Plan Review Details - Permit 06101010
Plan Review Stops For Permit 06101010
Review Stop AD ADDRESSING
Rev No 2 Status N Date 2006-11-06 Cont ID  
Sent By swurafti Date 2006-11-06 Time 11:50 Rev Time 0.00
Received By swurafti Date 2006-11-06 Time 11:50 Sent To  
Notes
2006-11-04 17:18:55WORK FOR SUITE #300 AS NOTED AND SHOWN ON PLANS.

Review Stop AD ADDRESSING
Rev No 1 Status N Date 2006-10-31 Cont ID  
Sent By swurafti Date 2006-10-31 Time 11:07 Rev Time 0.00
Received By swurafti Date 2006-10-26 Time 14:53 Sent To  
Notes
2006-10-31 11:09:10DIDN'T NEED TO SEND TO ADDRESSING

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-02-12 Cont ID  
Sent By rmcdouga Date 2007-02-12 Time 16:46 Rev Time 0.00
Received By rmcdouga Date 2007-02-12 Time 16:46 Sent To  
Notes
2007-02-12 16:48:03NEW SHEET A-1 IS OK FOR BUILDING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-01-09 Cont ID  
Sent By rmcdouga Date 2007-01-09 Time 09:44 Rev Time 0.00
Received By rmcdouga Date 2007-01-09 Time 09:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-11-07 Cont ID  
Sent By rmcdouga Date 2006-11-07 Time 08:31 Rev Time 0.00
Received By rmcdouga Date 2006-11-07 Time 08:31 Sent To  
Notes
2006-11-07 09:30:37DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SPECIFY THE LOCATIONS OF THE EXIT LIGHTS ON THE
 PLANS. SEE FBC 1006.3.
  
 3) FBC 1008.1.2 DOOR SWING.
 EGRESS DOORS SHALL BE SIDE-HINGED SWINGING. DOORS SHALL
 SWING IN THE DIRECTION OF EGRESS TRAVEL WHERE SERVING
 AN OCCUPANT LOAD OF 50 OR MORE PERSONS OR A GROUP H
 OCCUPANCY.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-06-19 Cont ID  
Sent By dpalmer Date 2007-06-19 Time 16:15 Rev Time 0.00
Received By dpalmer Date 2007-03-06 Time 09:29 Sent To  
Notes
2007-06-19 16:06:58THE COMMENTS FROM PREVIOUS REVIEW WERE NOT CORRECTED/
 PROJECT WAS PLACED ON HOLD ON 3/6/07 AS THE ENGINEER OF
 RECORD DID NOT AGREE WITH THE ELECTRICAL PLAN REVIEW
 COMMENTS. THIS OFFICE WAS GOING TO LET NEW
 PLANS/DOCUMENTS TO BE BROUGHT HOWEVERNO CONTACT WAS
 MADE.
 FRONT COUNTER SPOKE TO LYNN ON 4/12/07TO HAVE PLANS
 PICKED UP. PLANS ARE TO BE PICKED UP FOR CODE
 CORRECTIONS FOR PREVIOUS COMMENTS FOR COMPLIANCE WITH
 NEC 645 AND NFPA-75.
 RULING UNDER THE BUILDING OFFICIAL WAS GIVEN TO THE
 ENGINEER WITHIN A WEEK AFTER3/6/07 . SUPPORTING
 DOCUMENTS FROM THE NEC HANDBOOK WAS FAXED TO THE
 ENGINNEER. NO CONTACT WAS MADE AFTER THAT.
 PLANS WERE OUT FRONT ON HOLD, HOWEVER ARE NOT PICKED UP
 FOR CORRECTIONS.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-02-11 Cont ID  
Sent By dpalmer Date 2007-02-11 Time 12:27 Rev Time 0.00
Received By dpalmer Date 2007-02-11 Time 12:08 Sent To  
Notes
2007-02-11 12:27:47*** UNSAT ***
  
  
 1) NOTE: PLEASE SEE NEW PLANS CALL THIS ROOM A TELCO
 ROOM AND NOTED AS EXISTING, HOWEVER RESPONSE LETTER
 MENTIONS IN SEVERAL LOCATIONS THAT THIS IS AN EXISTING
 IT ROOM AND IS AN IT ROOM AND NO CONSTRUCTION OR
 ELECTRICAL CODES ARE MET FOR CONSTRUCTION FOR THIS ROOM
 OR EQUIPMENT PLACED IN THIS LOCATION. PLEASE SEE THE
 NFPA-75AND NEC 645 AS THIS CONSIDERATION IS ALSO
 BASED ON THE LIFE SAFETY ISSUES TO OCCUPANTS OUTSIDE
 THIS ROOM AND AREA AS WELL AS THE OTHER CONSIDERATIONS
 FOR INSIDE SUCH A ROOM.
 PLEASE SEE PREVIOUS NOTES, IF THIS IS AN IT ROOM AND
 FALLS UNDER ANY OF THE CHARACTERISTICS OF AS STATED IN
 CHAPTER 2, THEN PLEASE KNOW REQUIREMENTS FOR BRINGING
 UP TO CODE SHALL APPLY.
 PLEASE SEE FBC 106.1.2, 102.1 AND 104.6 OF THE
 ADMINISTRATIVE SECTION OF THE FBC AS ADOPTED BY THE
 CITY OF WEST PALM BEACH.
  
  
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE NOTE #1 FROM THE PREVIOUS REVIEW. IF THIS
 ROOM IS BEING DESIGNATED AS AN IT ROOM AS SHOWN ON
 PLANS AND ALL EQUIPMENT IN ROOM IS FOR EQUIPMENT AS
 DEFINED FOR AN IT ROOM, THEN PLEASE KNOW EVEN IF THIS
 WAS NOT CONSTRUCTED TO THE NFPA-75 STANDARDS, IT ALSO
 MAY HAVE BEEN CONVERTED AT SOME POINT WITH OR WITHOUT
 CORRECTION INFORMATION OR PERMITTING FOR SUCH USE.
 PLEASE SEE NFPA-75 AND NEC 645, AND APPLY NOTES AND
 CODE ACCORDINGLY.
 PLEASE KNOW, IF THESE DO NOT APPLY AND THIS ROOM IS NOT
 INDEED FOR THE PURPOSE AND USE, AND THEN PLEASE ADJUST
 PLANS ACCORDINGLY.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-12-30 Cont ID  
Sent By dpalmer Date 2006-12-30 Time 16:24 Rev Time 0.00
Received By dpalmer Date 2006-12-30 Time 16:17 Sent To  
Notes
2006-12-30 16:26:32** UNSAT 2ND REVIEW **
  
 1) NOTE: PLEASE SEE NOTE #1 FROM THE PREVIOUS REVIEW.
 IF THIS ROOM IS BEING DESIGNATED AS AN IT ROOM AS SHOWN
 ON PLANS AND ALL EQUIPMENT IN ROOM IS FOR EQUIPMENT AS
 DEFINED FOR AN IT ROOM, THEN PLEASE KNOW EVEN IF THIS
 WAS NOT CONSTRUCTED TO THE NFPA-75 STANDARDS, IT ALSO
 MAY HAVE BEEN CONVERTED AT SOME POINT WITH OR WITHOUT
 CORRECTION INFORMATION OR PERMITTING FOR SUCH USE.
 PLEASE SEE NFPA-75 AND NEC 645, AND APPLY NOTES AND
 CODE ACCORDINGLY.
 PLEASE KNOW, IF THESE DO NOT APPLY AND THIS ROOM IS NOT
 INDEED FOR THE PURPOSE AND USE,THEN PLEASE ADJUST
 PLANS ACCORDINGLY.
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-11-04 Cont ID  
Sent By dpalmer Date 2006-11-04 Time 17:34 Rev Time 0.00
Received By dpalmer Date 2006-11-04 Time 17:17 Sent To  
Notes
2006-11-04 17:34:50*** UNSAT ***
  
 1) NOTE: PLEASE PROVIDE AND SHOW NEW OR EXISTING
 ELECTRICAL DISCONNECTING MEANS FOR ALL ELECTRICAL IN
 THE "IT" ROOM. PLEASE SHOW THE NEW OR EXISTING "EPO" .
 PLEASE SEE NFPA-75,
 NEC 645.10 ETC.
 PLEASE NOTE ON PLANS, THAT ALL CONSTRUCTION
 REQUIREMENTS FOR "IT" ROOM MEET EXISTING CODE AS BEING
 SHOWN AS AN EXISTING "IT" ROOM, OR PROVIDE PERMIT
 NUMBER(S) FOR WHEN THIS WORK WAS PERMITTED.
 PLEASE ALSO EXPLAIN RATIONAL OF RECEPTS AND CIRCUITS
 OUTSIDE THE "IT" ROOM WHICH ARE BEING FED FROM THIS
 PANEL.???
 PLANS AND WORK WHICH HAS , OR IS BEING DONE IS UNCLEAR.
  
 PLANS FOR THIS SCOPE AND SCOPE OF WORK RECENTLY APPLIED
 FOR SEEMS BE SUBMITTED IN A "PIECE MEAL" FASHION.
  
 2) NOTE: PLEASE EXPLAIN NOTE FOR METERING. PLEASE SEE
 WORK BEING PROPOSED UNDER SEPARATE PERMIT HAS NOT
 COMMENCED OR PERMITTED AT THIS TIME. PLEASE VERIFY IF
 THIS IS ONE TENANT AND ONE METER , MAINS GROUPED
 ACCESSIBLE AND LOCATED FOR TENANT??
  
 3) NOTE: PLEASE KNOW AS PER FBC 2004 EXISTING AREAS
 BEING RENOVATED AND BRING SYSTEMS UP TO CODE SHALL BE
 CONSIDERED IN A ONE YEAR PERIOD OF TIME.
  
  
 ** PLEASE SUBMIT MORE INFORMATION AND EXPLANATION OF
 WORK. PLEASE SEE NOTES ABOVE FOR VERIFICATION OF
 EXISTING AS SHOWN CAN NOT BE VERIFIED MEETING CODE
 COMPLIANCE AT THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-02-13 Cont ID  
Sent By mawillia Date 2007-02-13 Time 14:10 Rev Time 0.00
Received By mawillia Date 2007-02-13 Time 14:10 Sent To  
Notes
2007-02-13 14:11:37*****APPROVED*****
  
  
  
  
 PLAN SHEETS A-1 AND E-2 WERE RE-STAMPED, INITIALED,
 AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-01-09 Cont ID  
Sent By mawillia Date 2007-01-09 Time 12:38 Rev Time 0.00
Received By mawillia Date 2007-01-09 Time 12:38 Sent To  
Notes
2007-01-09 12:43:14*****APPROVED*****
  
  
  
 ALL FIRE PLAN REVIEW COMMENTS OF 11/14/2006 HAVE BEEN
 ADDRESSED.PLAN SHEETS A-1 AND E-2 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-11-14 Cont ID  
Sent By mawillia Date 2006-11-14 Time 10:36 Rev Time 0.00
Received By mawillia Date 2006-11-14 Time 10:58 Sent To  
Notes
2006-11-14 10:57:11*****UNSAT*****
  
  
  
 1.NFPA 101 - 2003 EDITION AND FLORIDA FIRE PREVENTION
 CODE - 2004 EDITION SHALL BE REFERENCED.
  
 2. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.ACCUMULATIONS OF COMBUSTIBLE WASTE AND DUST DEBRIS
 SHALL BE REMOVED FROM THE STRUCTURE AND ITS IMMEDIATE
 VICINITY AT THE END OF EACH SHIFT OR MORE FREQUENTLY AS
 NECESSARY FOR SAFE OPERATIONS.
  
 4.EXITS TO REMAIN CLEAR AND UNOBSTRUCTED.
  
 5.INDICATE/DISPLAY/SHOW LOCATION OF EXIT LIGHTS,
 EMERGENCY LIGHTS, FIRE EXTINGUISHERS, AND FIRE
 PROTECTION SYSTEMS. HOW WILL THEY BE AFFECTED BY THE
 SCOPE OF THE WORK?
  
 6.IF THE FIRE ALARM AND/OR FIRE SPRINKLER SYSTEM
 IS/ARE TO BE MODIFIED DUE TO THE SCOPE OF THE WORK,
 SEPARATE SHOP DRAWINGS/PLANS AND PERMIT IS REQUIRED.
  
  
  
 TO EXPEDITE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW AND/OR WHERE EACH ITEM WAS
 ADDRESSED.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-11-14 Cont ID  
Sent By mawillia Date 2006-11-14 Time 10:59 Rev Time 0.00
Received By mawillia Date 2006-11-14 Time 10:59 Sent To  
Notes
2006-11-14 11:04:36SEE 2ND FIRE PLAN REVIEW (ACTUALLY THE 1ST) FOR
 COMMENTS

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-03-03 Cont ID  
Sent By adarroug Date 2007-03-03 Time 15:43 Rev Time 0.00
Received By adarroug Date 2007-03-03 Time 15:43 Sent To E
Notes
2007-03-03 15:43:45TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-02-09 Cont ID  
Sent By adarroug Date 2007-02-09 Time 10:06 Rev Time 0.00
Received By adarroug Date 2007-02-09 Time 10:06 Sent To  
Notes
2007-02-09 10:08:39TO "BOB"#9

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-14 Cont ID  
Sent By adarroug Date 2006-12-14 Time 15:04 Rev Time 0.00
Received By adarroug Date 2006-12-14 Time 15:04 Sent To  
Notes
2006-12-30 16:17:38TO BOB #17 12/30
2006-12-14 15:05:15WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-11-14 Cont ID  
Sent By mawillia Date 2006-11-14 Time 11:06 Rev Time 0.00
Received By mawillia Date 2006-11-02 Time 16:11 Sent To  
Notes
2006-11-06 10:07:08TO "BOB"#1
2006-11-02 16:11:39WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-02-13 Cont ID  
Sent By tgordon Date 2007-02-13 Time 10:48 Rev Time 0.25
Received By tgordon Date 2007-02-13 Time 10:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-11-06 Cont ID  
Sent By tgordon Date 2006-11-06 Time 10:35 Rev Time 0.30
Received By tgordon Date 2006-11-06 Time 10:35 Sent To  
Notes
***NONE***