2006-11-28 12:03:35 | BUILDING PLAN REVIEW |
| PERMIT: 06110087 |
| ADD: 3199 CUMBERLAND DR |
| CONT: DCS ELECTRIC |
| TEL: (561)7224690 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1STREVIEW |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2 ) FL S S 713.13 |
| NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT BEFORE A |
| PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| IF THE WORK DESCRIBED IN THE NOTICE OF |
| COMMENCEMENT IS NOT ACTUALLY COMMENCED |
| WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. |
| |
| 3) DCS ELECTRIC HAAS A EC STATE LICENSE, WHEN THE |
| MAJORITY OF THE WORK IS NOT ELECTRIC, THE "PRIME PERMIT |
| " HAS TO BE SIGNED BY EITHER A POLLUTANT STORAGE |
| SYSTEMS CONTRACTOR OR IF GASOLINE A MECHANICAL |
| CONTRACTOR. |
| 489.105 |
| I)"MECHANICAL CONTRACTOR" MEANS A CONTRACTOR WHOSE |
| SERVICES ARE UNLIMITED IN THE EXECUTION OF CONTRACTS |
| REQUIRING THE EXPERIENCE, KNOWLEDGE, AND SKILL TO |
| INSTALL, MAINTAIN, REPAIR, FABRICATE, ALTER, EXTEND, OR |
| DESIGN, WHEN NOT PROHIBITED BY LAW, CENTRAL |
| AIR-CONDITIONING, REFRIGERATION, HEATING, AND |
| VENTILATING SYSTEMS, INCLUDING DUCT WORK IN CONNECTION |
| WITH A COMPLETE SYSTEM ONLY TO THE EXTENT SUCH DUCT |
| WORK IS PERFORMED BY THE CONTRACTOR AS IS NECESSARY TO |
| MAKE COMPLETE AN AIR-DISTRIBUTION SYSTEM, BOILER AND |
| UNFIRED PRESSURE VESSEL SYSTEMS, LIFT STATION EQUIPMENT |
| AND PIPING, AND ALL APPURTENANCES, APPARATUS, OR |
| EQUIPMENT USED IN CONNECTION THEREWITH, AND ANY DUCT |
| CLEANING AND EQUIPMENT SANITIZING WHICH REQUIRES AT |
| LEAST A PARTIAL DISASSEMBLING OF THE SYSTEM; TO |
| INSTALL, MAINTAIN, REPAIR, FABRICATE, ALTER, EXTEND, OR |
| DESIGN, WHEN NOT PROHIBITED BY LAW, PIPING, INSULATION |
| OF PIPES, VESSELS AND DUCTS, PRESSURE AND PROCESS |
| PIPING, PNEUMATIC CONTROL PIPING, GASOLINE TANKS AND |
| PUMP INSTALLATIONS AND PIPING FOR SAME, STANDPIPES, AIR |
| PIPING, VACUUM LINE PIPING, OXYGEN LINES, NITROUS OXIDE |
| PIPING, INK AND CHEMICAL LINES, FUEL TRANSMISSION |
| LINES, LIQUEFIED PETROLEUM GAS LINES WITHIN BUILDINGS, |
| AND NATURAL GAS FUEL LINES WITHIN BUILDINGS; TO |
| REPLACE, DISCONNECT, OR RECONNECT POWER WIRING ON THE |
| LOAD SIDE OF THE DEDICATED EXISTING ELECTRICAL |
| DISCONNECT SWITCH; TO INSTALL, DISCONNECT, AND |
| RECONNECT LOW VOLTAGE HEATING, VENTILATING, AND |
| AIR-CONDITIONING CONTROL WIRING; AND TO INSTALL A |
| CONDENSATE DRAIN FROM AN AIR-CONDITIONING UNIT TO AN |
| EXISTING SAFE WASTE OR OTHER APPROVED DISPOSAL OTHER |
| THAN A DIRECT CONNECTION TO A SANITARY SYSTEM. THE |
| SCOPE OF WORK FOR SUCH CONTRACTOR SHALL ALSO INCLUDE |
| ANY EXCAVATION WORK INCIDENTAL THERETO, BUT SHALL NOT |
| INCLUDE ANY WORK SUCH AS POTABLE WATER LINES OR |
| CONNECTIONS THERETO, SANITARY SEWER LINES, SWIMMING |
| POOL PIPING AND FILTERS, OR ELECTRICAL POWER WIRING. |
| |
| P)"POLLUTANT STORAGE SYSTEMS CONTRACTOR" MEANS A |
| CONTRACTOR WHOSE SERVICES ARE LIMITED TO, AND WHO HAS |
| THE EXPERIENCE, KNOWLEDGE, AND SKILL TO INSTALL, |
| MAINTAIN, REPAIR, ALTER, EXTEND, OR DESIGN, WHEN NOT |
| PROHIBITED BY LAW, AND USE MATERIALS AND ITEMS USED IN |
| THE INSTALLATION, MAINTENANCE, EXTENSION, AND |
| ALTERATION OF, POLLUTANT STORAGE TANKS. ANY PERSON |
| INSTALLING A POLLUTANT STORAGE TANK SHALL PERFORM SUCH |
| INSTALLATION IN ACCORDANCE WITH THE STANDARDS ADOPTED |
| PURSUANT TO S. 376.303. |
| |
| 4) PLEASE PROVIDE THE LOCATION OF THIS UNIT WITH THE |
| LOCATION OF THE STRUCTURE, LOCATE ALL WINDOWS, DOORS , |
| AND SOFFIT VENTS, PROVIDE THE DISTANCE AWAY FROM THE |
| FUEL TANK TO THE STRUCTURE.ALSO INDICATE WHAT THIS IS A |
| FUEL TANK TOO? |
| |
| 5) PROVIDE HOW THE FUEL TANK WILL BE BOLTED DOWN TO |
| RESIST THE MOMENT OF OVERTURNING. |
| 1609.1.3 ANCHORAGE AGAINST OVERTURNING , UPLIFT AND |
| SLIDING. |
| STRUCTURAL MEMBERS AND SYSTEMS AND COMPONENTS AND |
| CLADDING IN A BUILDING OR STRUCTURE SHALL BE ANCHORED |
| TO RESIST WIND-INDUCED OVERTURNING , UPLIFT AND SLIDING |
| AND TO PROVIDE CONTINUOUS LOAD PATHS FOR THESE FORCES |
| TO THE FOUNDATION. WHERE A PORTION OF THE RESISTANCE TO |
| THESE FORCES IS PROVIDED BY DEAD LOAD, THE DEAD LOAD, |
| INCLUDING THE WEIGHT OF SOILS AND FOUNDATIONS, SHALL BE |
| TAKEN AS THE MINIMUM DEAD LOAD LIKELY TO BE IN PLACE |
| DURING A DESIGN WIND EVENT. WHERE THE ALTERNATE BASIC |
| LOAD COMBINATIONS OF SECTION 1605.3.2 ARE USED, ONLY |
| TWO-THIRDS OF THE MINIMUM DEAD LOAD LIKELY TO BE IN |
| PLACE DURING A DESIGN WIND EVENT SHALL BE USED. |
| |
| 6)NOTE, PROVISO: THE TANK IS ALSO LOCATED IN A A-8 |
| FLOOD ZONE, |
| THE FINISHED FLOOR LEVEL SHALL BE |
| VERIFIED BY A SIGNED AND SEALED |
| ELEVATION CERTIFICATE. |
| |
| BUILDING PLAN REVIEW |