Plan Review Details - Permit 06110515
Plan Review Stops For Permit 06110515
Review Stop G GAS REVIEW
Rev No 4 Status P Date 2007-04-27 Cont ID  
Sent By mperson Date 2007-04-27 Time 08:38 Rev Time 0.45
Received By mperson Date 2007-04-27 Time 08:38 Sent To PC
Notes
2007-04-27 08:40:33REVISION: CHANGED PIPE MATERIAL, SIZE AND BTU LOAD

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2007-02-13 Cont ID  
Sent By mperson Date 2007-02-13 Time 15:52 Rev Time 0.33
Received By mperson Date 2007-02-13 Time 15:52 Sent To PC
Notes
2007-02-13 16:33:24REVISION DENIED
 REFERENCE: FBC-2004 FUEL GAS; FLORIDA ADMINISTRATIVE
 CODE; CITY OF WEST PALM BEACH GAS PERMIT (REVISION)
 REQUIREMENTS;
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN
 REVIEW TO MEET CODE COMPLIANCE:
  
 1. PLEASE NOTE THAT THE ORIGINAL CONSTRUCTION
 DOCUMENTS ARE SIGNED, DATED AND SEALED BY AN ENGINEER.
 PER FLORIDA ADMINISTRATIVE CODE 61G15-23.002, ANY
 REVISIONS TO THE CONSTRUCTION DOCUMENTS SHALL BE SIGNED
 SEALED AND DATED BY THE ENGINEER OF RECORD EUGENE
 PILHUJ, LICENSE NUMBER, P.E. FL. REG. 49832. PLEASE
 CORRECT AND RESUBMIT.
  
 2. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: NOT ALL CORRESPONDING LENGTHS ARE INDICATED ON
 THE REVISION, PLEASE CORRECT AND RESUBMIT.
  
 3. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE: NOT ALL PIPING MATERIALS OR SIZES ARE INDICATED
 ON THE RESUBMITTAL AND PLEASE NOTE THAT THE REVISED GAS
 DRAWING IS SIZED WRONG . PLEASE REFERENCE THE ATTACHED
 FBC-2004 FUEL GAS SIZING TABLES FOR THE REVISION
 RESUBMITTAL.
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: THE ADDED LONGEST LENGTH OF THE INDICATED PIPE
 COMES TO 60'-11", BUT NOT ALL CORRESPONDING LENGTHS ARE
 INDICATED ON ALL CUT SECTIONS OF PIPEON THE REVISION.
 PLEASE CORRECT AND INDICATE THE LONGEST LENGTH ON THE
 RESUBMITTED REVISION.
  
 5. INDICATE THE DELIVERY PRESSURE (PSI)
 ON THE RESUBMITTED REVISION
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 NOTE: THE DELIVERY PRESSURE IS NOT INDICATED ON THE
 REVISION, PLEASE CORRECT THIS ON THE RESUBMITTED
 REVISION.
  
 **********IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-01-11 Cont ID  
Sent By mperson Date 2007-01-11 Time 14:07 Rev Time 0.33
Received By mperson Date 2007-01-11 Time 14:07 Sent To PC
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-12-01 Cont ID  
Sent By mperson Date 2006-12-01 Time 13:15 Rev Time 0.55
Received By mperson Date 2006-12-01 Time 13:15 Sent To PC
Notes
2006-12-01 13:50:08DENIED
 REFERENCE: FBC-2004 FUEL GAS AND THE CITY OF WEST PALM
 BEACH GAS PERMIT APPLICATION REQUIREMENTS
  
 THE FOLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN
 REVIEW TO MEET CITY AND CODE COMPLIANCE:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: THE SUBMITTED ISOMETRIC DRAWING DOES NOT INDICATE
 ALL CORRESPONDING LENGTHS.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE:THE ONLY MATERIAL INDICATED AS BEING USED IS PE.
 PER FBC-2004 FUEL GAS , SECTION 403.6 PLASTIC PIPE,
 TUBING AND FITTINGS SHALL BE USED OUTSIDE, UNDERGROUND,
 ONLY. PLEASE INDICATE ALL PIPING MATERIALS BEING USED
 (ABOVE AND UNDERGROUND) ON THE RESUBMITTED ISOMETRIC.
  
 3. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 NOTE: PLEASE SUBMIT CALCULATIONS OF WATER HEATER
 LOCATION.
  
 4. ON THE MASTER PERMIT #05120933 THERE ALREADY A SHEET
 P-3. PLEASE CHANGE THE RESUBMITTEDSHEET TO P-4 TO
 ADVOID CONFUSION.
  
 5. THE LONGEST LENGTH INDICATED ON THE DRAWINGS IS
 WRONG ON THE FLOOR PLAN DRAWING THE THE LONGEST LENGTH
 CALCULATES55' AND ON THE ISOMETRIC THE LONGEST LENGTH
 CALCULATES 63' WITH THE MEASUREMENTS GIVEN BUT IS
 LISTED AS 48'. ALL THREE OF THESE CALCULATIONS ARE
 WRONG BECAUSE NOT ALL OF THE CORRESPONDING LENGTHS ARE
 INDICATED ON THE ISOMETRIC GAS RISER DIAGRAM. PLEASE
 CORRELATE THE LONGEST LENGTH ON THE RESUBMITTAL.
  
 6. PLEASE CORRELATE THE SLEEVE INDICATED ON THE FLOOR
 PLAN WITH THE ISOMETRIC GAS RISER DIAGRAM.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-04-23 Cont ID  
Sent By adarroug Date 2007-04-23 Time 11:13 Rev Time 0.00
Received By adarroug Date 2007-04-23 Time 11:13 Sent To G
Notes
2007-04-23 11:13:46TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-02-08 Cont ID  
Sent By adarroug Date 2007-02-08 Time 12:44 Rev Time 0.00
Received By adarroug Date 2007-02-08 Time 12:44 Sent To G
Notes
2007-02-08 12:45:10TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-01-09 Cont ID  
Sent By adarroug Date 2007-01-09 Time 09:59 Rev Time 0.00
Received By adarroug Date 2007-01-09 Time 09:59 Sent To P
Notes
2007-01-09 10:00:02TO "G" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-12-01 Cont ID  
Sent By mperson Date 2006-12-01 Time 13:50 Rev Time 0.00
Received By mperson Date 2006-11-16 Time 16:10 Sent To  
Notes
2006-11-16 16:10:18TO "G" BOX