Plan Review Details - Permit 06110607
Plan Review Stops For Permit 06110607
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-12-05 Cont ID  
Sent By mawillia Date 2006-12-05 Time 15:26 Rev Time 0.00
Received By mawillia Date 2006-12-05 Time 15:26 Sent To  
Notes
2006-12-05 15:28:59*****APPROVED*****
  
  
  
  
 COMMENTS FROM 1ST FIRE PLAN REVIEW HAVE BEEN ADDRESSED

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-11-30 Cont ID  
Sent By mawillia Date 2006-11-30 Time 16:36 Rev Time 0.00
Received By mawillia Date 2006-11-30 Time 16:36 Sent To  
Notes
2006-11-30 17:00:03*****DENIED*****
  
  
  
 1.SHEET 1 (OF THE THREE SHEET PLAN SET) UNACCEPTABLE.
 THE UPDATED PLANS ARE TO BE PRESENTED WITH NO INK,
 PENCIL, WHITE-OUTED, OR ANY OTHER HAND DRAWN MARKINGS.
  
 2.FIRE SPRINKLER SYSTEM IS TO BE MONITORED.
  
 3.COORDINATE WITH THE GENERAL AND/OR FIRE CONTRACTOR
 THAT THE DOUBLE DETECTOR BE CHAINED AND LOCKED UPON THE
 COMPLETION OF THE FINAL FIRE ALARM FINAL.
  
 4.ELECTRONIC SWITCHES IN ADDITION TO CHAIN AND LOCK
 IS REQUIRED FOR DOUBLE CHECK DETECTOR ASSEMBLY.
  
 5.KNOX LOCKING CAPS ARE REQUIRED FOR NEW FIRE
 DEPARTMENT CONNECTIONS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-11-30 Cont ID  
Sent By mawillia Date 2006-11-30 Time 16:35 Rev Time 0.00
Received By mawillia Date 2006-11-20 Time 16:34 Sent To  
Notes
2006-11-30 16:34:44TO "F" BOX