Plan Review Details - Permit 06120085
Plan Review Stops For Permit 06120085
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-02-06 Cont ID  
Sent By jgomez Date 2007-02-06 Time 14:44 Rev Time 0.50
Received By jgomez Date 2007-02-06 Time 14:44 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-12-11 Cont ID  
Sent By jgomez Date 2006-12-11 Time 12:56 Rev Time 0.50
Received By jgomez Date 2006-12-11 Time 11:05 Sent To  
Notes
2006-12-11 11:29:36BUILDING REVIEW 2ND CHECKLIST:
 1- PROVIDE RAS 117 CALCULATIONS FOR ENHANCED FASTENING
 AT PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7 ON LAST PAGE OF DADE COUNTY NOA
 02-1219.01.FASTENER SPACING TABLE SUBMITTED CAN'T BE
 USED IN THIS AREA. TABLE IS ONLY GOOD FOR120MPH WIND
 ZONE. THE CITY IS IN 140MPH WIND ZONE. ON THE OTHER
 HAND TABLE APPLIES TO NAIL ENHANCEMENT IN THE FIELD
 AREA ONLY.
  
 2- A)SUBMITTED WIND UPLIFT PRESSURE CALCULATIONS FOR
 ROOF NEED TO BE SIGNED AND SEALED BY THE ENGINEER WHO
 MADE THE CALCULATIONS AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTES. ENGINEER TO PROVIDE ALL HIS
 INFORMATION AS REQUIRED BY FLORIDA ADMINISTRATIVE CODE
 SEC. 61G15-23.002.
  
 B) ENGINEER TO IDENTIFY SPECIFIC APPROVEDASSEMBLY
 FROM THE NOA SUBMITTED.
  
 C) CALCULATIONS ARE DONE FOR NOA 02.0710.01. NOA
 SUBMITTED IS 02-1219.01. INFORMATION NEED TO MATCH.
  
 D) ENGINEER TO PROVIDE ALL THE INFORMATION ON TOP OF
 FORM. INFORMATION WAS ERASED WITH WHITE OUT.
  
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-12-05 Cont ID  
Sent By shill Date 2006-12-05 Time 11:24 Rev Time 0.00
Received By shill Date 2006-12-05 Time 11:24 Sent To  
Notes
2006-12-05 11:28:07****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 ROOFING PERMIT; ONLY CHECKED ITEMS APPLY
  
 ____1.)A NOTICE OF COMMENCEMENT MUST BE FILED WITH
 THE CLERK OF COURTS PRIOR TO PERMIT PICKUP, FS713.13.
  
 _XX_2.)CONTRACTOR IS TO PROVIDE THE FOLLOWING
 INFORMATION ON THE APPLICATION, SEE ATTACHED POLICY:
  
 MEAN ROOF HEIGHT
  ROOF PITCH
  ROOF DECK TYPE
  AREA OF EACH ROOF TYPE
  
 ____3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED IN ADDITION TO THE EVALUATION REPORT
 SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG
  
 _XX_4.)FOR THE FLAT DECK, SELECT THE APPROVED
 ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER
 IF THE OPTIONS HAVE DIFFERENT PRESSURE LIMITATIONS.
  
 _XX_5.)FOR THE FLAT DECK, SPECIFY THE ENHANCED
 FASTENING FOR CORNER AND PERIMETER ZONES.
  
 ____ 6.)ON THE TILE PRODUCT APPROVAL, INDICATE WHICH
 METHOD OF ATTACHMENT YOU ARE USING.
  
 ____ 7.)SEE PRODUCT LIMITATION #7.CALCULATIONS
 PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF
 CONSULTANT REQUIRED FOR ENHANCED FASTENING.
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-12-11 Cont ID  
Sent By adarroug Date 2006-12-11 Time 09:59 Rev Time 0.00
Received By adarroug Date 2006-12-11 Time 09:59 Sent To B
Notes
2006-12-11 10:00:07TO "JGOMEZ" DESK/RESUB