2006-11-03 11:32:03 | UNSAT |
| REFERENCE: FBC-2004 FUEL GAS |
| |
| THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN |
| REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. (NOTE: THE SUBMITTED DRAWING IS NOT AN |
| ISOMETRIC AND DOES NOT INDICATE ALL CUT SECTIONS OF |
| PIPE OR CORRESPONDING LENGTHS. PLEASE SEE THE ISOMETRIC |
| EXAMPLE OF THE SUBMITTED GAS SYSTEM WITH THE PROVIDED |
| INFORMATION. PLEASE PROVIDE ALL ABOVE GROUND PIPE |
| LENGTHS AND INDICATE THE EXISTING GAS WITH MP |
| REGULATORS TO SAID RESIDENCE. PLEASE REFERENCE THE |
| ATTACHED PERMIT INFORMATION INDICATING THAT SAID |
| ADDRESS HAS GAS.) |
| |
| 2. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. (NOTE: PLEASE |
| INDICATE ALL ABOVE GROUND MATERIAL TYPES.) |
| |
| 3. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33). (NOTE: SAID ADDRESS HAS EXISTING GAS, PLEASE |
| PROVIDE EXISTING BTU LOAD.) |
| |
| 4. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). (NOTE: PLEASE PROVIDE THE |
| EXISTING SYSTEMS LONGEST LENGTH) |
| |
| END OF COMMENTS: |
| |