Plan Review Details - Permit 06110560
Plan Review Stops For Permit 06110560
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-03-24 Cont ID  
Sent By mjacobs Date 2007-03-24 Time 12:32 Rev Time 0.00
Received By mjacobs Date 2007-03-24 Time 12:30 Sent To PC
Notes
2007-03-24 12:32:06BUILDING PLAN REVIEW
 PERMIT: 06110560
 ADD: 2814 S.DIXIE HWY #102
 CONT: KARNS CONST. CORP.
 TEL: (561)805-7528
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2ND
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FBC. 106.3.5THE EXAMINATION OF THE DOCUMENTS BY
 THE BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING
 MINIMUM CRITERIA AND DOCUMENTS: A FLOOR PLAN; SITE
 PLAN; FOUNDATION PLAN; FLOOR/LAYOUT;AND ALL EXTERIOR
 ELEVATIONS WITH THE ACCESSIBLE ROUTE TO EACH UNIT IN
 COMPLIANCE WITH FBC. 11-4.3.
  
 3)106.1.1W.P.B. ADMINISTRATIVE CODE CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE.
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES.
 SUCH INFORMATION SHALL BE SPECIFIC
 AND THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE
 TERM "LEGAL" OR ITS RQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION".
  
 4)IF THE NEW 4" CONCRETE SLAB IS CONSTRUCTED AT EACH
 DOOR HOW DOES EACH ENTRANCE COMPLY WITH THE
 ACCESSIBILITY CODE? SHOW COMPLIANCE. SEE 2004 FBC. FIG
 11 AND 12 OF CH. 11.SHEET 1 SHOWS THE ACCESSIBLE
 ROUTE TO SUITE 'A' ONLY WHAT ABOUT THE OTHER SUITES?
 ALSO FBC. 11-4.8.1 ANY PARTOF AN ACCESSIBLE ROUTE WITH
 A SLOPE GREATER THAN 1:20 SHALL BE CONSIDERED A RAME
 AND SHALL COMPLY WITH SECTION 11-4.8.
  
 5)WHEN RESUBMITING, HAVE THE FRONT COUNTER STAFF
 ADJUST THE VALUE OF THE PROJECT AND PAY THE ADDITIOINAL
 FEES ACCORDINGLY. FOR MORE INFORMATION SEE WPB.
 AMENDMENTS 108.3.
  
 6)SEE INFORMATION ABOUT THE CONSTRUCTION OF THE
 DUMPSTER ENCLOSURE IN THE PACKAGE AND FOLLOW THOSE
 GUIDELINES.
  
 7)FBC. 1210.2 WALLS WITHIN 2 FEET OF WATER CLOSETS
 SHALL HAVE A SMOOTH, HARD, AND NONABLORBENT SURFACE, TO
 A HEIGHT OF 4 FEET ABOVE THE FLOOR, AND EXCEPT FOR
 STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS
 SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE.
  
 8)ALL THE PRODUCT APPROVALS SUBMITTED SHALL BE
 APPROVED IN WRITING "(NO PHOTO-COPIES ALLOWED)" BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL.THE ONES
 SUBMITTED ARE PHOTOCOPIES. WPB.AMENDMENTS 106.3.3.
  
 9)ALL PAGES SUBMITTED SHALL BE SIGNED, DATED AND SEAL
 BY THE ARCHITECT OR ENGINEER IN RESPONSIBLE CHARGE. SEE
 F.A.C. 61G15-23.002 AND 61G1-16.004 / 471.025. FOR MORE
 INFORMATION. THE MECHINICAL SHEETS (M-1) HAS A
 CORPORATE SEAL. THIS SEAL HAS NO BEARING ON THE
 DRAWINGS. SHEET (M-2) IS NOT SEAL. NOTE ALL SIGNATURES
 SHALL BE ORIGINAL.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-12-21 Cont ID  
Sent By mjacobs Date 2006-12-21 Time 11:38 Rev Time 0.00
Received By mjacobs Date 2006-12-21 Time 07:24 Sent To  
Notes
2006-12-21 11:31:06BUILDING PLAN REVIEW
 PERMIT:06110560
 ADD:2814 S. DIXIE HWY
 CONT:KARNS CONSTRUCTION
 TEL: (561)805-7528
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 NOTE: ANY OTHER OCCUPANCY OTHER THAN WHAT IS STATED
 BY THE DESIGNER OF RECORD SHALL REQUIRE A SEPERATE
 PERMIT.
  
 1) 106.3.3* PRODUCT APPROVALS- 2004
 THOSE PRODUCTS THAT ARE RGULATED BY DCA. RULE 9B-72
 SHALL BE REVIEWED AND APPROVED IN WRITTING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. SUBMIT PRODUCT APPROVALS FOR
 THE IMPACT WINDOWS/DOORS/ROOF AND STOREFRONT.
  
 2)W.P.B. AMENDMENTS 108.3*IF IN THE OPINION OF THE
 BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING,ALTERATION APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL,ELECTRIC,PLUMBING,MECHANICAL,INTERIOR
 FINISH,ARCHITECTURAL AND DESIGN FEES,MARKETING COSTS,
 AND OVERHEAD AND PROFIT. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS
 SERVICES.
  
 3)SHEET #1. IN REFERENCE TO THE DUMPSTER PAD, SEE
 REQUIREMENTS DETAILS IN PACKAGE AND COMPLY
 ACCORDINGLY.
  
 4) FBC 11-4.3 SHOW THE ACCESSIBLE ROUTE TO THE BUILDING
 COMPLYING WITH THIS SECTION.
  
 5)SHEET #2. THE CODE SECTION ON THE DRAWINGS IN
 REFERENCE TO ROOF DOWNSPOUTS IS FROM THE 2001 FBC. SEE
 FBC 2004 FOR CORRECT REFERENCE.
  
 6)FBC 1503.4 UNLESS ROOF ARE SLOPED TO DRAIN OVER
 ROOF EDGES, DESIGN AND INSTALLATION OF ROOF DRAINAGE
 SYSTEMS SHALL COMPLY WITH THE FBC PLUMBING CH. 11.
  
 7)1503.4.3
 WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT
 PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR
 PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4
 INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND
 SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED
 VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET
 SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING.
  
  
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-03-10 Cont ID  
Sent By dpalmer Date 2007-03-10 Time 18:19 Rev Time 0.00
Received By dpalmer Date 2007-03-10 Time 18:19 Sent To  
Notes
2007-03-10 18:19:41** UNSAT 2ND REVIEW **
  
  
 1) NOTE: PLEASE CORRELATE ELECTRICAL LIGHTING PLANS
 WITH THE ENERGY CALCULATIONS SUBMITTED. PLEASE SEE THE
 NUMBER OF FIXTURES; THE WATTAGE PER FIXTURE AND THE
 TOTAL DO NOT CORRELATE WITH THAT OF THE FIXTURES AND
 LIGHTING ON PLANS.
 PLEASE SEE THE ENERGY CALCULATIONS DO NOT INDICATE AN
 EXTERIOR LIGHTING, YET THE PLANS INDICATE EXTERIOR
 LIGHTING.
 13-415.1.AB.1.1
 13-415.2
  
 2) NOTE: PLEASE SEE FBC 103.1, 103.1.1.1 AS THE ENERGY
 CALCULATIONS MUST BE SIGNED, DATED AND SEALED BY THE
 DESIGN PROFESSIONAL EVEN WHEN/IF FALLING UNDER THE
 EXCEPTIONS THAT A MECHANICAL CONTRACTOR PERFORMS THE
 SCOPE OF WORK.
 PLEASE KNOW THE SCOPE DOES NOT APPEAR TO FALL UNDER THE
 EXCEPTIONS UNDER FS 471.003.
 ** PLEASE ALSO SEE THE MECHANICAL PLANS WHICH CONTAIN
 TITLE BLOCKS FROM AN ENGINEER AND ENGINEERING FIRM, YET
 THERE IS A SIGNATURE AND SEAL ON THESE SHEETS FROM A
 MECHANICAL CONTRACTOR. THIS IS NOT PERMITTED UNDER
 FLORIDA STATUTES 471.025 AND FLORIDA ADMINISTRATIVE
 CODE 61G15-23.002
 PLEASE ALSO SEE THE 2ND MECHANICAL SHEET IN EACH SET
 DOES NOT CONTAIN ANY SIGNATURE, DATE OR SEAL FROM
 ANYONE.
  
 3) NOTE: PLEASE KNOW DUE TO THE COMMENTS ONE SET OF
 PLANS AND ENERGY CALCULATIONS WILL BE RETAINED BY THIS
 OFFICE.
 **PLEASE BE SURE RE-PRINT THE 2ND SET OF ELECTRICAL. AS
 PLUMBING IS ON THE SAME SHEET WITH ELECTRICAL, PLUMBING
 WILL NEED TO RE-STAMP SHEETS IN SETS WHEN PLANS ARE
 CORRECTED AND RESUBMITTED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-12-07 Cont ID  
Sent By dpalmer Date 2006-12-07 Time 08:49 Rev Time 0.00
Received By dpalmer Date 2006-12-07 Time 08:49 Sent To  
Notes
2006-12-07 08:49:43*** UNSAT ***
  
 1) NOTE:PLEASE SEE LOADS FOR SHOW WINDOWS NEED TO BE
 CLARIFIED PER 220.12A. PLEASE SEE AS THE VA IS NOT
 SHOWN AND NO LOAD SUMMARY IS SHOWN, THE VA PER FOOT CAN
 NOT BE VERIFIED.
 210.62
  
 2) NOTE: PLEASE VERIFY THE LOAD SHOWN FOR THE SIGN
 CIRCUIT(S). PLEASE SEE 600.5, WHICH REFERENCES TO
 220.3B6 FOR THE MINIMUM VA TO USE TO FIGURE FOR SIGN
 CIRCUITS. PLEASE SEE THE LOAD OF 5A?S FOR EACH DOES NOT
 CORRELATE TO THE MINIMUM VA REQUIRED.
 PLEASE SEE NO LOAD SUMMARY IS SHOWN TO VERIFY THIS.
  
 3) NOTE: PLEASE CORRELATE LOADS ON PANEL FOR KNOWN
 RECEPTS ON A CIRCUIT. 220.13
  
 4) NOTE: PLEASE SEE A NOTE ON "E" UNIT INDICATES
 RECEPTACLE ABOVE CEILING AS TYPICAL FOR EACH SIGN
 CIRCUIT. PLEASE SEE 600.5, AS IT ONLY REQUIRES A
 CIRCUIT. PLEASE SEE 400.8(2) WHICH DO NOT PERMIT
 RECEPTACLES ABOVE CEILINGS AS THIS WOULD THEN CREATE
 THE ISSUE OF CORDS BEING RUN THROUGH CEILINGS WHICH IS
 NOT PERMITTED.
 PLEASE REVISE.
  
 5) NOTE: PLEASE CLARIFY THE GROUNDING ELECTRODE SYSTEM
 AS SHOWN. RISER SHOWS THE MAIN GROUNDING ELECTRODE
 BEING "TAPPED" AND SHOWN TO EACH MAIN DISCONNECT??
 PLEASE SEE 250.24B, 250.6. PLEASE KNOW WHEN INSTALLING
 THE GUTTER, THE NEUTRAL CONDUCTOR WOULD BE "BONDED" TO
 THE GUTTER WHICH MAY CONTAIN THE SOLE CONNECTION OF THE
 GEC. PLEASE SEE ONLY ONE SET OF PHASE AND NEUTRAL
 CONDUCTORS WOULD THEN BE ROUTED TO EACH METER AND MAIN.
 EACH NEUTRAL WOULD BE BONDED TO THE ENCLOSURE AT THE
 FIRST MEANS OF DISCONNECT.
 PLEASE SEE AS SHOWN THIS SEEM TO BE AN INTERESTING
 SCENARIO AT THE CONNECTION POINT SHOWN AT THE GROUND
 LEVEL LOCATION.
 ** PLEASE SEE THIS BEING AN EXISTING BUILDING AND THE
 CONCRETE ENCASED ELECTRODE ON AN EXISTING BUILDING IS
 NOT REQUIRED TO BE ATTACHED. PLEASE KNOW IF SHOWN ON
 GROUNDING ELECTRODE DETAIL BEING REQUIRED THEN THIS
 WILL BE REQUIRED IN THE FIELD. PLEASE VERIFY THIS BEING
 REQUIRED AND POSSIBLY AFFECTING THE STRUCTURAL
 INTEGRITY OF THE EXISTING FOOTER.
  
 6) NOTE: PLEASE LIST THE FOLLOWING RELEVANT CODES ON
 THE PLANS. 2002 NFPA-70, 2003 NFPA-101
  
 7) NOTE: PLEASE CORRELATE LOADS, OVER CURRENT
 PROTECTION, CONDUCTORS ETC FOR THE A/C SYSTEMS. PLEASE
 SEE ELECTRICAL PLANS SEEM TO INDICATE A POSSIBLE 5KW
 LOAD, HOWEVER AS KW RATINGS/ KVA LOADS ARE NOT SHOWN,
 THESE ARE UNCLEAR AT THIS TIME. PLEASE SEE MECHANICAL
 PLANS CALL FOR 8KW AND 10KW UNITS.
 PLEASE SEE 424.3B, 310.16, 240.4 ETC
 FBC 106.1.2 ADMIN SECTION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-12-12 Cont ID  
Sent By mawillia Date 2006-12-12 Time 16:10 Rev Time 0.00
Received By mawillia Date 2006-12-12 Time 16:10 Sent To  
Notes
2006-12-12 16:11:04*****DENIED*****
  
  
  
 1.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE
 PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED.
  
 2.CONSTRUCTION, ALTERATION, OR DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241.
  
 3.COMBUSTIBLE WASTE, DUST, AND DEBRIS SHALL BE
 REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR MORE
 FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 4.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID
 PROPERTY OR VICINITY THEREOF (INCLUDING FIRE LANES).
  
 5.GASOLINE POWERED EQUIPMENT FOR DEMOLITION
 ACTIVITIES SHALL NOT BE USED TO PREVENTTHE
 POSSIBILITY OF CARBON DIOXIDE POISONING.
  
 6.SHOW/DISPLAY THE ADDRESS OF THE STRUCTURE ON THE
 EXTERIOR ELEVATION WHICH FRONTS SOUTH DIXIE HIGHWAY. AS
 PER WEST PALM BEACH CODE, THE NUMERICAL ADDRESS SHALL
 BE NO LESS THAN 6' IN HEIGHT AND 1" IN WIDTH.
 ADDITIONALLY, DISPLAY THE UNIT NUMBER (3" IN HEIGHT AND
 1" IN WIDTH) FOR THE FRONT ENTRANCE TO DISTINGUISH ONE
 UNIT FROM THE OTHER. FRONT UNIT NUMBERS SHALL NOT BE ON
 THE DOORS OR WINDOWS, HOWEVER REAR UNIT NUMBER CAN BE
 INSTALLED ON THE DOOR.HURRICANE SHUTTERS SHALL NOT
 BLOCK VISIBILITY OF BUILDING AND/OR UNIT ADDRESS.
  
 7.INTERIOR FINISH CLASSIFICATION IN AN UNSPRINKLERED
 BUILDING SHALL BE "A" OR "B".
  
 8.FIRE EXTINGUISHERS TO BE 2A:10BC RATED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 SHEET INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
 CAPT. MICHEAL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-20 Cont ID  
Sent By adarroug Date 2007-04-20 Time 12:00 Rev Time 0.00
Received By adarroug Date 2007-04-20 Time 12:00 Sent To  
Notes
2007-04-20 12:00:30TO "BOB"#10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-31 Cont ID  
Sent By jleech Date 2007-01-31 Time 14:49 Rev Time 0.00
Received By jleech Date 2006-11-20 Time 08:20 Sent To  
Notes
2006-12-06 15:29:30TO "BOB"#5--5 APPLICATIONS
2006-11-27 08:20:30WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-03-15 Cont ID  
Sent By tgordon Date 2007-03-15 Time 16:23 Rev Time 0.20
Received By tgordon Date 2007-03-15 Time 16:23 Sent To  
Notes
2007-03-15 16:23:42*** DENIED ***
 1) AS NOTED IN LAST REVIEW 11-21-06 NOTE #2. SEE
 COOLING LOAD CALCULATIONS SHOW THAT ALL FIVE BAYS
 TOGETHER WILL NEED OVER 460 TONS OF A/C, PLEASE SUBMIT
 CORRECTED COOLING LOAD CALCULATIONS, PER 2004 FBC
 13-407.1.ABC.1.
  
 2) THE ENGINEER EDWARD J. KRANZ WILL NEED TO SEAL THE
 MECHANICAL PLANS AS HIS INFORMATION IS IN THE TITLE
 BLOCK, SEE FAC 61G15-23.002. (SEE PLANS, PAGES M-1 AND
 M-2).
  
 3) SEE PLANS, PAGE M-1 "O/A INTAKE" IF THIS IS TYPICAL
 OF 5 PLEASE STATE SO ON PLANS IF NOT GIVE INFORMATION
 AT EACH INTAKE.
  
 4) SEE PLANS, PAGE M-1 " 6 INCH DUCT TO EXHAUST WALL
 LOUVER" IF TYPICAL OF 5 STATE SO ON PLANS IF NOT GIVE
 INFORMATION AT EACH EXHAUST.
  
 5) SEE PLANS, PAGE 4 ELECTRICAL PLANS SHOW 7 A/C
 CONDENSER UNITS, MECHANICAL PLANS ONLY SHOW 5, PLEASE
 CORRECT ELECT. PLANS.
  
 6) SEE PLANS, PAGE M-2A/C SCHEDULE SHOWS THE WRONG
 EQUIPMENT MANUFACTURE, CAPACITY (TOTAL) BTU'S, SENSIBLE
 BTU'S, AND A INCORRECT MODEL NUMBER FOR AHU #1. PLEASE
 REVIEW SUBMITTED MANUFACTURER'S SPECIFICATION'S FOR THE
 GOODMAN A/C AND CORRECT.
  
 7) SEE ELECTRICAL REVIEW NOTE #2 AND 3. AS A RESULT OF
 DOCUMENTS BEING RETAINED PLEASE BE CERTAIN TWO COPY'S
 OF ALL INFORMATION IS BEING SUBMITTED.
  
 8)SEE ATTACHED NOTICE FS 553.80(2)(B) REGARDING FOUR
 TIMES THE FEE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-11-21 Cont ID  
Sent By tgordon Date 2006-11-21 Time 16:22 Rev Time 0.30
Received By tgordon Date 2006-11-21 Time 16:21 Sent To P
Notes
2006-11-21 16:22:39*** DENIED ***
 1) PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC
 13-101.1.1.6 .
  
 2) SEE COOLING LOAD CALCULATIONS PAGE 1, LOAD CAL'S
 SHOW THAT ALL FIVE BAYS TOGETHER WILL NEED OVER 460
 TONS OF A/C, PLEASE RE-DO LOAD CAL'S.
  
 3) CONDENSER UNITS APPEAR TO BE LOCATED IN THE BACK
 OFFICES, PLEASE CORRECT..
  
 4) PLEAS SHOW ON THE PLANS EQUIPMENT LISTING, THE
 SENSIBLE AND TOTAL BTU'S.
  
 5) PLEASE SHOW THE LOCATION OF ALL GRILLS.
  
 6) SEE UNIT B, PLEASE LABEL GRILLS IN BACK OFFICE.
  
 7) PLEASE PROVIDE DETAIL ON BATHROOM EXHAUST DUCTS, ARE
 THEY INDEPENDENTLY DUCTED TO THE OUTDOORS?
  
 8) PLEASE SHOW THE SIZE OF ALL SUPPLY AND RETURN AIR
 DUCTS (SEE HIGH LIGHTS ON PLANS).
  
 9) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-03-10 Cont ID  
Sent By jleech Date 2007-03-10 Time 13:18 Rev Time 0.00
Received By jleech Date 2007-03-10 Time 13:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-01-31 Cont ID  
Sent By jleech Date 2007-01-31 Time 14:47 Rev Time 0.00
Received By jleech Date 2007-01-31 Time 14:47 Sent To  
Notes
2007-01-31 14:48:33SEE PLUMBINGNOTES UNDER PERMIT # 06110563.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-03-14 Cont ID  
Sent By eschneid Date 2007-03-14 Time 13:25 Rev Time 0.00
Received By eschneid Date 2007-03-14 Time 13:25 Sent To  
Notes
2007-03-14 13:25:26FAILED - 2ND REVIEW
  
 1) THE LETTER BY ROBERT BELL, DATED DECEMBER 27, 2007,
 STATES THAT THE VALUE OF THE RENOVATION TOTALS
 $230,000.THE APPRAISAL INCLUDED WITH THE RESUBMITTAL
 PACKAGE GIVES A VALUE OF THE ENTIRE SITE (LAND AND
 STRUCTURE).THE LANDSCAPE CODE SPECIFICALLY STATES
 THAT A SITE IS EXEMPT FROM THE REQUIREMENTS OF THE CODE
 IF THE RENOVATION DOES NOT EXCEED 50% OF THE VALUE OF
 THE STRUCTURE.IF NO EVIDENCE IS PROVIDED THAT THE
 VALUE OF THE STRUCTURE EXCEEDS $460,000, THE SITE SHALL
 BE BROUGHT INTO COMPLIANCE WITH THE LANDSCAPE CODE
 (SECTION 94-441).
  
 2) THE LANDSCAPE COMPLIANCE LISTED IN COMMENT #1
 REQUIRES A LANDSCAPE PLAN PREPARED BY A REGISTERED
 LANDSCAPE ARCHITECT.
  
 3) WHAT WILL BE PLANTED IN THE PLANTERS?PROVIDE AN
 IRRIGATION PLAN FOR THE PLANTERS.
  
 4) THE ZONING AND LAND DEVELOPMENT REGULATIONS ALLOW A
 MAXIMUM OF 85% IMPERVIOUS SURFACE.THE EXISTING SITE
 IS CURRENTLY NONCONFORMING AS IT HAS 90.56% IMPERVIOUS
 SURFACE (8,060 SQ. FT.).THE IMPERVIOUS SURFACE ON THE
 SITE MAY NOT EXCEED THIS AMOUNT.THE PROPOSED PLANS
 SHOW AN INCREASE IN IMPERVIOUS SURFACE.THIS IS NOT
 PERMITTED AND SHALL BE CORRECTED.IT MAY REQUIRE
 REMOVING IMPERVIOUS SURFACE IN ANOTHER AREA TO MAKE UP
 THE DIFFERENCE.
  
 5) THE PROPOSED DUMPSTER ENCLOSURE SHOWN ON THE PLAN
 DOES NOT MEET THE CODE REQUIREMENTS.A SET OF PLANS,
 STAMPED APPROVED BY THE CITY'S ENGINEERING SERVICES
 DEPARTMENT, SHOWING THE DUMPSTER AND ENCLOSURE SIZE AND
 LOCATION IS REQUIRED.THE SCREEN WALL FOR THE DUMPSTER
 MAY NOT BE CHAIN LINK W/SLATS.THE SPECIFICATIONS OF
 THE SCREEN HEDGE ARE REQUIRED (SPECIES, HEIGHT,
 LOCATION AND PLANTING) ON A LANDSCAPE PLAN PREPARED
 FOLLOWING THE PROVISIONS OF SECTION 94-448(D)(2) OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS.AN IRRIGATION
 PLAN IS REQUIRED.
  
 6) NO ACCESSIBLE ROUTE TO ALL OF THE BAYS IS SHOWN.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-01-31 Cont ID  
Sent By eschneid Date 2007-01-31 Time 13:49 Rev Time 0.00
Received By eschneid Date 2007-01-31 Time 13:49 Sent To  
Notes
2007-01-31 13:50:12FAILED
  
 1) THE VALUE OF THE 5 PERMITS TOTALS $95,000 AND THE
 PROPERTY APPRAISER SHOWS THE VALUE OF THE STRUCTURE AT
 $84,000.THIS REQUIRES THAT THE SITE BE BROUGHT INTO
 COMPLIANCE WITH THE LANDSCAPE CODE (SECTION 94-441).
  
 2) A LANDSCAPE PLAN PREPARED BY A REGISTERED LANDSCAPE
 ARCHITECT IS REQUIRED.
  
 3) EXISTING AND PROPOSED IMPERVIOUS SURFACE
 CALCULATIONS ARE REQUIRED.THE PROPOSED PLANS APPEAR
 TO SHOW AN INCREASE IN IMPERVIOUS MATERIAL.
  
 4) NO DUMPSTER DETAIL PROVIDED.THE DUMPSTER ENCLOSURE
 SHOWN ON THE PLAN DOES NOT APPEAR TO MEET THE CODE
 REQUIREMENTS.
  
 5) NO ACCESSIBLE ROUTE TO ALL OF THE BAYS IS SHOWN.
  
 6) THE PARKING SPACES ON THE WESTERN SIDE OF THE SITE
 ENCROACH INTO THE CURB CUT ON BOTH DIXIE AND MONCEAUX
 AND THUS PRESENT AN UNSAFE SITUATION.THE CURB CUTS
 SHALL BE CLOSED WHERE CONFLICTS EXIST OR THE PARKING
 SPACES SHALL BE ELIMINATED.
  
 7) NO SURVEY WAS PROVIDED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.