Plan Review Details - Permit 06110802
Plan Review Stops For Permit 06110802
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-12-21 Cont ID  
Sent By btrobaug Date 2006-12-21 Time 17:33 Rev Time 0.50
Received By btrobaug Date 2006-12-15 Time 07:14 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-16 Cont ID  
Sent By adarroug Date 2007-04-16 Time 11:22 Rev Time 0.00
Received By adarroug Date 2007-04-16 Time 11:22 Sent To P
Notes
2007-04-16 11:22:23TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-12-26 Cont ID  
Sent By btrobaug Date 2006-12-26 Time 11:10 Rev Time  
Received By mperson Date 2006-12-15 Time 07:14 Sent To PC
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-04-27 Cont ID  
Sent By mperson Date 2007-04-27 Time 09:00 Rev Time 0.15
Received By mperson Date 2007-04-27 Time 09:00 Sent To PC
Notes
2007-04-27 09:04:06REVISION: SUBMITTAL TO CHANGE PUMP BASE PLATE TO
 GALVANIZED STEEL.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-01-26 Cont ID  
Sent By mperson Date 2007-01-26 Time 16:18 Rev Time 0.45
Received By mperson Date 2007-01-26 Time 16:18 Sent To PC
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-12-26 Cont ID  
Sent By btrobaug Date 2006-12-26 Time 10:52 Rev Time 0.45
Received By mperson Date 2006-12-26 Time 10:52 Sent To PC
Notes
2006-12-26 11:10:08DENIED
 REFERENCE: FBC-2004 PLUMBING AND FBC-2004
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW:
  
 1. PLEASE PROVIDE A DETAIL INDICATING BOOSTER PUMP
 LOCATION TO STRUCTURES AND HOW BOOSTER PUMPS ARE TO BE
 ANCHORED TO MEET 140 MILES PER HOUR WINDSPER FBC-2004
 SECTIONS1603.1.4 WIND DESIGN DATA, AND1609.1.3
 ANCHORAGE AGAINST OVERTURNING, UPLIFT AND SLIDING.
  
 2. PROVIDE NOTICE OF COMMENCEMENT RECORDED WITH THE
 CLERK OF THE COURT BEFORE A PERMIT CAN BE ISSUED.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721