Plan Review Details - Permit 06110497
Plan Review Stops For Permit 06110497
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-12-22 Cont ID  
Sent By mjacobs Date 2006-12-22 Time 15:01 Rev Time 0.00
Received By mjacobs Date 2006-12-20 Time 18:14 Sent To PC
Notes
2006-12-20 18:53:02BUILDING PLAN REVIEW
 PERMIT:06110497
 ADD:10130 NORTHLAKE BLVD. #651
 CONT:POWER SECURE INC.
 TEL: (866)347-5455
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW : 1ST
 ACTION: DENIED
  
 1) 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 2)SHOW CLEARLY ON THE DRAWINGS THE DISTANCE THE
 GENERATOR WILL BE INSTALLED FROM THE BUILDING.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-12-06 Cont ID  
Sent By dpalmer Date 2006-12-06 Time 19:36 Rev Time 0.00
Received By dpalmer Date 2006-12-06 Time 19:07 Sent To  
Notes
2006-12-06 19:43:36***********UNSAT *************
  
 PUBLIX GENERATOR
 #651
  
 1) NOTE:PLEASE SEE VALUE FOR SCOPE AHS BEEN INCREASED
 TO THE COST OF OTHER TYPICAL GENERATORS APPLIED FOR IN
 THIS JURISDICTION.PLEASE KNOW FALSIFYING INFORMATION
 ON AN APPLICATION IS GROUNDS FOR TURNING OVER TO THE
 STATE ECLB. PLEASE KNOW THIS COMMENT HAS BEEN MADE ON
 ALL OTHER PROJECTS SUBMITTED BY THIS CONTRACTOR FOR THE
 SAME SCOPE OF WORK AND THIS IS STILL BEING SUBMITTED
 WITH VALUES WAY LOW FOR ANY LABOR OR MATERIALS. PLEASE
 KNOW ANY FUTURE PROJECTS WILL NOT BE PROCESSED OR
 REVIEWED IF THIS IS DONE. THIS HAS NOW BEEN DOCUMENTED
 AS THE FOURTH PROJECT LOCATED IN THE CITY OF WEST PALM
 BEACH WHERE THE APPLICATIONS HAVE BEEN SUBMITTED BELOW
 ANY LEVELS OF VALUE ACCURATE TO THE SCOPE OF WORK.
 THE VALUE OF $10K ON PERMIT APPLICATION SUBMITTED IS
 EXTREMELY LOW.
 PLEASE KNOW THAT VALUE SHALL BE ALL LABOR AND MATERIALS
 EVEN IF MATERIALS ARE OWNER SUPPLIED.PLEASE SEE FBC
 2004, ADMINISTRATIVE CODE SECTION 108.3 AS ADOPTED BY
 THE CITY OF WEST PALM BEACH.
 PLEASE KNOW, UNDER CONTRACTING LAWS AND RULES SET UP
 AND ADOPTED INTO FLORIDA
 STATUTES, 489, FBC ADMINISTRATIVE SECTION
 105.5.1 ANY INFORMATION PROVIDED ON OFFICIAL PERMIT
 APPLICATION IF KNOWINGLY BEING FALSIFIED CAN
 VOID/REVOKE SUCH PERMIT/ APPLICATION.
 ** PLEASE KNOW THESE FEES OF $1975.80 ARE DUE AT THIS
 TIME AND WILL BE REQUIRED TO BE PAID BEFORE PICKING UP
 PLANS. NO EXCEPTIONS.
  
 2) NOTE: PLEASE KNOW, ANY SYSTEMS LOCATED IN A FLOOD
 ZONE "A" WILL BE REQUIRED TO BE MOUNTED AT A MIN OF 6"
 ABOVE BFE. PLEASE SEE BUILDING REVIEW COMMENTS.
  
 3) NOTE: PLEASE SUBMIT SPECS/MANUFACTURE CUT SHEETS.
 APS/ ATS DO NOT INDICATE THE REQUIRED MEANS OF
 DISCONNECT AS REQUIRED BY 230.76,230.79, 225.31-39.
 PLEASE SEE A MANUAL MEANS OF DISCONNECT COULD NOT BE
 LOCATED RATED FOR THE LOAD SERVED ON THE OUTSIDE OF
 EQUIPMENT SUBMITTED.
 THIS WAS NEVER VERIFIED FROM PREVIOUS PERMIT PULLED FOR
 PREVIOUS PROJECT.
 NO PERMITS WILL BE RELEASED UNLESS THIS IS VERIFIED ON
 ALL SUBMITTED SPECS AND PLANS SUBMITTED BEFORE PERMIT
 IS ISSUED.
 PLEASE SEE ALL EQUIPMENT SHALL BE LISTED FOR USE.90.7,
 110.3
  
 4) NOTE: PLEASE INDICATE THE OCP AT THE GEN. PLEASE SEE
 445.13 AS IT HAS COME TO OUR ATTENTION ON A PREVIOUS
 PROJECT THAT THE GEN MAY NOT CONTAIN OCP AND CAN NOT BE
 VERIFIED AT THIS TIME.
  
 5) NOTE: PLEASE SEE NO LOAD CALCULATIONS WERE SUBMITTED
 FOR REVIEW. PLEASE SUBMIT.
 PLEASE SUBMIT AND INDICATE ANY LOAD SHEDDING DETAILS IF
 APPLICABLE.
 702.5, 220
  
 6) NOTE: PLEASE PROVIDE INFORMATION IF THE GEN WILL BE
 FEEDING ANY "LEGALLY REQUIRED STAND-BY SYSTEMS". PLANS
 TO INDICATE THIS, NOT ONLY IN A RESPONSE LETTER.
  
 7) NOTE:PLEASE SEE PLANS SHALL INDICATE THE CURRENT
 CODES IN EFFECT FOR INSTALLATION AS FOLLOWS. PLEASE SEE
 FBC 2004 CHAPTER 27FOR ADOPTED CODES RELEVANT TO
 POWER GENERATORS.
 2002 NFPA-70, 2002 NFPA-110(WHERE CLASS 1 OR 2)
  
 8) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE GENERATOR. NONE SUBMITTED AT THIS TIME,
 UNABLE TO REVIEW.
 110.3, 90.7. ETC
 FCB 106.1.2
  
 9) NOTE: PLEASE SEE THE APS/ATS IS BECOMING THE NEW
 FIRST MEANS OF DISCONNECT HOWEVER THE NEW GROUNDING
 ELECTRODE SYSTEMS DOES NOT SEEM TO BE COMPLETE AS PER
 250.50.
 PLEASE SEE GROUNDING DETAIL MENTIONS NEW SLAB STEEL
 WHICH IS OK, HOWEVER PLEASE INDICATE ATTACHMENT.
 THESE NEW SLAB/STEEL ATTACHMENTS DO NOT MEET THE MIN
 REQUIREMENTS PER
 250.50, 250.52, 250.104
 IF SLAB STEEL IS ONLY BEING BONDED, THEN PLEASE
 INDICATE.
 PLEASE COMPLETE GROUNDING ELECTRODE SYSTEM(S) AND
 BONDING FOR ALL AS ABOVE.
 PLEASE SEE DETAIL STILL INDICATES THE NEUTRAL AND
 EXISTING GROUNDING ELECTRODE SYSTEM BEING BONDED AT THE
 EXISTING SERVICE WHICH WILL PARALLEL THE NEW SYSTEM
 REQUIRED.
 250.6, 250.24B.
  
 10) NOTE: PLEASE SEE SETS OF CONDUITS AND FEEDERS DO
 NOT SEEM TO INDICATE THE NEW REQUIRED "EQUIPMENT
 GROUNDING CONDUCTOR" TO THE EXISTING MAINS. THESE ARE
 NO LONGER THE FIRST MEANS OF DISCONNECT.
 250.110,250.122,250.24B, 250.6, AS NOTED ABOVE IN NOTE
 #9
  
 11) NOTE:PLEASE KNOW, BASED ON ALL PREVIOUS PROJECTS,
 IS THIS UNIT GOING TO BE "BI-FUEL"??
 IF SO, SUBMIT ALL INFORMATION AND SPECS ON UNIT(S).
 90.7, 110.3
  
 12) NOTE: PLEASE KNOW AS THE ORIGINAL PROJECT AT STORE
 #50 LOCATED AT 828 SOUTHERN BLVD HAS NOT PASSED
 INSPECTIONS AND THERE ARE SEVERAL UNANSWERED QUESITONS
 ON PROJECT,AS STATED ON OTHER GENERATOR PERMITS,
 THESE WILL NOT BE ISSUED UNTIL ALL CODE COMPLIANCE IS
 MET ON THE ORIGINAL PROJECT.
 PLEASE KNOW ALL PERMITS EXPIRE WITHIN 6 MONTHS OF IN-
 ACTIVITY.
 FBC ADMIN SECTION 105.3.2
  
  
 ** PLEASE KNOW, AS MUCH INFORMATION WAS NOT SUBMITTED,
 A COMPLETE REVIEW COULD NOT BE DONE.
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-01-04 Cont ID  
Sent By mawillia Date 2007-01-04 Time 20:33 Rev Time 0.00
Received By mawillia Date 2007-01-04 Time 20:27 Sent To  
Notes
2007-01-04 21:25:54*****DENIED*****
  
  
  
 1.CONSTRUCTION AND/OR DEMOLITION OPERATIONS IN OR
 AROUND THE AREA OF WORK SHALL NOT INTERFERE WITH
 EMERGENCY RESPONSE ACCESS TO THE BUILDING(S) OR THE
 VICINITY THEREOF (INCLUDING FIRE LANES).
  
 2.PLEASE DESCRIBE ANY AND ALL LIFE SAFETY EQUIPMENT
 PLANNED TO BE SUPPLIED BY THE GENERATOR.
  
 3.STATIONARY GENERATORS USED FOR EMERGENCY OR STANDBY
 POWER SHALL BE INSTALLED, TESTED, MAINTAINED, AND
 COMPLY WITH NFPA 110.
  
 4.DIESEL FUEL STORAGE SHALL COMPLY WITH NFPA 30.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
 4.

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-01-08 Cont ID  
Sent By jleech Date 2007-01-08 Time 13:52 Rev Time 0.00
Received By jleech Date 2007-01-08 Time 13:52 Sent To  
Notes
2007-01-08 14:10:31DENIED;
 NOT ENOUGH INFORMATION TO DO A GAS FUEL REVIEW. SUBMIT
 MANUFACTURE'S SPEC, AND CUT SHEETS FOR GENERATOR. IS
 THIS A BI-FUEL GENERATOR LIKE THE ONE ON SOUTHERN
 BLVD.?
 GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-08 Cont ID  
Sent By jleech Date 2007-01-08 Time 14:12 Rev Time 0.00
Received By jleech Date 2006-11-16 Time 10:00 Sent To  
Notes
2006-11-27 16:56:14TO "COMM" BD#34
2006-11-16 10:01:02WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-11-28 Cont ID  
Sent By tgordon Date 2006-11-28 Time 15:34 Rev Time 0.30
Received By tgordon Date 2006-11-28 Time 15:34 Sent To  
Notes
2006-11-28 16:01:42*** DENIED ***
 1) DUE TO THE 1000 GAL. FUEL TANK THE PLANS NEED TO BE
 APPROVED BY THE FL. DEPT. OF ENVIRONMENTAL PROTECTION
 (2300 N. JOG RD. W.P.B. (561) 233-2400) BEFORE APPLYING
 FOR PERMIT.
  
 2) INFORMATIONAL ONLY. PER 2004 FBC, FUEL GAS -
 POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURER'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY COMBUSTION
 ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE RESISTANCE
 RATING OF 1 HOUR OR (2) THE WEATHERPROOF ENCLOSURE IS
 CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS
 SHOULD NOT TERMINATE UNDER STRUCTURES OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO
 THE VENTILATION INTAKES.
  
 GENERATORS SHALL MAINTAIN THE REQUIRED ABOVE
 MENTIONED CLEARANCES TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS.
  
 FUEL STORAGE TANK MUST BE A MINIMUM DISTANCE OF 5 FEET
 FROM BUILDING, SEE NFPA 30 CH. 4, 4.3.2.1.1.
  
 FOLLOW MANUFACTURER'S RECOMMENDED
 CLEARANCES AROUND EQUIPMENT FOR
 SERVICING,AND PROVIDE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS AT THE JOBSITE
 FOR THE FIELD INSPECTOR.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status N Date 2007-01-08 Cont ID  
Sent By jleech Date 2007-01-08 Time 13:52 Rev Time 0.00
Received By jleech Date 2007-01-08 Time 13:51 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2006-12-06 Cont ID  
Sent By lfranco Date 2006-12-06 Time 13:55 Rev Time 0.00
Received By lfranco Date 2006-12-06 Time 09:15 Sent To I
Notes
2006-12-06 13:41:44PLANNING AND ZONING:***** FAILED *******
  
 1.PROVIDE RESPONSES TO COMMENTS IN WRITING.
  
 2.A MINOR AMENDMENT TO THE IBIS RESIDENTIAL PLANNED
 DEVELOPMENT (RPD), MASTER PLAN WILL BE REQUIRED. AN
 APPLICATION WILL NEED TO BE FILED TO THE PLANNING AND
 ZONING DEPARTMENT AND APPROVED PRIOR TO SIGN-OFF OF
 BUILDING PERMIT.THE COMMENTS BELOW REFLECT THE
 INFORMATION NEEDED ON SITE PLAN, PRIOR TO SUBMITTAL OF
 THE MINOR AMENDMENT TO THE IBIS RESIDENTIAL PLANNED
 DEVELOPMENT.
  
 3.PROVIDE A DETAIL, WITH DIMENSIONS OF THE AREA WHERE
 THE GENERATOR IS PROPOSED.THIS INCLUDES DIMENSIONS
 OF THE ROADWAY CLEARANCE, SINCE THE GENERATOR IS
 PROPOSED ON THE DRIVE AISLE, VEHICLE ACCESS WAY.
  
 THE SITE PLAN SHALL INCLUDE THE FOLLOWING:
  
 A. SCREENING AND ELEVATION OF WALL/HEDGES AROUND
 GENERATOR AND SETBACK DISTANCE FROM PROPERTY LINE.
  
  
 4.PURSUANT TO SECTION 94-444(B) OPEN SPACE
 STANDARDS:
  
 (B) FUEL OR OIL OR PROPANE TANKS, GENERATORS SHALL NOT
 BE PERMITTED UNLESS APPROPRIATE SCREENING IS PROVIDED.
 SCREENING SHALL BE CONSTRUCTED OF BRICK, DECORATIVE
 CONCRETE, OTHER DECORATIVE MASONRY, OR COMPARABLY
 DURABLE WOOD AND STEEL.
  
 WALLS SHALL BE LANDSCAPED WITH SHRUBS AND HEDGES
 PLANTED AT TWO-FOOT INTERVALS.A FOUR-SIDED ENCLOSURE
 WITH MASONRY, OR COMPARABLY DURABLE WOOD AND STEEL, AN
 OBSCURING GATE IS REQUIRED AS A CONDITION FOR SITE PLAN
 APPROVAL.
  
 THE SCREENING SHALL ENCLOSE THE ENTIRE GENERATOR.
  
 5.PURSUANT TO SECTION 94-305(B)(4) SETBACKS (B)(4)
 SETBACK ENCROACHMENT:
 MECHANICAL EQUIPMENT SHALL NOT PROJECT MORE THAN 4 FEET
 INTO A SETBACK.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME AT THE
 NUMBER BELOW.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1435