Plan Review Details - Permit 06120062
Plan Review Stops For Permit 06120062
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-19 Cont ID  
Sent By shill Date 2007-01-19 Time 16:10 Rev Time 0.00
Received By shill Date 2007-01-19 Time 16:10 Sent To  
Notes
2007-01-19 16:12:03****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY
  
 _XX_1.A NOTICE OF COMMENCEMENT MUST BE FILED WITH
 THE CLERK OF COURTS PRIOR TO PERMIT ISSUANCE,
 FS713.13.
  
  
 _XX_4.COMPLETE THE ATTACHED INSTALLATION SCHEDULE
 OR PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT.
  
  
 _XX_ 9.TWO COPIES OF ALL DOCUMENTS REQUIRED.ONLY
 ONE FLOOR PLAN WAS SUBMITTED.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-19 Cont ID  
Sent By shill Date 2007-01-19 Time 16:12 Rev Time 0.00
Received By shill Date 2006-12-04 Time 15:24 Sent To  
Notes
2006-12-04 15:25:22TO "MISC" BOX#1