Plan Review Details - Permit 06120107
Plan Review Stops For Permit 06120107
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-01-24 Cont ID  
Sent By mjacobs Date 2007-01-24 Time 14:18 Rev Time 0.00
Received By mjacobs Date 2007-01-24 Time 14:14 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-01-23 Cont ID  
Sent By mjacobs Date 2007-01-23 Time 06:37 Rev Time 0.00
Received By mjacobs Date 2007-01-23 Time 06:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-03 Cont ID  
Sent By mjacobs Date 2007-01-03 Time 10:04 Rev Time 0.00
Received By mjacobs Date 2007-01-03 Time 07:23 Sent To  
Notes
2007-01-03 10:04:49BUILDING PLAN REVIEW
 PERMIT:06120107
 ADD:580 VILLAGE BLVD #380
 CONT: G.A. RAY INC.
 TEL: (561)630-4861
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)THE CLAIMED VALUATION ON THE APPLICATION IS LOW.
 FOR PERMITTING PURPOSES VALUATION OF BUILDING AND
 SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL ELECTRIC, PLUMBING, MECHINICAL, INTERIOR
 FINISH, ARCHITECTURAL AND DESIGN FEES MARKETING COSTS,
 OVERHEAN AND PROFIT EXCLUDING LAND VALUE. OUR VALUATION
 REFERENCE IS ICC (BVD), MARSHALL-SWIFT AND MEANS COSTS
 ANALYSIS. FBC.108.3*
  
 2) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 -----------------------------------
 ) SQ. FT. FOOTPRINT
 ) SQ. FT. UNDER ROOF (TOTAL)
 ) OCCUPANT LOAD
  
 3) 11-4.24.5 SHOW THE CLEAR FLOOR SPACE ON THE FLOOR
 PLAN. A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48
 INCHESCOMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED
 IN FRONT OF A SINK TO ALLOW FORWARD APPROACH.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-01-18 Cont ID  
Sent By dpalmer Date 2007-01-18 Time 16:46 Rev Time 0.00
Received By dpalmer Date 2007-01-18 Time 16:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-12-21 Cont ID  
Sent By dpalmer Date 2006-12-21 Time 13:20 Rev Time 0.00
Received By dpalmer Date 2006-12-21 Time 11:49 Sent To  
Notes
2006-12-21 13:22:15** UNSAT **
  
 1) NOTE: PLEASE PROVIDE MAXIMUM TIMES ON OVER
 RIDE/MOTION SENSING DEVICES.
 PLEASE INDICATE THE LIGHTING POWER DENSITIES FOR AREA.
  
 PLEASE SEE COMMON ARE CORRIDOR WHICH INDICATE A SWITCH
 TYPE OF MOTION DEVICE LOCATED AT ONE END OF AREA.
 PLEASE EITHER ADD AN ADDITIONAL DEVICE AT THE OTHER END
 OF HALL WAY FOR EGRESS OR PERHAPS A CEILING MOUNTED
 DEVICE? 360 DEGREE?PLEASE SEE LS 101 7.8, 7.9
 PLEASE SEE FBC 2004, 13-415.1.ABC.1.1, .1.2 AND .1.3
 13-415.2.ABC.1
  
 2) NOTE: PLEASE INDICATE THE MINIMUM CIRCUITING ON
 PLANS AT THIS TIME AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE. IT IS KNOWN TO THIS OFFICE THAT THE
 CIRCUITING WILL MOST LIKELY BE REVISED DURING
 CONSTRUCTION AND THOSE CAN BE REVISED AT A LATER DATE,
 HOWEVER THIS IS REQUIRED AT THIS TIME.
 PLEASE SEE THE LIGHTING ON PLANS IS NOT IDENTIFIED ON
 PANEL SCHEDULE.
 PLEASE BE SURE ROOMS AND AREAS ARE DESIGNATED. IE :
 OFFICE #5 RECEPTS, OFFICE LTS ETC.
 408.4, 310.16, 240.4,
 FBC 106.1.2, 106.1.3.5.2
  
 3) NOTE: PLEASE BE SURE TO STATE ALL THE RELEVANT CODES
 ON PLANS AS FOLLOWS AS THE CODES HAVE CHANGED.
 2002 NEC,(NFPA-70) , 2003 NFPA-101, 2002 NFPA-72 AND
 2004 FBC.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-01-24 Cont ID  
Sent By mawillia Date 2007-01-24 Time 12:20 Rev Time 0.00
Received By mawillia Date 2007-01-24 Time 12:20 Sent To B
Notes
2007-01-24 12:22:22*****APPROVED*****
  
  
 ALL COMMENTS FROM PREVIOUS FIRE PLAN REVIEW HAVE BEEN
 ADDRESSED.SHEET 2 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-12-27 Cont ID  
Sent By mawillia Date 2006-12-27 Time 10:21 Rev Time 0.00
Received By mawillia Date 2006-12-27 Time 10:21 Sent To  
Notes
2006-12-27 10:50:33*****DENIED*****
  
  
  
 1.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE
 PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 INTERFERE OR HINDER ACCESS TO OR EGRESS FROM OTHER
 SUITES ON THE FLOOR OR THE BUILDING.
  
 4.WILL THERE BE ADEQUATE VISIBILITY TOWARDS THE EXIT
 SIGN LIGHT FROM THE FRONT DOOR OF THE #3 OFFICE?IF
 NOT, AN ADDITIONAL EXIT LIGHT WILL BE REQUIRED.
  
 5.IT IS STATED IN THE REFLECTED CEILING /LIGHTING
 NOTE #9 THAT THE ENTIRE SPACE WILL BE FIRE SPRINKLED,
 WHEREAS IN THE POWER PLAN NOTE #8 IT STATES "NO FIRE
 ALARM AT THIS SPACE" ;HOW WILL THE FIRE SPRINKLER
 SYSTEM BE MONITORED?
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-01-18 Cont ID  
Sent By adarroug Date 2007-01-18 Time 12:13 Rev Time 0.00
Received By adarroug Date 2007-01-18 Time 12:13 Sent To  
Notes
2007-01-18 12:14:48TO "BOB"#4

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-05 Cont ID  
Sent By jleech Date 2007-01-05 Time 09:23 Rev Time 0.00
Received By jleech Date 2006-12-06 Time 08:47 Sent To  
Notes
2006-12-21 09:34:18TO "BOB"#10
2006-12-06 08:48:10WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-01-18 Cont ID  
Sent By tgordon Date 2007-01-18 Time 15:10 Rev Time 0.25
Received By tgordon Date 2007-01-18 Time 15:10 Sent To  
Notes
2007-01-18 15:11:41NEW PAGES SUBMITTED (RE-STAMP).

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-12-21 Cont ID  
Sent By tgordon Date 2006-12-21 Time 13:59 Rev Time 0.25
Received By tgordon Date 2006-12-21 Time 13:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-01-20 Cont ID  
Sent By jleech Date 2007-01-20 Time 10:08 Rev Time 0.00
Received By jleech Date 2007-01-20 Time 10:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-01-05 Cont ID  
Sent By jleech Date 2007-01-05 Time 09:23 Rev Time 0.00
Received By jleech Date 2007-01-05 Time 09:23 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved