Plan Review Details - Permit 06110744
Plan Review Stops For Permit 06110744
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-12-11 Cont ID  
Sent By lursu Date 2006-12-11 Time 16:14 Rev Time 0.00
Received By lursu Date 2006-12-11 Time 16:14 Sent To  
Notes
2006-12-11 16:15:47ASSIGN PERMIT TO UNIT 400 ( UNIT 0001, UNDER PCN =
 74434321060360060)
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 E-MAIL:[email protected]
2006-12-10 08:03:05MADE COPY AND SENT TO ADDRESSING. DV PALMER

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-04-09 Cont ID  
Sent By jwitmer Date 2007-04-09 Time 14:53 Rev Time 0.77
Received By jwitmer Date 2007-04-09 Time 14:43 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-01-30 Cont ID  
Sent By jwitmer Date 2007-01-30 Time 10:32 Rev Time 1.22
Received By jwitmer Date 2007-01-30 Time 10:32 Sent To  
Notes
2007-01-30 10:37:13BUILDING PLAN REVIEW
 PERMIT: 06110744
 ADD: 444 W RAILROAD AVSUITE# 400
 CONT:PBM DEVELOPMENT
 TEL: (561)715-1800
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) PBM DEVELOPMENT REQUIES A CERTIFICATE OF
 AUTHORIZATION.
 481.219 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL
 SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-12-13 Cont ID  
Sent By jwitmer Date 2006-12-13 Time 12:06 Rev Time 1.55
Received By jwitmer Date 2006-12-13 Time 11:35 Sent To  
Notes
2006-12-13 12:24:14BUILDING PLAN REVIEW
 PERMIT: 06110744
 ADD: 444 W RAILROAD AVSUITE# 400
 CONT:PBM DEVELOPMENT
 TEL: (561)715-1800
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) ADDITIONAL INFORMATION REQUIRED. 106.1.2*
 THIS COMMENT SHALL DEAL WITH THE EXIT ACCESS CORRIDOR.
 THE SHELL PERMIT REMOVED THE EXIT ACCESS CORRIDORS
 FROM
  
 THEIR SCOPE OF WORK.
 EITHER ONE OF TWO THINGS WILL NEED TO HAPPEN. UNDER THE
 SHELL PERMIT PUT A REVISION IN TFOR THE FOURTH FLOOR
 CORRIDORS OR MAKE THE FOURTH FLOOR CORRIDORS PART OF
 THIS PERMIT.
 SHEET A-02 INDICATES THAT THE EXIT ACCESS CORRIDORS ARE
 EXISTING.
  
 3) SHEET A-02THE FOLLOWING DOORS ARE MISSING THE 18"
 ON
 THE LATCH/ PULL SIDEOF THE DOOR: 404, 408,409 & 416.
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARANCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARANCES SHALL BE
 CLEAR & LEVEL.11-4.4.4 PROTRUDING OBJECTS. OBJECTS
 PROJECTING FROM WALLS (FOR EXAMPLE, TELEPHONES) WITH
 THEIR
 LEADING EDGES BETWEEN 27 INCHES AND 80 INCHES (685 MM
 AND 2030 MM)
 ABOVE THE FINISHED FLOOR SHALL PROTRUDE NO MORE THAN 4
 INCHES (102 MM)
 INTO WALKS, HALLS, CORRIDORS, PASSAGEWAYS, OR AISLES
 [SEE FIGURE 11-8 (A)].
 OBJECTS MOUNTED WITH THEIR LEADING EDGES AT OR BELOW 27
 INCHES (685 MM)
 ABOVE THE FINISHED FLOOR MAY PROTRUDE ANY AMOUNT [SEE
 FIGURE 11-8 (A) AND
 FIGURE 11-8 (B)]. FREE-STANDING OBJECTS MOUNTED ON
 POSTS OR PYLONS MAY
 OVERHANG 12 INCHES (305 MM) MAXIMUM FROM 27 INCHES TO
 80 INCHES
 (685 MM TO 2030 MM) ABOVE THE GROUND OR FINISHED FLOOR
 [SEE FIGURE 11-8 (C)
 AND FIGURE 11-8 (D)]. PROTRUDING OBJECTS SHALL NOT
 REDUCE THE CLEAR WIDTH OF AN
 ACCESSIBLE ROUTE OR MANEUVERING SPACE [SEE FIGURE 11-8
 (E)].
 1003.3.3 HORIZONTAL PROJECTIONS.
 ELEMENTS CANNOT PROJECT OVER A WALKING SURFACE MORE
 THAN 4 INCHES (102 MM)
 WHEN THEY ARE LOCATED BETWEEN 27 AND 80 INCHES (686 AND
 2032 MM) ABOVE
 THE FLOOR. HANDRAILS CAN PROJECT UP TO 4? INCHES (114
 MM) FROM THE WALL.
  
 4) SHEET A-02 RESTROOM 407, PLEASE PROVIDE TURNING
 RADIUS WITHIN THE RESTROOM.
 11-4.2.3 WHEELCHAIR TURNING SPACE. THE SPACE REQUIRED
 FOR A WHEELCHAIR TO M
 AKE A 180-DEGREE TURN IS A CLEAR SPACE OF 60 INCHES
 (1525 MM) DIAMETER [SEE
 FIGURE 11-3 (A)] OR A T-SHAPED SPACE [SEE FIGURE 11-3
 (B)].
  
 5) SHEET A-02 RESTROOM PLEASE INDICATE THE CLEAR FLOOR
 SPACE REQUIRED FOR THE PLUMBING FIXTURES. 11-4.22.2
 DOORS. ALL DOORS TO
 ACCESSIBLE TOLIET ROOMS SHALL COMPLY
 WITH 11-4.13. DOORS SHALL NOT SWING INTO
 CLEAR FLOOR SPACE REQUIRED FOR ANY
 FIXTURE.
  
 6) SHEETA-06 BREAK ROOM THE PLANS DO NOT INDICATE A
 SINK BUT THE PLUMBING ISOMETRIC DOES.
 PLEASE PROVIDE CABINET DETAILSCOMPLYING WITH:
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
  
 7)SHEET A-05 INDICATES VARIOUS DETAILS WITH CROWN
 MOULDINGS, NO MENTION OF TYPE OF MATERIAL,
 2604.1 GENERAL.
 PLASTIC MATERIALS INSTALLED AS INTERIOR FINISH OR TRIM
 SHALL COMPLY WITH CHAPTER 8 . FOAM PLASTICS SHALL ONLY
 BE INSTALLED AS INTERIOR FINISH WHERE APPROVED IN
 ACCORDANCE WITH THE SPECIAL PROVISIONS OF SECTION
 2603.8 . FOAM PLASTICS THAT ARE USED AS INTERIOR FINISH
 SHALL ALSO MEET THE FLAME SPREAD INDEX REQUIREMENTS FOR
 INTERIOR FINISH IN ACCORDANCE WITH CHAPTER 8 . FOAM
 PLASTICS INSTALLED AS INTERIOR TRIM SHALL COMPLY WITH
 SECTION 2604.2 .
 TRIM
 2604.2 INTERIOR TRIM .
 FOAM PLASTIC USED AS INTERIOR TRIM SHALL COMPLY WITH
 SECTIONS 2604.2.1 THROUGH 2604.2.4 .
  
 2604.2.1 DENSITY.
 THE MINIMUM DENSITY OF THE INTERIOR TRIM SHALL BE 20
 PCF (320 KG/M 3 ).
  
 2604.2.2 THICKNESS.
 THE MAXIMUM THICKNESS OF THE INTERIOR TRIM SHALL BE 0.5
 INCH (12.7 MM) AND THE MAXIMUM WIDTH SHALL BE 8 INCHES
 (204 MM).
  
 2604.2.3 AREA LIMITATION.
 THE INTERIOR TRIM SHALL NOT CONSTITUTE MORE THAN 10
 PERCENT OF THE AGGREGATE WALL AND CEILING AREA OF ANY
 ROOM OR SPACE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-04-24 Cont ID  
Sent By dpalmer Date 2007-04-24 Time 14:08 Rev Time 0.00
Received By dpalmer Date 2007-04-24 Time 13:20 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-04-12 Cont ID  
Sent By dpalmer Date 2007-04-12 Time 16:14 Rev Time 0.00
Received By dpalmer Date 2007-04-12 Time 15:50 Sent To  
Notes
2007-04-12 16:15:37** UNSAT **
  
 1) NOTE: PLEASE SEE THE NEW REVISED ENERGY CALCULATIONS
 ARE NOT SEALED BY THE ENGINEER OF RECORD AS REQUIRED
 PER 13-103.1.1.1
 PLEASE SUBMIT SIGNED, DATED AND SEALED. FS 471.025
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-04-04 Cont ID  
Sent By dpalmer Date 2007-04-04 Time 13:04 Rev Time 0.00
Received By dpalmer Date 2007-04-04 Time 12:09 Sent To  
Notes
2007-04-04 13:04:12** UNSAT 2ND REVIEW **
  
 1) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEW. THE
 ENERGY CALCULATIONS AND/OR PERFORMANCE DENSITIES WERE
 NOT SHOWN IN COMPLIANCE. PLEASE SEE THE TYPE, AND
 AMOUNT OF FIXTURES, WATTAGE(S) ETC AS SHOWN ON PLANS DO
 NOT CORRELATE WITH THE ENERGY CALCULATIONS SUBMITTED.
 PLEASE ADJUST AND REVISE 13-415.1.AB.1.1, 13-415.2
 PLEASE SEE THE METHOD OF CONTROL FOR LIGHTING ON ENERGY
 CALCULATIONS NEEDS TO CORRELATE WITH PLANS.
 (AUTOMATED/OCCUPANCY/TIMERS ETC).
  
 2) NOTE: PLEASE SEE THAT NO HAND DRAWN CHANGES ARE
 PERMITTED ON PLANS.
 PLEASE BE SURE TO STATE THE MAXIMUM TIMES FOR OCCUPANCY
 TYPE DEVICES ON PLANS.
 13-415.1.ABC.1.1
  
 3) NOTE: PLEASE SEE THE REQUIRED LICENSE NUMBER FOR
 FIRM IS MISSING FROM SEVERAL SHEETS IN BOTH SETS OF
 PLANS. THIS IS NOT ONLY REQUIRED ON ONE SHEET, THIS IS
 REQUIRED FOR EVERY SHEET WHICH CONTAINS THE SAID TITLE
 BLOCK FOR FIRM. (PBM). FS 481.219, FAC 61G1-16.004
 THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADES.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-01-25 Cont ID  
Sent By dpalmer Date 2007-01-25 Time 14:32 Rev Time 0.00
Received By dpalmer Date 2007-01-25 Time 14:32 Sent To  
Notes
2007-01-25 14:33:05** UNSAT **
  
 1) NOTE: PLEASE SEE NOTE #1 FROM PREVIOUS REVIEW. IT IS
 NOTED THAT APPLICATION HAS BEEN MADE TO DBPR, HOWEVER
 UNTIL ISSUANCE OF THE FIRM LICENSE NUMBER HAS BEEN
 DONE, CONFIRMED AND ON TITLE BLOCKS, WE ARE NOT ABLE TO
 STAMP OR PASS PLANS EVEN IF APPLICATION IS MADE. PLEASE
 KNOW THAT THIS OFFICE HAS BEEN IN CONTACT WITH THE
 STATE'S LEGAL COUNSEL ON THIS MATTER AND WE HAVE BEEN
 INFORMED DIRECTLY ON THIS MATTER.
 FS 481.219, FAC 61G1-16.004.
  
 2) NOTE: PLEASE SEE SECRETARIES FILE AREA MISSING
 CONTROL FOR LIGHTING PER 13-415.1.ABC.1.1, .1.2 PLEASE
 SEE KNOW THIS WAS NOT IN PREVIOUS REVIEW NOTES, HOWEVER
 PLEASE SUBMIT/INCLUDE ENERGY/PERFORMANCE CALCULATIONS
 FOR LIGHTING ALLOWANCES PER 13-415.1.AB.1, 13-415.2
  
 3) NOTE: PLEASE SEE ADDRESS IS STILL MISSING FROM THE
 TITLE BLOCKS ON EACH SHEET. 61G1-16.004/ 61G15-23.002
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-12-10 Cont ID  
Sent By dpalmer Date 2006-12-10 Time 08:24 Rev Time 0.00
Received By dpalmer Date 2006-12-10 Time 07:34 Sent To I
Notes
2006-12-10 08:26:42** UNSAT **
  
  
 1) NOTE: PLEASE SEE MISSING COMPLETE INFORMATION FOR A
 TITLE BLOCK FOR THE ARCHITECT OF RECORD. PLEASE SEE
 ATTACHED SHEET FROM DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATION. PLEASE SEE NO ADDRESS
 INFORMATION ETC.
 PLEASE KNOW IF WORKING THROUGH PBM DEVELOPMENT, AND PBM
 IS OFFERING ARCHITECTURAL SERVICES, THEN PBM WOULD BE
 REQUIRED TO LIST THEIR CERTIFICATE OF AUTHORIZATION
 NUMBER. (IF APPLICABLE).
 FLORIDA ADMINISTRATIVE CODE 61G1-16.004, FLORIDA
 STATUTES 481.219
 **THIS IS NOT A COMMENT RELATED TO KAMM CONSULTING,
 HOWEVER TITLE BLOCKS ARE REQUIRED FOR ALL SHEETS PER
 ABOVE AND WHETHER OR NOT COMMENT IS MADE BY ANY OTHER
 TRADE.
  
 2) NOTE: PLEASE LIST THE FOLLOWING MINIMUM CODES
 RELEVANT TO THIS PROJECT AND DESIGN.
 2002 NFPA-72, 2002 NFPA-70, 2003 NFPA-101
 ** 2004 FBC**
  
 3) NOTE: PLEASE SEE MISSING LIGHTING CONTROL FOR ALL
 PER 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE SEE
 MISSING CONTROLS FOR COMMON AREAS. PLEASE SEE OVER
 RIDES DEVICES FOR THESE AREAS ALSO DEPENDING ON
 "SYSTEM" OR DEVICES CHOSEN. PLEASE SEE THE SYMBOL
 LEGEND FOR ALL DEVICES SHALL INDICATE ALL MAXIMUM TIMES
 FOR DEVICES. (30MINS FOR OCCUPANCY SENSOR TYPE AND 4HRS
 MAX FOR TIMER TYPE)
 PLEASE PROVIDE SCHEDULING FOR ANY PROPOSED SYSTEM.
 PLEASE SEE ALL AREAS CONTAIN FLOOR TO CEILING HEIGHT
 PARTITIONS SHALL CONTAIN DEVICE(S) FOR CONTROL. (PLEASE
 SEE STORAGE)
 PLEASE SEE 13-415.2, 13-415.2.ABC.1 FOR MISSING MAXIMUM
 PERMITTED LIGHTING POWER DENSITIES.
 ** PLEASE SUBMIT THE ABOVE. AS THERE ARE ITEMS NOT YET
 SUBMITTED, A REVIEW OF SAID SYSTEM/DEVICES ETC CAN NOT
 BE FULLY ACCOMPLISHED AT THIS TIME.
  
 4) NOTE: PLEASE PROVIDE A DETAIL ON ALL EMERGENCY
 AND/OR EXIT LIGHTING WIRED AHEAD OF ANY OVER RIDE
 CONTROL DEVICES PER 700.12E. PLEASE SEE A
 CLOUDED/HIGHLIGHTED NOTE MAY ALSO BE DONE. THIS AHJ HAS
 BEEN HAVING MANY INSTANCES WHERE EMERGENCY AND EXIT
 LIGHTS ARE BEING WIRED ON THE LOAD SIDE OF OC/ TIMER
 DEVICES.
  
 5) NOTE: PLEASE INDICATE ALL CONTINUOUS LOADS AT 125%.
 215.3, 230.42 ETC.
 FBC 106.1.2 ADMIN SECTION.
  
 6) NOTE: PLEASE KNOW EITHER AT THIS POINT OR BEFORE
 FINAL, A REVISION FOR ALL CIRCUITS TO SPECIFIC ROOMS
 AND AREAS WILL BE REQUIRED. (LIGHTING CIRCUITS ETC.)
 408.4.
 ALL RECEPTACLE CIRCUITS ARE OK AS SHOWN.
  
 7) NOTE:** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDEDSHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.PLEASE KNOW ONLY
 ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
2006-12-10 07:35:20REMOVED FROM INCOMING, WILL BEROUTED BACK TO INCOMING
 ONCE REVIEW IS DONE TO WAIT FOR COMMBOB.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-04-16 Cont ID  
Sent By mawillia Date 2007-04-16 Time 13:39 Rev Time 0.00
Received By mawillia Date 2007-04-16 Time 13:21 Sent To  
Notes
2007-04-16 13:39:18*****APPROVED*****
  
  
 PLAN SHEETS LS-01, E2.1, FA2.1 AND FS2.1 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-04-04 Cont ID  
Sent By mawillia Date 2007-04-04 Time 17:20 Rev Time 0.00
Received By mawillia Date 2007-04-04 Time 17:14 Sent To  
Notes
2007-04-04 17:19:33*****APPROVED*****
  
  
  
 ALL COMMENTS FROM THE 02/06/07 FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;THE APPROPIATE PLAN SHEET(S) TO BE
 STAMPED WHEN ALL OTHER PLAN REVIEWS HAVE BEEN
 SATISFIED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-02-06 Cont ID  
Sent By mawillia Date 2007-02-06 Time 10:59 Rev Time 0.00
Received By mawillia Date 2007-02-06 Time 10:58 Sent To  
Notes
2007-02-06 11:01:10*****DENIED*****
  
  
 01.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE
 PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED.
  
 02. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 03.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT
 OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 04.THE COMPLETE ADDRESS OF WHERE THE SCOPE OF WORK
 WILL BE CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.
  
 05.DISPLAY THE TENANT SPACE NUMBER FOR THIS SITE SO
 THAT IT IS DISTINGUISHABLE FROM OTHER TENANT SITES ON
 THE FLOOR.AS PER WEST PALM BEACH CODE, THOSE NUMBERS
 SHALL BE NO LESS THAN 3" IN HEIGHT.
  
 06.DOOR(S) LEADING DIRECTLY TO THE FOURTH FLOOR
 CORRIDOR SHALL BE AN APPROVED, LISTED, AND LABELED FIRE
 DOOR & ASSEMBLY IN ACCORDANCE WITH THE REQUIREMENTS OF
 NFPA 80.
  
 07.WHAT IS INTERIOR FINISH CLASSIFICATION FOR THE
 WALLS AND CEILINGS IN THE EXITS, EXIT ACCESS CORRIDORS,
 AND IN ALL OTHER AREAS?
  
 08.PROVIDE A LIFE SAFETY PLAN SHEET WHICH INDICATES
 THE TRAVEL DISTANCE TO THE EXIT(S).ALSO ON THIS
 SHEET, INDICATE THE LOCATION OFFIRE EXTINGUISHER(S)
 AT DISTANCES TO SATISFY THE 75' TRAVEL DISTANCE
 REQUIREMENT.
  
 09.ON SHEET FA0.1, FIRE ALARM NOTE #17 SHOULD BE
 CHANGED TO "INITIATE A GENERAL FIRE ALARM".
  
 10.PROVIDE A LAYOUT OF THE FIRE SPRINKLER SYSTEM FOR
 THIS TENANT SPACE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-12-26 Cont ID  
Sent By mawillia Date 2006-12-26 Time 10:57 Rev Time 0.00
Received By mawillia Date 2006-12-26 Time 10:57 Sent To  
Notes
2006-12-26 11:23:06*****DENIED*****
  
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 3.DISPLAY THE TENANT SPACE NUMBER FOR THIS SITE SO
 THAT IT IS DISTINGUISHABLE FROM OTHER TENANT SPACES ON
 THE FLOOR.AS PER WEST PALM BEACH CODE, THOSE NUMBERS
 SHALL BE NO LESS THAN 3" IN HEIGHT.
  
 4.WHAT IS INTERIOR FINISH CLASSIFICATION FOR THE
 WALLS AND CEILINGS IN THE EXITS AND EXIT ACCESS
 CORRIDORS?
  
 5.ADDRESS BUILDING REVIEW COMMENTS IN REGARDS TO EXIT
 ACCESS ANDMANEUVERING CLEARANCES.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-04-23 Cont ID  
Sent By adarroug Date 2007-04-23 Time 10:06 Rev Time 0.00
Received By adarroug Date 2007-04-23 Time 10:06 Sent To E
Notes
2007-04-23 10:07:02TO "BOB"#6

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-04-11 Cont ID  
Sent By adarroug Date 2007-04-11 Time 15:11 Rev Time 0.00
Received By adarroug Date 2007-04-11 Time 15:11 Sent To  
Notes
2007-04-11 15:11:28TO "BOB"#16

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-04-03 Cont ID  
Sent By spalmer Date 2007-04-03 Time 17:30 Rev Time 0.00
Received By spalmer Date 2007-04-03 Time 17:30 Sent To  
Notes
2007-04-03 17:31:01TO BOB # 12

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-03-30 Cont ID  
Sent By spalmer Date 2007-03-30 Time 18:46 Rev Time 0.00
Received By spalmer Date 2007-03-30 Time 18:46 Sent To  
Notes
2007-03-30 18:46:22WAITING FOR BOB BOARD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-01-24 Cont ID  
Sent By adarroug Date 2007-01-24 Time 16:46 Rev Time 0.00
Received By adarroug Date 2007-01-24 Time 16:46 Sent To  
Notes
2007-01-24 16:51:06TO "BOB"#7--NEW SHEETS FOR "M"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-03 Cont ID  
Sent By jleech Date 2007-01-03 Time 10:06 Rev Time 0.00
Received By jleech Date 2006-11-29 Time 18:03 Sent To  
Notes
2006-12-12 17:24:35TO "BOB"#7
2006-11-29 18:03:47WAITING FOR "BOB" BOARD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-04-24 Cont ID  
Sent By tgordon Date 2007-04-24 Time 10:45 Rev Time 0.15
Received By tgordon Date 2007-04-24 Time 10:45 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-04-04 Cont ID  
Sent By tgordon Date 2007-04-04 Time 13:58 Rev Time 0.25
Received By tgordon Date 2007-04-04 Time 13:57 Sent To  
Notes
2007-04-04 14:08:33*** DENIED ***
 1) SEE ELECTRICAL REVIEW NOTE #3 REGARDING MISSING FIRM
 LICENSE NUMBER FOR PBM DEVELOPMENT FROM TITLE BLOCK,
 SEE FAC 61G1-16.004, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-02-02 Cont ID  
Sent By tgordon Date 2007-02-02 Time 11:12 Rev Time 0.25
Received By tgordon Date 2007-02-02 Time 11:12 Sent To  
Notes
2007-02-02 11:14:20*** DENIED ***
 1) SEE ELECTRICAL REVIEW NOTES 1 AND 3, PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-02-02 Cont ID  
Sent By tgordon Date 2006-12-14 Time 08:43 Rev Time 0.30
Received By tgordon Date 2006-12-14 Time 08:43 Sent To  
Notes
2006-12-14 08:45:442-2-07 .SEE ELECTRICAL REVIEW 1-25-07NOTES 1 AND
 3.
  
 NOTE:ONE SET OF MECHANICAL PLANS COULD NOT BE STAMPED
 AS IT IS MISSING PAGE M0.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-04-04 Cont ID  
Sent By jleech Date 2007-04-04 Time 07:40 Rev Time 0.00
Received By jleech Date 2007-04-04 Time 07:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-02-03 Cont ID  
Sent By jleech Date 2007-02-03 Time 09:34 Rev Time 0.00
Received By jleech Date 2007-02-03 Time 09:21 Sent To  
Notes
2007-02-03 09:33:14DENIED;
 1. SEE ELECTRICAL NOTES # 1 AND # 3.
 2. A/C DRAWING PAGE M2.1 SHOWS THE RETURN AIR IS NOT
 DUCTED, SO AREA ABOVE DROPPED CEILING IS A PLENUM.
 PLEASE REVISE NOTE # 11 ON PLUMBINGNOTES , PAGE
 P0.1, TO READ NO PVC TO BE USED.
 3. LAST REVIEW #5WAS NOT ADDRESSED. WATER HAMMER
 ARRESTORS TO BE INSTALLED PER MANUFACTURE'S
 INSTALLATION INSTRUCTIONS, AS CLOSED TO THE SOURCE,
 (FIXTURE) AS POSSIBLE. ONE WATER RISER DIAGRAM MARKED
 IN RED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-02-03 Cont ID  
Sent By jleech Date 2007-01-03 Time 09:49 Rev Time 0.00
Received By jleech Date 2007-01-03 Time 09:49 Sent To  
Notes
2007-01-03 10:02:27DENIED;
 1.PLEASE SHOW HANDICAP CLEAR FLOOR SPACE ON FLOOR PLAN
 FOR BREAK SINK AND LAVATORY, AND THE TURNING RADIUS IN
 BATHROOM.
 2.SHOW A DETAIL OF BREAK SINK WITH ALL MEASUREMENT
 REQUIRED TO MEET H/C REQUIREMENTS SEE FBC-2004 CHAPTER
 11 SEC. 11-4.24.2 THRU 11-4.24.7.
 3.SHOWA DETAIL OF BATHROOM WITH ALL REQUIRED
 MEASUREMENTS W/C SEC11-4.16.2 THRU 11-4.16.7 AND
 LAVATORY 11-4.19.2 THRU 11-4.19.6.
 4.BATHROOM DOOR TO SWING OUT. CANNOT SWING INTO CLEAR
 FLOOR SPACE OF LAV.
 5. WATER HAMMER ARRESTORS ARE TO BE INSTALLED PER
 FBC-2004 PLUMBING SECTION 604.9 AND MANUFACTURER'S
 SPECIFICATIONS, AS CLOSE TO THE SOURCE.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695