Plan Review Details - Permit 06110667
Plan Review Stops For Permit 06110667
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-06-18 Cont ID  
Sent By jwitmer Date 2007-06-18 Time 07:01 Rev Time 1.11
Received By jwitmer Date 2007-06-18 Time 07:01 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-03-29 Cont ID  
Sent By jwitmer Date 2007-03-29 Time 14:45 Rev Time 1.11
Received By jwitmer Date 2007-03-29 Time 14:45 Sent To  
Notes
2007-03-29 14:48:02BUILDING PLAN REVIEW
 PERMIT: 06110667
 ADD: 422 SUNSET RD
 CONT: BURKHARDT CONSTRUCTION
 TEL: (561)718-2602
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
  
 --- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) THE PLANS WILL NEED TO PASS THE ZONING REQUIREMENTS
 SET FORTH UNDER CASE NUMBER 3172 AS FAR AS LOCATION OF
 THE SPRAY BOOTH AND MIXING ROOM.
  
 BUILDING PROVISO: UNDER THE BUILDING BASE PERMIT THE
 SPRAY BOOTH/ MIXING BOOTH WERE REMOVED, THUS NO MSDS
 SHEETS WERE REQUIRED FOR COMBUSTIBLE OR FLAMMIBLE
 LIQUIDS WERE REQUIRED.
 AS PART OF THE SPRAY BOOTH REQUIREMENTS FOR PERMIT
 ISSUANCE THE MSDS SHEETS WILL BE REQUIRED TO BE
 REVIEWED BY PLAN REVIEW BEFORE A CERTIFICATE OF
 COMPLETION WILL BE ISSUED, AND PROVIDE THE AMOUNTS OF
 FLAMMIBLE AND COMBUSTIBLE LIQUIDS TO BE STORED ON SITE.
 IF THE AMOUNTS EXCEED THOSE LISTED IN TABLE 307.1
 INDICATE COMPLIANCE WITH THIS SECTION.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-17 Cont ID  
Sent By jwitmer Date 2007-01-10 Time 11:19 Rev Time 0.00
Received By jwitmer Date 2007-01-10 Time 06:35 Sent To  
Notes
2007-01-10 07:03:09BUILDING PLAN REVIEW
 PERMIT: 06110667
 ADD: 422 SUNSET RD
 CONT: BURKHARDT CONSTRUCTION
 TEL: (561)718-2602
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
  
 --- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) PLEASE SUBMIT PLANS FOR THE PREMANUFACTURED SPRAY
 BOOTH, & PAINT MIXING ROOM.
 416.2 SPRAY ROOMS.
 SPRAY ROOMS SHALL BE ENCLOSED WITH FIRE BARRIER WALLS
 AND HORIZONTAL ASSEMBLIES OR
 BOTH WITH NOT LESS THAN A 1-HOUR FIRE-RESISTANCE
 RATING.
  
 416.2.1 SURFACES.
 THE INTERIOR SURFACES OF SPRAY ROOMS SHALL BE SMOOTH
 AND SHALL BE SO CONSTRUCTED TO PERMIT THE FREE PASSAGE
 OF EXHAUST AIR FROM ALL PARTS OF THE INTERIOR AND TO
 FACILITATE WASHING AND CLEANING, AND SHALL BE SO
 DESIGNED TO CONFINE RESIDUES WITHIN THE ROOM. ALUMINUM
 SHALL NOT BE USED.
  
  
 416.3 SPRAYING SPACES.
 SPRAYING SPACES SHALL BE VENTILATED WITH AN EXHAUST
 SYSTEM TO PREVENT THE ACCUMULATION
 OF FLAMMABLE MIST OR VAPORS IN ACCORDANCE WITH THE
 FLORIDA BUILDING CODE, MECHANICAL .
 WHERE SUCH SPACES ARE NOT SEPARATELY ENCLOSED,
 NONCOMBUSTIBLE SPRAY CURTAINS SHALL
 BE PROVIDED TO RESTRICT THE SPREAD OF FLAMMABLE
 VAPORS.
  
 PLEASE PROVIDE INFORMATION HOW THE EXHAUST DUCT AND
 ROOF VENT WILL STAY ATTACHED TO THE ROOF IN A 140MPH
 EVENT.
 NO PERMIT APPLICATION HAS BEEN FILED TO HOOK UP THE
 EXHAUST DUCT FOR THE SPRAY BOOTH NOR THE GAS FIRED
 HEATER FOR SPRAY BOOTH.
  
 416.4 FIRE PROTECTION.
 AN AUTOMATIC FIRE-EXTINGUISHING SYSTEM SHALL BE
 PROVIDED IN ALL SPRAY , DIP AND IMMERSING SPACES AND
 STORAGE ROOMS, AND SHALL BE INSTALLED IN ACCORDANCE
 WITH CHAPTER 9 .PLEASE PROVIDE ADITIONAL INFORMATION.
 AT THIS TIME THERE HAS BEEN NO PERMIT APPLICATION BEEN
 FILED FOR THE FIRE SUPRESSION SYSTEM THAT IS REQUIRED
 FOR THE SPRAY BOOTH. SHEET 3 OF 4 INDICATES UNIT TO BE
 DESIGNED TO:
 A) AUTOMATIC WATER SPRINKLERS
 B) DRY CHEMICAL
 C) HALON 1211/ 1301
 PLEASE HIGHLIGHT WHICH SYSTEM IS TO BE USED, AND
 PROVIDE ADDITIONAL INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-05-11 Cont ID  
Sent By dpalmer Date 2007-05-11 Time 11:44 Rev Time 0.00
Received By dpalmer Date 2007-05-11 Time 11:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-03-04 Cont ID  
Sent By dpalmer Date 2007-03-04 Time 13:34 Rev Time 0.00
Received By dpalmer Date 2007-03-04 Time 13:16 Sent To  
Notes
2007-03-04 13:35:16** UNSAT 2ND REVIEW**
  
 1) NOTE: PLEASE SEE PREVIOUS NOTES WHICH REFERENCED TO
 NEC 516 FOR INFORMATION TO BE DETAINED AND PROVIDED ON
 PLANS; HOWEVER AT THIS TIME ONLY THE INFORMATION FOR
 THE EXISTING DISCONNECT WHICH WAS UNDER PREVIOUS
 PERMITTED PLANS IS BEING SHOWN.
 PLEASE SEE 516.3B1-B4 EXAMPLES IN THE NEC WHICH IS
 REQUIRED FOR THE SPECIFIC INSTALLATION SHOWING THE
 LOCATIONS, CLASS AND DIVISIONS ON PLANS.
 PLEASE SEE THE SUBMITTALS WHICH ARE FOR THE PAINT BOOTH
 DO NOT SHOW WHETHER OR NOT THE PANEL IS INSIDE OR
 OUTSIDE THE BOOTH? SHOWN ON WALL/ BUT NOT CLEAR FOR
 LOCATION.
  
 2) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME AND DOES NOT APPLY.
  
 ** PLEASE SEE THESE LOCATIONS SHALL BE CLEAR FOR USE OF
 MIXING ROOM AND BOOTH.
 FBC 106.1.2 ADMIN SECTION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-12-06 Cont ID  
Sent By dpalmer Date 2006-12-06 Time 20:06 Rev Time 0.00
Received By dpalmer Date 2006-12-06 Time 20:01 Sent To  
Notes
2006-12-06 20:07:09*** UNSAT ***
  
 1) NOTE: PLEASE SEE PLANS FOR THE ORIGINAL PERMIT AS IT
 STATES SPRAY BOOTH UNDER A SEPARATE PERMIT. THIS
 INCLUDES ELECTRICAL. PLEASE SUBMIT COMPLETED SIGNED,
 DATED AND SEALED PLANS FOR ELECTRICAL SYSTEMS, HOOK UP
 ETC
 THIS RECORD SET OF PLANS SHALL INCLUDE LOCATION, LAYOUT
 ETC OF ALL EXISTING WORK AND PROPOSED LOCATIONS WHICH
 WERE CROSSED OUT ON THE PREVIOUS PLANS WHICH WERE TO BE
 UNDER SEPARATE PERMITS.
 AS INFORMATION NEEDED WS NOT SUBMITTED, A COMPLETE
 REVIEW COULD NOT BE DONE AND THERE MAY BE COMMENTS ON
 THE FOLLOWING REVIEW.
 PLEASE SEE NEC 516
 FBC 106.1.2, 106.1.3, 106.3.5.1 ETC
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-05-22 Cont ID  
Sent By mawillia Date 2007-05-22 Time 16:48 Rev Time 0.00
Received By mawillia Date 2007-05-22 Time 16:31 Sent To  
Notes
2007-05-22 16:47:58*****APPROVED*****
  
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED;PLAN SHEET E-1.1 STAMPED, INITIALED,
 AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-03-31 Cont ID  
Sent By mawillia Date 2007-03-31 Time 17:04 Rev Time 0.00
Received By mawillia Date 2007-03-31 Time 16:56 Sent To  
Notes
2007-03-31 17:03:53****UNSAT*****NEED ADDITIONAL INFO
  
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW WILL BE SATISFIED IN CONJUNCTION WITH
 MECHANICAL PLAN REVIEW COMMENTS BEING ADDRESSED.
  
  
 4.WHAT WILL BE THE DIRECTION OF THE PAINT SPRAY
 VAPORS UPON LEAVING THE PAINT DUCTS?
  
 5.PLEASE INDICATE THE SEPARATION DISTANCE BETWEEN THE
 INTAKE AND EXHAUST DUCTS.2004 FBC/M 502.7.3.6
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-8056722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-01-29 Cont ID  
Sent By mawillia Date 2007-01-29 Time 11:04 Rev Time 0.00
Received By mawillia Date 2007-01-29 Time 11:04 Sent To  
Notes
2007-01-29 11:15:13****UNSAT*****NEED ADDITIONAL INFO
  
  
  
 1.PLEASE INDICATE IF THIS A SINGLE TENANT ARRANGEMENT
 IN THE BUILDING.
  
 2.PROVIDE UL NUMBER AND WALL DETAIL FOR THE 1 HOUR
 RATED WALL.
  
 3.INDICATE THE FIRE RATING FOR THE EXISTING DOORS IN
 THE 1 HOUR RATED WALL.
  
 4.WHAT WILL BE THE DIRECTION OF THE PAINT SPRAY
 VAPORS UPON LEAVING THE PAINT DUCTS?
  
 5.PLEASE INDICATE THE SEPARATION DISTANCE BETWEEN THE
 INTAKE AND EXHAUST DUCTS.2004 FBC/M 502.7.3.6
  
 6.ILLUSTRATE REQUIRED GROUNDING AND BONDING FOR THE
 BOOTH OR ADD TO NOTES THAT THE BOOTH WILL BE PROPERLY
 GROUNDED AND BONDED.
  
 7. PROVIDE PRODUCT APPROVAL RATING AND SIZE OF SAFETY
 STORAGE CABINET.
  
 8.FIRE EXTINGUISHER(S) WITH A RATING OF AT LEAST
 2A:10BC SHALL BE CERTIFIED AND TAGGED.
  
 9.THE FIRE SUPPRESSION SYSTEM FOR THE BOOTH WILL
 REQUIRE SEPARATE PLANS AND PERMIT.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-8056722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-05-03 Cont ID  
Sent By shill Date 2007-05-03 Time 11:21 Rev Time 0.00
Received By shill Date 2007-05-03 Time 11:21 Sent To  
Notes
2007-05-10 09:38:35TO "COMM" BD#52
2007-05-03 11:22:14WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-02-23 Cont ID  
Sent By adarroug Date 2007-02-23 Time 16:11 Rev Time 0.00
Received By adarroug Date 2007-02-23 Time 16:11 Sent To  
Notes
2007-02-28 09:53:08TO "COMM" BD#2
2007-02-23 16:11:59WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-29 Cont ID  
Sent By mawillia Date 2007-01-29 Time 11:17 Rev Time 0.00
Received By mawillia Date 2006-11-21 Time 15:36 Sent To  
Notes
2006-12-05 13:37:27TO "COMM" BD#42
2006-11-21 15:40:51WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-08-15 Cont ID  
Sent By tgordon Date 2007-08-15 Time 10:36 Rev Time 0.15
Received By tgordon Date 2007-08-15 Time 10:36 Sent To  
Notes
2007-08-15 10:38:02RECIVED SUBMITTAL FOF SPRAY BOOTH.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-05-18 Cont ID  
Sent By tgordon Date 2007-05-18 Time 11:36 Rev Time 0.40
Received By tgordon Date 2007-05-18 Time 11:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-03-08 Cont ID  
Sent By tgordon Date 2007-03-08 Time 13:36 Rev Time 0.35
Received By tgordon Date 2007-03-08 Time 13:36 Sent To  
Notes
2007-03-08 13:39:37*** FAILED ***
 1) PLEASE SHOW ON PLANS THAT THE EXHAUST TERMINATION
 COMPLIES WITH THE FOLLOWING.
  
 *** 2004 FBC/M 502.7.3.6 TERMINATION POINT.
 THE TERMINATION POINT FOR EXHAUST DUCTS DISCHARGING TO
 THE ATMOSPHERE SHALL BE LOCATED WITH THE FOLLOWING
 MINIMUM DISTANCES.
 1.FOR DUCTS CONVEYING EXPLOSIVE OR FLAMMABLE
 VAPORS, FUMES OR DUSTS: 30 FEET (9144 MM) FROM THE
 PROPERTY LINE; 10 FEET (3048 MM) FROM OPENINGS INTO THE
 BUILDING; 6 FEET (1829 MM) FROM EXTERIOR WALLS AND
 ROOFS; 30 FEET (9144 MM) FROM COMBUSTIBLE WALLS AND
 OPENINGS INTO THE BUILDING WHICH ARE IN THE DIRECTION
 OF THE EXHAUST DISCHARGE; 10 FEET (3048 MM) ABOVE
 ADJOINING GRADE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-12-22 Cont ID  
Sent By tgordon Date 2006-12-22 Time 13:58 Rev Time 0.45
Received By tgordon Date 2006-12-22 Time 13:58 Sent To  
Notes
2006-12-22 14:07:10*** DENIED ***
 1) PLEASE SUBMIT SITE PLAN SHOWING SPRAY BOOTH EXHAUST
 DUCT LOCATION TO PROPERTY LINES, BUILDING, AND HEIGHT
 OF EXHAUST OUTLET. SEE 2004 FBC/M 502.7.3.6. (I COULD
 NOT FIND THIS INFORMATION ON THE BUILDING PLANS
 SUBMITTED FOR PERMIT #06010452).
  
 2) SHOW HOW EXHAUST DUCT IS TO BE SECURED TO WITHSTAND
 140 MPH WINDS, SEE 2004 FBC 1609.
  
 3) IF USING A GAS HEATER PLEASE PROVIDE INFORMATION
 REGARDING COMBUSTION AND MAKE-UP AIR, SEE 2004 FBC/M
 701.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 3 Status P Date 2007-06-15 Cont ID  
Sent By jbabcock Date 2007-06-15 Time 17:09 Rev Time 0.00
Received By jbabcock Date 2007-06-15 Time 17:09 Sent To I
Notes
2007-06-15 17:10:37APPROVED WITH PROVISO:
  
 ***PROVISO***
 APPROVAL IS CONTINGENT UPON THE FOLLOWING:
 LANDSCAPE PERMIT # 07050913 SHALL BE APPROVED PRIOR TO
 THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY FOR ALL
 PERMITS.
 MASTER PERMIT# 06010452
 PERMIT# 06110667 (PAINT BOOTH AND MIXING ROOM)
 PERMIT #07030949 (OFFICE REMODEL)

Review Stop Z ZONING
Rev No 2 Status F Date 2007-03-07 Cont ID  
Sent By jbabcock Date 2007-03-07 Time 17:35 Rev Time 0.00
Received By jbabcock Date 2007-03-07 Time 17:35 Sent To  
Notes
2007-03-07 17:35:26PLANNING AND ZONING: ***FAILED***
  
 1. RESPOND TO THE FOLLOWING COMMENTS IN WRITING.
  
 2. IN ACCORDANCE WITH THE FINAL ORDER FOR CASE NO.
 3172, CONDITION 1. D.:
  
 THE PAINT BOOTH AND MIXING ROOMS SHALL BE LOCATED 140
 FEET FROM THE NORTH PROPERTY LINE AND 37 FEET FROM THE
 SOUTH PROPERTY LINE IN ACCORDANCE WITH THE REVISED SITE
 PLAN SUBMITTED TO THE RECORD APRIL 6, 2006.
  
 3. PROVIDE THE PROPOSED LOCATION AS MEASURED FROM THE
 NORTH PROPERTY LINE TO THE STRUCTURE. CURRENTLY, THE
 DIMENSION IS PROVIDED TO THE ROW NOT THE PROPERTY
 LINE.
  
 4. THE PROPOSED LOCATION FROM THE SOUTH PROPERTY LINE
 TO THE STRUCTURE AT 31?-1? DOES NOT COMPLY WITH THE
 CONDITION FROM COMMENT # 2.
  
 5. PERMIT SHALL NOT BE PASSED UNTIL A SEPERATE
 LANDSCAPING PERMIT IS SUBMITTED AND APPROVED. PURSUANT
 TO SECTION 94-441 THE LANDSCAPING, TREE PROTECTION, AND
 SCREENING REQUIREMENTS OF THIS SECTION SHALL APPLY TO
 ALL DEVELOPMENT WITHIN THE CITY, EXCEPT THOSE
 DEVELOPMENTS EXEMPTED IN SUBSECTION (C) OF THIS
 SECTION.REFER TO SECTION 94-441 (C)(2)IN THIS CASE
 TO SHOW THAT THE RENOVATIONS, REPAIR, ALTERATION OR
 REDEVELOPMENT DOES NOT EXCEED 50 PERCENT OF THE VALUE
 OF THE STRUCTURE.
  
 FOR ANY ADDITIONAL INFORMATION OR QUESTIONS YOU MAY
 CONTACT:
  
 JULIA BABCOCK
 PLANNER
 OFFICE: (561) 822-1442
 EMAIL: [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2007-01-09 Cont ID  
Sent By lfranco Date 2007-01-09 Time 10:58 Rev Time 0.00
Received By JBABCOCK Date 2007-01-09 Time 10:59 Sent To I
Notes
2007-01-09 09:07:40PLANNING AND ZONING:FAILED
  
 1. RESPOND TO THESE COMMENTS IN WRITING.
  
 2. PURSUANT TO THE FINAL ORDER, CONDITION D (PAGE 5),
 THE SITE PLAN DOES NOT MATCH THE ORIGINAL SITE PLAN
 APPROVED APRIL 6, 2006 UNDER ZBA CASE NO. 3172.
 ATTACHED FOR YOUR RECORDS IS THE APPLICABLE SITE PLAN.
  
 3. PURSUANT TO THE FINAL ORDER, CONDITION C.(PAGE 5), A
 UNITY OF TITLE SHALL BE OBTAINED FOR THE PROPERTIES.
 PROVIDE DOCUMENTATION ACCORDINGLY.
  
 4. THE REDUCED SITE PLAN SUBMITTED DOES NOT PROVIDE AN
 ACCURATE SCALE. FULL SIZE PLANS SHALL BE SUBMITTED FOR
 REVIEW.
  
 SHOULD YOU HAVE ANY QUESTIONS CONTACT:
  
 JULIA BABCOCK
 PLANNER
 CITY OF WEST PALM BEACH
 (561)822-1442