Plan Review Details - Permit 06120027
Plan Review Stops For Permit 06120027 |
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
F |
Date |
2007-07-10 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-07-09 |
Time |
12:26 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-07-09 |
Time |
12:21 |
Sent To |
PC |
|
Notes |
2007-07-09 12:26:14 | | | SUBMITTAL DENIED | | | | AN ELECTRICAL SUBMITTAL IN LETTER FORM FROM THE | | ENGINEER, VERIFYING CODE COMPLIANCE FOR AN UNPERMITTED | | INSTALLATION, IS UNACCEPTABLE. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
N |
Date |
2007-06-28 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-06-28 |
Time |
14:45 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-06-28 |
Time |
14:44 |
Sent To |
PC |
|
Notes |
2007-06-28 14:57:45 | | | | | | | | | RESTAMP./WRT. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2007-02-27 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-02-27 |
Time |
15:08 |
Rev Time |
2.00 |
Received By |
btrobaug |
Date |
2007-02-27 |
Time |
15:08 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2006-12-13 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2006-12-13 |
Time |
` |
Rev Time |
1.00 |
Received By |
btrobaug |
Date |
2006-12-13 |
Time |
06:35 |
Sent To |
|
|
Notes |
2006-12-13 07:38:22 | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | 1} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT | | CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE | | EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS | | EQUAL TO OR GREATER THAN THE AVAILABLE FAULT. | | | | 2} IF USING ARTICLE 220.30 TO CALCULATE THE LOAD FOR | | THIS SERVICE, THEN TABLE 220.32CANNOT BE USED. SEE | | CLARIFICATION OF USE IN 220.32(C). INDICATE WHICH IS | | BEING USED ON THE PLAN. | | NOTE: ALL ARTICLES COMMENTED ON ARE FROM THE 2002 | | NEC. | | | | 3} THE NOTE REGARDING 220.84 IS INCORRECT AND MUST BE | | CHANGED TO REFLECT THE CODE IN EFFECT AT TIME OF | | APPLICATION. | | | | 4} THE LAUNDRY CIRCUIT REQUIRED BY 220.16(B) WAS NOT | | INCLUDED IN THE CALCULATION. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW. | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-06-19 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-06-19 |
Time |
09:58 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-06-19 |
Time |
09:58 |
Sent To |
E |
|
Notes |
2007-06-19 09:58:22 | TO "BTROBAUG" DESK/RESTAMP |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-02-27 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-02-27 |
Time |
15:08 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2006-12-01 |
Time |
15:58 |
Sent To |
PC |
|
Notes |
2006-12-01 15:59:00 | TO "E" BOX |
|
|
|