Plan Review Details - Permit 06110105
Plan Review Stops For Permit 06110105
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-01-10 Cont ID  
Sent By rmcdouga Date 2007-01-10 Time 08:33 Rev Time 0.00
Received By rmcdouga Date 2007-01-10 Time 07:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-11-14 Cont ID  
Sent By rmcdouga Date 2006-11-14 Time 12:44 Rev Time 0.00
Received By rmcdouga Date 2006-11-14 Time 12:18 Sent To  
Notes
2006-11-14 12:45:02DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SPECIFY THE CONSTRUCTION TYPE BASED ON THE 2004 FBC
 DESIGNATIONS. SEE FBC TABLE 601. SPECIFY A OR B.
  
 3) THE COVER SHEET SPECIFIES SUITE # 905 UNDER PROJECT
 DATA AND THE TITLE BLOCKS LIST SUITE # 605. PLEASE
 CORRECT.
  
 4) CLARIFY THE SCOPE OF WORK. THE FIRST ITEM LISTED
 REFERS TO DEMO PLAN 4 ON A-1, WHICH IS A FINISH
 SCHEDULE.
  
 5) THE DOOR HARDWARE IS REQUIRED TO COMPLY WITH FBC
 11-4.13.9 FOR ACCESSIBILITY.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-12-30 Cont ID  
Sent By dpalmer Date 2006-12-30 Time 16:41 Rev Time 0.00
Received By dpalmer Date 2006-12-30 Time 16:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-11-14 Cont ID  
Sent By dpalmer Date 2006-11-14 Time 09:23 Rev Time 0.00
Received By dpalmer Date 2006-11-14 Time 08:50 Sent To  
Notes
2006-11-14 09:25:04***** UNSAT*****
  
 1) NOTE:PLEASE SUBMIT AND INDICATE LOADS ON EXISTING
 PANEL "HP6". PLEASE SEE 220.3, 220.10,220.11, 220.13
 AND 215.3, 230.42 FOR CONTINUOUS LOADS..
  
 2) NOTE: PLEASE SEE CODES FOR ADA REQUIREMENTS FOR ANY
 HORN/STROBES WHICH MAY BE REPLACED. PLEASE SEE FBC
 11-4.28.2, 11-4.28.3(4). PLEASE INDICATE THESE MINIMUM
 AMOUNTS IF THESE DEVICES ARE PART OF THE SCOPE OF
 WORK.
  
 3) NOTE: PLEASE COMPLETE PANEL SCHEDULE FOR ROOMS AND
 AREAS FOR CIRCUITING.
 IE: OFFICE 610, CIRCUIT #X, 614, #-Y ETC
 310.16, 240.4, 408.4,
 FBC ADMIN SECTION 106.1.2
  
 4) NOTE: PLEASE SEE RISER SHOWS A DISCONNECT FROM THE
 PANEL "HP" , HOWEVER COULD NOT LOCATE THE LOCATION OF
 THIS ON THE PLANS?.
 PLEASE SHOW.
 FBC 106.1.2 ADMIN SECT.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
 **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF
 THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE
 DO NOT HESITATEIN CONTACTING THIS REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-01-09 Cont ID  
Sent By mawillia Date 2007-01-09 Time 13:05 Rev Time 0.00
Received By mawillia Date 2007-01-09 Time 13:05 Sent To  
Notes
2007-01-09 13:06:50*****APPROVED*****
  
  
  
 ALL FIRE PLAN REVIEW COMMENTS OF 11/20/2006 HAVE BEEN
 ADDRESSED.PLAN SHEETS A-1 AND E-2 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-11-20 Cont ID  
Sent By mawillia Date 2006-11-20 Time 12:50 Rev Time 0.00
Received By mawillia Date 2006-11-20 Time 12:50 Sent To  
Notes
2006-11-20 13:12:57****DENIED****
  
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.COMPLIANCE WITH FLORIDA FIRE PREVENTION CODE 2004
 EDITION SHALL BE REFERENCED.
  
 3.PLEASE INDICATE/DISPLAY/SHOW THE LOCATION OF ANY
 FIRE PROTECTION SYSTEM DEVICES INCLUDING FIRE
 EXTINGUISHER(S).HOW WILL THEY BE AFFECTED BY THE
 SCOPE OF THE WORK?
  
 4.IF THE FIRE ALARM AND (OR) FIRE SRINKLER SYSTEM ARE
 TO BE MODIFIED DUE TO THE SCOPE OF WORK, SEPARATE PLANS
 AND PERMIT ARE REQUIRED.
  
 5.PLEASE EXPLAIN THE LACK OF EXIT LIGHTS IN THE AREA
 OF DOORS LEADING TO THE COMMON CORRIDOR FROM EXISTING
 RECEPTION [605] AND OPEN OFFICE [622].
  
 6.PLEASE PROVIDE INTERIOR FINISH CLASSIFICATION FOR
 WALLS AND CEILING.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-13 Cont ID  
Sent By adarroug Date 2006-12-13 Time 16:33 Rev Time 0.00
Received By adarroug Date 2006-12-13 Time 16:33 Sent To  
Notes
2006-12-30 16:33:05TO BOB # 18 12/30
2006-12-13 16:34:07WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-12-13 Cont ID  
Sent By adarroug Date 2006-11-20 Time 16:33 Rev Time 0.00
Received By adarroug Date 2006-11-07 Time 10:01 Sent To  
Notes
2006-11-12 14:16:24TO "BOB"#15
2006-11-07 10:01:19WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-11-13 Cont ID  
Sent By tgordon Date 2006-11-13 Time 14:28 Rev Time 0.30
Received By tgordon Date 2006-11-13 Time 14:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-11-20 Cont ID  
Sent By jleech Date 2006-11-20 Time 15:00 Rev Time 0.00
Received By jleech Date 2006-11-20 Time 15:00 Sent To  
Notes
2006-11-20 14:54:37NO PLUMBING SHOWN ON PLANS.