Plan Review Details - Permit 06120112
Plan Review Stops For Permit 06120112
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-02-22 Cont ID  
Sent By jgomez Date 2007-02-22 Time 15:08 Rev Time 0.50
Received By jgomez Date 2007-02-22 Time 15:08 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-02-08 Cont ID  
Sent By jgomez Date 2007-02-08 Time 12:48 Rev Time 0.50
Received By jgomez Date 2007-02-08 Time 12:45 Sent To  
Notes
2007-02-08 13:01:42BUILDING REVIEW SECOND CHECKLIST;
 1- INSTALLATION SCHEDULE SUBMITTED STATES THAT
 STRUCTURE TO BE ATTACHED TO IS CONCRETE. THIS HOUSE IS
 A CONCRETE BLOCK STRUCTURE, NOT CONCRETE. REVISE AS
 REQUIRED.
  
 2- SHEET 2 OF 4 OF DRAWING 05-421 IDENTIFIES BOTTOM
 SHUTTER INSTALLATION TO BE DETAIL F, WHICH IS THE
 F-TRACK/DIRECT MOUNT SECTION. CLEARLY INDICATE SPECIFIC
 INSTALLATION FOR TOP PORTION?.NEED THIS INFORMATION
 TO VERIFY COMPLIANCE WITH TABLE 2 ON SHEET 3 OF 4.
 MINIMUM PANEL LENGTH IS DETERMINED BY THE TYPE OF
 INSTALLATION.SEE MINIMUM SIZE REQUIRED AND REVISE
 INSTALLATION SCHEDULE ACCORDINGLY.
  
 3- INSTALLATION SCHEDULE IS INCOMPLETE. MISSING ANCHOR
 SPACING FOR STORM SHUTTERS AT OPENINGS 9 THRU 14.
 COMPLETE INFORMATION AS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-19 Cont ID  
Sent By jgomez Date 2007-01-19 Time 16:55 Rev Time 0.50
Received By jgomez Date 2007-01-19 Time 16:55 Sent To  
Notes
2007-01-19 16:55:48BUILDING REVIEW CHECKLIST:
 1- PROVIDE APPROVED PRODUCT APPROVAL AS REQUIRED BY DCA
 RULE 9B-72 FOR STORM SHUTTERS.DRAWINGS SUBMITTED ARE
 NOT AN APPROVED PRODUCT APPROVAL.
  
 2-OWES $7.68 FOR UPDATED VALUATION AS REQUIRED BY
 SEC. 108.3 CITY AMENDMENTS TO FBC 2004.
  
 5- INSTALLATION SCHEDULE USED IS TOO OLD. PLEASE USE
 ATTACHED SAMPLE OF REVISED INSTALLATION SCHEDULE WHICH
 PROVIDES ALL REQUIRED INFORMATION FOR PLAN REVIEW. FILL
 IN ALL INFORMATION TO AVOID DELAYS. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-02-16 Cont ID  
Sent By adarroug Date 2007-02-16 Time 09:03 Rev Time 0.00
Received By adarroug Date 2007-02-16 Time 09:03 Sent To B
Notes
2007-02-16 09:03:52TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-02-02 Cont ID  
Sent By adarroug Date 2007-02-02 Time 10:57 Rev Time 0.00
Received By adarroug Date 2007-02-02 Time 10:57 Sent To B
Notes
2007-02-02 10:57:32TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-19 Cont ID  
Sent By jgomez Date 2007-01-19 Time 16:56 Rev Time 0.00
Received By jgomez Date 2006-12-06 Time 14:23 Sent To  
Notes
2006-12-06 14:23:31TO "MSIC" BOX#1