Plan Review Details - Permit 06110401
Plan Review Stops For Permit 06110401
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-01-18 Cont ID  
Sent By shill Date 2007-01-18 Time 14:46 Rev Time 0.00
Received By shill Date 2007-01-18 Time 14:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-11-30 Cont ID  
Sent By btrobaug Date 2006-11-30 Time 17:00 Rev Time 0.50
Received By btrobaug Date 2006-11-30 Time 16:36 Sent To M
Notes
2006-11-30 17:00:49 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW PRIOR TO ROUGH
 INSPECTION.
  
  
 1} PROVIDE MANUFACTURERS SPECIFICATIONS AND
 RECOMMENDATION, REGARDING CLEARANCES FOR THE
 GENERATOR.
  
 2} PROVIDE SPECIFICATIONS FOR THE TRANSFER SWITCH.
  
 3}PROVIDE A PANEL SCHEDULE FOR THE
 EMERGENCY/GENERATOR PANEL.
  
 4} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
 DO THIS ON A SITE PLAN, NOT ON THE SURVEY, 106.1.3
 FBC.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-12-12 Cont ID  
Sent By mperson Date 2006-12-12 Time 14:51 Rev Time 0.45
Received By mperson Date 2006-12-12 Time 14:51 Sent To B
Notes
2006-12-12 15:24:39DENIED
 REFERENCE: FBC-2004 FUEL GAS AND FBC-2004 CHAPTER 1
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN
 REVIEW TO MEET CODE COMPLIANCE:
  
 1. NOTE: ONLY ONE SET OF GAS DRAWINGS AND SUBMITTALS
 WERE SUBMITTED WITH THE GEN/RES PERMIT APPLICATION.A
 MINIMUM OF TWO (2) COMPLETE SETS OF GAS DRAWINGS AND
 SUBMITTALS ARE REQUIRED FOR PLAN REVIEW PER FBC-2004
 CHAPTER 1, SECTION 106.1.
  
 2. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: PLEASE INCLUDE BOTH THE ABOVE AND UNDERGROUND
 PIPING AND THE LOCATION OF THE 1ST AND 2ND STAGE
 REGULATORS.
  
 3. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE: PLEASE INCLUDE BOTH THE ABOVE AND UNDERGROUND
 PIPING MATERIALS AND SIZES.
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
 NOTE: NEED MANUFACTURER SHEETS AND INSTALLATION
 INSTRUCTIONS REGAURDING CLEARENCES FOR THE GENERATOR.
 PLEASE SUBMIT MANUFACTURER SHEETS OF 1ST AND 2ND STAGE
 REGULATORS.
  
 6. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 7. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 8. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-11-17 Cont ID  
Sent By adarroug Date 2006-11-17 Time 10:05 Rev Time 0.00
Received By adarroug Date 2006-11-17 Time 10:05 Sent To E
Notes
2006-11-17 10:05:33TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-18 Cont ID  
Sent By shill Date 2007-01-18 Time 14:47 Rev Time 0.00
Received By shill Date 2006-11-13 Time 15:34 Sent To  
Notes
2006-11-13 15:34:29TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-12-01 Cont ID  
Sent By tgordon Date 2006-12-01 Time 15:33 Rev Time 0.15
Received By tgordon Date 2006-12-01 Time 15:33 Sent To G
Notes
2006-12-01 15:34:59*** DENIED ***
 1) SEE ZONING REVIEW NOTES, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-11-16 Cont ID  
Sent By mmclean Date 2006-11-16 Time 07:07 Rev Time 0.00
Received By mmclean Date 2006-11-16 Time 07:07 Sent To I
Notes
2006-11-16 07:13:33DENIED,
 1. PLEASE PROVIDE THE HOA APPROVAL FOR THE PROPOSED
 GENERATOR AND GAS TANK WITHIN THE FRONT SETBACK.
 2. PLEASE PROVIDE THE DISTANCE OF THE PROPOSED
 GENERATOR AND GAS TANK FROM THE FRONT PROPERTY LINE.
 3. PLEASE PROVIDE ALL THE UTITILTY EASEMENT RELEASES
 FOR THE 12FT UTILITY EASEMENT. THE PROPOSED
 GENERATOR/GAS TANK WILL ENROACH IN THE 12 U.E BASE ON
 THE REQUIRED GUIDELINES.
 4. THE PROPOSED GENERATOR SHALL NOT BE CLOSER THAN 11FT
 FROM CORNER SIDE PROPERTY LINE.
 5. THE PROPOSED GAS TANK SHALL NOT BE CLOSER THAN 16FT
 FROM FRONT PROPERTY LINE AND 11FT FROM THE SIDE
 PROPERTY LINE.
 6. THE PROPOSED GENERATOR MUST BE SCREENED WITH A
 LANDSCAPE BUFFER FROM VIEW.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720