Plan Review Details - Permit 06110605
Plan Review Stops For Permit 06110605
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-11-20 Cont ID  
Sent By cthroop Date 2019-11-20 Time 08:49 Rev Time 0.00
Received By cthroop Date 2019-11-20 Time 08:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-05-01 Cont ID  
Sent By rmcdouga Date 2007-05-01 Time 14:16 Rev Time 0.00
Received By rmcdouga Date 2007-05-01 Time 12:36 Sent To  
Notes
2007-05-01 14:13:48DENIED BY BUILDING
  
 1) THE NOTICE OF COMMENCEMENT HAS EXPIRED AND WILL NEED
 TO BE RE-RECORDED. FS 713.13 REQUIRES THE WORK TO START
 WITHIN 90 DAYS OF THE DATE THE NOC IS RECORDED.
  
 2) SPECIFY WHICH ONE OF THE APPROVED ASSEMBLIES LISTED
 IN THE JOHNS MANVILLE BUR ROOFING SYSTEM WILL BE
 INSTALLED. CIRCLE THE APPROPIATE INFORMATION ON THE
 NOA. SUBMIT SIGNED AND SEALED RAS 117 CALCULATIONS FROM
 A FLORIDA REGISTERED ENGINEER, ARCHITECT OR REGISTERED
 ROOF CONSULTANT AS REQUIRED BY GENERAL LIMITATION
 NUMBER 7 ON PAGE 19 OF THE NOA. NOTE: NONE OF THE
 ASSEMBLIES WITH LIMITATION NUMBER 9, WHICH DOES NOT
 ALLOW THE SPECIFIED PRESSURES TO BE INCREASED, CAN BE
 USED IN ROOF ZONE 3.
  
 3) A SEPARATE PERMIT WILL BE REQUIRED FOR THE AWNINGS.
  
 4) ADDITIONAL PERMITS WILL BE REQUIRED FOR ELECTRICAL,
 PLUMBING, ETC.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-19 Cont ID  
Sent By kstevens Date 2007-01-22 Time 13:33 Rev Time 0.00
Received By rmcdouga Date 2007-01-19 Time 16:14 Sent To P
Notes
2007-01-19 16:56:45DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SHEET A2 SPECIFIES STRUCTURE IS TYPE VI UNPROTECTED
 CONSTRUCTION. THE 2004 FBC HAS CHANGED THIS TO
 CONSTRUCTION TYPE V-B.PLEASE REVISE.
  
 3) A SEPARATE PERMIT WILL BE REQUIRED FOR THE AWNINGS.
  
 4) ADDITIONAL PERMITS WILL BE REQUIRED FOR ELECTRICAL,
 PLUMBING, ETC.
  
 5) ROOF SCUPPERS ARE REQUIRED. SPECIFY THE SIZES AND
 LOCATIONS. THE ADDITIONAL AREA OF THE NEW ROOF AND
 INCREASED PARAPET WALLS MUST BE CONSIDERED. 1503.4.2
 SCUPPER .
 WHERE REQUIRED FOR ROOF DRAINAGE, A SCUPPER SHALL
 BE PLACED LEVEL WITH THE ROOF SURFACE IN A WALL OR
 PARAPET. THE SCUPPER SHALL BE LOCATED AS DETERMINED BY
 THE SLOPE AND THE CONTRIBUTING AREA OF THE ROOF. THE
 EXTERIOR FACING OR LINING OF ASCUPPER , IF
 METAL, SHALL BE THE SAME AS FLASHING MATERIAL REQUIRED
 BY SECTIONS 1503 THROUGH 1510 FOR THE PARTICULAR TYPE
 OF COVERING SPECIFIED FOR THE BUILDING. FOR OTHER TYPE
 MATERIALS, FOLLOW MANUFACTURER?S SPECIFICATIONS.
 1503.4.3
 WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS
 NOT PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN
 WALLS OR PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR
 MORE THAN 4 INCHES (102 MM) ABOVE THE FINISHED ROOF
 COVERING AND SHALL BELOCATED AS CLOSE AS PRACTICAL
 TO REQUIRED VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND
 PARAPET SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING.
  
 6) 1503.6 PROTECTION AGAINST DECAY AND TERMITES.
 CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT
 LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR
 SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON
 ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM)
 HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON
 A ROOF ABOVE ANOTHER ROOF.
  
 7)THE SECTION MARKER FOR 3 / A3.1 ON SHEET A2 IS
 INCORRECTLY INDICATED THROUGH THE THE WINDOW INSTEAD OF
 THE DOOR.
  
 8) PLEASE INDICATE THE PROPERTY LINES IN RELATION TO
 THE STRUCTURE. 3202.3 ENCROACHMENTS 8 FEET OR MORE
 ABOVE GRADE.
 ENCROACHMENTS 8 FEET (2438 MM) OR MORE ABOVE GRADE
 SHALL COMPLY WITH SECTIONS 3202.3.1 THROUGH 3202.3.4 .
  
 3202.2.2 ARCHITECTURAL FEATURES.
 COLUMNS OR PILASTERS, INCLUDING BASES AND MOLDINGS
 SHALL NOT PROJECT MORE THAN 12 INCHES (305 MM). BELT
 COURSES, LINTELS, SILLS, ARCHITRAVES, PEDIMENTS AND
 SIMILAR ARCHITECTURAL FEATURES SHALL NOT PROJECT MORE
 THAN 4 INCHES (102 MM).
  
 9)ON SHEET S3 THE ROOF SHEATHING FASTENER SPACING IS
 INCORRECT. FBC TABLE 2304.9.1 REQUIRES 6" OC AT ZONES 1
 & 2AND 4" OC IN ZONE 3.
  
 10)SUBMIT PRODUCT APPROVALS FOR THE FOOF COVERING AT
 THE NEW ROOF AREA.
  
 11) THE WRONG FLORIDA PRODUCT APPROVAL COVER SHEET &
 FL# FOR THE 3000/L-3000 STOREFRONTS WAS SUBMITTED. THE
 CORRECT ONE IS FL6297.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2007-01-22 Cont ID  
Sent By rmcdouga Date 2007-01-22 Time 10:16 Rev Time  
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status N Date 2019-11-20 Cont ID  
Sent By rsklarew Date 2019-11-20 Time 09:01 Rev Time 0.00
Received By rsklarew Date 2019-11-20 Time 09:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-05-07 Cont ID  
Sent By mawillia Date 2007-05-07 Time 12:35 Rev Time 0.00
Received By mawillia Date 2007-05-07 Time 12:19 Sent To  
Notes
2007-05-07 12:32:59*****UNSAT*****
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
  
 1.AS PER WEST PALM BEACH CODE, NUMERICAL ADDRESSES
 ARE REQUIRED ON THE BUILDING FRONTING NORTHWOOD ROAD.
 IF THE SCOPE OF EXTERIOR MODIFICATION REQUIRES THAT THE
 ADRESS(ES) BE REMOVED OR COMPROMISED,PLEASE DETAIL
 HOW NUMERICAL PREMISES IDENTIFICATION WILL BE
 MAINTAINED DURING THE SCOPE OF WORK.
  
 2.ON THE APPROPIATE BUILDING ELEVATION, SHOW THE
 ADDRESS NUMBERS FOR THE TENANT SPACES.AS PER CITY
 CODE, NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND 1"
 IN WIDTH.ON SHEET A3, DISPLAY THE ADDRESS NUMBERS FOR
 THE TENANT SPACES
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INDICATE HOW/WHERE
 EACH ITEM WAS ADDRESSED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2007-01-22 Cont ID  
Sent By mawillia Date 2007-01-22 Time 14:01 Rev Time 0.00
Received By mawillia Date 2007-01-22 Time 14:00 Sent To  
Notes
2007-01-22 14:22:04*****PROVISO*****
  
  
  
 1.AS PER WEST PALM BEACH CODE, NUMERICAL ADDRESSES
 ARE REQUIRED ON THE BUILDING FRONTING NORTHWOOD ROAD.
 IF THE SCOPE OF EXTERIOR MODIFICATION REQUIRES THAT THE
 ADRESS(ES) BE REMOVED OR COMPROMISED,PLEASE DETAIL
 HOW NUMERICAL PREMISES IDENTIFICATION WILL BE
 MAINTAINED DURING THE SCOPE OF WORK.
  
 2.ON THE APPROPIATE BUILDING ELEVATION, SHOW THE
 ADDRESS NUMBES FOR THE TENANT SPACES.AS PER CITY
 CODE, NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND 1"
 IN WIDTH.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INDICATE HOW/WHERE
 EACH ITEM WAS ADDRESSED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-04-13 Cont ID  
Sent By adarroug Date 2007-04-13 Time 14:01 Rev Time 0.00
Received By adarroug Date 2007-04-13 Time 14:01 Sent To  
Notes
2007-04-13 14:04:29TO "COMM' BD#30

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By adarroug Date   Time 16:15 Rev Time 0.00
Received By kstevens Date 2006-12-16 Time 16:15 Sent To B
Notes
2006-12-16 16:16:19TO "MISC" BOX#2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-22 Cont ID  
Sent By kstevens Date 2007-01-22 Time 13:13 Rev Time 0.00
Received By kstevens Date 2006-11-27 Time 15:36 Sent To FIRE
Notes
2006-11-27 15:38:44TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-01-22 Cont ID  
Sent By rmcdouga Date 2007-01-22 Time 10:16 Rev Time 0.00
Received By rmcdouga Date 2007-01-22 Time 10:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2007-05-30 Cont ID  
Sent By kstevens Date 2007-05-30 Time 11:59 Rev Time 0.00
Received By kstevens Date 2007-05-30 Time 11:59 Sent To  
Notes
2007-05-30 12:01:17ROOF COMMENTS ADDRESSED. NO PLUMBING WORK SHOWN

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-01-22 Cont ID  
Sent By kstevens Date 2007-01-22 Time 11:22 Rev Time 0.00
Received By kstevens Date 2007-01-22 Time 11:22 Sent To  
Notes
2007-01-22 13:13:20DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
  
 1. SUBMIT CALCULATIONS FOR THE PRIMARY AND SECONDARY
 ROOF DRAINS. SHOW THE SQUARE FOOTAGE OF THE AREAS BEING
 DRAINED. SHOW 1/2 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS ADDED TO THE SF OF THE ROOF. PLEASE SHOW THE
 NEW AREA BEING ADDED TO THE ROOF WHERE THE LOWER ROOF
 WILL BE COVERED BY THE NEW ROOF. INDICATE THE SIZE OF
 THE EXISTING ROOF DRAINS AND THE PIPING SIZE OF THE
 RWL'S AND BLDG. STORM DRAIN PIPING. SECTIONS 1106 &
 1107 WITH ALL SUBSECTIONS & TABLES. SECTION 106.1.1.
  
 2. SHT A3 MORE INFORMATION IS REQUIRED. DETAILS 1 & 2
 INDICATE THAT THE ROOF ELEVATION IS 13'2", BUT DETAIL 2
 SHOWS ONE 6"X12" SCUPPER WHICH APPEARS TO BE BELOW THE
 ROOF ELEVATION. PLEASE CLARIFY. SECTION 106.1.1.
  
 3. SHT A3.1 DETAIL 1 INDICATE THE ELEVATION OF THE
 EXISTING ROOF AND THE ELEVATION OF THE NEW ROOF. PLEASE
 PROVIDE A DETAIL SHOWING HOW THE NEW ROOF CONNECTS TO
 THE EXISTING ROOF WHICH IS INDICATED AS 13'2".
  
 4. SUBMIT A DETAIL FOR THE EXISTING ROOF SHOWING ALL
 EXISTING PRIMARY AND SECONDARY ROOF DRAINS.
  
 5. SHT A3.1 DETAILS 4 & 5 LOWER ROOF IS NOT INDICATED
 ON THE ELEVATION SECTIONS ON SHT A-3. PLEASE INDICATE
 WHERE THESE LOWER ROOFS ARE ON THE ELEVATIONS TO
 CLARIFY THE LOCATIONS. SECTION 106.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 3 Status N Date 2019-11-20 Cont ID  
Sent By rsklarew Date 2019-11-20 Time 09:01 Rev Time 0.00
Received By rsklarew Date 2019-11-20 Time 09:01 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2007-04-20 Cont ID  
Sent By jbabcock Date 2007-04-20 Time 16:13 Rev Time 0.00
Received By jbabcock Date 2007-04-20 Time 16:13 Sent To I
Notes
2007-04-20 16:15:14PLANNING AND ZONING-***FAILED***
  
 1. PROVIDE RESPONSES TO COMMENTS IN WRITING.
  
 2. THE BUILDING PERMIT APPLICATION UNDER ?PROJECT
 DETAIL? DESCRIBES EXTERIOR MODIFICATIONS INCLUDING THE
 NEW WINDOWS. THEREFORE, THE WINDOWS SHALL BE INCLUDED
 ON THIS BUILDING PERMIT AND NOT ON A SEPARATE PERMIT.
  
 3. PURSUANT TO SECTION 94-210 (D)(8)LANDSCAPE
 REGULATIONS: ALL PROPERTIES SHALL BE BROUGHT INTO
 COMPLIANCE WITH THE LANDSCAPE REGULATIONS PROVIDED IN
 THIS CHAPTER AT SUCH TIME THAT A BUILDING PERMIT IS
 ISSUED FOR WORK VALUED AT
 $5,000.00 OR MORE. THE PLANNING DIRECTOR
 SHALL HAVE AUTHORITY TO GRANT A ONE-TIME, THREE-MONTH
 EXTENSION. PROVIDE LANDSCAPE PLAN THAT COMPLIES
 ACCORDINGLY.
  
 4. PROVIDE A SIGNED AND SEALED SURVEY THAT IS NOT MORE
 THAN A YEAR OLD.
  
 5. PURSUANT TO SECTION 94-213 (D) (5)STOREFRONTS
 ARE REQUIRED ON THE FRONTAGE LINES AND SHALL BE
 DIRECTLY ACCESSIBLE FROM SIDEWALKS. EACH STOREFRONT
 MUST HAVE CLEAR GLAZED AREAS, EQUAL TO A MINIMUM OF 70
 PERCENT OF ITS FACADE, BETWEEN
 TWO AND EIGHT FEET FROM THE GROUND.
 PROVIDE DIMENSIONS OF WINDOWS WHICH COMPLY WITH THE
 MINIMUM GLAZING REQUIREMENT OF 70%
  
  
  
  
 FOR ANY ADDITIONAL INFORMATION OR QUESTIONS YOU MAY
 CONTACT:
  
 JULIA BABCOCK
 PLANNER
 OFFICE: (561) 822-1442
 EMAIL: [email protected]
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2006-12-09 Cont ID  
Sent By mmclean Date 2006-12-09 Time 15:10 Rev Time 0.00
Received By mmclean Date 2006-12-09 Time 15:10 Sent To I
Notes
2006-12-09 15:19:05DENIED,
 1. PLEASE PROVIDE TWO COPIES OF SURVEYS SHOWING THE
 LOCATION OF THE PROPOSED WORK (NO HIGHLIGHTING).NEED
 TO SEE THE PROJECTION OF THE PROPOSED AWNING.
 2. PLEASE PROVIDE THE DIMENSION OF THE PROPOSED
 AWNINGS. PLANS SUBMITTED DOES NOT SHOW THE DIMENSION.
  
 NOTE: AWNINGS SHALL BE SYMPATHETIC TO THE ARCHITECTURE
 OF THE BUILDING. AWNINGS MUST BE RECTANGULAR IN SHAPE
 WITH STRAIGHT EDGES.AWNINGS AT THE SIDEWALK LEVEL
 SHALL PROJECT A MIN OF 4FT FROM THE BUILDING FACADE.
 AWNINGS SHALL NOT HAVE A BOTTOM SOFFIT OR SIDE PANELS.
  
 3. PLEASE PROVIDE THE PERCENTAGE OF GLAZINGOF ITS
 STOREFORE FACADE. THE MINIMUM IS 70%.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720