Plan Review Details - Permit 06120023
Plan Review Stops For Permit 06120023
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-02-05 Cont ID  
Sent By lmartine Date 2007-02-05 Time 17:18 Rev Time 0.00
Received By lmartine Date 2007-02-05 Time 17:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-03-05 Cont ID  
Sent By btrobaug Date 2007-03-05 Time 08:07 Rev Time 0.50
Received By btrobaug Date 2007-03-05 Time 07:50 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-12-11 Cont ID  
Sent By btrobaug Date 2006-12-11 Time 11:44 Rev Time 0.50
Received By btrobaug Date 2006-12-11 Time 06:56 Sent To P
Notes
2006-12-11 11:32:29 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT.
  
 2} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-02-22 Cont ID  
Sent By adarroug Date 2007-02-22 Time 18:03 Rev Time 0.00
Received By adarroug Date 2007-02-22 Time 18:03 Sent To E
Notes
2007-02-22 18:03:24TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-05 Cont ID  
Sent By lmartine Date 2007-02-05 Time 17:19 Rev Time 0.00
Received By lmartine Date 2006-12-01 Time 15:57 Sent To  
Notes
2006-12-01 15:58:18TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-12-12 Cont ID  
Sent By tgordon Date 2006-12-12 Time 11:21 Rev Time 0.15
Received By tgordon Date 2006-12-12 Time 11:21 Sent To B
Notes
2006-12-12 11:22:39NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-02-27 Cont ID  
Sent By mperson Date 2007-02-27 Time 15:12 Rev Time 0.33
Received By mperson Date 2007-02-27 Time 15:12 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-12-12 Cont ID  
Sent By mperson Date 2006-12-12 Time 09:01 Rev Time 0.45
Received By mperson Date 2006-12-12 Time 09:01 Sent To M
Notes
2006-12-12 09:47:43DENIED
 REFERENCE: FBC-2004 PLUMBING AND FBC-2004 CHAPTER 1
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET 3 OF 3 THE SANITARY PLUMBING RISER DIAGRAM
 DOES NOT REFLECT THE FLOOR PLAN. THE WATER CLOSETS ARE
 MISSING, SINKS ARE INDICATED IN BATHROOMS THAT ARE NOT
 ON THE FLOOR PLAN. KITCHEN SINK IS MISLABLED AS A LAV.
 PLEASE NOTE THAT ONLY CHANGES TO THEPLUMBING SYSTEM
 NEED TO BE INDICATED ON A SANITARY RISER DIAGRAM. IN
 THIS SUBMITTAL THE ONLY CHANGE IN THE SANITARY SYSTEM
 IS THE RELOCATION OF A LAVATORY IN THE FIRST FLOOR BATH
 AND IT IS NOT INDICATED ON THE SANITARY RISER DIAGRAM.
 PLEASE CORRECT THIS ON THE RESUBMITTAL.
  
 2. PER FBC-2004 PLUMBING, TABLE 403.1: ONE (1)
 AUTOMATIC CLOTHES WASHER CONNECTOR IS REQUIRED AND ITS
 LOCATION NEEDS TO BE INDICATED ON THE RESUBMITTED
 DRAWINGS AS EXISTING, RELOCATED OR NEW. IF IT IS
 RELOCATED OR NEW IT NEEDS TO BE INDICATED ON THE FLOOR
 PLAN AND THE RESUBMITTED SANTARY RISER DIAGRAM.
  
 3. PLEASE NOTE ON THE RESUBMITTED DRAWINGS ON SHEET 2
 OF 3 THAT THE RELOCATED WATER HEATER WILL COMPLY WITH
 FBC-2004 PLUMBING, SECTION 607.3 THERMAL EXPANSION
 CONTROL.
  
 4. PLEASE INDICATE ON SHEET 2 OF 3 IF THE KITCHEN SINK
 IS EXISTING, RELOCATED OR NEW. IF IT IS RELOCATED OR
 NEW IT NEEDS TO BE INDICATED ON THE FLOOR PLAN AND THE
 RESUBMITTED SANITARY RISER DIAGRAM.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  