Plan Review Stops For Permit 06100894 |
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
P |
Date |
2006-11-20 |
|
|
Cont ID |
|
Sent By |
lursu |
Date |
2006-11-20 |
Time |
14:01 |
Rev Time |
0.00 |
Received By |
lursu |
Date |
2006-10-24 |
Time |
14:31 |
Sent To |
|
|
Notes |
2006-10-24 14:31:51 | NEED AN EXTENSION FOR THIS ADDRESS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2007-01-17 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2007-01-17 |
Time |
13:04 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2007-01-17 |
Time |
11:08 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2007-01-08 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2007-01-08 |
Time |
06:53 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2007-01-08 |
Time |
05:59 |
Sent To |
PC |
|
Notes |
2006-12-23 19:12:01 | NEW SHEETS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2006-11-07 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2006-11-07 |
Time |
13:04 |
Rev Time |
0.00 |
Received By |
alange |
Date |
2006-11-07 |
Time |
12:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2007-02-21 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-02-21 |
Time |
18:59 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-02-21 |
Time |
18:47 |
Sent To |
PC |
|
Notes |
2007-02-21 19:00:35 | LOAD TOTAL FOR EXISTING TENANT AND ADDED LOAD TO BE | | REVISED., LOADS OK. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2007-01-13 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-01-13 |
Time |
12:59 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-01-13 |
Time |
12:27 |
Sent To |
FIRE |
|
Notes |
2007-01-13 12:59:57 | STAMPED ELECTRICAL,. | | PLANS ROUTED TO FIRE AS THE FA SHEETS IN EACH EACH | | NEEDS STAMPING FOR REVIEW. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2006-12-23 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-12-23 |
Time |
19:11 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-12-23 |
Time |
18:45 |
Sent To |
|
|
Notes |
2006-12-23 19:11:27 | **UNSAT 2ND REVIEW ** | | | | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW WHICH IS | | STILL IN NEED OF ADDRESSING. | | PLEASE SEE NOTES BELOW ARE TAKEN DIRECTLY FROM PREVIOUS | | REVIEW AND NOTED WITH AN OK, NO WITH FURTHER | | EXPLANATION. | | PLEASE SEE SOME MAY BE NOTED NO/OK WHICH WOULD INDICATE | | COMMENT WAS PARTIALLY ADDRESSED. | | | | 1) NOTE: OK. | | | | 2) NOTE: OK, HOWEVER SEE WHITE-OUT ON PLANS WHICH IS | | NOT PERMITTED ON PLANS WHETHER OR NOT THEY ARE SIGNED | | AND SEALED BY AN ENGINEER OR ARCHITECT. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2 AND .1.3 FOR | | AUTOMATED LIGHTING CONTROL OF SOME TYPE REQUIRED. IF | | OCC SENSOR TYPE, PLEASE INDICATE MAX TIME OF 30MINS, IF | | TIMER TYPE, PLEASE INDICATE THE MAX OF 4HRS. | | | | 3) NOTE:NO, PLEASE SEE THE TABLE/BLOCK AS SHOWN DOES | | NOT CORRELATE. PLEASE SEE THE FIRST THING IS IF USING | | THE SPACE BY SPACE IN TABLE B, THEN PLEASE SEE AREAS | | SHALL BE BROKEN DOWN FOR USE. PLEASE SEE ALL MAY NOT BE | | ONLY SHOWN AS OFFICE, UNLESS ALL IS ONE OPEN OFFICE | | SPACE OR IF ALL ARE INDEED OFFICES. | | PLEASE SEE THE MAX LPD AS SHOWN DOES NOT CORRELATE. | | PLEASE SEE 1.1 TIMES(X) THE SQ FT OF1450 IS NOT 1600. | | (MAY NOT ROUND UP) | | PLEASE SEE THE FIXTURE WATTAGE DOES NOT CORRELATE TO | | THE FIXTURE LEGEND. PLEASE SEE EVEN IF FIXTURES WERE | | 58WATTS EACH, 58 TIMES 30 IS 1740 WHICH EXCEEDS THE | | ALLOWANCE EVEN AS SHOWN. | | PLEASE SEE WATTAGE ON EACH FIXTURE IS 64, OR AT LEAST | | BY THE INFORMATION AS SHOWN ON FIXTURE LEGEND WHICH | | WOULD PLACE THE WATTAGE AT 1920. | | PLEASE ADJUST AND SEE TABLE B. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE INDICATE THE MAX WATTAGE(LIGHTING POWER | | DENSITIES ) PER 13.415.2.ABC.1, (OFFICE, ETC SPACE.) | | CAN BE SHOWN ON A BLOCK ON PLANS. | | | | 4) NOTE: OK. | | | | ** NEW NOTE ** | | | | 1) NOTE: PLEASE CLARIFY IF THE CONTINUOUS LOADS ARE | | SHOWN AT 125%. 215.3, 230.42 | | THIS COMMENT WAS NOT MADE ON PREVIOUS REVIEW. | | | | * ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2006-10-31 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-10-31 |
Time |
07:01 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-10-30 |
Time |
08:03 |
Sent To |
I |
|
Notes |
2006-10-31 07:01:17 | ** UNSAT ** | | | | 1) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES | | ARE REFLECTED ON SAID PLANS. | | 2002 NFPA-70, 2002 NFPA-72, 2003 NFPA-101 . | | FBC 2004 | | | | 2) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2 AND .1.3 | | FOR AUTOMATED LIGHTING CONTROL OF SOME TYPE REQUIRED. | | IF OCC SENSOR TYPE, PLEASE INDICATE MAX TIME OF 30MINS, | | IF TIMER TYPE, PLEASE INDICATE THE MAX OF 4HRS. | | | | 3) NOTE: PLEASE INDICATE THE MAX WATTAGE(LIGHTING POWER | | DENSITIES ) PER 13.415.2.ABC.1, (OFFICE, ETC SPACE.) | | CAN BE SHOWN ON A BLOCK ON PLANS. | | | | 4) NOTE: PLEASE CLARIFY THE 2ND TRANSFORMER SHOWN ON | | TRANSFORMER SCHEDULE, HOWEVER COULD NOT LOCATE THIS ON | | RISER, ON PANEL SCHEDULE OR ON PLANS.?? | | UNABLE TO VERIFY AT THIS TIME. | | | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | 2006-10-30 08:04:03 | REMOVED FROM INCOMING , IN ELECTRICAL FOR REVIEW. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2007-01-16 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-01-16 |
Time |
09:26 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-01-16 |
Time |
09:26 |
Sent To |
|
|
Notes |
2007-01-16 09:29:12 | *****APPROVED***** | | | | | | SHEETS A 1.2, FA 0.1, AND FA 2.1 WERE STAMPED, | | INITIALED, AND DATED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2006-12-26 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2006-12-26 |
Time |
15:36 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2006-12-26 |
Time |
15:36 |
Sent To |
|
|
Notes |
2006-12-26 15:41:53 | *****APPROVED***** | | | | | | | | | | FIRE TO STAMP AND SIGN WHEN ALL PLAN REVIEWS HAVE BEEN | | SATISFIED |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2006-11-20 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2006-11-20 |
Time |
11:54 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2006-11-20 |
Time |
11:54 |
Sent To |
AD |
|
Notes |
2006-11-20 12:09:09 | ****UNSAT**** | | | | | | | | 1.FLORIDA FIRE PREVENTION CODE 2004 EDITION SHALL BE | | REFERENCED. | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 3.SINCE THE SCOPE OF THE WORK WILL REQUIRE | | MODIFICATION OF THE FIRE PROTECTION SYSTEM(S), SEPARATE | | PERMITS AND PLANS WILL BE REQUIRED. | | | | 4.AS PER WPB FIRE PREVENTION, DUCT DETECTORS SHALL | | INITIATE A GENERAL FIRE ALARM.(MAKE CHANGE TO FIRE | | ALARM NOTE #17, SHEET FA 0.1) | | | | 5.CORRECT SPELLING OF "FIRE" ON SHEET FA2.1, KEY NOTE | | #2. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, | | INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH | | ITEM WAS ADDRESSED. | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2007-02-20 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-02-20 |
Time |
10:08 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-02-20 |
Time |
10:08 |
Sent To |
E |
|
Notes |
2007-02-20 10:08:55 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2007-01-12 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-01-12 |
Time |
09:07 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-01-12 |
Time |
09:07 |
Sent To |
E |
|
Notes |
2007-01-12 09:07:45 | TO "DPALMER" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2006-12-12 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-12-12 |
Time |
18:43 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-12-12 |
Time |
18:43 |
Sent To |
|
|
Notes |
2006-12-22 13:26:17 | TO "BOB"#9 | 2006-12-12 18:44:01 | WAITING FOR "BOB"--NEW SHEETS FOR "M" AND "BLDG" |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2006-11-20 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2006-11-20 |
Time |
12:10 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2006-10-26 |
Time |
09:55 |
Sent To |
|
|
Notes |
2006-11-01 10:22:00 | TO "BOB"#10 | 2006-10-26 09:57:59 | WAITING FOR "BOB" |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2006-12-26 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2006-12-26 |
Time |
10:36 |
Rev Time |
0.25 |
Received By |
tgordon |
Date |
2006-12-26 |
Time |
10:36 |
Sent To |
|
|
Notes |
2006-12-23 19:12:59 | NEW SHEET |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2006-11-01 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2006-11-01 |
Time |
14:14 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2006-11-01 |
Time |
14:14 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2007-01-06 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-01-06 |
Time |
09:40 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-01-06 |
Time |
09:40 |
Sent To |
|
|
Notes |
2007-01-06 09:50:18 | PASSED/PROVISO - WATER HAMMER ATTESTORS SHALL BE | | LOCATED NEAR THE FIXTURE, NOT IN THE CEILING. PDI-WH | | 201--SINK DEPTH MAXIMUM 6-1/2" DEPTH PER SECTION | | 11-4.24.4. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2006-11-13 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2006-11-13 |
Time |
13:31 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2006-11-13 |
Time |
13:31 |
Sent To |
|
|
Notes |
2006-11-13 13:36:42 | DENIED | | REFERENCE: FBC-2004 CHAPTER 11 | | | | 1. SHT A6.2.1. DETAIL 9 SHOW THE FOLLOWING: | | A. 11-4.24.3 KNEE CLEARANCE | | B. 11-4.24.4 SINK DEPTH | | C. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH | | REQUIRED AND SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH | | THE SINK). CABINET DOORS ARE NOT APPROVED IN THE CLEAR | | FLOOR SPACE. | | D. 11-4.24.6EXPOSED PIPES & SURFACES | | E. 11-4.24.7FAUCETS | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | | | |
|
|