Plan Review Details - Permit 06110392
Plan Review Stops For Permit 06110392
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-01-11 Cont ID  
Sent By btrobaug Date 2007-01-11 Time 10:44 Rev Time 0.75
Received By btrobaug Date 2007-01-08 Time 06:56 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-11-30 Cont ID  
Sent By btrobaug Date 2006-11-30 Time 15:26 Rev Time 0.50
Received By btrobaug Date 2006-11-28 Time 17:37 Sent To I
Notes
2006-11-30 15:25:58 
  
 DENIED/INCOMPLETE INFORMATION
  
 1} PLEASE PROVIDE A FLOOR PLAN LOCATING THE EQUIPMENT
 TO BE ADDED, AND EXISTIONG EQUIPMENT AT THE SAME
 LOCATION SO THAT A REVIEW CAN BE MADE TO DETERMINE
 COMPLIANCE WITH 110.26INDICATE FIRE RATED WALLS,
 FLOORS OR OTHER ITEMS PENETRATED BY THE CONDUITS.
  
 2} PROVIDE A LOAD CALCULATION FOR THE EXISTING 400 AMP
 PANEL THAT FEEDS THE NEW EQUIPMENT. INDICATE EXISTING
 LOADS AND THE ADDED TRANSFORMER LOAD. 215.5 NEC.
  
 3} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS
 AMENDED.
  
 4} PLEASE PROVIDE A PANEL SCHEDULE AND DESIGNATION FOR
 THE 200 AMP PANEL BEING ADDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-28 Cont ID  
Sent By adarroug Date 2006-12-28 Time 11:38 Rev Time 0.00
Received By adarroug Date 2006-12-28 Time 11:38 Sent To E
Notes
2006-12-28 11:38:29TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-11-30 Cont ID  
Sent By btrobaug Date 2006-11-30 Time 15:28 Rev Time 0.00
Received By btrobaug Date 2006-11-13 Time 15:58 Sent To PC
Notes
2006-11-13 15:58:50TO "E" BOX