Plan Review Details - Permit 06101087
Plan Review Stops For Permit 06101087 |
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2006-11-17 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-11-17 |
Time |
13:48 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-11-17 |
Time |
13:48 |
Sent To |
M |
|
Notes |
2006-11-17 13:48:25 | TO "M" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2006-11-03 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2006-11-03 |
Time |
11:19 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2006-11-01 |
Time |
17:14 |
Sent To |
|
|
Notes |
2006-11-01 17:15:07 | TO "M" BOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2006-12-27 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2006-12-27 |
Time |
15:54 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2006-12-27 |
Time |
15:54 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2006-11-29 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2006-11-29 |
Time |
07:09 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2006-11-29 |
Time |
07:08 |
Sent To |
|
|
Notes |
2006-11-29 07:32:54 | PROVISO: | | 1.PLAN SHEET M-1 NOTE 3 INDICATES THE RETURN AIR TO | | BE DUCTED.THE DUCT LAYOUT INDICATES TRANSFER GRILLES | | WITH THE RETURN AIR GRILLE IS DIRECTRLY UNDER THE AHU. | | PLEASE NOTE,THE ATTIC SHALL NOT SERVE AS A RETURN AIR | | PLENUM.THE PLANS DO NOT REFLECT THE RETURN AIR BEING | | DUCTED FROM THE BOTTOM.HOW WILL THIS BE DONE WITH THE | | UNISTRUT AND DRAIN PAN THIS UNDER THE AHU.IF THE | | RETURN AIR IS DUCTED PLEASE PROVIDE A REVISION SHOWING | | LAYOUT, THE GRILLE AND DUCT SIZES.PLEASE PROVIDE A | | REVISION PRIOR TO INSPECTION. | | | | 2.ACCESS TO THE AHU SHALL COMPLY WITH 2004 FMC | | 306.3. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS | | AT (561)805-6719 OR E-MAIL [email protected]. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2006-11-03 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2006-11-03 |
Time |
09:15 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2006-11-03 |
Time |
08:54 |
Sent To |
|
|
Notes |
2006-11-03 10:28:04 | DENIED: | | 1.PLEASE INDICATE IF THE AHU IS ABOVE THE CEILING OR | | IN A CLOSET.THE PLAN SHOWS A 24"X24" RAF 6" AFF | | WHICH WOULD INDICATE THE AHU IS IN A CLOSET.HOW DO | | YOU ENTER THE BEDROOM AREA THROUGH THE AHU CLOSET OR IS | | THE BEDROOM DOOR MISSING, PLEASE CLARIFY.THE | | APPROVED ARCHITECTURAL PLANS INDICATE AHU IS IN THE | | ATTIC. | | | | 2.PROVIDE HANGING DETAIL FOR HORIZONTAL INSTALLATION | | OR A SUPPORT DETAIL FOR A VERTICAL UNIT. | | | | 3.PLEASE INDICATE IF THE RETURN AIR IS DUCTED OR IF | | THE CLOSET OR CEILING IS A PLENUM.PLEASE NOTE PER | | 2004 FMC 602.2.1,MATERIALS EXPOSED IN A PLENUM SHALL | | BE NON-COMBUSTIBLE . | | | | 4.PLAN STATES EXHAUST FAN NOT REQUIRED, OPERABLE | | WINDOW EXCEPTION (2004 FMC 402.3.1) WILL BE TAKEN. | | PLEASE NOTE, 3 SQUARE FEET OF CLEAR OPENING IS REQUIRED | | TO TAKE THIS EXCEPTION. | | | | 5.12"X8" TRANSFER GRILL FOR THE MASTER BEDROOM IS NOT | | SIZED IN ACCORDANCE WITH 2004 FMC EXCEPTION 2 & 3. | | | | 6.PLEASE PROVIDE A COPY OF THE APPROVED ENERGY | | CALCULATIONS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS | | AT (561)805-6719 OR E-MAIL [email protected]. |
|
|
|