Plan Review Details - Permit 06110560
Plan Review Stops For Permit 06110560 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2007-03-24 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2007-03-24 |
Time |
12:32 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2007-03-24 |
Time |
12:30 |
Sent To |
PC |
|
Notes |
2007-03-24 12:32:06 | BUILDING PLAN REVIEW | | PERMIT: 06110560 | | ADD: 2814 S.DIXIE HWY #102 | | CONT: KARNS CONST. CORP. | | TEL: (561)805-7528 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW 2ND | | ACTION: DENIED | | | | 1)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | BER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | 2)FBC. 106.3.5THE EXAMINATION OF THE DOCUMENTS BY | | THE BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING | | MINIMUM CRITERIA AND DOCUMENTS: A FLOOR PLAN; SITE | | PLAN; FOUNDATION PLAN; FLOOR/LAYOUT;AND ALL EXTERIOR | | ELEVATIONS WITH THE ACCESSIBLE ROUTE TO EACH UNIT IN | | COMPLIANCE WITH FBC. 11-4.3. | | | | 3)106.1.1W.P.B. ADMINISTRATIVE CODE CONSTRUCTION | | DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE | | THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED | | AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE | | PROVISIONS OF THIS CODE. | | DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN | | THE FORM OF NOTES OR | | OTHERWISE, AS TO THE QUALITY OF MATERIALS, WHERE | | QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL | | CODES. | | SUCH INFORMATION SHALL BE SPECIFIC | | AND THE TECHNICAL CODES "SHALL NOT BE | | CITED AS A WHOLE OR IN PART, NOR THE | | TERM "LEGAL" OR ITS RQUIVALENT BE USED | | AS A SUBSTITUTE FOR SPECIFIC | | INFORMATION". | | | | 4)IF THE NEW 4" CONCRETE SLAB IS CONSTRUCTED AT EACH | | DOOR HOW DOES EACH ENTRANCE COMPLY WITH THE | | ACCESSIBILITY CODE? SHOW COMPLIANCE. SEE 2004 FBC. FIG | | 11 AND 12 OF CH. 11.SHEET 1 SHOWS THE ACCESSIBLE | | ROUTE TO SUITE 'A' ONLY WHAT ABOUT THE OTHER SUITES? | | ALSO FBC. 11-4.8.1 ANY PARTOF AN ACCESSIBLE ROUTE WITH | | A SLOPE GREATER THAN 1:20 SHALL BE CONSIDERED A RAME | | AND SHALL COMPLY WITH SECTION 11-4.8. | | | | 5)WHEN RESUBMITING, HAVE THE FRONT COUNTER STAFF | | ADJUST THE VALUE OF THE PROJECT AND PAY THE ADDITIOINAL | | FEES ACCORDINGLY. FOR MORE INFORMATION SEE WPB. | | AMENDMENTS 108.3. | | | | 6)SEE INFORMATION ABOUT THE CONSTRUCTION OF THE | | DUMPSTER ENCLOSURE IN THE PACKAGE AND FOLLOW THOSE | | GUIDELINES. | | | | 7)FBC. 1210.2 WALLS WITHIN 2 FEET OF WATER CLOSETS | | SHALL HAVE A SMOOTH, HARD, AND NONABLORBENT SURFACE, TO | | A HEIGHT OF 4 FEET ABOVE THE FLOOR, AND EXCEPT FOR | | STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS | | SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY | | MOISTURE. | | | | 8)ALL THE PRODUCT APPROVALS SUBMITTED SHALL BE | | APPROVED IN WRITING "(NO PHOTO-COPIES ALLOWED)" BY THE | | DESIGNER OF RECORD PRIOR TO SUBMITTAL.THE ONES | | SUBMITTED ARE PHOTOCOPIES. WPB.AMENDMENTS 106.3.3. | | | | 9)ALL PAGES SUBMITTED SHALL BE SIGNED, DATED AND SEAL | | BY THE ARCHITECT OR ENGINEER IN RESPONSIBLE CHARGE. SEE | | F.A.C. 61G15-23.002 AND 61G1-16.004 / 471.025. FOR MORE | | INFORMATION. THE MECHINICAL SHEETS (M-1) HAS A | | CORPORATE SEAL. THIS SEAL HAS NO BEARING ON THE | | DRAWINGS. SHEET (M-2) IS NOT SEAL. NOTE ALL SIGNATURES | | SHALL BE ORIGINAL. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | 805-6726 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2006-12-21 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2006-12-21 |
Time |
11:38 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2006-12-21 |
Time |
07:24 |
Sent To |
|
|
Notes |
2006-12-21 11:31:06 | BUILDING PLAN REVIEW | | PERMIT:06110560 | | ADD:2814 S. DIXIE HWY | | CONT:KARNS CONSTRUCTION | | TEL: (561)805-7528 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW 1ST | | ACTION: DENIED | | | | NOTE: ANY OTHER OCCUPANCY OTHER THAN WHAT IS STATED | | BY THE DESIGNER OF RECORD SHALL REQUIRE A SEPERATE | | PERMIT. | | | | 1) 106.3.3* PRODUCT APPROVALS- 2004 | | THOSE PRODUCTS THAT ARE RGULATED BY DCA. RULE 9B-72 | | SHALL BE REVIEWED AND APPROVED IN WRITTING BY THE | | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | JURISDICTIONAL APPROVAL. SUBMIT PRODUCT APPROVALS FOR | | THE IMPACT WINDOWS/DOORS/ROOF AND STOREFRONT. | | | | 2)W.P.B. AMENDMENTS 108.3*IF IN THE OPINION OF THE | | BUILDING OFFICIAL, THE CLAIMED VALUATION OF | | BUILDING,ALTERATION APPEARS TO BE UNDERESTIMATED ON THE | | APPLICATION, THE PERMIT SHALL BE DENIED. FOR PERMITTING | | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE | | TOTAL REPLACEMENT VALUE TO INCLUDE | | STRUCTURAL,ELECTRIC,PLUMBING,MECHANICAL,INTERIOR | | FINISH,ARCHITECTURAL AND DESIGN FEES,MARKETING COSTS, | | AND OVERHEAD AND PROFIT. OUR VALUATION REFERENCE IS ICC | | (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS | | SERVICES. | | | | 3)SHEET #1. IN REFERENCE TO THE DUMPSTER PAD, SEE | | REQUIREMENTS DETAILS IN PACKAGE AND COMPLY | | ACCORDINGLY. | | | | 4) FBC 11-4.3 SHOW THE ACCESSIBLE ROUTE TO THE BUILDING | | COMPLYING WITH THIS SECTION. | | | | 5)SHEET #2. THE CODE SECTION ON THE DRAWINGS IN | | REFERENCE TO ROOF DOWNSPOUTS IS FROM THE 2001 FBC. SEE | | FBC 2004 FOR CORRECT REFERENCE. | | | | 6)FBC 1503.4 UNLESS ROOF ARE SLOPED TO DRAIN OVER | | ROOF EDGES, DESIGN AND INSTALLATION OF ROOF DRAINAGE | | SYSTEMS SHALL COMPLY WITH THE FBC PLUMBING CH. 11. | | | | 7)1503.4.3 | | WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT | | PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR | | PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4 | | INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND | | SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED | | VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET | | SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN | | ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING. | | | | | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | 805-6726 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2007-03-10 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-03-10 |
Time |
18:19 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-03-10 |
Time |
18:19 |
Sent To |
|
|
Notes |
2007-03-10 18:19:41 | ** UNSAT 2ND REVIEW ** | | | | | | 1) NOTE: PLEASE CORRELATE ELECTRICAL LIGHTING PLANS | | WITH THE ENERGY CALCULATIONS SUBMITTED. PLEASE SEE THE | | NUMBER OF FIXTURES; THE WATTAGE PER FIXTURE AND THE | | TOTAL DO NOT CORRELATE WITH THAT OF THE FIXTURES AND | | LIGHTING ON PLANS. | | PLEASE SEE THE ENERGY CALCULATIONS DO NOT INDICATE AN | | EXTERIOR LIGHTING, YET THE PLANS INDICATE EXTERIOR | | LIGHTING. | | 13-415.1.AB.1.1 | | 13-415.2 | | | | 2) NOTE: PLEASE SEE FBC 103.1, 103.1.1.1 AS THE ENERGY | | CALCULATIONS MUST BE SIGNED, DATED AND SEALED BY THE | | DESIGN PROFESSIONAL EVEN WHEN/IF FALLING UNDER THE | | EXCEPTIONS THAT A MECHANICAL CONTRACTOR PERFORMS THE | | SCOPE OF WORK. | | PLEASE KNOW THE SCOPE DOES NOT APPEAR TO FALL UNDER THE | | EXCEPTIONS UNDER FS 471.003. | | ** PLEASE ALSO SEE THE MECHANICAL PLANS WHICH CONTAIN | | TITLE BLOCKS FROM AN ENGINEER AND ENGINEERING FIRM, YET | | THERE IS A SIGNATURE AND SEAL ON THESE SHEETS FROM A | | MECHANICAL CONTRACTOR. THIS IS NOT PERMITTED UNDER | | FLORIDA STATUTES 471.025 AND FLORIDA ADMINISTRATIVE | | CODE 61G15-23.002 | | PLEASE ALSO SEE THE 2ND MECHANICAL SHEET IN EACH SET | | DOES NOT CONTAIN ANY SIGNATURE, DATE OR SEAL FROM | | ANYONE. | | | | 3) NOTE: PLEASE KNOW DUE TO THE COMMENTS ONE SET OF | | PLANS AND ENERGY CALCULATIONS WILL BE RETAINED BY THIS | | OFFICE. | | **PLEASE BE SURE RE-PRINT THE 2ND SET OF ELECTRICAL. AS | | PLUMBING IS ON THE SAME SHEET WITH ELECTRICAL, PLUMBING | | WILL NEED TO RE-STAMP SHEETS IN SETS WHEN PLANS ARE | | CORRECTED AND RESUBMITTED. | | | | * ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2006-12-07 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-12-07 |
Time |
08:49 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-12-07 |
Time |
08:49 |
Sent To |
|
|
Notes |
2006-12-07 08:49:43 | *** UNSAT *** | | | | 1) NOTE:PLEASE SEE LOADS FOR SHOW WINDOWS NEED TO BE | | CLARIFIED PER 220.12A. PLEASE SEE AS THE VA IS NOT | | SHOWN AND NO LOAD SUMMARY IS SHOWN, THE VA PER FOOT CAN | | NOT BE VERIFIED. | | 210.62 | | | | 2) NOTE: PLEASE VERIFY THE LOAD SHOWN FOR THE SIGN | | CIRCUIT(S). PLEASE SEE 600.5, WHICH REFERENCES TO | | 220.3B6 FOR THE MINIMUM VA TO USE TO FIGURE FOR SIGN | | CIRCUITS. PLEASE SEE THE LOAD OF 5A?S FOR EACH DOES NOT | | CORRELATE TO THE MINIMUM VA REQUIRED. | | PLEASE SEE NO LOAD SUMMARY IS SHOWN TO VERIFY THIS. | | | | 3) NOTE: PLEASE CORRELATE LOADS ON PANEL FOR KNOWN | | RECEPTS ON A CIRCUIT. 220.13 | | | | 4) NOTE: PLEASE SEE A NOTE ON "E" UNIT INDICATES | | RECEPTACLE ABOVE CEILING AS TYPICAL FOR EACH SIGN | | CIRCUIT. PLEASE SEE 600.5, AS IT ONLY REQUIRES A | | CIRCUIT. PLEASE SEE 400.8(2) WHICH DO NOT PERMIT | | RECEPTACLES ABOVE CEILINGS AS THIS WOULD THEN CREATE | | THE ISSUE OF CORDS BEING RUN THROUGH CEILINGS WHICH IS | | NOT PERMITTED. | | PLEASE REVISE. | | | | 5) NOTE: PLEASE CLARIFY THE GROUNDING ELECTRODE SYSTEM | | AS SHOWN. RISER SHOWS THE MAIN GROUNDING ELECTRODE | | BEING "TAPPED" AND SHOWN TO EACH MAIN DISCONNECT?? | | PLEASE SEE 250.24B, 250.6. PLEASE KNOW WHEN INSTALLING | | THE GUTTER, THE NEUTRAL CONDUCTOR WOULD BE "BONDED" TO | | THE GUTTER WHICH MAY CONTAIN THE SOLE CONNECTION OF THE | | GEC. PLEASE SEE ONLY ONE SET OF PHASE AND NEUTRAL | | CONDUCTORS WOULD THEN BE ROUTED TO EACH METER AND MAIN. | | EACH NEUTRAL WOULD BE BONDED TO THE ENCLOSURE AT THE | | FIRST MEANS OF DISCONNECT. | | PLEASE SEE AS SHOWN THIS SEEM TO BE AN INTERESTING | | SCENARIO AT THE CONNECTION POINT SHOWN AT THE GROUND | | LEVEL LOCATION. | | ** PLEASE SEE THIS BEING AN EXISTING BUILDING AND THE | | CONCRETE ENCASED ELECTRODE ON AN EXISTING BUILDING IS | | NOT REQUIRED TO BE ATTACHED. PLEASE KNOW IF SHOWN ON | | GROUNDING ELECTRODE DETAIL BEING REQUIRED THEN THIS | | WILL BE REQUIRED IN THE FIELD. PLEASE VERIFY THIS BEING | | REQUIRED AND POSSIBLY AFFECTING THE STRUCTURAL | | INTEGRITY OF THE EXISTING FOOTER. | | | | 6) NOTE: PLEASE LIST THE FOLLOWING RELEVANT CODES ON | | THE PLANS. 2002 NFPA-70, 2003 NFPA-101 | | | | 7) NOTE: PLEASE CORRELATE LOADS, OVER CURRENT | | PROTECTION, CONDUCTORS ETC FOR THE A/C SYSTEMS. PLEASE | | SEE ELECTRICAL PLANS SEEM TO INDICATE A POSSIBLE 5KW | | LOAD, HOWEVER AS KW RATINGS/ KVA LOADS ARE NOT SHOWN, | | THESE ARE UNCLEAR AT THIS TIME. PLEASE SEE MECHANICAL | | PLANS CALL FOR 8KW AND 10KW UNITS. | | PLEASE SEE 424.3B, 310.16, 240.4 ETC | | FBC 106.1.2 ADMIN SECTION. | | | | * ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2006-12-12 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2006-12-12 |
Time |
16:10 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2006-12-12 |
Time |
16:10 |
Sent To |
|
|
Notes |
2006-12-12 16:11:04 | *****DENIED***** | | | | | | | | 1.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE | | PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED. | | | | 2.CONSTRUCTION, ALTERATION, OR DEMOLITION OPERATIONS | | SHALL COMPLY WITH NFPA 241. | | | | 3.COMBUSTIBLE WASTE, DUST, AND DEBRIS SHALL BE | | REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR MORE | | FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | 4.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT | | INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID | | PROPERTY OR VICINITY THEREOF (INCLUDING FIRE LANES). | | | | 5.GASOLINE POWERED EQUIPMENT FOR DEMOLITION | | ACTIVITIES SHALL NOT BE USED TO PREVENTTHE | | POSSIBILITY OF CARBON DIOXIDE POISONING. | | | | 6.SHOW/DISPLAY THE ADDRESS OF THE STRUCTURE ON THE | | EXTERIOR ELEVATION WHICH FRONTS SOUTH DIXIE HIGHWAY. AS | | PER WEST PALM BEACH CODE, THE NUMERICAL ADDRESS SHALL | | BE NO LESS THAN 6' IN HEIGHT AND 1" IN WIDTH. | | ADDITIONALLY, DISPLAY THE UNIT NUMBER (3" IN HEIGHT AND | | 1" IN WIDTH) FOR THE FRONT ENTRANCE TO DISTINGUISH ONE | | UNIT FROM THE OTHER. FRONT UNIT NUMBERS SHALL NOT BE ON | | THE DOORS OR WINDOWS, HOWEVER REAR UNIT NUMBER CAN BE | | INSTALLED ON THE DOOR.HURRICANE SHUTTERS SHALL NOT | | BLOCK VISIBILITY OF BUILDING AND/OR UNIT ADDRESS. | | | | 7.INTERIOR FINISH CLASSIFICATION IN AN UNSPRINKLERED | | BUILDING SHALL BE "A" OR "B". | | | | 8.FIRE EXTINGUISHERS TO BE 2A:10BC RATED. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | SHEET INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. | | | | CAPT. MICHEAL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-04-20 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-04-20 |
Time |
12:00 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-04-20 |
Time |
12:00 |
Sent To |
|
|
Notes |
2007-04-20 12:00:30 | TO "BOB"#10 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-01-31 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2007-01-31 |
Time |
14:49 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2006-11-20 |
Time |
08:20 |
Sent To |
|
|
Notes |
2006-12-06 15:29:30 | TO "BOB"#5--5 APPLICATIONS | 2006-11-27 08:20:30 | WAITING FOR "BOB" |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2007-03-15 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-03-15 |
Time |
16:23 |
Rev Time |
0.20 |
Received By |
tgordon |
Date |
2007-03-15 |
Time |
16:23 |
Sent To |
|
|
Notes |
2007-03-15 16:23:42 | *** DENIED *** | | 1) AS NOTED IN LAST REVIEW 11-21-06 NOTE #2. SEE | | COOLING LOAD CALCULATIONS SHOW THAT ALL FIVE BAYS | | TOGETHER WILL NEED OVER 460 TONS OF A/C, PLEASE SUBMIT | | CORRECTED COOLING LOAD CALCULATIONS, PER 2004 FBC | | 13-407.1.ABC.1. | | | | 2) THE ENGINEER EDWARD J. KRANZ WILL NEED TO SEAL THE | | MECHANICAL PLANS AS HIS INFORMATION IS IN THE TITLE | | BLOCK, SEE FAC 61G15-23.002. (SEE PLANS, PAGES M-1 AND | | M-2). | | | | 3) SEE PLANS, PAGE M-1 "O/A INTAKE" IF THIS IS TYPICAL | | OF 5 PLEASE STATE SO ON PLANS IF NOT GIVE INFORMATION | | AT EACH INTAKE. | | | | 4) SEE PLANS, PAGE M-1 " 6 INCH DUCT TO EXHAUST WALL | | LOUVER" IF TYPICAL OF 5 STATE SO ON PLANS IF NOT GIVE | | INFORMATION AT EACH EXHAUST. | | | | 5) SEE PLANS, PAGE 4 ELECTRICAL PLANS SHOW 7 A/C | | CONDENSER UNITS, MECHANICAL PLANS ONLY SHOW 5, PLEASE | | CORRECT ELECT. PLANS. | | | | 6) SEE PLANS, PAGE M-2A/C SCHEDULE SHOWS THE WRONG | | EQUIPMENT MANUFACTURE, CAPACITY (TOTAL) BTU'S, SENSIBLE | | BTU'S, AND A INCORRECT MODEL NUMBER FOR AHU #1. PLEASE | | REVIEW SUBMITTED MANUFACTURER'S SPECIFICATION'S FOR THE | | GOODMAN A/C AND CORRECT. | | | | 7) SEE ELECTRICAL REVIEW NOTE #2 AND 3. AS A RESULT OF | | DOCUMENTS BEING RETAINED PLEASE BE CERTAIN TWO COPY'S | | OF ALL INFORMATION IS BEING SUBMITTED. | | | | 8)SEE ATTACHED NOTICE FS 553.80(2)(B) REGARDING FOUR | | TIMES THE FEE. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2006-11-21 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2006-11-21 |
Time |
16:22 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2006-11-21 |
Time |
16:21 |
Sent To |
P |
|
Notes |
2006-11-21 16:22:39 | *** DENIED *** | | 1) PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC | | 13-101.1.1.6 . | | | | 2) SEE COOLING LOAD CALCULATIONS PAGE 1, LOAD CAL'S | | SHOW THAT ALL FIVE BAYS TOGETHER WILL NEED OVER 460 | | TONS OF A/C, PLEASE RE-DO LOAD CAL'S. | | | | 3) CONDENSER UNITS APPEAR TO BE LOCATED IN THE BACK | | OFFICES, PLEASE CORRECT.. | | | | 4) PLEAS SHOW ON THE PLANS EQUIPMENT LISTING, THE | | SENSIBLE AND TOTAL BTU'S. | | | | 5) PLEASE SHOW THE LOCATION OF ALL GRILLS. | | | | 6) SEE UNIT B, PLEASE LABEL GRILLS IN BACK OFFICE. | | | | 7) PLEASE PROVIDE DETAIL ON BATHROOM EXHAUST DUCTS, ARE | | THEY INDEPENDENTLY DUCTED TO THE OUTDOORS? | | | | 8) PLEASE SHOW THE SIZE OF ALL SUPPLY AND RETURN AIR | | DUCTS (SEE HIGH LIGHTS ON PLANS). | | | | 9) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | ACCOMPANYING DATA SHALL BEAR THE PRINTED NAME AND | | SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. PER | | FBC 104.2.1. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2007-03-10 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2007-03-10 |
Time |
13:18 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2007-03-10 |
Time |
13:18 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2007-01-31 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2007-01-31 |
Time |
14:47 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2007-01-31 |
Time |
14:47 |
Sent To |
|
|
Notes |
2007-01-31 14:48:33 | SEE PLUMBINGNOTES UNDER PERMIT # 06110563. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2007-03-14 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2007-03-14 |
Time |
13:25 |
Rev Time |
0.00 |
Received By |
eschneid |
Date |
2007-03-14 |
Time |
13:25 |
Sent To |
|
|
Notes |
2007-03-14 13:25:26 | FAILED - 2ND REVIEW | | | | 1) THE LETTER BY ROBERT BELL, DATED DECEMBER 27, 2007, | | STATES THAT THE VALUE OF THE RENOVATION TOTALS | | $230,000.THE APPRAISAL INCLUDED WITH THE RESUBMITTAL | | PACKAGE GIVES A VALUE OF THE ENTIRE SITE (LAND AND | | STRUCTURE).THE LANDSCAPE CODE SPECIFICALLY STATES | | THAT A SITE IS EXEMPT FROM THE REQUIREMENTS OF THE CODE | | IF THE RENOVATION DOES NOT EXCEED 50% OF THE VALUE OF | | THE STRUCTURE.IF NO EVIDENCE IS PROVIDED THAT THE | | VALUE OF THE STRUCTURE EXCEEDS $460,000, THE SITE SHALL | | BE BROUGHT INTO COMPLIANCE WITH THE LANDSCAPE CODE | | (SECTION 94-441). | | | | 2) THE LANDSCAPE COMPLIANCE LISTED IN COMMENT #1 | | REQUIRES A LANDSCAPE PLAN PREPARED BY A REGISTERED | | LANDSCAPE ARCHITECT. | | | | 3) WHAT WILL BE PLANTED IN THE PLANTERS?PROVIDE AN | | IRRIGATION PLAN FOR THE PLANTERS. | | | | 4) THE ZONING AND LAND DEVELOPMENT REGULATIONS ALLOW A | | MAXIMUM OF 85% IMPERVIOUS SURFACE.THE EXISTING SITE | | IS CURRENTLY NONCONFORMING AS IT HAS 90.56% IMPERVIOUS | | SURFACE (8,060 SQ. FT.).THE IMPERVIOUS SURFACE ON THE | | SITE MAY NOT EXCEED THIS AMOUNT.THE PROPOSED PLANS | | SHOW AN INCREASE IN IMPERVIOUS SURFACE.THIS IS NOT | | PERMITTED AND SHALL BE CORRECTED.IT MAY REQUIRE | | REMOVING IMPERVIOUS SURFACE IN ANOTHER AREA TO MAKE UP | | THE DIFFERENCE. | | | | 5) THE PROPOSED DUMPSTER ENCLOSURE SHOWN ON THE PLAN | | DOES NOT MEET THE CODE REQUIREMENTS.A SET OF PLANS, | | STAMPED APPROVED BY THE CITY'S ENGINEERING SERVICES | | DEPARTMENT, SHOWING THE DUMPSTER AND ENCLOSURE SIZE AND | | LOCATION IS REQUIRED.THE SCREEN WALL FOR THE DUMPSTER | | MAY NOT BE CHAIN LINK W/SLATS.THE SPECIFICATIONS OF | | THE SCREEN HEDGE ARE REQUIRED (SPECIES, HEIGHT, | | LOCATION AND PLANTING) ON A LANDSCAPE PLAN PREPARED | | FOLLOWING THE PROVISIONS OF SECTION 94-448(D)(2) OF THE | | ZONING AND LAND DEVELOPMENT REGULATIONS.AN IRRIGATION | | PLAN IS REQUIRED. | | | | 6) NO ACCESSIBLE ROUTE TO ALL OF THE BAYS IS SHOWN. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1435. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2007-01-31 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2007-01-31 |
Time |
13:49 |
Rev Time |
0.00 |
Received By |
eschneid |
Date |
2007-01-31 |
Time |
13:49 |
Sent To |
|
|
Notes |
2007-01-31 13:50:12 | FAILED | | | | 1) THE VALUE OF THE 5 PERMITS TOTALS $95,000 AND THE | | PROPERTY APPRAISER SHOWS THE VALUE OF THE STRUCTURE AT | | $84,000.THIS REQUIRES THAT THE SITE BE BROUGHT INTO | | COMPLIANCE WITH THE LANDSCAPE CODE (SECTION 94-441). | | | | 2) A LANDSCAPE PLAN PREPARED BY A REGISTERED LANDSCAPE | | ARCHITECT IS REQUIRED. | | | | 3) EXISTING AND PROPOSED IMPERVIOUS SURFACE | | CALCULATIONS ARE REQUIRED.THE PROPOSED PLANS APPEAR | | TO SHOW AN INCREASE IN IMPERVIOUS MATERIAL. | | | | 4) NO DUMPSTER DETAIL PROVIDED.THE DUMPSTER ENCLOSURE | | SHOWN ON THE PLAN DOES NOT APPEAR TO MEET THE CODE | | REQUIREMENTS. | | | | 5) NO ACCESSIBLE ROUTE TO ALL OF THE BAYS IS SHOWN. | | | | 6) THE PARKING SPACES ON THE WESTERN SIDE OF THE SITE | | ENCROACH INTO THE CURB CUT ON BOTH DIXIE AND MONCEAUX | | AND THUS PRESENT AN UNSAFE SITUATION.THE CURB CUTS | | SHALL BE CLOSED WHERE CONFLICTS EXIST OR THE PARKING | | SPACES SHALL BE ELIMINATED. | | | | 7) NO SURVEY WAS PROVIDED. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1435. |
|
|
|