Plan Review Details - Permit 06100832
Plan Review Stops For Permit 06100832
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2006-11-02 Cont ID  
Sent By dpalmer Date 2006-11-02 Time 07:02 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-03-21 Cont ID  
Sent By dpalmer Date 2007-03-21 Time 18:33 Rev Time 0.00
Received By dpalmer Date 2007-03-21 Time 18:21 Sent To PC
Notes
2007-03-21 18:35:02RISER APPEARS TO SHOW CONDUIT AND SERVICE ENTRANCE
 CONDUCTORS RUN ABOVEAND INSIDE ROOM. IF THIS IS NOT
 UNDERGROUND OR OUTSIDE THE BUILDING, THESE ARE REDLINED
 TO EB ENCASED IN CONCRETE PER 695-6A AND NFPA-20 9.3.1

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-12-20 Cont ID  
Sent By dpalmer Date 2006-12-20 Time 20:14 Rev Time 0.00
Received By dpalmer Date 2006-12-20 Time 19:55 Sent To PC
Notes
2006-12-20 20:16:23** THIS PERMIT FOR THE ELECTRICAL HOOK UP AND NEW
 SERVICE FEED FOR THE EXISTING FIRE PUMP AND CONTROLLER
 WHICH WAS SET/INSTALLED UNDER 06040045

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-12-10 Cont ID  
Sent By dpalmer Date 2006-12-10 Time 09:24 Rev Time 0.00
Received By dpalmer Date 2006-12-10 Time 09:14 Sent To PC
Notes
2006-12-10 09:25:05***** UNSAT *********
  
  
 1) NOTE: PLEASE SEE PLANS INDICATE EXISTING FPC,
 HOWEVER NEW CONTROLLER UNDER SEPARATE PERMIT. THAT
 PERMIT WAS ONLY TO PLACE CONTROLLER, NOT TO DO ANY
 ELECTRICAL HOOK UP. PLEASE NOTE ON PLANS AS NEW UNDER
 "(OTHER PERMIT NUMBER)".
  
 2) NOTE: PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS
 AS WERE SUBMITTED UNDER THE OTHER PERMIT. EACH PERMIT
 SHALL CONTAIN ALL DOCUMENTS RELEVANT TO INSTALLATION?
 FIRE PUMP AND FIRE PUMP CONTROLLER.
 THIS IS NEEDED TO CORRELATE HP RATING, CODE LETTER OF
 MOTOR FOR MAX LOCKED ROTOR CURRENT ETC.
 THIS IS ALSO REQUIRED FOR EACH RECORD SET OF PLANS.
 110.3, 90.7, ETC
 FBC 106.1.2
  
 3) NOTE: PLEASE SEE A 4X FEE WAS ISSUED AT JOBSITE AND
 HOLD WAS IN SYSTEM, THE ADDITIONAL FEE FOR WORK DONE
 WITHOUT PERMITS IS $333.00 WHICH IS REQUIRED AT THIS
 TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-11-02 Cont ID  
Sent By dpalmer Date 2006-11-02 Time 07:21 Rev Time 0.00
Received By dpalmer Date 2006-11-02 Time 07:01 Sent To PC
Notes
2006-11-02 07:21:11***** UNSAT *********
  
  
 ** PLEASE KNOW, PLANS HAVE ONLY BEEN SUBMITTED FOR
 "PLAN REVIEW" ONLY AND HAVE NOT BEEN SUBMITTED FOR
 PERMIT AT THIS TIME.
  
 1) NOTE: PLEASE KNOW WHEN FINAL APPLICATION IS MADE FOR
 INSTALLATION AND WIRING FOR FPC, THIS CAN NOT BE DONE
 BY A GC, CGC ETC. THIS MUST BE AN ELECTRICAL CONTRACTOR
 WHO APPLIES.
  
 2) NOTE: PLEASE SEE PLANS INDICATE EXISTING FPC,
 HOWEVER NEW CONTROLLER UNDER SEPARATE PERMIT. THAT
 PERMIT WAS ONLY TO PLACE CONTROLLER, NOT TO DO ANY
 ELECTRICAL HOOK UP. PLEASE NOTE ON PLANS AS NEW UNDER
 "(OTHER PERMIT NUMBER)".
  
 3) NOTE: PLEASE CLARIFY THE OCP ON THE FPC AS SHOWN.
 SHOWS 1000A, HOWEVER THIS IS BE TAKEN THAT THIS IS THE
 LRC?? PLEASE INDICATE THE NORMAL/ STANDARD OCP RATING.
 PLEASE VERIFY THIS AS THE SEC'S SHOWN ARE ONLY SIZED AT
 2/0'S WHICH ARE RATED FOR 175A'S ONLY PER 310.16,
 110.14.
 PLEASE VERIFY AND SHOW.
  
 4) NOTE: PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS
 AS WERE SUBMITTED UNDER THE OTHER PERMIT. EACH PERMIT
 SHALL CONTAIN ALL DOCUMENTS RELEVANT TO INSTALLATION.?
 FIRE PUMP AND FIRE PUMP CONTROLLER.
 THIS IS NEEDED TO CORRELATE HP RATING, CODE LETTER OF
 MOTOR FOR MAX LOCKED ROTOR CURRENT ETC.
 110.3, 90.7, ETC
 FBC 106.1.2
  
 5) NOTE: PLEASE SEE VALUE ON SCOPE OF WORK WHEN
 APPLICATION IS MADE MAY BE ADJUSTED. PLEASE VERIFY AS
 THE VALUE SEEMS LOW.
 FBC 108.3.
  
 6) NOTE: PLEASE MAKE NOTE OF THE CONDUITS ENTERING THE
 FPC SHALL BE ENCASED IN CONCRETE.
 NFPA-20, NFPA-70
 PLEASE BE SURE THE ABOVE CODES ARE STATED ON PLANS AT A
 MIN.
 PLEASE SEE 695 OF THE NEC AND CHAPTERS 6 AND 7 FOR
 INSTALLATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2006-11-02 Cont ID  
Sent By dpalmer Date 2006-11-02 Time 07:02 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2006-11-02 Cont ID  
Sent By dpalmer Date 2006-11-02 Time 07:02 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-03-16 Cont ID  
Sent By adarroug Date 2007-03-16 Time 10:54 Rev Time 0.00
Received By adarroug Date 2007-03-16 Time 10:54 Sent To E
Notes
2007-03-16 10:55:19TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-12-17 Cont ID  
Sent By adarroug Date 2006-12-17 Time 13:01 Rev Time 0.00
Received By adarroug Date 2006-12-17 Time 13:01 Sent To E
Notes
2006-12-17 13:02:50TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-04 Cont ID  
Sent By adarroug Date 2006-12-04 Time 11:14 Rev Time 0.00
Received By adarroug Date 2006-12-04 Time 11:14 Sent To B
Notes
2006-12-04 11:14:56TO "DPALMER" DESK/RESUB--PROJ TO PERMIT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-11-02 Cont ID  
Sent By   Date 2006-11-02 Time   Rev Time 0.00
Received By adarroug Date 2006-10-23 Time 15:05 Sent To  
Notes
2006-10-23 15:06:17TO "DPALMER" DESK/PER "RBROWN"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-11-02 Cont ID  
Sent By dpalmer Date 2006-11-02 Time 07:02 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-11-02 Cont ID  
Sent By dpalmer Date 2006-11-02 Time 07:02 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2006-11-02 Cont ID  
Sent By dpalmer Date 2006-11-02 Time 07:02 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***