR #43, 1/3 DVP | 2006-12-06 11:08:45 | WAITING FOR "COMM" BD |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
F |
Date |
2007-08-01 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-08-01 |
Time |
19:56 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-08-01 |
Time |
15:32 |
Sent To |
|
|
Notes |
2007-08-01 19:56:08 | 3RD REVIEW: DENIED | | | | FBC 2004 CODE FAMILY W/ 2005 REVISIONS | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | 1. OK | | | | 2. OK | | | | 3. A) NATURAL VENTILATION IS NOT AN AVAILABLE OPTION IN | | THIS APPLICATION. FBC,M 402.1 REQUIRES OPENINGS TO THE | | OUTDOORS. THE DWELLING UNIT GARAGE DOORS OPEN TO AN | | ENCLOSED PARKING GARAGE AREA WHICH DOES NOT QUALIFY AS | | OUTDOORS. | | | | B) THE VENTILATION REQUIREMENTS FOR GARAGES, SEPARATE | | FOR EACH DWELLING UNIT, IN ACCORDANCE WITH TABLE 403.3, | | IS 100 CFM PER CAR. IN THIS CASE, EACH GARAGE WOULD | | REQUIRE 200 CFM OF OUTDOOR AIR. THE COMMON GARAGE AREA | | WILL REQUIRE 1.5 CFM PER SQ.FT OF FLOOR AREA. | | RECIRCULATION OF AIR FROM THIS SPACE IS PROHIBITED PER | | FBC,M TABLE 403.3 NOTE (B). AS SUCH, THE INDIVIDUAL | | DWELLING UNIT GARAGES ARE REQUIRED TO COMMUNICATE | | DIRECTLY WITH THE OUTDOORS FOR THEIR REQUIRED 200 CFM | | OF OUTDOOR AIR. | | | | C) THE COMMON GARAGE AREA VENTILATION SYSTEM MAY RUN | | INTERMITTENTLY IF IT IS DESIGNED IN ACCORDANCE WITH | | FBC,M SEC. 404. | | | | 4. THIS COMMENT IS NOW ENCOMPASSED IN COMMENT #3. | | | | 5. OK | | | | 6. OK | | | | 7. THE BALANCED RETURN EXCEPTIONS TO FBC,M 601.4 STILL | | HAVE NOT BEEN MET. NOTE THAT UNDER EXCEPTION #3 ALL | | SUPPLY INTO THE MASTER SUITE SHALL BE INCLUDED. | | EXAMPLE: UNIT A MASTER SUITE ISFED BY A 10X8 DUCT WHICH | | IS 80 SQ.IN. A 10" FLEX (RETURN JUMPER AS SOWN ON PLAN) | | IS 78.5 SQ.IN. IT IS SMALLER THAN THE SUPPLY WHEN THE | | EXCEPTION REQUIRES IT TO BE 1 1/2 TIMES LARGER THAN THE | | SUPPLY. IN ADDITION, THE RETURN FROM THE MASTER AND | | BEDROOM 2 IS BEING CARRIED BY ONE 10X10 DUCT, WHICH IS | | 100 SQ.IN. WITH 80 SQ.IN. SUPPL FEEDING THE MASTER AND | | 50 SQ.IN. FEEDING BEDROOM 2 (8" ROUND SUPPLY), THAT IS | | A TOTAL OF 130 SQ.IN. OF SUPPLY BEING RETURNED BY A 100 | | SQ. IN. JUMPER. THIS DOES NOT QUALIFY AS BALANCED | | RETURN EVEN IF THE EXCEPTIONS TO 601.4 ARE NOT CLAIMED. | | PROVIDE BALANCED RETURN FROM ALL HABITABLE ROOMS AS | | REQUIRED BY FBC,M 601.4. | | | | COMMENTS 8 THROUGH 10 ARE OK. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J REGUEIRO | | 561.805.6719 | | [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2007-04-21 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-04-21 |
Time |
13:40 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-04-21 |
Time |
11:17 |
Sent To |
|
|
Notes |
2007-04-21 13:39:27 | -------2ND REVIEW: DENIED-------- | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | PERVIOUS COMMENTS FOR THE PURPOSE OF CONTINUITY. | | | | 1. OK | | | | 2. OK | | | | 3. PLEASE SHOW MEANS OF MECHANICAL EXHAUST FOR GARAGE | | ON MECHANICAL PLANS. FBC,M 403.3, FBC 106.1.1 | | | | 4. OK PENDING RESPONSE TO COOMENT #3. | | | | 5. IF YOU CHOOSE TO LEAVE THESE NOTES ON PLAN, THOSE | | ELEMENTS WILL BE REQUIRED TO BE INSTALLED AT ROUGH | | INSPECTION. CONSULT MANUFACTURER'S INSTALLATION | | ISTRUCTIONS TO SEE IF ANOTHER METHOD OF VIBRATION | | ISOLATION IS AVAILABLE. | | | | 6. OK | | | | 7. THIS ISSUE WAS NOT ADDRESSED. IF RETURN TRANSFERS | | ARE NOT REDESIGNED TO MEET THE EXCEPTIONS UNDER FBC,M | | 601.4, A FIELD TEST WILL BE REQUIRED AT FINAL | | INSPECTION TO DETERMINE IF BALANCED RETURN HAS BEEN | | ACHIEVED WITH A PRESSURE DIFFERENTIAL OF 0.01" WC OR | | LESS. | | | | 8. OK | | | | 9. OK | | | | 10. (A) PER DETAIL ON M-5, IS IT THE INTENT OF THE | | DESIGNER TO HAVE A COMBINATION OF 4" ROUND, 10X3 AND | | 6X3 ROOF JACKS? DETAIL INDICATES SIZE OF ROOF JACK IS | | TO MATCH SIZE OF EXHAUST DUCT GOING TO ROOF. | | (B) THIS TYPE OF ROOF JACK WILL NOT WORK FOR DRYER | | EXHAUST. SCREENS ARE PROHIBITED AND BACKDRAFT DAMPER IS | | REQUIRED PER FBC,M 504.4. PROVIDE DETAIL FOR DRYER | | EXHAUST TERMINATION IN ACCORDANCE WITH THIS SECTION. | | (C) PG M-3: CLOTHES DRYERS ARE TO BE EXHAUSTED IN | | ACCORDANCE WITH DRYER MANUFACTURER'S INSTALLATION | | INSTRUCTIONS PER FBC,M 504.1. VERIFY WITH INSTRUCTIONS | | THAT 6X3 DUCT IS AN ACCEPTABLE ALTERNATIVE TO 4" ROUND | | DUCT AND THAT SQUARE 90 DEGREE ELBOWS ARE ACCEPTABLE IN | | LEIU OF 4" ROUND RADIUS 90 DEGREE ELBOWS. PROVIDE | | MANUFACTURER'S INSTALLATION INSTRUCTIONS TO SHOW | | COMPLIANCE IF THIS TYPE OF DUCT IS TO BE USED. | | | | | | REVIEWED BY: | | RONALD J REGUEIRO | | 561.805.6719 | | [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2007-03-12 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-01-25 |
Time |
14:22 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-01-23 |
Time |
14:17 |
Sent To |
|
|
Notes |
2007-01-29 14:27:34 | ----------------DENIED----------------- | | | | 1.PAGE M1, UNIT A 3RD FLOOR: PLAN SHOWS WASHER/DRYER IN | | CLOSET WITH AIR HANDLER. CLOTHES WASHERS, CLOTHES | | DRYERS SHALL NOT BE LOCATED IN MECHANICAL CLOSETS USED | | AS RETURN AIR PLENUMS PER FBC SEC. 13-610.1.ABC.3.7 | | | | 2.PAGE M1, UNIT A 3RD FLOOR: PLAN SHOWS 10X3 EXHAUST | | DUCT IN A/C CLOSET. FOR PURPOSES OF CONTAMINATION | | PREVENTION, EXHAUST DUCTS UNDER POSITIVE PRESSURE SHALL | | NOT EXTEND INTO OR PASS THROUGH DUCTS OR PLENUMS PER | | FBC,M 601.3 | | | | 3.GARAGE EXHAUST FANS ARE CALLED FOR ON EF SCHEDULE. | | FANS ALONG WITH DUCTS AND DISCHARGE LOCATIONS ARE NOT | | SHOWN ON MECHANICAL PLAN. | | | | 4.FAN SCHEDULE SHOWS EF 3 (GARAGE) TO BE CONTROLLED BY | | A TIME CLOCK. THIS FAN SHOULD RUN CONTINUOUS PER FBC,M | | T403.3 | | | | 5.FAN SCHEDULE: NOTES 1,2 DO NOT USUALLY APPLY TO | | 'RESIDENTIAL' TYPE CEILING MOUNTED EXHAUST FANS. IS THE | | INTENT TO HAVE THESE ITEMS INSTALLED ON BATHROOM | | EXHAUST FANS? | | | | 6.FAN SCHEDULE SHOWS THREE DIFFERENT FAN TYPES. FANS | | ARE NOT IDENTIFIED BY TYPE ON MECHANICAL PLANS. PLEASE | | INDICATE ON PLAN WHICH TYPE OF FAN GOES IN EACH | | LOCATION. | | | | 7.FBC,M 601.4 REQUIRES BALANCED RETURN IN ALL HABITABLE | | ROOMS. A PRESSURE DIFFERENTIAL OF .01" WC OR LESS IS | | REQUIRED UNLESS RETURNS ARE DESIGNED TO MEET THE | | EXCEPTIONS AS STATED IN THIS SECTION. IF RETURNS ARE | | NOT DESIGNED TO THESE EXCEPTIONS, A FIELD TEST WILL BE | | REQUIRED AT FINAL INSPECTION TO DETERMINE IF PRESSURE | | DIFFERENTIAL IS CODE COMPLIANT. | | | | 8.HVAC SPECIFICATIONS NOTE # 19 CITES 2001 FBC(M) TABLE | | 403.3. PLEASE REFERENCE 2004 FBC(M). ALSO TABLE 403.3 | | DOES NOT RELATE TO CONDENSATE OVERFLOW PROTECTION. | | PLEASE CLARIFY (307.2.3 RELATES TO CONDENSATE | | DISPOSAL/OVERFLOW PROTECTION) | | | | 9.HVAC SPECIFICATIONS NOTE #24 INDICATES FRESH AIR | | DAMPERS TO BE CONTROLLED BY T-STAT. AHU SCHEDULE STATES | | MECHANICAL FRESH AIR IS NOT REQUIRED. PLEASE CLARIFY. | | | | 10. PLEASE PROVIDE DETAIL SHOWING BATH AND DRYER | | EXHAUST TERMINATIONS AT ROOF. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL OR EMAIL: | | RONALD J REGUEIRO | | 561-805-6734 | | [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2007-07-18 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-07-18 |
Time |
07:26 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-07-18 |
Time |
07:25 |
Sent To |
|
|
Notes |
2007-07-18 11:16:59 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 CHAPTER 1 | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | ****FROM PREVIOUS REVIEW: | | ********FROM PREVIOUS REVIEWS:******** | | | | 1. OK | | 2. OK | | 3. OK | | 4. OK | | 5. OK | | 6. OK | | 7. OK | | 8. OK | | 9. OK | | 10. OK | | 11. OK | | 12. OK | | 13. OK | | 14. OK | | 15. OK | | | | 16. SHTS IR-1, LP-1 & LP-2 LANDSCAPE ARCHITECT LICENSE | | IS NULL & VOID PER DBPR WESITE. (SEE ATTACHED SHEET). | | ONE SET OF SHEETS SHALL BE RETAINED FOR POSSIBLE REVIEW | | BY THE STATE LANDSCAPE ARCHITECTURAL BOARD AS THIS SEAL | | HAS BEEN NULL & VOID SINCE 11/30/95. | | ****NO RESPONSE, NOT ADDRESSED. | | ******RESPONSE NOTED, BUT THE SEAL USED IS NOT | | APPROVED. PER FAC 61G1-16.002 THE SEAL SHALL BE 2" IN | | DIAMETER. PLEASE RESEAL THE PLANS. | | | | 17. OK | | 18. OK | | | | ***********NEW COMMENTS*********** | | | | 1B. OK | | 2B. OK | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2007-05-02 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-05-02 |
Time |
17:17 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-05-02 |
Time |
17:17 |
Sent To |
|
|
Notes |
2007-05-02 17:57:03 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 CHAPTER 1 | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | ****FROM PREVIOUS REVIEW: | | | | 1. ALL ARCHITECTURAL SHEETS. THE FIRM LICENSE NUMBER, | | (CERTIFICATE OF AUTHORIZATION), IS REQUIRED IN THE | | TITLE BLOCK OF EACH SHEET. FAC 61G1-16.004(2) & FS | | 481.219, 481.2055. | | ****NO RESPONSE, NOT ADDRESSED. | | | | 2. SHT A3.4 SUBMIT CALCULATIONS FOR PRIMARY AND | | SECONDARY ROOF DRAINS. SHOW THE SQUARE FOOTAGE OF EACH | | AREA AS WELL AS 1/2 AREA OF ALL VERTICAL WALLS | | INCLUDING PARAPETS. ALSO INDICATE ANY AREA OF A ROOF | | THAT DRAINS FROM ABOVE IF APPLICABLE. SECTIONS 1106 & | | 1107 WITH ALL SUBSECTIONS. | | ****NO RESPONSE, NOT ADDRESSED. | | | | 3. SHT A3.4 DETAIL 4, SECONDARY DRAINS SHALL BE A | | MINIMUM 2" HIGHER THAN THE MAIN DRAIN. AS SHOWN THEY | | ARE ONLY ABOUT 3/4" ABOVE THE MAIN DRAINS. THIS IS | | REQUIRED SO THAT THE SECONDARY DRAINS WILL NOT DRAIN | | STORM WATER UNLESS THERE IS A BLOCKAGE IN THE PRIMARY | | DRAINS.--SUBMIT A DETAIL SHOWING THE ELEVATION AT | | THE FLOOR AT THE PATIO DOOR, AND INDICATE THE ELEVATION | | OF THE PRIMARY DRAIN AND THE SECONDARY DRAIN. SECTION | | 106.1.1. | | ****NO RESPONSE, NOT ADDRESSED. | | | | 4. SHT A3.5 SHOWS 6" OVERFLOW DRAINS CONNECTING TO | | MANHOLES. SECTION 1107.2 REQUIRES THE DISCHARGE TO BE | | ABOVE GRADE IN AN OBSERVABLE LOCATION. PLEASE CHANGE | | TERMINATION POINT FOR THE OVERFLOW DRAINS.--ONE 7" | | DOWNSPOUT DOES NOT SHOW THE PIPING TO THE MANHOLE. | | PLEASE SHOW ALL PIPING. SECTION 106.1.1. | | ****NO RESPONSE, NOT ADDRESSED. | | | | 5. SHTS A4.1 & A5.1. SHT A4.1 SHOWS THE GUTTER TO BE | | CONTINUOUS AROUND THE INSIDE OF THE BLDG ROOF EXCEPT AT | | THE CHIMNEYS. SHT A5.1 ONLY SHOWS THE GUTTER AT THE | | MAIN ROOF SECTIONS, AND NO GUTTER AT THE HIP ROOF | | SECTIONS. ALSO NO DOWNSPOUTS ARE INDICATED AT THE HIP | | ROOF SECTIONS. PLEASE CLARIFY. SECTION 106.1.1. ****NO | | RESPONSE, NOT ADDRESSED. | | | | 6. OK | | | | 7. SHT P-1 THE SANITARY PARTIAL RISER DIAGRAMS DO NOT | | REFLECT THE FLOOR PLAN IN MANY INSTANCES. ALL OFFSETS | | SHALL BE SHOWN ON THE RISER DIAGRAM, SOME EXTRA PIPING | | IS SHOWN, SOME FIXTURE BRANCH LINES ARE NOT SHOWN.-- | | THE AUTOMATIC CLOTHES WASHER FIXTURE DRAIN SHALL | | CONNECT TO A BRANCH DRAIN OR A DRAINAGE STACK A MINIMUM | | OF 3" IN DIAMETER. SECTION 406.3.-- SEE RED LINE | | NOTES ON ONE SET OF PLUMBING PLANS. SECTION 106.1.1. | | ****NO RESPONSE. PARTAL RISER 2ND FLOOR DOES NOT | | REFLECT THE NEW FLOOR PLAN, NOR DOES THE 3RD FLOORM/B | | TUB. SEE RED LINE CORRECTIONS.--SHOW ALL VENT | | PIPING AND WATER PIPING ON THE FLOOR PLAN TO REFLECT | | THE RISER DIAGRAMS. VENT OFFSETS ARE NOT SHOWN ON THE | | FLOOR PLAN.--THE WATER RISER DIAGRAM DOES NOT SHOW | | THE WATER PIPING & WATER HAMMER ARRESTOR FOR THE REF. | | WITH ICE MAKER NOR IS IT SHOWN ON THE FLOOR PLAN. | | | | 8. SHT P-2 THE SANITARY PARTIAL RISER DIAGRAMS DO NOT | | REFLECT THE FLOOR PLAN IN MANY INSTANCES. ALL OFFSETS | | SHALL BE SHOWN ON THE RISER DIAGRAM, SOME EXTRA PIPING | | IS SHOWN, SOME FIXTURE BRANCH LINES ARE NOT SHOWN, THE | | VENT & SANT LINES ARE CROSSED FROM FLOOR TO FLOOR.-- | | THE AUTOMATIC CLOTHES WASHER FIXTURE DRAIN SHALL | | CONNECT TO A BRANCH DRAIN OR A DRAINAGE STACK A MINIMUM | | OF 3" IN DIAMETER. SECTION 406.3.-- SEE RED LINE | | NOTES ON ONE SET OF PLUMBING PLANS. SECTION 106.1.1. | | ****NO RESPONSE. OFFSET FROM THE POWDER ROOM TO BATH #2 | | IS NOT SHOWN ON THE FLOOR PLAN, AND THE RISER INDICATES | | THE RISER GOING IN THE WRONG DIRECTION.--RISERS | | FROM THE 1ST FLOOR BY BATH#3 TO THE 2ND FLOOR BY THE | | POWDER ROOM ARE CROSSED.--PARTIAL RISER TO BATH #2 | | DOES NOT REFLECT THE FLOOR PLAN.--THE WATER LINE & | | WATER HAMMER ARRESTOR TO THE ICE MAKER IN THE REF IS | | NOT SHOWN ON THE WATER RISER NOR ON THE FLOOR PLAN.-- | | SHOW ALL VENT OFFSETS AND WATER PIPING ON THE FLOOR | | PLAN. | | | | 9. SHT P-3 THE SANITARY PARTIAL RISER DIAGRAMS DO NOT | | REFLECT THE FLOOR PLAN IN MANY INSTANCES. ALL OFFSETS | | SHALL BE SHOWN ON THE RISER DIAGRAM, SOME EXTRA PIPING | | IS SHOWN, SOME FIXTURE BRANCH LINES ARE NOT SHOWN, BATH | | 2 INDICATES A TUB ON THE RISER, BUT SHOWS A SHOWER ON | | THE FLOOR PLAN. THE KITCHEN SHOWS A 3" TO THE 3RD | | FLOOR. PLEASE INDICATE WHERE THIS LINE IS TERMINATING. | | --THE AUTOMATIC CLOTHES WASHER FIXTURE DRAIN SHALL | | CONNECT TO A BRANCH DRAIN OR A DRAINAGE STACK A MINIMUM | | OF 3" IN DIAMETER. SECTION 406.3.-- SEE RED LINE | | NOTES ON ONE SET OF PLUMBING PLANS. SECTION 106.1.1. | | ****NO RESPONSE. PARTIAL RISERS FOR THE 3RD FLOOR NEED | | TO IDENTIFY VENTS WHEN REVENTING FROM ONE RISER TO | | ANOTHER.--NO WATER LINE OR WATER HAMMER ARRESTOR | | FOR THE ICE MAKER IN THE REF SHOWN ON THE RISER NOR ON | | THE FLOOR PLAN.--PARTIAL WATER TO THE DISH WASHER | | SHOW COLD WATER SUPPLY. HOT WATER REQUIRED.--SHOW | | VENTS AND WATER SUPPLY PIPING ON THE FLOOR PLAN. | | | | 10. SHT P-4 THE SANITARY PARTIAL RISER DIAGRAMS DO NOT | | REFLECT THE FLOOR PLAN IN MANY INSTANCES. ALL OFFSETS | | SHALL BE SHOWN ON THE RISER DIAGRAM, SOME EXTRA PIPING | | IS SHOWN, SOME FIXTURE BRANCH LINES ARE NOT SHOWN. THE | | VENT FROM THE FIRST FLOOR, BATHROOM 3 IS NOT SHOWN ON | | THE FLOOR PLAN OF THE SECOND FLOOR. --THE | | AUTOMATIC CLOTHES WASHER FIXTURE DRAIN SHALL CONNECT TO | | A BRANCH DRAIN OR A DRAINAGE STACK A MINIMUM OF 3" IN | | DIAMETER. SECTION 406.3.-- SEE RED LINE NOTES ON ONE | | SET OF PLUMBING PLANS. SECTION 106.1.1. | | ****NO RESPONSE. OFFSETS OF THE VENTS ARE NOT SHOWN ON | | THE FLOOR PLAN.--IDENTIFY WHERE ALL REVENT PIPING | | IS CONNECTING TO.--MASTER BATH RISER DOES NOT | | REFLECT THE FLOOR PLAN.--PARTIAL WATER RISER 2ND | | FLOOR DOES NOT REFLECT THE FLOOR PLAN.--1ST FLOOR | | PIPING SHOWS EXTRA UNDERGROUND PIPING. PLEASE CLARIFY. | | --SHOW ALL VENT PIPING & WATER PIPING ON THE FLOOR | | PLAN.--IDENTIFY THE RISER THAT THE W/M AND M/BATH | | CONNECT TO ON THE FLOOR PLAN 2ND FLOOR. | | | | 11. SUBMIT A WATER RISER DIAGRAM FOR EACH TYPE OF UNIT. | | SHOW ALL PIPE SIZES, VALVES AND WATER HAMMER ARRESTORS | | REQUIRED BY SECTION 604.9. (ICE MAKERS, DISHWASHERS, & | | WASH MACHINES). SECTION 106.3.5.1.3(3)(13). | | ****NO PIPING SHOWN ON THE FLOOR PLAN OR RISER DIAGRAMS | | FOR THE ICE MAKERS IN THE REF'S. | | | | 12. SUBMIT A STORM RISER DIAGRAM FOR THE PRIMARY | | DRAINAGE AND SECONDARY DRAINAGE SYSTEMS. SHOW ALL PIPE | | SIZES, OFFSETS, AND INDICATE SQUARE FOOTAGE BEING | | DRAINED.SECTION 106.3.5.1.3(7)(13). | | ****NO RESPONSE, NOT ADDRESSED. | | | | 13. OK. | | | | 14. SHT P-5 WATER HEATER DETAIL. PLEASE INDICATE THE | | TERMINATION POINT FOR THE EMERGNECY PAN DRAIN AND THE | | T/P RELIEF DISCHARGE LINE. SECTIONS 504.6.1 & 504.7.2. | | ****MORE INFORMATION IS REQUIRED ON THE DETAIL. IT | | SHOWS A 4" HOUSE KEEPING PAD, THE THE DRAIN LINES | | APPEAR TO DROP DOWN TO THE GARAGE FLOOR. PLEASE | | INDICATE HOW THIS WILL COMPLY WITH THE CODE SECTIONS | | FOR THESE LINES TO BE 6" ABOVE GRADE AND NOT HAVE ANY | | TRAPPED SECTIONS PER SECTIONS 504.6.1 & 504.7.2. SUBMIT | | AN ISOMETRIC FOR EACH TYPICAL P/T & PAN DRAIN LINE. | | | | 15. SHT IR-1 THE CONTROLLER AND THE RAIN SENSOR LOCTION | | ARE REQUIRED ON THE PLAN. SECTION 106.1.1.--THE | | BACKFLOW PREVENTOR SHALL BE INSTALLED BYA LICENCED | | PLUMBING CONTRACTOR.--A SEPARATE IRRIGATION PERMIT | | IS REQUIRED. SECTION 105.1. | | ****NO RESPONSE, NOT ADDRESSED. | | | | 16. SHTS IR-1, LP-1 & LP-2 LANDSCAPE ARCHITECT LICENSE | | IS NULL & VOID PER DBPR WESITE. (SEE ATTACHED SHEET). | | ONE SET OF SHEETS SHALL BE RETAINED FOR POSSIBLE REVIEW | | BY THE STATE LANDSCAPE ARCHITECTURAL BOARD AS THIS SEAL | | HAS BEEN NULL & VOID SINCE 11/30/95. | | ****NO RESPONSE, NOT ADDRESSED. | | | | 17. SHTS IR-1, LP-1 & LP-2THE LANDSCAPE FIRM LICENSE | | NUMBER AS WELL AS THE PRINTED NAME OF THE PERSON | | SEALING THE DOCUMENT SHALL BE IN THE TITLE BLOCK OF | | EACH SHEET. FAC 61G1-16.004(2)(6) & FS 481.2055. ****NO | | RESPONSE, NOT ADDRESSED. | | | | | | 18. THE MANHOLES, TRENCH DRAINS, STORM DRAINS AND | | RELATED PIPING SHALL BE DESIGNED BY THE BUILDING | | ENGINEER, AND INSTALLED BY THE PLUMBING CONTRACTOR AS | | THIS IS WITHIN THE FOOTPRINT OF THE BUILDING. THE CIVIL | | ENGINEER, AND THE SITE CONTRACTOR CAN ONLY DESIGN AND | | INSTALL UP TO FIVE FEET OF THE BUILDING STRUCTURE. FS | | 489. | | (INFORMATIONAL) | | | | ***********NEW COMMENTS*********** | | | | 1B. SHTS LP-1, LP-2 & IR-1 THE LANDSCAPE FIRM LICENSE | | NUMBER PER FLA STATE DBPR WEBSITE IN IN APPLICANT | | STATUS. (SEE ATTACHED SHEET). AS SUCH THESE PLANS CAN | | NOT BE APPROVED.--WHEN APPROVED SHEETS ARE | | SUBMITTED, THE DATE THE SEAL AND SIGNATURE OF THE | | LANDSCAPE ARCHITECT ARE AFFIXED TO THE PLANS, THE DATE | | SHALL BE ALSO AFFIXED BELOW THE SIGNATURE. FAC | | 61G1-16.004(5) & FS 481.2055. | | | | 2B. COMPLETE RISERS FROM THE HORIZONTAL BUILDING | | ISOMETRIC DIAGRAM TO THE VTRSHALL BE SUBMITTED AS | | PARTIAL RISER DIAGRAMS ARE HARD TO FOLLOW AND NOT ALL | | INFORMATION REQUIRED ON THE PARTIAL RISERS IS BEING | | SUBMITTED SUCH AS OFFSETS, VENTING, REVENTING ETC. | | SECTION 106.3.5.1.3. THE RISER DIAGRAMS SHALL REFLECT | | THE PIPING ON THE FLOOR PLAN. SECTION 106.1.1. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2007-02-03 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-02-03 |
Time |
09:50 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-02-02 |
Time |
18:58 |
Sent To |
|
|
Notes |
2007-02-03 12:58:40 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 CHAPTER 1 | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | 1. ALL ARCHITECTURAL SHEETS. THE FIRM LICENSE NUMBER, | | (CERTIFICATE OF AUTHORIZATION), IS REQUIRED IN THE | | TITLE BLOCK OF EACH SHEET. FAC 61G1-16.004(2) & FS | | 481.219, 481.2055. | | | | 2. SHT A3.4 SUBMIT CALCULATIONS FOR PRIMARY AND | | SECONDARY ROOF DRAINS. SHOW THE SQUARE FOOTAGE OF EACH | | AREA AS WELL AS 1/2 AREA OF ALL VERTICAL WALLS | | INCLUDING PARAPETS. ALSO INDICATE ANY AREA OF A ROOF | | THAT DRAINS FROM ABOVE IF APPLICABLE. SECTIONS 1106 & | | 1107 WITH ALL SUBSECTIONS. | | | | 3. SHT A3.4 DETAIL 4, SECONDARY DRAINS SHALL BE A | | MINIMUM 2" HIGHER THAN THE MAIN DRAIN. AS SHOWN THEY | | ARE ONLY ABOUT 3/4" ABOVE THE MAIN DRAINS. THIS IS | | REQUIRED SO THAT THE SECONDARY DRAINS WILL NOT DRAIN | | STORM WATER UNLESS THERE IS A BLOCKAGE IN THE PRIMARY | | DRAINS.--SUBMIT A DETAIL SHOWING THE ELEVATION AT | | THE FLOOR AT THE PATIO DOOR, AND INDICATE THE ELEVATION | | OF THE PRIMARY DRAIN AND THE SECONDARY DRAIN. SECTION | | 106.1.1. | | | | 4. SHT A3.5 SHOWS 6" OVERFLOW DRAINS CONNECTING TO | | MANHOLES. SECTION 1107.2 REQUIRES THE DISCHARGE TO BE | | ABOVE GRADE IN AN OBSERVABLE LOCATION. PLEASE CHANGE | | TERMINATION POINT FOR THE OVERFLOW DRAINS.--ONE 7" | | DOWNSPOUT DOES NOT SHOW THE PIPING TO THE MANHOLE. | | PLEASE SHOW ALL PIPING. SECTION 106.1.1. | | | | 5. SHTS A4.1 & A5.1. SHT A4.1 SHOWS THE GUTTER TO BE | | CONTINUOUS AROUND THE INSIDE OF THE BLDG ROOF EXCEPT AT | | THE CHIMNEYS. SHT A5.1 ONLY SHOWS THE GUTTER AT THE | | MAIN ROOF SECTIONS, AND NO GUTTER AT THE HIP ROOF | | SECTIONS. ALSO NO DOWNSPOUTS ARE INDICATED AT THE HIP | | ROOF SECTIONS. PLEASE CLARIFY. SECTION 106.1.1. | | | | 6. ALL PLUMBING, MECHANICAL, ELECTRICAL & SL SHEETS. | | THE ENGINEERS SEAL SHALL IMPRESS THE REQUIRED | | INFORMATION ON EACH SHEET. MANY SHEETS ONLY SHOW A | | PORTION OF REQUIRED INFORMATION. PLEASE MAKE SURE ALL | | INFORMATION REQUIRED BY FAC 61G15-23.001(1)(2), | | 61G15-23.002(1)(2) AND FS 471.025 IS IMPRESSED ON EACH | | SHEET WHEN SEALING THE PLANS. | | | | 7. SHT P-1 THE SANITARY PARTIAL RISER DIAGRAMS DO NOT | | REFLECT THE FLOOR PLAN IN MANY INSTANCES. ALL OFFSETS | | SHALL BE SHOWN ON THE RISER DIAGRAM, SOME EXTRA PIPING | | IS SHOWN, SOME FIXTURE BRANCH LINES ARE NOT SHOWN.-- | | THE AUTOMATIC CLOTHES WASHER FIXTURE DRAIN SHALL | | CONNECT TO A BRANCH DRAIN OR A DRAINAGE STACK A MINIMUM | | OF 3" IN DIAMETER. SECTION 406.3.-- SEE RED LINE | | NOTES ON ONE SET OF PLUMBING PLANS. SECTION 106.1.1. | | | | 8. SHT P-2 THE SANITARY PARTIAL RISER DIAGRAMS DO NOT | | REFLECT THE FLOOR PLAN IN MANY INSTANCES. ALL OFFSETS | | SHALL BE SHOWN ON THE RISER DIAGRAM, SOME EXTRA PIPING | | IS SHOWN, SOME FIXTURE BRANCH LINES ARE NOT SHOWN, THE | | VENT & SANT LINES ARE CROSSED FROM FLOOR TO FLOOR.-- | | THE AUTOMATIC CLOTHES WASHER FIXTURE DRAIN SHALL | | CONNECT TO A BRANCH DRAIN OR A DRAINAGE STACK A MINIMUM | | OF 3" IN DIAMETER. SECTION 406.3.-- SEE RED LINE | | NOTES ON ONE SET OF PLUMBING PLANS. SECTION 106.1.1. | | | | 9. SHT P-3 THE SANITARY PARTIAL RISER DIAGRAMS DO NOT | | REFLECT THE FLOOR PLAN IN MANY INSTANCES. ALL OFFSETS | | SHALL BE SHOWN ON THE RISER DIAGRAM, SOME EXTRA PIPING | | IS SHOWN, SOME FIXTURE BRANCH LINES ARE NOT SHOWN, BATH | | 2 INDICATES A TUB ON THE RISER, BUT SHOWS A SHOWER ON | | THE FLOOR PLAN. THE KITCHEN SHOWS A 3" TO THE 3RD | | FLOOR. PLEASE INDICATE WHERE THIS LINE IS TERMINATING. | | --THE AUTOMATIC CLOTHES WASHER FIXTURE DRAIN SHALL | | CONNECT TO A BRANCH DRAIN OR A DRAINAGE STACK A MINIMUM | | OF 3" IN DIAMETER. SECTION 406.3.-- SEE RED LINE | | NOTES ON ONE SET OF PLUMBING PLANS. SECTION 106.1.1. | | | | 10. SHT P-4 THE SANITARY PARTIAL RISER DIAGRAMS DO NOT | | REFLECT THE FLOOR PLAN IN MANY INSTANCES. ALL OFFSETS | | SHALL BE SHOWN ON THE RISER DIAGRAM, SOME EXTRA PIPING | | IS SHOWN, SOME FIXTURE BRANCH LINES ARE NOT SHOWN. THE | | VENT FROM THE FIRST FLOOR, BATHROOM 3 IS NOT SHOWN ON | | THE FLOOR PLAN OF THE SECOND FLOOR. --THE | | AUTOMATIC CLOTHES WASHER FIXTURE DRAIN SHALL CONNECT TO | | A BRANCH DRAIN OR A DRAINAGE STACK A MINIMUM OF 3" IN | | DIAMETER. SECTION 406.3.-- SEE RED LINE NOTES ON ONE | | SET OF PLUMBING PLANS. SECTION 106.1.1. | | | | 11. SUBMIT A WATER RISER DIAGRAM FOR EACH TYPE OF UNIT. | | SHOW ALL PIPE SIZES, VALVES AND WATER HAMMER ARRESTORS | | REQUIRED BY SECTION 604.9. (ICE MAKERS, DISHWASHERS, & | | WASH MACHINES). SECTION 106.3.5.1.3(3)(13). | | | | 12. SUBMIT A STORM RISER DIAGRAM FOR THE PRIMARY | | DRAINAGE AND SECONDARY DRAINAGE SYSTEMS. SHOW ALL PIPE | | SIZES, OFFSETS, AND INDICATE SQUARE FOOTAGE BEING | | DRAINED.SECTION 106.3.5.1.3(7)(13). | | | | 13. SHT P-5CONDENSATE RISER DIAGRAM. THE CONDENSATE | | SHALL HAVE A RELIEF VENT, (RETURN BEND), INSTALLED AS | | THE CONDENSATE EXITS THE BUILDING. | | | | 14. SHT P-5 WATER HEATER DETAIL. PLEASE INDICATE THE | | TERMINATION POINT FOR THE EMERGNECY PAN DRAIN AND THE | | T/P RELIEF DISCHARGE LINE. SECTIONS 504.6.1 & 504.7.2. | | | | 15. SHT IR-1 THE CONTROLLER AND THE RAIN SENSOR LOCTION | | ARE REQUIRED ON THE PLAN. SECTION 106.1.1.--THE | | BACKFLOW PREVENTOR SHALL BE INSTALLED BYA LICENCED | | PLUMBING CONTRACTOR.--A SEPARATE IRRIGATION PERMIT | | IS REQUIRED. SECTION 105.1. | | | | 16. SHTS IR-1, LP-1 & LP-2 LANDSCAPE ARCHITECT LICENSE | | IS NULL & VOID PER DBPR WESITE. (SEE ATTACHED SHEET). | | ONE SET OF SHEETS SHALL BE RETAINED FOR POSSIBLE REVIEW | | BY THE STATE LANDSCAPE ARCHITECTURAL BOARD AS THIS SEAL | | HAS BEEN NULL & VOID SINCE 11/30/95. | | | | 17. SHTS IR-1, LP-1 & LP-2THE LANDSCAPE FIRM LICENSE | | NUMBER AS WELL AS THE PRINTED NAME OF THE PERSON | | SEALING THE DOCUMENT SHALL BE IN THE TITLE BLOCK OF | | EACH SHEET. FAC 61G1-16.004(2)(6) & FS 481.2055. | | | | 18. THE MANHOLES, TRENCH DRAINS, STORM DRAINS AND | | RELATED PIPING SHALL BE DESIGNED BY THE BUILDING | | ENGINEER, AND INSTALLED BY THE PLUMBING CONTRACTOR AS | | THIS IS WITHIN THE FOOTPRINT OF THE BUILDING. THE CIVIL | | ENGINEER, AND THE SITE CONTRACTOR CAN ONLY DESIGN AND | | INSTALL UP TO FIVE FEET OF THE BUILDING STRUCTURE. FS | | 489. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
4 |
Status |
F |
Date |
2008-03-18 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2008-02-12 |
Time |
08:20 |
Rev Time |
0.00 |
Received By |
eschneid |
Date |
2008-02-12 |
Time |
08:20 |
Sent To |
|
|
Notes |
2008-03-18 08:21:24 | FAILED | | | | APPLICANT HAS SATISFIED CONDITION #5 - FDOT PERMIT. | | FINAL ROW PERMIT WILL BE REQUIRED PRIOR TO THE ACTUAL | | RELOCATION OF THE STREET CLOSURE.SEE HISTORY BELOW: | | | | 2/12/08 FDOT GRANTS CONCEPTUAL APPROVAL TO RELOCATE THE | | STREET CLOSURES, WHICH SATISFIES P&Z COMMENT. 2/4/08 | | DAVID LAWRENCE, ARCHITECT, NOTIFIES ERIC SCHNEIDER, | | P&Z, THAT FDOT WILL NOT PROCESS THE ROW PERMIT W/O CITY | | SIGN-OFF. | | | | ALL OTHER COMMENTS FROM JULY 11, 2007 REVIEW STILL | | APPLY. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
F |
Date |
2007-07-11 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2007-07-11 |
Time |
16:38 |
Rev Time |
0.00 |
Received By |
eschneid |
Date |
2007-07-11 |
Time |
16:38 |
Sent To |
|
|
Notes |
2007-07-11 16:45:30 | FAILED | | | | 1) THE PLANS WILL BE REQUIRED TO CONFORM TO THE CITY | | COMMISSION?S STREET CLOSURE RELOCATION PLAN.THE | | STREET CLOSURES AT 28TH AND 29TH STREET SHALL BE | | RELOCATED TO THE MID-BLOCK LOCATION (EAST OF THE | | PROJECT ENTRANCE).RELOCATED STREET CLOSURE LOCATIONS | | SHALL BE SHOWN ON THE PLANS.NOTE THAT PLANS FOR THE | | RELOCATED STREET CLOSURE DESIGN WILL NEED TO BE | | APPROVED BY THE CITY COMMISSION (JULY 16) AND | | CONSTRUCTED BY THE DEVELOPER.PLEASE SUBMIT THE CITY | | RIGHT-OF-WAY PERMIT APPROVING THE CONSTRUCTION OF THE | | RELOCATED STREET CLOSURES. (PARTIAL REPEAT) | | | | 2) PROVIDE THE RECORDED PUBLIC ACCESS EASEMENT FOR THAT | | PORTION OF THE SIDEWALK LOCATED ON THE SITE ALONG | | BROADWAY AVENUE AND FOR THE SIDEWALK ALONG THE ALLEY. | | THE EASEMENT LANGUAGE SHALL BE APPROVED BY THE OFFICE | | OF THE CITY ATTORNEY PRIOR TO RECORDATION. (REPEAT) | | | | 3) PROVIDE THE RECORDED PERPETUAL MAINTENANCE AGREEMENT | | FOR THE REBUILT, PAVERED ALLEY.THE MAINTENANCE | | AGREEMENT LANGUAGE SHALL BE APPROVED BY THE OFFICE OF | | THE CITY ATTORNEY PRIOR TO RECORDATION. (REPEAT) | | | | 4) BMUD REQUIRES THAT SIDEWALKS ALONG BROADWAY BE A | | MINIMUM OF 8 FEET IN CLEAR WIDTH.THE SITE PLAN | | (SIGNED AND SEALED 6/26/07) AND THE CIVIL PLANS | | (REVISION 6/25/07, SIGNED AND SEALED 6/27/07) APPROVED | | WITH THE FOUNDATION PERMIT SHOW THIS STANDARD BEING | | MET, BUT THE PLANS SUBMITTED WITH THIS PERMIT DO NOT | | ADDRESS THE COMMENT. | | | | 5) AN APPROVED FDOT ACCESS CONNECTION PERMIT TO MOVE | | THE 29TH STREET CLOSURE IS REQUIRED. (REPEAT) | | | | 6) THE APPROVED ELEVATIONS DESIGNATE THIS AS A | | MEDITERRANEAN STYLE BUILDING WITH A BARREL TILE ROOF. | | SOME PAGES/DETAILS HAVE BEEN CORRECTED (EX. SHEET | | A7.1), BUT THERE ARE STILL REFERENCES TO ASPHALT | | SHINGLES (SHEETS A5.1 AND A5.2) AND THE ENTRY OVERHANG | | DETAILS (SHEET A5.3) SHOW SHINGLES NOT TILE.(PARTIAL | | REPEAT) | | | | 7) BONDS WILL BE REQUIRED FOR ALL IMPROVEMENTS IN THE | | RIGHTS-OF-WAY. (REPEAT) | | | | 8) THE CONSTRUCTION STAGING PLAN APPEARS WELL THOUGHT | | OUT.PLEASE PROVIDE DETAILS OF THE TEMPORARY BARRIERS. | | THESE SHALL NOT ALLOW ANY TRAFFIC TO FLOW THROUGH TO | | THE NEIGHBORHOOD WHILE THE NEW CLOSURES ARE BEING | | RECONSTRUCTED.ADDITIONALLY, PLEASE SUBMIT FOR | | REQUIRED PERMITS TO PREPARE THE CONSTRUCTION STAGING | | AREAS. | | | | 9) PLEASE NOTE THAT THE LANDSCAPE REQUIRED IN THE | | STREET CLOSURES IS TO BE SABAL PALMS PER THE COMMISSION | | APPROVED STREET CLOSURE PLAN. | | | | 10) PLEASE REVISE SHEETS LP-1 AND LP-2 TO INCORPORATE | | THE REDLINE NOTES MADE BY ALAN BARATTA, LANDSCAPE | | PLANNER (561) 822-1462, ON ONE OF THE PERMIT SUBMITTAL | | SETS.CONTACT HIM DIRECTLY FOR ANY CLARIFICATION. | | | | CONTACT ERIC SCHNEIDER (561) 822-1435. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2007-04-05 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2007-04-05 |
Time |
14:39 |
Rev Time |
0.00 |
Received By |
eschneid |
Date |
2007-04-05 |
Time |
14:39 |
Sent To |
|
|
Notes |
2007-04-05 14:44:01 | FAILED | | | | 1) THE PLANS WILL BE REQUIRED TO CONFORM TO THE CITY | | COMMISSION?S STREET CLOSURE RELOCATION PLAN. | | COMPACTORS W/ENCLOSURES ARE TO BE LOCATED ON THE SOUTH | | SIDE OF THE BUILDING.THE STREET CLOSURES AT 28TH AND | | 29TH STREET SHALL BE RELOCATED TO THE MID-BLOCK | | LOCATION (EAST OF THE PROJECT ENTRANCE).RELOCATED | | STREET CLOSURE LOCATIONS SHALL BE SHOWN ON THE PLANS. | | NOTE THAT PLANS FOR THE RELOCATED STREET CLOSURE DESIGN | | WILL NEED TO BE APPROVED BY THE CITY COMMISSION AND | | CONSTRUCTED BY THE DEVELOPER. | | | | 2) SUPPLY A RECORDED UNITY OF TITLE FOR THE ENTIRE SITE | | TO THE PLANNING AND ZONING DEPARTMENT. | | | | 3) PROVIDE THE RECORDED PUBLIC ACCESS EASEMENT FOR THAT | | PORTION OF THE SIDEWALK LOCATED ON THE SITE ALONG | | BROADWAY AVENUE AND FOR THE SIDEWALK ALONG THE ALLEY. | | THE EASEMENT LANGUAGE SHALL BE APPROVED BY THE OFFICE | | OF THE CITY ATTORNEY PRIOR TO RECORDATION. | | | | 4) PROVIDE THE RECORDED PERPETUAL MAINTENANCE AGREEMENT | | FOR THE REBUILT, PAVERED ALLEY.THE MAINTENANCE | | AGREEMENT LANGUAGE SHALL BE APPROVED BY THE OFFICE OF | | THE CITY ATTORNEY PRIOR TO RECORDATION. | | | | 5) PROVIDE PROOF THAT THE PROVISION OF ORDINANCE NOS. | | 3994-06 AND 3995-06 REQUIRING NORTHWOOD SG, LLC, OR ANY | | SUCCESSOR DEVELOPER OF THE TOWNHOUSE PROJECTS, TO POST | | A BOND TO THE CITY IN THE AMOUNT DETERMINED BY THE | | DIRECTOR OF ENGINEERING SERVICES TO COVER THE COSTS | | ASSOCIATED WITH THE INSTALLATION OF ALL REQUIRED STREET | | SIGNS, TRAFFIC CONTROL SIGNS AND ROAD STRIPING HAS BEEN | | MET. | | | | 6) PROVIDE THE PLANS SHOWING HOW THE UTILITY LINES IN | | THE ALLEY WILL BE BURIED UNDERGROUND, TO INCLUDE THE | | LOCATION OF THE REMAINING ABOVE GROUND UTILITY POLES. | | | | 7) THE ALLEY NAME IS ?OLD NORTHWOOD LANE.? | | | | 8) BMUD REQUIRES THAT SIDEWALKS ALONG BROADWAY BE A | | MINIMUM OF 8 FEET IN CLEAR WIDTH.PROVIDE A DETAIL OF | | THE F-CURB ALONG BROADWAY AVENUE FOR VERIFICATION OF | | THE DIMENSIONS SHOWN ON THE SIMONS AND WHITE CIVIL | | PLANS.PLEASE NOTE THAT THE GUTTER MAY NOT BE COUNTED | | AS PART OF THE SIDEWALK WIDTH. | | | | 9) AN APPROVED FDOT ACCESS CONNECTION PERMIT TO MOVE | | THE 29TH STREET CLOSURE IS REQUIRED. | | | | 10) PROVIDE THE COMPACTOR ENCLOSURE TRANSITION AT | | SIDEWALK AND STREET LEVEL.THE COMPACTOR IS TO BE AT | | STREET LEVEL.THE ADJACENT SIDEWALK WILL NEED TO BE | | SHOWN SLOPING DOWN TO THE RECESS ADJACENT TO THE | | COMPACTOR ENCLOSURE OPENING. | | | | 11) THE APPROVED ELEVATIONS DESIGNATE THIS AS A | | MEDITERRANEAN STYLE BUILDING WITH A BARREL TILE ROOF. | | THE SUBMITTED SOFFIT DETAIL (SHEET A7.1) AS WELL AS | | OTHER DETAILS SHOW A SHINGLE ROOF.THE ROOF IS TO BE | | BARREL TILE IN KEEPING WITH THE ELEVATIONS AND | | RENDERINGS SHOWN IN THE COUNTLESS NEIGHBORHOOD MEETINGS | | AND BEFORE THE CITY COMMISSION. | | | | 12) BONDS WILL BE REQUIRED FOR ALL IMPROVEMENTS IN THE | | RIGHTS-OF-WAY. | | | | 13) A CONSTRUCTION STAGING PLAN IS REQUIRED.THE PLAN | | SHALL INCLUDE HOW THE CONSTRUCTION TRAFFIC WILL BE KEPT | | OUT OF THE OLD NORTHWOOD NEIGHBORHOOD, WHERE WORKER | | PARKING WILL TAKE PLACE, AND THE CONSTRUCTION PHASING, | | ESPECIALLY HOW THE STREET CLOSURES WILL BE RELOCATED IN | | RELATIONSHIP TO THE CONSTRUCTION OF THE BUILDING. | | | | 14) THE PLANS SHALL SHOW THE SIDEWALK ADJACENT TO THE | | ALLEY CONTINUING TO 28TH AND 29TH STREETS CROSSINGS. | | | | CONTACT ERICSCHNEIDER @ (561) 822-1435. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2007-01-19 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2007-01-19 |
Time |
14:29 |
Rev Time |
0.00 |
Received By |
eschneid |
Date |
2007-01-11 |
Time |
11:49 |
Sent To |
|
|
Notes |
2007-01-19 14:30:54 | FAILED | | | | 1) THE PLANS WILL BE REQUIRED TO CONFORM TO THE CITY | | COMMISSION?S STREET CLOSURE RELOCATION PLAN.THIS WILL | | BE DETERMINED AT THE WORKSHOP ON FEBRUARY 5, 2007. | | | | 2) THE SURVEY SHALL SHOW ALL OF THE EXISTING | | IMPROVEMENTS IN THE ALLEY ADJACENT TO THE RESIDENCES ON | | THE EAST SIDE OF THE ALLEY (EX. FENCES, LANDSCAPE, | | ETC.). | | | | 3) SUPPLY A RECORDED UNITY OF TITLE FOR THE ENTIRE SITE | | TO THE PLANNING AND ZONING DEPARTMENT. | | | | 4) PROVIDE THE RECORDED PUBLIC ACCESS EASEMENT FOR THAT | | PORTION OF THE SIDEWALK LOCATED ON THE SITE.THE | | EASEMENT LANGUAGE SHALL BE APPROVED BY THE OFFICE OF | | THE CITY ATTORNEY PRIOR TO RECORDATION. | | | | 5) PROVIDE THE RECORDED PERPETUAL MAINTENANCE AGREEMENT | | FOR THE REBUILT, PAVERED ALLEY.THE MAINTENANCE | | AGREEMENT LANGUAGE SHALL BE APPROVED BY THE OFFICE OF | | THE CITY ATTORNEY PRIOR TO RECORDATION. | | | | 6) PROVIDE PROOF THAT THE PROVISION OF ORDINANCE NOS. | | 3994-06 AND 3995-06 REQUIRING NORTHWOOD SG, LLC, OR ANY | | SUCCESSOR DEVELOPER OF THE TOWNHOUSE PROJECTS, TO POST | | A BOND TO THE CITY IN THE AMOUNT DETERMINED BY THE | | DIRECTOR OF ENGINEERING SERVICES TO COVER THE COSTS | | ASSOCIATED WITH THE INSTALLATION OF ALL REQUIRED STREET | | SIGNS, TRAFFIC CONTROL SIGNS AND ROAD STRIPING HAS BEEN | | MET. | | | | 7) PROVIDE THE PLANS SHOWING HOW THE UTILITY LINES IN | | THE ALLEY WILL BE BURIED UNDERGROUND, TO INCLUDE THE | | LOCATION OF THE REMAINING ABOVE GROUND UTILITY POLES. | | | | 8) PROVIDE THE DETAILS FOR THE REBUILT, PAVERED ALLEY. | | | | 9) BMUD REQUIRES THAT SIDEWALKS ALONG BROADWAY BE A | | MINIMUM OF 8 FEET IN CLEAR WIDTH.THE SIMONS AND WHITE | | CIVIL PLANS SHOW THE SIDEWALK ALONG BROADWAY AT 5 FEET | | WIDE AND ONLY 2 FEET ON THE SITE FOR A TOTAL WIDTH OF | | ONLY 7 FEET. | | | | 10) THE SITE/LANDSCAPE AND CIVIL PLANS SHALL AGREE. | | THE FOLLOWING ITEMS DO NOT MATCH ON THE DIFFERING | | PLANS: | | | | A) LAYOUT OF THE COMPACTOR AND ADJOINING SIDEWALK. | | | | B) MAILBOX LOCATION MISSING ON SIMMONS AND WHITE | | PLANS. | | | | C) STABILIZED AND PLANTING AREA ALONG THE ALLEY - | | REQUIRED 5 FOOT WIDE STABILIZED AREA AND 4 FOOT WIDE | | PLANTING AREA.ONLY 8 FEET 7 INCH TOTAL SHOWN ON | | SHEETS 2 AND 3 OF 11 OF SIMONS AND WHITE PLANS, WHERE 9 | | FEET ARE REQUIRED.SIMONS AND WHITE PLAN SHEET 5 OF 11 | | SHOWS THE CORRECT 9 FOOT WIDTH IN THE SECTION DIAGRAM. | | | | 11) PROVIDE THE COMPACTOR SPECS/DETAIL AND A DETAIL | | SHOWING THE COMPACTOR BIN CURBING AT STREET LEVEL. | | | | 12) THE APPROVED ELEVATIONS DESIGNATE THIS AS A | | MEDITERRANEAN STYLE BUILDING WITH A BARREL TILE ROOF. | | THE SUBMITTED ELEVATIONS SHOW A SHINGLE ROOF.PLEASE | | NOTE THAT THE BARREL TILE IS CORRECTLY SHOWN ON | | ARCHITECTURAL SHEETS A8.2 AND A8.3. | | | | 13) THE REAR ELEVATION NEEDS TO VERIFY THE MINIMUM 25% | | GLAZING REQUIREMENT IS MET. | | | | 14) THE LANDSCAPE PLANS NEED TO SHOW PIGEON PLUM TREES | | AS ORIGINALLY APPROVED.THE LIVE OAKS ARE TOO LARGE A | | SPECIES FOR THE 4 FOOT WIDE LANDSCAPE STRIP AND TOO | | CLOSE TO THE FACE OF THE BUILDING TO ENSURE LONG TERM | | HEALTHY GROWTH. | | | | 15) PROVIDE DETAILS OF THE 5 FOOT STABILIZED AREA. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1435. |
|
|
|