Plan Review Details - Permit 06100894
Plan Review Stops For Permit 06100894
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-11-20 Cont ID  
Sent By lursu Date 2006-11-20 Time 14:01 Rev Time 0.00
Received By lursu Date 2006-10-24 Time 14:31 Sent To  
Notes
2006-10-24 14:31:51NEED AN EXTENSION FOR THIS ADDRESS

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-01-17 Cont ID  
Sent By mjacobs Date 2007-01-17 Time 13:04 Rev Time 0.00
Received By mjacobs Date 2007-01-17 Time 11:08 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-01-08 Cont ID  
Sent By mjacobs Date 2007-01-08 Time 06:53 Rev Time 0.00
Received By mjacobs Date 2007-01-08 Time 05:59 Sent To PC
Notes
2006-12-23 19:12:01NEW SHEETS

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-11-07 Cont ID  
Sent By alange Date 2006-11-07 Time 13:04 Rev Time 0.00
Received By alange Date 2006-11-07 Time 12:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-02-21 Cont ID  
Sent By dpalmer Date 2007-02-21 Time 18:59 Rev Time 0.00
Received By dpalmer Date 2007-02-21 Time 18:47 Sent To PC
Notes
2007-02-21 19:00:35LOAD TOTAL FOR EXISTING TENANT AND ADDED LOAD TO BE
 REVISED., LOADS OK.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-01-13 Cont ID  
Sent By dpalmer Date 2007-01-13 Time 12:59 Rev Time 0.00
Received By dpalmer Date 2007-01-13 Time 12:27 Sent To FIRE
Notes
2007-01-13 12:59:57STAMPED ELECTRICAL,.
 PLANS ROUTED TO FIRE AS THE FA SHEETS IN EACH EACH
 NEEDS STAMPING FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-12-23 Cont ID  
Sent By dpalmer Date 2006-12-23 Time 19:11 Rev Time 0.00
Received By dpalmer Date 2006-12-23 Time 18:45 Sent To  
Notes
2006-12-23 19:11:27**UNSAT 2ND REVIEW **
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW WHICH IS
 STILL IN NEED OF ADDRESSING.
 PLEASE SEE NOTES BELOW ARE TAKEN DIRECTLY FROM PREVIOUS
 REVIEW AND NOTED WITH AN OK, NO WITH FURTHER
 EXPLANATION.
 PLEASE SEE SOME MAY BE NOTED NO/OK WHICH WOULD INDICATE
 COMMENT WAS PARTIALLY ADDRESSED.
  
 1) NOTE: OK.
  
 2) NOTE: OK, HOWEVER SEE WHITE-OUT ON PLANS WHICH IS
 NOT PERMITTED ON PLANS WHETHER OR NOT THEY ARE SIGNED
 AND SEALED BY AN ENGINEER OR ARCHITECT.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2 AND .1.3 FOR
 AUTOMATED LIGHTING CONTROL OF SOME TYPE REQUIRED. IF
 OCC SENSOR TYPE, PLEASE INDICATE MAX TIME OF 30MINS, IF
 TIMER TYPE, PLEASE INDICATE THE MAX OF 4HRS.
  
 3) NOTE:NO, PLEASE SEE THE TABLE/BLOCK AS SHOWN DOES
 NOT CORRELATE. PLEASE SEE THE FIRST THING IS IF USING
 THE SPACE BY SPACE IN TABLE B, THEN PLEASE SEE AREAS
 SHALL BE BROKEN DOWN FOR USE. PLEASE SEE ALL MAY NOT BE
 ONLY SHOWN AS OFFICE, UNLESS ALL IS ONE OPEN OFFICE
 SPACE OR IF ALL ARE INDEED OFFICES.
 PLEASE SEE THE MAX LPD AS SHOWN DOES NOT CORRELATE.
 PLEASE SEE 1.1 TIMES(X) THE SQ FT OF1450 IS NOT 1600.
 (MAY NOT ROUND UP)
 PLEASE SEE THE FIXTURE WATTAGE DOES NOT CORRELATE TO
 THE FIXTURE LEGEND. PLEASE SEE EVEN IF FIXTURES WERE
 58WATTS EACH, 58 TIMES 30 IS 1740 WHICH EXCEEDS THE
 ALLOWANCE EVEN AS SHOWN.
 PLEASE SEE WATTAGE ON EACH FIXTURE IS 64, OR AT LEAST
 BY THE INFORMATION AS SHOWN ON FIXTURE LEGEND WHICH
 WOULD PLACE THE WATTAGE AT 1920.
 PLEASE ADJUST AND SEE TABLE B.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE THE MAX WATTAGE(LIGHTING POWER
 DENSITIES ) PER 13.415.2.ABC.1, (OFFICE, ETC SPACE.)
 CAN BE SHOWN ON A BLOCK ON PLANS.
  
 4) NOTE: OK.
  
 ** NEW NOTE **
  
 1) NOTE: PLEASE CLARIFY IF THE CONTINUOUS LOADS ARE
 SHOWN AT 125%. 215.3, 230.42
 THIS COMMENT WAS NOT MADE ON PREVIOUS REVIEW.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-10-31 Cont ID  
Sent By dpalmer Date 2006-10-31 Time 07:01 Rev Time 0.00
Received By dpalmer Date 2006-10-30 Time 08:03 Sent To I
Notes
2006-10-31 07:01:17** UNSAT **
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES
 ARE REFLECTED ON SAID PLANS.
 2002 NFPA-70, 2002 NFPA-72, 2003 NFPA-101 .
 FBC 2004
  
 2) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2 AND .1.3
 FOR AUTOMATED LIGHTING CONTROL OF SOME TYPE REQUIRED.
 IF OCC SENSOR TYPE, PLEASE INDICATE MAX TIME OF 30MINS,
 IF TIMER TYPE, PLEASE INDICATE THE MAX OF 4HRS.
  
 3) NOTE: PLEASE INDICATE THE MAX WATTAGE(LIGHTING POWER
 DENSITIES ) PER 13.415.2.ABC.1, (OFFICE, ETC SPACE.)
 CAN BE SHOWN ON A BLOCK ON PLANS.
  
 4) NOTE: PLEASE CLARIFY THE 2ND TRANSFORMER SHOWN ON
 TRANSFORMER SCHEDULE, HOWEVER COULD NOT LOCATE THIS ON
 RISER, ON PANEL SCHEDULE OR ON PLANS.??
 UNABLE TO VERIFY AT THIS TIME.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2006-10-30 08:04:03REMOVED FROM INCOMING , IN ELECTRICAL FOR REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-01-16 Cont ID  
Sent By mawillia Date 2007-01-16 Time 09:26 Rev Time 0.00
Received By mawillia Date 2007-01-16 Time 09:26 Sent To  
Notes
2007-01-16 09:29:12*****APPROVED*****
  
  
 SHEETS A 1.2, FA 0.1, AND FA 2.1 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-12-26 Cont ID  
Sent By mawillia Date 2006-12-26 Time 15:36 Rev Time 0.00
Received By mawillia Date 2006-12-26 Time 15:36 Sent To  
Notes
2006-12-26 15:41:53*****APPROVED*****
  
  
  
  
 FIRE TO STAMP AND SIGN WHEN ALL PLAN REVIEWS HAVE BEEN
 SATISFIED

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-11-20 Cont ID  
Sent By mawillia Date 2006-11-20 Time 11:54 Rev Time 0.00
Received By mawillia Date 2006-11-20 Time 11:54 Sent To AD
Notes
2006-11-20 12:09:09****UNSAT****
  
  
  
 1.FLORIDA FIRE PREVENTION CODE 2004 EDITION SHALL BE
 REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.SINCE THE SCOPE OF THE WORK WILL REQUIRE
 MODIFICATION OF THE FIRE PROTECTION SYSTEM(S), SEPARATE
 PERMITS AND PLANS WILL BE REQUIRED.
  
 4.AS PER WPB FIRE PREVENTION, DUCT DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM.(MAKE CHANGE TO FIRE
 ALARM NOTE #17, SHEET FA 0.1)
  
 5.CORRECT SPELLING OF "FIRE" ON SHEET FA2.1, KEY NOTE
 #2.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-02-20 Cont ID  
Sent By adarroug Date 2007-02-20 Time 10:08 Rev Time 0.00
Received By adarroug Date 2007-02-20 Time 10:08 Sent To E
Notes
2007-02-20 10:08:55TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-01-12 Cont ID  
Sent By adarroug Date 2007-01-12 Time 09:07 Rev Time 0.00
Received By adarroug Date 2007-01-12 Time 09:07 Sent To E
Notes
2007-01-12 09:07:45TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-12 Cont ID  
Sent By adarroug Date 2006-12-12 Time 18:43 Rev Time 0.00
Received By adarroug Date 2006-12-12 Time 18:43 Sent To  
Notes
2006-12-22 13:26:17TO "BOB"#9
2006-12-12 18:44:01WAITING FOR "BOB"--NEW SHEETS FOR "M" AND "BLDG"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-11-20 Cont ID  
Sent By mawillia Date 2006-11-20 Time 12:10 Rev Time 0.00
Received By mawillia Date 2006-10-26 Time 09:55 Sent To  
Notes
2006-11-01 10:22:00TO "BOB"#10
2006-10-26 09:57:59WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-12-26 Cont ID  
Sent By tgordon Date 2006-12-26 Time 10:36 Rev Time 0.25
Received By tgordon Date 2006-12-26 Time 10:36 Sent To  
Notes
2006-12-23 19:12:59NEW SHEET

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-11-01 Cont ID  
Sent By tgordon Date 2006-11-01 Time 14:14 Rev Time 0.30
Received By tgordon Date 2006-11-01 Time 14:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-01-06 Cont ID  
Sent By kstevens Date 2007-01-06 Time 09:40 Rev Time 0.00
Received By kstevens Date 2007-01-06 Time 09:40 Sent To  
Notes
2007-01-06 09:50:18PASSED/PROVISO - WATER HAMMER ATTESTORS SHALL BE
 LOCATED NEAR THE FIXTURE, NOT IN THE CEILING. PDI-WH
 201--SINK DEPTH MAXIMUM 6-1/2" DEPTH PER SECTION
 11-4.24.4.

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-11-13 Cont ID  
Sent By kstevens Date 2006-11-13 Time 13:31 Rev Time 0.00
Received By kstevens Date 2006-11-13 Time 13:31 Sent To  
Notes
2006-11-13 13:36:42DENIED
 REFERENCE: FBC-2004 CHAPTER 11
  
 1. SHT A6.2.1. DETAIL 9 SHOW THE FOLLOWING:
 A. 11-4.24.3 KNEE CLEARANCE
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH
 REQUIRED AND SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH
 THE SINK). CABINET DOORS ARE NOT APPROVED IN THE CLEAR
 FLOOR SPACE.
 D. 11-4.24.6EXPOSED PIPES & SURFACES
 E. 11-4.24.7FAUCETS
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  