Plan Review Details - Permit 06110600
Plan Review Stops For Permit 06110600
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2007-01-08 Cont ID  
Sent By lursu Date 2007-01-08 Time 14:25 Rev Time 0.00
Received By lursu Date 2007-01-08 Time 14:25 Sent To  
Notes
2007-01-08 14:28:17BASED ON THE LOCATION MAP SUPPLIED , THE ELECTRICAL
 SERVICE IS LOCATED ABOUT 160 LF WEST OF SARATOGA RD
 INSIDE THE NEW DOG PARK.
 PERMIT WAS ATTACHED TO THE PARK ADDRESS :2301 SARATOGA
 RD.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2006-12-04 Cont ID  
Sent By lursu Date 2006-12-04 Time 09:46 Rev Time 0.00
Received By lursu Date 2006-12-04 Time 09:46 Sent To PC
Notes
2006-12-04 09:48:20LOCATION MAP IS REQUIRED TO DETERMINE THE LOCATION FOR
 THE ELECTRICAL SERVICE
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-01-25 Cont ID  
Sent By shill Date 2007-01-25 Time 17:40 Rev Time 0.00
Received By shill Date 2007-01-25 Time 17:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-01-24 Cont ID  
Sent By shill Date 2007-01-24 Time 16:43 Rev Time 0.00
Received By shill Date 2007-01-24 Time 16:43 Sent To  
Notes
2007-01-24 16:44:44****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
 COMMENTS FROM FIRST REVIEW, NOT ADDRESSED
  
 1.)ORIGINAL SIGNATURES REQUIRED PER FBPE (PHOTOCOPIES
 SUBMITTED).
  
 2.)THE STRUCTURAL NOTES REFER TO FBC1606, NOT THE
 CORRECT CODE NUMBER IN FBC2004 FOR WIND.
  
 NEW COMMENT:
  
 3.)SEE ATTACHED FS553.80(2)(B).

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-04 Cont ID  
Sent By shill Date 2007-01-04 Time 15:49 Rev Time 0.00
Received By shill Date 2007-01-04 Time 15:49 Sent To  
Notes
2007-01-04 15:50:45****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
 1.)ORIGINAL SIGNATURES REQUIRED PER FBPE (PHOTOCOPIES
 SUBMITTED).
  
 2.)THE STRUCTURAL NOTES REFER TO FBC1606, NOT THE
 CORRECT CODE NUMBER IN FBC2004 FOR WIND.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-01-24 Cont ID  
Sent By btrobaug Date 2007-01-24 Time 16:27 Rev Time 0.50
Received By btrobaug Date 2007-01-24 Time 16:15 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-01-04 Cont ID  
Sent By btrobaug Date 2007-01-04 Time 15:25 Rev Time 0.50
Received By btrobaug Date 2007-01-04 Time 14:24 Sent To B
Notes
2007-01-04 15:14:13 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE FEEDER CONDUCTORS DO NOT HAVE THE AMPACITY FOR
 THE 100 AMP OCP. 310.16. INDICATE THE VOLTAGE OF THE
 SERVICE.
  
 2} INDICATE THE OCP FOR THE #6 CONDUCTORS FEEDING THE
 POLES.
  
 3} PLEASE SUBMIT SPECIFICATIONS FOR THE POLES INDICATED
 ON THE PLAN, INCLUDE AMPERAGE AND VOLTAGE RATINGS FOR
 THE LUMINAIRES.
  
 4} PROVIDE A RISER DIAGRAM OF THE PROPOSED SERVICE.
  
 5} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2., BOTH
 SETS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-11-29 Cont ID  
Sent By btrobaug Date 2006-11-29 Time 17:48 Rev Time 0.34
Received By btrobaug Date 2006-11-29 Time 17:41 Sent To I
Notes
2006-11-29 17:48:13NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. PLKEASE INCREASE THE VALUE
 ON THE APPLICATION AND PAY ADDITIONAL FEES PRIOR TO
 RESUBMITTING.
  
 2} PLEASE SUBMIT SPECIFICATIONS FOR THE POLES INDICATED
 ON THE PLAN.
  
 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-01-18 Cont ID  
Sent By adarroug Date 2007-01-18 Time 14:57 Rev Time 0.00
Received By adarroug Date 2007-01-18 Time 14:57 Sent To E
Notes
2007-01-18 14:57:46TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-26 Cont ID  
Sent By adarroug Date 2006-12-26 Time 09:10 Rev Time 0.00
Received By adarroug Date 2006-12-26 Time 09:10 Sent To E
Notes
2006-12-26 09:11:30TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-11-29 Cont ID  
Sent By btrobaug Date 2006-11-29 Time 17:48 Rev Time 0.00
Received By btrobaug Date 2006-11-20 Time 11:33 Sent To PC
Notes
2006-11-20 11:33:15TO "E" BOX