Plan Review Details - Permit 06101087
Plan Review Stops For Permit 06101087
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-11-17 Cont ID  
Sent By adarroug Date 2006-11-17 Time 13:48 Rev Time 0.00
Received By adarroug Date 2006-11-17 Time 13:48 Sent To M
Notes
2006-11-17 13:48:25TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-11-03 Cont ID  
Sent By pkrauss Date 2006-11-03 Time 11:19 Rev Time 0.00
Received By pkrauss Date 2006-11-01 Time 17:14 Sent To  
Notes
2006-11-01 17:15:07TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-12-27 Cont ID  
Sent By pkrauss Date 2006-12-27 Time 15:54 Rev Time 0.00
Received By pkrauss Date 2006-12-27 Time 15:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-11-29 Cont ID  
Sent By pkrauss Date 2006-11-29 Time 07:09 Rev Time 0.00
Received By pkrauss Date 2006-11-29 Time 07:08 Sent To  
Notes
2006-11-29 07:32:54PROVISO:
 1.PLAN SHEET M-1 NOTE 3 INDICATES THE RETURN AIR TO
 BE DUCTED.THE DUCT LAYOUT INDICATES TRANSFER GRILLES
 WITH THE RETURN AIR GRILLE IS DIRECTRLY UNDER THE AHU.
 PLEASE NOTE,THE ATTIC SHALL NOT SERVE AS A RETURN AIR
 PLENUM.THE PLANS DO NOT REFLECT THE RETURN AIR BEING
 DUCTED FROM THE BOTTOM.HOW WILL THIS BE DONE WITH THE
 UNISTRUT AND DRAIN PAN THIS UNDER THE AHU.IF THE
 RETURN AIR IS DUCTED PLEASE PROVIDE A REVISION SHOWING
 LAYOUT, THE GRILLE AND DUCT SIZES.PLEASE PROVIDE A
 REVISION PRIOR TO INSPECTION.
  
 2.ACCESS TO THE AHU SHALL COMPLY WITH 2004 FMC
 306.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected].

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-11-03 Cont ID  
Sent By pkrauss Date 2006-11-03 Time 09:15 Rev Time 0.00
Received By pkrauss Date 2006-11-03 Time 08:54 Sent To  
Notes
2006-11-03 10:28:04DENIED:
 1.PLEASE INDICATE IF THE AHU IS ABOVE THE CEILING OR
 IN A CLOSET.THE PLAN SHOWS A 24"X24" RAF 6" AFF
 WHICH WOULD INDICATE THE AHU IS IN A CLOSET.HOW DO
 YOU ENTER THE BEDROOM AREA THROUGH THE AHU CLOSET OR IS
 THE BEDROOM DOOR MISSING, PLEASE CLARIFY.THE
 APPROVED ARCHITECTURAL PLANS INDICATE AHU IS IN THE
 ATTIC.
  
 2.PROVIDE HANGING DETAIL FOR HORIZONTAL INSTALLATION
 OR A SUPPORT DETAIL FOR A VERTICAL UNIT.
  
 3.PLEASE INDICATE IF THE RETURN AIR IS DUCTED OR IF
 THE CLOSET OR CEILING IS A PLENUM.PLEASE NOTE PER
 2004 FMC 602.2.1,MATERIALS EXPOSED IN A PLENUM SHALL
 BE NON-COMBUSTIBLE .
  
 4.PLAN STATES EXHAUST FAN NOT REQUIRED, OPERABLE
 WINDOW EXCEPTION (2004 FMC 402.3.1) WILL BE TAKEN.
 PLEASE NOTE, 3 SQUARE FEET OF CLEAR OPENING IS REQUIRED
 TO TAKE THIS EXCEPTION.
  
 5.12"X8" TRANSFER GRILL FOR THE MASTER BEDROOM IS NOT
 SIZED IN ACCORDANCE WITH 2004 FMC EXCEPTION 2 & 3.
  
 6.PLEASE PROVIDE A COPY OF THE APPROVED ENERGY
 CALCULATIONS.
  