2006-12-12 09:47:43 | DENIED |
| REFERENCE: FBC-2004 PLUMBING AND FBC-2004 CHAPTER 1 |
| |
| THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING |
| PLAN REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1. SHEET 3 OF 3 THE SANITARY PLUMBING RISER DIAGRAM |
| DOES NOT REFLECT THE FLOOR PLAN. THE WATER CLOSETS ARE |
| MISSING, SINKS ARE INDICATED IN BATHROOMS THAT ARE NOT |
| ON THE FLOOR PLAN. KITCHEN SINK IS MISLABLED AS A LAV. |
| PLEASE NOTE THAT ONLY CHANGES TO THEPLUMBING SYSTEM |
| NEED TO BE INDICATED ON A SANITARY RISER DIAGRAM. IN |
| THIS SUBMITTAL THE ONLY CHANGE IN THE SANITARY SYSTEM |
| IS THE RELOCATION OF A LAVATORY IN THE FIRST FLOOR BATH |
| AND IT IS NOT INDICATED ON THE SANITARY RISER DIAGRAM. |
| PLEASE CORRECT THIS ON THE RESUBMITTAL. |
| |
| 2. PER FBC-2004 PLUMBING, TABLE 403.1: ONE (1) |
| AUTOMATIC CLOTHES WASHER CONNECTOR IS REQUIRED AND ITS |
| LOCATION NEEDS TO BE INDICATED ON THE RESUBMITTED |
| DRAWINGS AS EXISTING, RELOCATED OR NEW. IF IT IS |
| RELOCATED OR NEW IT NEEDS TO BE INDICATED ON THE FLOOR |
| PLAN AND THE RESUBMITTED SANTARY RISER DIAGRAM. |
| |
| 3. PLEASE NOTE ON THE RESUBMITTED DRAWINGS ON SHEET 2 |
| OF 3 THAT THE RELOCATED WATER HEATER WILL COMPLY WITH |
| FBC-2004 PLUMBING, SECTION 607.3 THERMAL EXPANSION |
| CONTROL. |
| |
| 4. PLEASE INDICATE ON SHEET 2 OF 3 IF THE KITCHEN SINK |
| IS EXISTING, RELOCATED OR NEW. IF IT IS RELOCATED OR |
| NEW IT NEEDS TO BE INDICATED ON THE FLOOR PLAN AND THE |
| RESUBMITTED SANITARY RISER DIAGRAM. |
| |
| **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| IN RED INK FOR REFERENCE FOR |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |