Plan Review Details - Permit 06110087
Plan Review Stops For Permit 06110087
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-11-28 Cont ID  
Sent By jwitmer Date 2006-11-28 Time 11:27 Rev Time 1.25
Received By jwitmer Date 2006-11-28 Time 11:27 Sent To  
Notes
2006-11-28 12:03:35BUILDING PLAN REVIEW
 PERMIT: 06110087
 ADD: 3199 CUMBERLAND DR
 CONT: DCS ELECTRIC
 TEL: (561)7224690
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) DCS ELECTRIC HAAS A EC STATE LICENSE, WHEN THE
 MAJORITY OF THE WORK IS NOT ELECTRIC, THE "PRIME PERMIT
 " HAS TO BE SIGNED BY EITHER A POLLUTANT STORAGE
 SYSTEMS CONTRACTOR OR IF GASOLINE A MECHANICAL
 CONTRACTOR.
 489.105
 I)"MECHANICAL CONTRACTOR" MEANS A CONTRACTOR WHOSE
 SERVICES ARE UNLIMITED IN THE EXECUTION OF CONTRACTS
 REQUIRING THE EXPERIENCE, KNOWLEDGE, AND SKILL TO
 INSTALL, MAINTAIN, REPAIR, FABRICATE, ALTER, EXTEND, OR
 DESIGN, WHEN NOT PROHIBITED BY LAW, CENTRAL
 AIR-CONDITIONING, REFRIGERATION, HEATING, AND
 VENTILATING SYSTEMS, INCLUDING DUCT WORK IN CONNECTION
 WITH A COMPLETE SYSTEM ONLY TO THE EXTENT SUCH DUCT
 WORK IS PERFORMED BY THE CONTRACTOR AS IS NECESSARY TO
 MAKE COMPLETE AN AIR-DISTRIBUTION SYSTEM, BOILER AND
 UNFIRED PRESSURE VESSEL SYSTEMS, LIFT STATION EQUIPMENT
 AND PIPING, AND ALL APPURTENANCES, APPARATUS, OR
 EQUIPMENT USED IN CONNECTION THEREWITH, AND ANY DUCT
 CLEANING AND EQUIPMENT SANITIZING WHICH REQUIRES AT
 LEAST A PARTIAL DISASSEMBLING OF THE SYSTEM; TO
 INSTALL, MAINTAIN, REPAIR, FABRICATE, ALTER, EXTEND, OR
 DESIGN, WHEN NOT PROHIBITED BY LAW, PIPING, INSULATION
 OF PIPES, VESSELS AND DUCTS, PRESSURE AND PROCESS
 PIPING, PNEUMATIC CONTROL PIPING, GASOLINE TANKS AND
 PUMP INSTALLATIONS AND PIPING FOR SAME, STANDPIPES, AIR
 PIPING, VACUUM LINE PIPING, OXYGEN LINES, NITROUS OXIDE
 PIPING, INK AND CHEMICAL LINES, FUEL TRANSMISSION
 LINES, LIQUEFIED PETROLEUM GAS LINES WITHIN BUILDINGS,
 AND NATURAL GAS FUEL LINES WITHIN BUILDINGS; TO
 REPLACE, DISCONNECT, OR RECONNECT POWER WIRING ON THE
 LOAD SIDE OF THE DEDICATED EXISTING ELECTRICAL
 DISCONNECT SWITCH; TO INSTALL, DISCONNECT, AND
 RECONNECT LOW VOLTAGE HEATING, VENTILATING, AND
 AIR-CONDITIONING CONTROL WIRING; AND TO INSTALL A
 CONDENSATE DRAIN FROM AN AIR-CONDITIONING UNIT TO AN
 EXISTING SAFE WASTE OR OTHER APPROVED DISPOSAL OTHER
 THAN A DIRECT CONNECTION TO A SANITARY SYSTEM. THE
 SCOPE OF WORK FOR SUCH CONTRACTOR SHALL ALSO INCLUDE
 ANY EXCAVATION WORK INCIDENTAL THERETO, BUT SHALL NOT
 INCLUDE ANY WORK SUCH AS POTABLE WATER LINES OR
 CONNECTIONS THERETO, SANITARY SEWER LINES, SWIMMING
 POOL PIPING AND FILTERS, OR ELECTRICAL POWER WIRING.
  
 P)"POLLUTANT STORAGE SYSTEMS CONTRACTOR" MEANS A
 CONTRACTOR WHOSE SERVICES ARE LIMITED TO, AND WHO HAS
 THE EXPERIENCE, KNOWLEDGE, AND SKILL TO INSTALL,
 MAINTAIN, REPAIR, ALTER, EXTEND, OR DESIGN, WHEN NOT
 PROHIBITED BY LAW, AND USE MATERIALS AND ITEMS USED IN
 THE INSTALLATION, MAINTENANCE, EXTENSION, AND
 ALTERATION OF, POLLUTANT STORAGE TANKS. ANY PERSON
 INSTALLING A POLLUTANT STORAGE TANK SHALL PERFORM SUCH
 INSTALLATION IN ACCORDANCE WITH THE STANDARDS ADOPTED
 PURSUANT TO S. 376.303.
  
 4) PLEASE PROVIDE THE LOCATION OF THIS UNIT WITH THE
 LOCATION OF THE STRUCTURE, LOCATE ALL WINDOWS, DOORS ,
 AND SOFFIT VENTS, PROVIDE THE DISTANCE AWAY FROM THE
 FUEL TANK TO THE STRUCTURE.ALSO INDICATE WHAT THIS IS A
 FUEL TANK TOO?
  
 5) PROVIDE HOW THE FUEL TANK WILL BE BOLTED DOWN TO
 RESIST THE MOMENT OF OVERTURNING.
 1609.1.3 ANCHORAGE AGAINST OVERTURNING , UPLIFT AND
 SLIDING.
 STRUCTURAL MEMBERS AND SYSTEMS AND COMPONENTS AND
 CLADDING IN A BUILDING OR STRUCTURE SHALL BE ANCHORED
 TO RESIST WIND-INDUCED OVERTURNING , UPLIFT AND SLIDING
 AND TO PROVIDE CONTINUOUS LOAD PATHS FOR THESE FORCES
 TO THE FOUNDATION. WHERE A PORTION OF THE RESISTANCE TO
 THESE FORCES IS PROVIDED BY DEAD LOAD, THE DEAD LOAD,
 INCLUDING THE WEIGHT OF SOILS AND FOUNDATIONS, SHALL BE
 TAKEN AS THE MINIMUM DEAD LOAD LIKELY TO BE IN PLACE
 DURING A DESIGN WIND EVENT. WHERE THE ALTERNATE BASIC
 LOAD COMBINATIONS OF SECTION 1605.3.2 ARE USED, ONLY
 TWO-THIRDS OF THE MINIMUM DEAD LOAD LIKELY TO BE IN
 PLACE DURING A DESIGN WIND EVENT SHALL BE USED.
  
 6)NOTE, PROVISO: THE TANK IS ALSO LOCATED IN A A-8
 FLOOD ZONE,
 THE FINISHED FLOOR LEVEL SHALL BE
 VERIFIED BY A SIGNED AND SEALED
 ELEVATION CERTIFICATE.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-11-17 Cont ID  
Sent By dpalmer Date 2006-11-17 Time 12:54 Rev Time 0.00
Received By dpalmer Date 2006-11-17 Time 12:36 Sent To  
Notes
2006-11-17 12:55:19**** UNSAT *****
  
 1) NOTE: PLEASE SEE AS THE MAJORITY OF THE INSTALLATION
 OF THE WORK INVOLVED IS NOT ELECTRICAL. PLEASE SEE
 SCOPE APPEARS TO BE OUT OF THAT OF AN ELECTRICAL
 CONTRACTOR. PLEASE KNOW A CONTRACTOR LICENSED TO
 INSTALL THIS SIZE FUEL TANK CAN BE THE PRIME
 CONTRACTOR, AND THE ELECTRICAL CAN BE THE SUB FOR THE
 ELECTRICAL HOOK UP.
 ** PLEASE SEE COMMENTS FROM OTHER TRADES WITH RESPECT
 TO WHO CAN INSTALL ETC.
 PLEASE SEE FS 489.
  
 2) NOTE: PLEASE PROVIDE A COMPLETE LAYOUT FOR THE
 ENTIRE INSTALLATION OF THE ELECTRICAL SYSTEM INCLUDING
 ALL HAZARDOUS LOCATIONS, CLEARANCES HEIGHTS/ELEVATIONS
 ETC.
 PLEASE SEE FUEL DISPENSING IN THE NEC,514.
 PLEASE ALSO SEE COMMENTS FROM OTHER TRADES AS THIS IS A
 750 GAL UNIT. PLEASE SEE MINIMUM CLEARANCES REQUIRED
 FROM BUILDINGS ETC WHICH WILL BE IN OTHER REVIEW
 COMMENTS.
  
 3) NOTE: PLEASE KNOW, EVEN WHEN PLANS ARE NOT REQUIRED
 TO BE DONE BY ARCHITECT OR ENGINEER, THEY ARE REQUIRED
 TO CONTAIN A PRINTED NAME AND SIGNATURE FOR THE
 DESIGNS.
 PLEASE KNOW BASED ON SCOPE OF WORK AND REQUIREMENTS FOR
 WIND LOADS AND THE SPECIALIZED REQUIREMENTS SHOWN,
 PLANS WILL BE REQUIRED TO BE DONE BY AN ARCHITECT OR
 ENGINEER.
 FBC ADMIN SECTION 106.3.1.2(5).
 PLEASE SEE COMMENTS FROM OTHER REVIEWER(S) AS THESE
 WILL GREATLY AFFECT THE PLANS SUBMITTED.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
 **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF
 THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE
 DO NOT HESITATEIN CONTACTING THIS REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-12-27 Cont ID  
Sent By mawillia Date 2006-12-27 Time 15:12 Rev Time 0.00
Received By mawillia Date 2006-12-27 Time 15:12 Sent To  
Notes
2006-12-27 15:37:01*****DENIED*****
  
  
  
 1.THE INSTALLATION OF FUEL TANKS AND REFUELING
 PROCESSES SHALL COMPLY WITH NFPA 30.
  
 2.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE
 WITH EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY OR
 VICINITY THEROF.
  
 3.PROVIDE THE DISTANCE OF THE PROPOSED TANK TO THE
 BUILDING'S WINDOWS, DOORS, OPENINGS, ETC.
  
 4.PROVIDE FIRE PROTECTION APPLIANCE LOCATIONS I.E.
 FIRE EXTINGUISHER(S) EMERGENCY SHUT-OFF VALVE(S), ETC.
  
 5.HOW WILL VEHICLE IMPACT PROTECTION BE
 ACCOMPLISHED.
  
 6.PROVIDE ANY OTHER INFORMATION THAT MAY
 INSTRUMENTAL IN THIS FIRE PLAN REVIEW.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETEER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-12-27 Cont ID  
Sent By mawillia Date 2006-12-27 Time 15:11 Rev Time 0.00
Received By mawillia Date 2006-11-04 Time 16:57 Sent To  
Notes
2006-11-16 11:34:21TO "COMM" BD#44
2006-11-04 16:57:57WAITING FOR "COMM' BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-11-17 Cont ID  
Sent By pkrauss Date 2006-11-17 Time 13:43 Rev Time 0.00
Received By pkrauss Date 2006-11-17 Time 13:43 Sent To  
Notes
2006-11-17 13:54:43DENIED:
 1.INSTALLATION OF FUEL TANKS NEED APPROVAL FROM
 DEPARTMENT OF EVIRONMENTAL REGULATION.PLEASE SUBMIT
 PLANS AT 3323 BELVEDERE RD, BUILDING #502, TO THE
 ATTENTION OF CHIP GREEN.YOU MAY CONTACT MR. GREEN AT
 233-2400 PRIOR TO SUBMITTAL OF PLANS.PLEASE RESUBMIT
 PLANS FOR REVIEW AFTER APPROVAL FROM DERM.
  
 2.PLEASE PROVIDE ANCHORING DETAIL SHOW COMPLIANCE
 WITH 2004 FMC 301.13.
  
 3.PLEASE INDICATE LOCATION OF FUEL TANKS IN RELATION
 TO BUILDINGS, WINDOWS, DOORS FRESH AIR INTAKES &
 PROPERTY LINES.SURVEY PROVIDED INDICATES PROPOSED
 TANKS ON THE RAISED CURB.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected].

Review Stop Z ZONING
Rev No 1 Status F Date 2006-12-05 Cont ID  
Sent By lfranco Date 2006-12-05 Time 16:49 Rev Time 0.00
Received By lfranco Date 2006-12-05 Time 15:11 Sent To I
Notes
2006-12-05 18:19:37PLANNING AND ZONING:***** FAILED *******
  
  
 1.PROVIDE RESPONSES TO COMMENTS IN WRITING.
  
 2.A MINOR AMENDMENT TO THE RESIDENTIAL PLANNED
 DEVELOPMENT (RPD), MASTER PLAN WILL BE REQUIRED. AN
 APPLICATION WILL NEED TO BE FILED TO THE PLANNING AND
 ZONING DEPARTMENT AND APPROVED PRIOR TO SIGN-OFF OF
 BUILDING PERMIT.THE COMMENTS BELOW REFLECT THE
 INFORMATION NEEDED ON SITE PLAN, PRIOR TO SUBMITTAL OF
 THE MINOR AMENDMENT TO THE RESIDENTIAL PLANNED
 DEVELOPMENT.
  
 3. PROVIDE A DETAIL, WITH DIMENSIONS OF THE AREA WHERE
 THE FUEL TANK IS PROPOSED.
  
 THE SITE PLAN SHALL INCLUDE THE FOLLOWING:
  
 A. SCREENING AND ELEVATION OF WALL/HEDGES AROUNDFUEL
 TANK, AND SETBACK DISTANCE FROM PROPERTY LINE.
  
 4.PURSUANT TO SECTION 94-444(B) OPEN SPACE
 STANDARDS:
  
 (B) FUEL OR OIL OR PROPANE TANKS, GENERATORS SHALL NOT
 BE PERMITTED UNLESS APPROPRIATE SCREENING IS
 PROVIDED. SCREENING SHALL BE CONSTRUCTED OF BRICK,
 DECORATIVE CONCRETE, OTHER DECORATIVE MASONRY, OR
 COMPARABLY DURABLE WOOD AND STEEL.
  
 WALLS SHALL BE LANDSCAPED WITH SHRUBS AND HEDGES
 PLANTED AT TWO-FOOT INTERVALS.A FOUR-SIDED ENCLOSURE
 WITH MASONRY, OR COMPARABLY DURABLE WOOD AND STEEL, AN
 OBSCURING GATE IS REQUIRED AS A CONDITION FOR SITE PLAN
 APPROVAL.
  
 THE SCREENING SHALL ENCLOSE BOTH FUEL TANK INCLUDING
 ROOFTOP EXHAUST.
  
 5.PURSUANT TO SECTION 94-305(B)(4) SETBACKS (B)(4)
 SETBACK ENCROACHMENT:
 MECHANICAL EQUIPMENT SHALL NOT PROJECT MORE THAN 4 FEET
 INTO A SETBACK.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME AT THE
 NUMBER BELOW.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1435