Plan Review Details - Permit 06101031
Plan Review Stops For Permit 06101031
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-03-06 Cont ID  
Sent By mjacobs Date 2007-03-06 Time 17:06 Rev Time 0.00
Received By mjacobs Date 2007-03-06 Time 17:06 Sent To PC
Notes
2007-03-06 17:07:47ENGINEERING FOR LIGHT POLES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-02-26 Cont ID  
Sent By mjacobs Date 2007-02-26 Time 16:26 Rev Time 0.00
Received By mjacobs Date 2007-02-24 Time 14:00 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-02-13 Cont ID  
Sent By mjacobs Date 2007-02-13 Time 10:04 Rev Time 0.00
Received By mjacobs Date 2007-02-13 Time 07:43 Sent To PC
Notes
2007-02-13 09:39:49BUILDING PLAN REVIEW
 PERMIT: 06101031
 ADD:2501 N.FLAGLER DR.
 CONT:G.A. RAY INC.
 TEL: (561)630-4861
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)F.A.C. 61G15-23.002A COVER OR INDEX SHEET FOR
 ENGINEERING SPECIFICATIONS MAY BE USED AND THAT SHEET
 MUST BE SIGNED, SEALED AND DATED BY THE ENGINEER IN
 RESPONSIBLE CHARGE OF THE PRODUCTION AND PREPARATION OF
 EACH SECTION OF THE ENGINEERING SPECIFICATION WITH
 SUFFICIENT INFORMATION ON THE COVER SHEET OR INDEX SO
 THAT THE WILL BE AWARE OF EACH PORTION OF THE
 SPECIFICATIONS FOR WHICH EACH PROFESSIONAL ENGINEER IS
 RESPONSIBLE. (INDICATE EACH PAGE ON THE COVER OR INDEX
 SHEET)
  
 3) THE ASCE REFERENCE STANDARD (ASCE 7-04) STATED IN
 THE ENGINEERING REPORT FOR THE LIGHT POLE IS INCORRECT.
 SEE FBC. 35.6R FOR MORE INFORMATION.
  
 4)2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-01-23 Cont ID  
Sent By mjacobs Date 2007-01-23 Time 10:50 Rev Time 0.00
Received By mjacobs Date 2007-01-23 Time 06:38 Sent To  
Notes
2007-01-23 10:50:25BUILDING PLAN REVIEW
 PERMIT: 0610
 ADD:
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)CLARIFY THE TOTAL NUMBER OF PARKING SPACES
 AVAILABLE. THE SPACES ON THE DRAWINGS DOES NOT MATCH
 THE NUMBER INDICATED ON SHEET A-1.00.
  
 3)FBC 11-4.6.3 PARKING ACCESS AISLES MUST BE NO LESS
 THAN 5 FEET WIDE AND MUST BE PART OF AN ACCESSIBLE
 ROUTE TO THE BUILDING OR FACILITY ENTRACE. TWO
 ACCESSIBLE SPACES MAY SHARE A COMMON ACCESS AISLE {SEE
 FIG 9(A)}. THE ACCESS AISLE SHALL BE STRIPED DIAGONALLY
 TO DESIGNATE IT AS A NO-PARKING ZONE. CURB RAMPS MUST
 BE LOCATED OUTSIDE OF THE DISABLED PARKING SPACES AND
 ACCESS AISLES.
  
 4)WPB AMENDMENTS. 106.1.3THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENTAL POLICY, STANDARDS FOR
 PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE
 CONFORMITY TO ITS RECORD AND RETENTION PROGRAM. THIS
 POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIXE, SHAPE,
 CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 MANAGEMENT. SOME OF THE PRODUCT APPROVALS SUBMITTED ARE
 ILLEGIBLE. SEE PRODUCT #S 05-0902.01 AND 05-1012.04.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-01-08 Cont ID  
Sent By mjacobs Date 2007-01-08 Time   Rev Time 0.00
Received By mjacobs Date 2007-01-08 Time 07:30 Sent To  
Notes
2007-01-08 09:57:26BUILDING PLAN REVIEW
 PERMIT:06101031
 ADD: 2501 N. FLAGLER DR.
 CONT: G.A. RAY INC.
 TEL: (561)630-4861
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST.
 ACTION: DENIED
  
  
 1) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2)PROVIDE A DEMO FLOOR PLAN SHOW THE EXISTING AND
 PROPOSED PLAN. SUBMIT A LEGEND SHOWING WHICH WALLS
 WILL BE REMOVED.
  
 3)A DETAIL DRAWING OF THE DRYWALL CEILING IS REQUIRED
 SHOWING ALL MATERIALS WIHIC WILL BE USED TO HOLD THE
 DRYWALL CEILINGS IN PLACE. WPB. AMEND.106.1.2
 ADDITIONAL DATA. THE
 BUILDING OFFICIAL MAY REQUIRE DETAILS, COMPUTATIONS,
 STRESS DIAGRAMS, AND OTHER
 DATA NECESSARY TO DESCRIBE THE
 CONSTRUCTION OR INSTALLATION AND THE
 BASIS OF CALCULATION. ALL DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 REQUIRED BY THE BUILDING OFFICIAL TO BE
 PREPARED BY AN ARCHITECT OR ENGINEER
 SHALL BE AFFIXED WITH THIER OFFICIAL
 SEAL, SIGNATURE AND DATE AS STATE LAW
 REQUIRES.
  
 4) INDICATE THE CLEAR FLOOR SPACE ON THE DRAWINGS FOR
 THE LAVATORIES AND WATER CLOSETS. SEE SECTIONS 11-4.19
 AND 11-4.16.
  
 5)ON THE PRODUCT APPROVAL FOR THE SHUTTERS HI-LIGHT
 OR CIRCLE THE ITEMS WHICH WILL BE USED. THE ANCHOR
 SCHEDULE SHALL ALSO BE HI-LIGHED OR CIRCLE INDICATING
 THE TYPE OF FASTENERS TO BE USED. NOTE: A SHUTTER
 SCHEDULE IS IN THE PACKAGE. EITHER FILL IT OUR OR
 PROVIDE A SIMILAR SCHEDULE WITH ALL REQUIRED
 INFORMATION.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-11-07 Cont ID  
Sent By alange Date 2006-11-07 Time 10:22 Rev Time 0.00
Received By alange Date 2006-11-07 Time 09:56 Sent To  
Notes
2006-11-07 10:25:57DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE AND A COPY
 SUBMITTED TO THIS OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE RE-RECORDED IF
 THE DESCRIBED IMPROVEMENT OR CONSTRUCTION IS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING.
  
 2.SUBMIT A LIFE SAFTEY PLAN.
  
 3. SHOW AN ELEVATION OF THE RECEPTION COUNTER AND
 SHOW COMPLIANCE WITH FBC 11-7.
  
 4.ALL PRODUCT APPROVALS SUBMITTED WITH QUALITY
 ASSURANCE SHALL HAVE THE FOLLOWING STATE APPROVAL
 ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL SHEETS THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM THE STATE. IF
 THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT AN
 APPLICATION FOR LOCAL PRODUCT APPROVAL OR SITE SPECIFIC
 FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 5.THOSE PRODUCT APPROVALS WHICH ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.WPB AMENDMENT TO FBC 106.3.3.
  
  
 6.A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE OR
 A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.SHOW HOW PLANS
 WILL COMPLY WITH THE SECTION(S) SELECTED.2004 FBC
 EXISTING BUILDING 301.5
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. SUBMIT ONE
 COPY OF OLD PAGES FOR REFERENCE . A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DEPARTMENT
 561-805-6672
  
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-02-18 Cont ID  
Sent By dpalmer Date 2007-02-18 Time 15:50 Rev Time 0.00
Received By dpalmer Date 2007-02-18 Time 15:50 Sent To  
Notes
2007-02-18 15:51:27REDLINED OLD LS PLANS TO SE REVISED LIGHTING ON E-1 AND
 NEW LS SHEETS.
 STAMPED ELECTRICAL.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-02-11 Cont ID  
Sent By dpalmer Date 2007-02-11 Time 13:33 Rev Time 0.00
Received By dpalmer Date 2007-02-11 Time 12:29 Sent To  
Notes
2007-02-11 13:34:16*** UNSAT 4TH REVIEW***
  
 ** PLEASE SEE NOTES FROM PREVIOUS REVIEWS WHICH STILL
 NEED TO BE ADDRESSED ALONG WITH NEW NOTES AS STATED
 BELOW.
  
  
 1) NOTE: PLEASE SEE IN ALL PREVIOUS REVIEWS IT WAS
 REQUESTED THAT ALL OLD/VOIDED SHEETS BE REMOVED FROM
 SETS AND TO INSERT NEW REVISED SHEETS INTO SETS, PLEASE
 INSERT NEW SHEETS AND ATTACH INTO SETS. PLEASE DO NOT
 ONLY INSERT SHEET LOOSELY INTO SETS.
 THIS WILL HELP IN PROCESSING THE PLANS FOR PERMITTING.
  
 2) NOTE: PLEASE SEE THE ORIGINAL REVIEW REQUESTED
 ENERGY CALCULATIONS AND PERFORMANCE CALCULATIONS WHICH
 MET THE 2004 FBC AND CHAPTER 13. THESE WERE SUBMITTED
 FOR REVIEW FOR THE 2ND REVIEW AND 3RD REVIEW WHICH
 NOTES REQUESTED FOR COMPLIANCE AND FOR ALL CALCULATIONS
 TO CORRELATE WITH THE PLANS SUBMITTED AND THERE WERE
 SUBSTANTIAL DIFFERENCES IN THE NUMBER OF FIXTURES,
 LOADS, WATTAGE(S), ETC.
 PLEASE SEE THAT THIS COMMENT IS STILL BEING MADE AS THE
 ENERGY CALCULATIONS DO NOT CORRELATE WITH PLANS OR
 FIXTURE LEGEND FOR FIXTURES, NUMBER OF FIXTURES,
 WATTAGES OF FIXTURES ETC.
 PLEASE SEE THERE ARE SEVERAL ITEMS WHICH DO NOT MATCH.
 PLEASE SEE OUTSIDE/EXTERIOR FIXTURES, PLEASE SEE
 INTERIOR FIXTURES ETC
 PLEASE SEE ALL.
 THE TOTALS DO NOT CORRELATE, TOTALS ON SOME OF THE
 FIXTURES ON FIXTURE LEGEND DOES NOT MATCH WITH PLANS
 AND # OF FIXTURES AS SHOWN. ETC.
 THIS WAS STATED IN ALL REVIEWS AFTER THE 1ST REVIEW AS
 THESE WERE SUBMITTED ON THE FIRST REVIEW WHICH WAS
 STILL REQUIRED UNDER THE 2004 FBC.
 PLEASE SEE THAT A METHOD A IS STILL BEING SHOWN,
 HOWEVER IT IS NOT CLEAR HOW THIS IS BEING USED WHEN
 THIS IS FOR TOTAL BUILDING COMPLIANCE AND OTHER AREAS
 AND TRADES OFFS ARE NOT BEING SHOWN OR INDICATED.
 (PREVIOUS REVIEWS).
 PLEASE SEE THE ELECTRICAL PLANS FOR FIXTURES WERE
 REVISED TO DELETE MANY FIXTURES HOWEVER THE
 ARCHITECTURAL AND LIFE SAFETY SHEETS WERE NOT REVISED
 TO REFLECT THESE CHANGES.
 PLEASE SEE FBC 2004 13-415.1.AB.1.
 PLEASE SEE 13-415.2.
  
 3) NOTE: PLEASE SEE THE WIND LOADS SEEMS TO BE OK,
 HOWEVER WILL BE REVIEWED BY THE STRUCTURAL REVIEWER.
 PLEASE SEE THE ELECTRICAL SHEETS STILL NOT INDICATE ANY
 REFERENCE TO THE 140MPH WIND LOAD REQUESTED ON PREVIOUS
 REVIEW.
  
 ** NEW NOTES DUE TO PLANS SUBMITTED AND CHANGES WHICH
 WERE NOT ON PREVIOUS PLANS.
  
 3) NOTE: PLEASE SEE RISER NOW SHOWS *EQUIPMENT
 GROUNDING CONDUCTORS FROM THE GUTTER TO THE FIRST MEANS
 OF DISCONNECT IS NOT PERMITTED PER 250.6.
 PLEASE SEE THE PREVIOUS COMMENTS REQUESTED TO SHOW THE
 CONDUCTORS FROM THE GUTTER TO EACH MAIN AND FOR *
 EQUIPMENT GROUNDING CONDUCTORS* AFTER THE FIRST MEANS
 OF DISCONNECT.
 PLEASE SEE 250.6 AND 250.24B AS THIS NOW CREATES
 OBJECTIONABLE CURRENTS BY PARALLELING THE NEUTRAL.
 PLEASE SEE THIS WOULD HAVE BEEN REDLINED, HOWEVER AS
 PLANS ARE COMING BACK FOR COMMENT #2, PLEASE CORRECT AT
 THIS TIME.
  
 4) NOTE: PLEASE SEE AS COMMENT #2 HAS BEEN REPEATED FOR
 CODE COMPLIANCE REVIEW THREE OR MORE TIMES FOR THE SAME
 CODE COMPLIANT COMMENT AND IT IS NECESSARY FOR THIS
 OFFICE TO REJECT PLANS FOR THIS, THE FS 553.80(2)(B) IS
 IN EFFECT AND A 4X FEE FOR THE PLAN REVIEW PORTION OF
 THE PERMIT FEE HAS NOW BEEN ASSESSED.
 THIS FEE IS A REQUIRED FEE PER THE FLORIDA STATUTES TO
 THE DESIGNER(S) OF RECORD AND MUST BE PAID BEFORE PLANS
 CAN BE RESUBMITTED FOR REVIEW.
 PLEASE SEE THAT ONE SET OF EACH ELECTRICAL PLAN AND
 ENERGY CALCULATIONS ARE BEING RETAINED BY THIS OFFICE.
 ONE SET OF THE ARCHITECTURAL AND LS PLANS MAY ALSO BE
 RETAINED.
 THE AMOUNT OF $1620 WILL BE DUE BEFORE PLANS CAN BE
 RESUBMITTED.
  
 ** IT IS RECOMMENDED THAT COMMENT #2 BE REVIEWED AND
 GONE THROUGH THOROUGHLY.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-01-21 Cont ID  
Sent By dpalmer Date 2007-01-21 Time 12:50 Rev Time 0.00
Received By dpalmer Date 2007-01-21 Time 12:11 Sent To  
Notes
2007-01-21 12:50:23** UNSAT 3RD REVIEW **
  
  
 ** PLEASE SEE SOME COMMENTS FROM THE PREVIOUS REVIEW
 ARE STILL IN NEED OF ADDRESSING ALONG WITH NEW COMMENTS
 BASED ON A COMPLETELY NEW ELECTRICAL RISER DIAGRAM
 BEING SUBMITTED.
  
  
 1) NOTE: PLEASE SEE THE PLANS NOW HAVE THE SITE
 LIGHTING FIXTURES AND CIRCUITS REMOVED WHEN BOTH THE
 PREVIOUS REVIEWS INDICATED THESE. PLEASE SEE ENERGY
 CALCULATIONS ARE STILL INDICATING THESE TO BE
 INSTALLED.
 PLEASE SEE THAT PLANS MUST SHOW THESE, POLE DETAIL,
 CIRCUITS, AND APPROPRIATE WIND LOADS.
 PLEASE KNOW ANY SHOP PLANS FOR THE POLES MAY BE
 SUBMITTED AT A LATER DATE AS A *PROVISO*; HOWEVER THE
 BASE INFORMATION ABOVE MUST BE SHOWN. (IF THESE ARE
 GOING TO BE DONE)??
 FBC 106.1.2, 106.3.5.1.2
 408.4, 310.16, 240.4 ETC.
 THIS WAS A COMMENT ON PREVIOUS REVIEW.
  
 2) NOTE: PLEASE SEE PREVIOUS NOTE MENTIONED THAT THE
 ENERGY CALCULATIONS DID NOT CORRELATE WITH THE
 ELECTRICAL FIXTURES AND LIGHTING AS SHOWN ON PLANS.
 THIS IS STILL THE CASE. PLEASE SEE THE AMOUNT AND TYPE
 OF FIXTURES AS SHOWN ON PLANS FAR EXCEED THAT OF ENERGY
 CALCULATIONS.
 PLEASE SEE 13-415.1.AB.1.1.
 PLEASE SEE CHAPTER 13, ALL, AS COMPLIANCE MUST BE MET
 FOR ALL AREAS. 106.1.2, 106.3.5.1.2
 THIS WAS THE SAME COMMENT ON PREVIOUS REVIEW.
 ** PLEASE KNOW AS THE COMMENT IS BEING REPEATED AND
 COMPLIANCE IS NOT BEING MET, PLEASE SUBMIT A COMPLETE
 FIXTURE LEGEND AND CORRELATE WITH ALL FIXTURE
 DESIGNATIONS ON PLANS.
 106.1.2, 106.3.5.1.2
  
 3) NOTE: PLEASE SEE 220.12, 220 AS STATED ON THE
 PREVIOUS REVIEW FOR TRACK LIGHTING LOADS AND HOW AND
 WHERE THESE ARE BEING FIGURED INTO CALCULATIONS.
  
 4) NOTE: PLEASE SEE RISER HAS BEEN COMPLETELY REVISED.
 PLEASE INCLUDE MISSING CONDUCTOR FROM METER TO GUTTER
 AND FROM GUTTER TO EACH OF THE NEW MAIN DISCONNECTS AS
 NOW SHOWN.
 240.4, 310.16, ETC.
 FBC 106.1.2 AND 106.3.5.1.2 ADMIN SECTIONS.
  
 5) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTORS FROM NEW MAINS TO PANELS. PLEASE KNOW EVEN
 AS THE USE OF EMT IS BEING SHOWN, UNLESS THE NEW LISTED
 CONNECTORS RATED FOR *EQUIPMENT GROUNDING * IS BEING
 USED AND EQUIPMENT GROUNDING CONDUCTOR SIZED PER
 250.122 SHALL BE INSTALLED.
 *THIS WOULD HAVE BEEN REDLINED IF THIS WERE THE ONLY
 COMMENT.
  
 6) NOTE: PLEASE SEE AS THE RISER IS NOW SHOWING A NEW
 PANEL *B*, THE PLANS DO NOT INCLUDE THIS? PLEASE SHOW
 THE LOCATION OF THE NEW PANEL WHICH IS NOW ADDED.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-01-05 Cont ID  
Sent By dpalmer Date 2007-01-05 Time 20:28 Rev Time 0.00
Received By dpalmer Date 2007-01-05 Time 19:21 Sent To  
Notes
2007-01-05 20:28:58** UNSAT **
  
  
 1) NOTE: PLEASE CORRELATE ELECTRICAL AND BUILDING
 PLANS.
 PLEASE SEE THE OFFICE SPACES IN THE ARCHITECTURAL
 SHEETS ARE BEING SHOWN NOT IN SCOPE OF WORK; HOWEVER
 THE ELECTRICAL SHEETS CLEARLY ARE INCLUDING THE
 ELECTRICAL AS REQUIRED IN SCOPE.
 PLEASE COMPLETE AND SEE THE FOLLOWING COMMENT.
 FBC 106.1.2 AND 106.3.5.1.2 FOR ADDITIONAL INFORMATION
 NEEDED.
  
 2) NOTE: PLEASE SEE THE FBC 2004 METHOD A ENERGY
 CALCULATIONS DO NOT CORRELATE WITH THE SAME SQUARE
 FOOTAGE ON THE PLANS AND ON APPLICATION.
 PLEASE SEE THE ENERGY CALCULATIONS INDICATE ONLY 20,
 40W LIGHT FIXTURES AND THE ELECTRICAL PLANS SHOW
 LIGHTING FIXTURES IN EXCESS OF WELL OVER 150+
 FIXTURES.
 PLEASE PROVIDE COMPLETED ENERGY CALCULATIONS WHICH
 CORRELATE WITH THE ELECTRICAL PLANS FOR ALL LIGHTING
 AND ENERGY USAGE.
 PLEASE SEE FBC 13-415.1.AB.1
  
 3) NOTE: PLEASE SEE 220.12 FOR LOADS ON TRACK LIGHTING
 TO BE SHOWN.
  
 4) NOTE: PLEASE SEE THE NOTE ADDED FOR WIND LOADS FOR
 LIGHT POLES IS NOT ENOUGH AND MAKES NO MENTION OF EVEN
 THE WIND LOAD RATINGS ETC. PLEASE SEE THE PREVIOUS
 REVIEW NOTE.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-11-03 Cont ID  
Sent By dpalmer Date 2006-11-03 Time 18:49 Rev Time 0.00
Received By dpalmer Date 2006-11-03 Time 18:03 Sent To  
Notes
2006-11-03 18:49:48** UNSAT ***
  
 1) NOTE: PLEASE PROVIDE SIGNED, DATED AND SEALED WIND
 LOAD CALCULATIONS FOR THE NEW PROPOSED SITE LIGHTING
 POLES. PLEASE BE SURE THE CALCULATIONS INCLUDE THE EPA
 FOR THE LIGHTING FIXTURES WHICH WILL BE INSTALLED.
 PLEASE SEE BLDG REVIEW COMMENTS FOR 140MPH 3 SECOND
 GUST, 120SUSTAINED. ETC
  
 2) NOTE: PLEASE INCLUDE THE FOLLOWING RELEVANT CODES ON
 PLANS AND DESIGN.
 2002 NFPA-70 (NEC), 2003 NFPA-101, 2002 NFPA-72 (WHEN
 APPLICABLE).
  
 3) NOTE: PLEASE SEE ELECTRICAL PANEL IS NOT PERMITTED
 IN OFFICE / STORAGE AREA. PLEASE SEE 240.24D, 408.7,
 110.26 ETC.
 PLEASE RELOCATE.
  
 4) NOTE: PLEASE SEE 250.6 AND 250.24 AS AN "EQUIPMENT
 GROUNDING CONDUCTOR" IS BEING INDICATED AHEADOF THE
 MAIN DISCONNECT.
 PLEASE KNOW, THIS SHALL ONLY BE INSTALLED AFTER THE
 FIRST MEANS OF DISCONNECT.
  
 5) NOTE: PLEASE CORRELATE THE EQUIPMENT GROUNDING
 CONDUCTOR ON RISER WITH THAT LISTED ON PANEL SCHEDULE.
 PLEASE SEE 250.122,
 FBC 106.1.2
  
 6) NOTE: PLEASE SEE MISSING CWP AS PART OF THE
 GROUNDING ELECTRODE SYSTEM. 250.50
  
 7) NOTE;: PLEASE SEE LOBBY WILL REQUIRED AN EMERGENCY
 BATTERY BACK UP LT OF SOME SORT TO MEET THE MIN
 LIGHTING LEVELS REQUIRED PER LS 101 7.8, 7.9 . (COMBO
 UNITS, MAY BE USED). (ONLY A SUGGESTION.
  
 8) NOTE: PLEASE PROVIDE CLARIFICATION OF ADJACENT
 OFFICE SPACE , NOTED A CONSTRUCTION OFFICES. IS THIS
 STILLPART OF THE SAME TENANT?
  
 9) NOTE: PLEASE CLARIFY THE ADJUSTEDSQ FT FOR SPACE.
 PLEASE SEE PERMIT APPLICATION, ENERGY CALCULATIONS, AND
 PLANS.
 PLEASE KNOW IF BLDG IS OVER 5K SQ FT, FBC 2004 CHAPTER
 WILL APPLY.
 PLEASE SEE 13-415.1.AB.1
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2006-11-03 18:04:22IN ELEC

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-02-06 Cont ID  
Sent By mawillia Date 2007-02-06 Time 14:14 Rev Time 0.00
Received By mawillia Date 2007-02-06 Time 14:14 Sent To  
Notes
2007-02-06 14:24:04*****APPROVED*****W/PROVISO
  
  
  
 SHEET LS-1.01 HAS BEEN STAMPED, INITIALED, AND DATED AS
 APPROVED.HOWEVER SHEET E-1 WILL NEED TO BE STAMPED BY
 FIRE WHEN THE ELECTRICAL PLAN REVIEW COMMENT HAS BEEN
 ADDRESSED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-01-09 Cont ID  
Sent By mawillia Date 2007-01-09 Time 14:09 Rev Time 0.00
Received By mawillia Date 2007-01-09 Time 14:09 Sent To  
Notes
2007-01-09 14:56:15*****UNSAT*****
  
 THE FOLLOWING COMMENTS TAKEN FROM PREVIOUS FIRE PLAN
 REVIEW OF 11/21/2006 ARE TO BE READDRESSED AS FOLLOWS:
  
  
  
 1.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 HINDER OR INTERFERE WITH EMERGENCY ACCESS TO THE SAID
 PROPERTY OR THE VICINITY THEREOF.ILLUSTRATE ON THE
 APPROPIATE PLAN SHEET THAT THIS HAS BEEN ACKNOWLEDGED.
  
 3.THE EXISTING BUILDING DOES NOT HAVE FIRE PROTECTION
 SYSTEM IN PLACE.INCLUDE IN THE SITE USE DATA TABLE
 (ON SHEET A-1.00) UNSPRINKLERED BUILDING
  
 **NEW COMMENT**
  
 1.IN REFERENCE TO THE SMOKE DETECTORS LISTED ON SHEET
 LS-1.01, ARE THEY TIED INTO A FIRE ALARM SYSTEM?IF
 THEY ARE NOT, THESE DEVICES SHOULD BE SHOWN AS SMOKE
 ALARMS (SA) IN LIEU OF SMOKE DETECTORS (SD).
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-11-21 Cont ID  
Sent By mawillia Date 2006-11-21 Time 09:34 Rev Time 0.00
Received By mawillia Date 2006-11-21 Time 09:34 Sent To  
Notes
2006-11-21 10:07:10*****DENIED*****
  
  
  
 1.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 HINDER OR INTERFERE WITH EMERGENCY ACCESS TO THE SAID
 PROPERTY OR THE VICINITY THEREOF.
  
 2.WHAT TYPE OF OCCUPANCY WILL THE PROPOSED STRUCTURE
 BE?
  
 3.DOES THE EXISTING BUILDING HAVE FIRE PROTECTION
 SYSTEM IN PLACE?IF SO, HOW WILL THEY BE AFFECTED BY
 THE SCOPE OF THE WORK?
  
 4.IF THE FIRE PROTECTION SYSTEM IS MODIFIED OR IS
 ADDED TO THE BUILDING, SEPARATE PERMIT AND PLANS ARE
 REQUIRED.
  
 5.PROVIDE A LIFE SAFETY PLAN WHICH INCLUDES ALL
 COMMON PATHS OF TRAVEL TO EXITS.
  
 6.INDICATE LOCATION OF 2A-10BC FIRE EXTINGUISHERS AT
 DISTANCES TO SATISFY THE 75' TRAVEL DISTANCE
 REQUIREMENT.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-03-06 Cont ID  
Sent By adarroug Date 2007-03-06 Time 09:50 Rev Time 0.00
Received By adarroug Date 2007-03-06 Time 09:50 Sent To B
Notes
2007-03-06 09:51:06TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-03-06 Cont ID  
Sent By adarroug Date 2007-03-06 Time 09:25 Rev Time 0.00
Received By adarroug Date 2007-03-06 Time 09:25 Sent To M
Notes
2007-03-06 09:25:59TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-02-16 Cont ID  
Sent By adarroug Date 2007-02-16 Time 16:26 Rev Time 0.00
Received By adarroug Date 2007-02-16 Time 16:26 Sent To  
Notes
2007-02-16 16:26:52TO "BOB"#17

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-02-09 Cont ID  
Sent By adarroug Date 2007-02-09 Time 11:09 Rev Time 0.00
Received By adarroug Date 2007-02-09 Time 11:09 Sent To  
Notes
2007-02-09 11:11:57TO "BOB"#10

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-01-20 Cont ID  
Sent By adarroug Date 2007-01-20 Time 12:57 Rev Time 0.00
Received By adarroug Date 2007-01-20 Time 12:57 Sent To  
Notes
2007-01-20 12:57:49TO "BOB"#5

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-19 Cont ID  
Sent By adarroug Date 2006-12-19 Time 10:34 Rev Time 0.00
Received By adarroug Date 2006-12-19 Time 10:34 Sent To  
Notes
2007-01-03 17:48:29TO "BOB"#13
2006-12-19 10:34:50WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-11-21 Cont ID  
Sent By mawillia Date 2006-11-21 Time 09:34 Rev Time 0.00
Received By mawillia Date 2006-10-30 Time 10:37 Sent To  
Notes
2006-11-03 14:44:48TO "BOB"#6
2006-10-30 10:38:26WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-03-06 Cont ID  
Sent By tgordon Date 2007-03-06 Time 14:30 Rev Time 0.30
Received By tgordon Date 2007-03-06 Time 14:30 Sent To  
Notes
2007-03-06 14:34:24REVISION TO MECHANICAL PLANS PAGE A/C-1
 *** PROVISO ***
 1) PROVIDE RETURN AIR FROM CORRIDOR TO EXISTING 3 TON
 ROOFTOP UNIT, SEE 2004 FBC/M 601.4.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-01-22 Cont ID  
Sent By tgordon Date 2007-01-22 Time 11:46 Rev Time 0.30
Received By tgordon Date 2007-01-22 Time 11:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-01-04 Cont ID  
Sent By tgordon Date 2007-01-04 Time 11:25 Rev Time 0.30
Received By tgordon Date 2007-01-04 Time 11:25 Sent To  
Notes
2007-01-04 11:31:03*** DENIED ***
 1) ONE SET OF PLANS PAGE AC-1 MECHANICAL IS MISSING
 SEAL, NEEDS TO BE SIGNED AND SEALED BY THE ENGINEER,
 PER FAC 61G15-23.002.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-11-06 Cont ID  
Sent By tgordon Date 2006-11-06 Time 11:34 Rev Time 0.40
Received By tgordon Date 2006-11-06 Time 11:34 Sent To  
Notes
2006-11-06 11:44:03*** DENIED ***
 1) PLEASE SHOW HOW OUTDOOR AIR IS TO GET TO THE 1 1/2
 TON AHU.
  
 2) SEE PAGE AC-1, OUTDOOR AIR CAL'S. SHOWS 440 CFM'S
 REQUIRED, BUT ONLY 250 CFM'S. ARE TO BE SUPPLIED,
 PLEASE EXPLAIN.
  
 3) RETURN AIR TRANSFER DUCT TO OFFICE #109 IS TO SMALL,
 SEE (A) PLEASE CORRECT.
 BALANCED RETURN AIR.
 MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-01-29 Cont ID  
Sent By jleech Date 2007-01-29 Time 08:19 Rev Time 0.00
Received By jleech Date 2007-01-29 Time 08:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-01-09 Cont ID  
Sent By jleech Date 2007-01-09 Time 08:34 Rev Time 0.00
Received By jleech Date 2007-01-09 Time 08:34 Sent To  
Notes
2007-01-09 09:00:55DENIED;
 1. (FROM FIRST REVIEW #3NOT ADDRESSED) SHOW TOTAL
 NUMBER OF EMPLOYEES MUST COMPLY WITH FBC-2004 TABLE
 403.1 (2B). SEPARATE FACILITIES EXCEPTIONS FOR SECTION
 403.2 MUST BE SHOWN ON PLANS.
 2. DEMO PLAN REQUIRED SHOWING ALL EXISTING PLUMBING TO
 BE REMOVED. ADD NOTE TO DEMO PAGE "NO DEAD ENDS
 PERMITED IN SANITARY DRAINAGE SYSYEM, INSPECTION
 REQUIRED) SEE SECTION 704.5 DEAD ENDS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-11-18 Cont ID  
Sent By jleech Date 2006-11-18 Time 07:23 Rev Time 0.00
Received By jleech Date 2006-11-18 Time 07:23 Sent To  
Notes
2006-11-18 07:43:36DENIED;
 1. BATHROOM DOOR SHALL NOT SWING INTO THE CLEAR FLOOR
 SPACE OF THE LAVATORY. FBC-2004 BUILDING CHAPTER 11
 SECTION 11-4.22.2.
 2. SHOW DETAIL DRAWINGS FOR HANDICAP BATHROOM, BREAK
 SINK, AND DRINKING FOUNTAIN. SHOW ALL REQUIRED
 MEASUREMENTS.
 SEE THE FOLLOWING SECTIONS IN CHAPTER 11 FOR
 REQUIREMENTS;
 TOILET11-4.16.1 THRU 11-4.16.6.
 LAVATORY11-4.19.1 THRU 11-4.19.6
 BREAK SINK 11-4.24.1 THRU 11-4.24.7
 DRINKING FOUNTAIN11-4.1.3(10),
 11-4.15.1 THRU 11-4.15.5
 3. SHOW COMPLIANCE TO FBC-2004 PLUMBING TABLE 403.1#2B
 SHOW TOTAL EMPLOYEES. MUST COMPLY WITH SEC 403.2. ONE
 DRINKING FOUNTAIN IS REQUIRED
 SEE SECTION 410.1, D/F MUST BE PART OF PLUMBING
 SYSTEM.
 4. SHOW CLEAR FLOOR SPACE AND TURNING RADIUS ON FLOOR
 PLAN WHERE REQUIRED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695