Plan Review Details - Permit 06100983
Plan Review Stops For Permit 06100983
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-11-03 Cont ID  
Sent By mjacobs Date 2006-11-03 Time 07:11 Rev Time 0.00
Received By mjacobs Date 2006-11-03 Time 06:58 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-10-30 Cont ID  
Sent By mjacobs Date 2006-10-30 Time 16:17 Rev Time 0.00
Received By mjacobs Date 2006-10-30 Time 14:19 Sent To PC
Notes
2006-10-30 16:17:52 
 BUILDING PLAN REVIEW
 PERMIT:06100983
 ADD:224 GRAY ST
 CONT:HORIZON ROOFING INC.
 TEL: (561)842-6120
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW2ND
 ACTION: DENIED
  
 1)ONCE AGAIN(A) THE CONTRACTOR FAILED TO INDICATE
 WHICH APPROVED ASSEMBLY SYSTEM TO BE USED. HI-LIGHT OR
 CIRCLE THE SYSTEM WHICH WILL BE USED FROM THE 44 PAGE
 REPORT.
 (B)THE SYSTEM PROVIDED STATES LIMITATION #7, SHOULD
 THE FASTENER RESISTANCE BE LESS THAN THAT REQUIRED, AS
 DETERMINED BY THE BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPARED, SIGNED AND SEALED BY A
 FLORIDA REGISTERED PROFESSIONAL ENGINEER,ARCHITECT OR
 REGISTERED ROOF CONSULTANT MAYBE SUBMITTED.
  
  
 2)THE ES LEGACY REPORT AND FL985-R1 DOES NOT
 CORRESPOND WITH EACH OTHER.SEE FLORIDABUILDING.ORG
 FOR NEW PRODUCT APPROVAL UPDATES. MAKE SURE THESTATE
 COVER SHEET MATCH THE NOA REPORTS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-26 Cont ID  
Sent By mjacobs Date 2006-10-26 Time 13:00 Rev Time 0.00
Received By mjacobs Date 2006-10-26 Time 12:48 Sent To PC
Notes
2006-10-26 13:00:44BUILDING PLAN REVIEW
 PERMIT:06100983
 ADD:224GRAY ST.
 CONT:HORIZON ROOFING INC.
 TEL: (561)842-6120
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW1ST.
 ACTION: DENIED
  
  
  
 1) THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 _XX__ CONTRACTOR FAILED TO INDICATE WHICH
 SYSTEM TO BE USED.
  
 _XX__ THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE _3__ .
  
 _XX__ THE SYSTEM PROVIDED STATES
 LIMITATION# 7, SHOULD THE FASTENER
 RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
 THE PRODUCT APPROVAL IS MISSING
 THE APPROVED ASSEMBLY.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-11-02 Cont ID  
Sent By adarroug Date 2006-11-02 Time 11:43 Rev Time 0.00
Received By adarroug Date 2006-11-02 Time 11:43 Sent To B
Notes
2006-11-02 11:44:00TO "MJACOBS"DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-30 Cont ID  
Sent By adarroug Date 2006-10-30 Time 11:22 Rev Time 0.00
Received By adarroug Date 2006-10-30 Time 11:22 Sent To B
Notes
2006-10-30 11:23:06TO "MJACOBS" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-26 Cont ID  
Sent By mjacobs Date 2006-10-26 Time 12:47 Rev Time 0.00
Received By mjacobs Date 2006-10-26 Time 12:47 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved